Design Standards
Volume 1 of 2 - May 2018
MIT Design Standards - Copyright 2018. All Rights Reserved.
Disclaimer:
Information in the MIT Design Standards (the “Standards”) is based on the collective experience
of the MIT contributors. It is to be considered an evolving set of standards and is offered for the
users' consideration and evaluation for individual projects prior to use. MIT does not warrant the
suitability of the Standards for every project and reserves the right to amend the content at any
time.
No statement, recommendation or suggestion is intended for any use which would infringe any
patent or copyright. These documents must be used in conjunction with the current MIT Contract
Documents and General Conditions for Construction. In addition, it is intended that the content
of the MIT Design Standards complies with applicable Federal, State and local codes and
regulations, and industry publications, including ASHRAE Guidebooks, OSHA Regulations, FM
recommendations, and applicable NFPA codes and standards. When applicable codes and/or
regulations are at variance with the MIT Design Standards or each other, the user’s compliance
with the more stringent requirement or standard will be expected.
MIT makes no endorsement, representation or warranty hereunder, express or implied, that these
Standards are complete, accurate, error-free, fit for a particular purpose, or will not infringe the
intellectual property rights of a third party, with respect to information included, or the materials,
products, systems or applications to which the information refers in the Standards. Inclusion of
manufacturers names is not intended as an endorsement of any manufacturer or of their products.
In no event shall MIT be liable for, and user accepts all risks resulting in, any damages (direct,
consequential, special or otherwise), claims, costs, or loss of profits incurred by the user or any
third party in connection with, or arising out of, the use, distribution, alteration, or retention of the
MIT Standards. The MIT Design Standards are not intended for use for non-MIT projects, nor as
contract drawings or specifications.
!"#$%$&'!()*+,!&)'$ -./$0"#1$
!"0$%$.+*&)2&3+.4$3/3!5-3$ -./$0"#1$
!"6$%$7&-$.'*$,.*$*(.8&'9$3!.'*.(*3$ -./$0"#1$
!":$%$7&-$5;5,+!&)'$<4.'$ -./$0"#1$
!"=$%$,>&4*$,.(5$,5'!5(3$ -./$0"#1$
!"?$%$,4.33())-3$.'*$45,!+(5$>.443$$ -./$0"#1$
!"@$%$,)--&33&)'&'9$$ -./$0"#1$
!"1$%$5'2&()'-5'!A$>5.4!>$.'*$3.B5!/$C5>3D$$ -./$0"#1$
!"E$%$>&3!)(&,$<(535(2.!&)'$.'*$&,)'&,$.(,>&!5,!+(5$ -./$0"#1$
!#"$%$4.7$*53&9'$ -./$0"#1$
!##$%$4.'*$3+(25/$ -./$0"#1$
!#0$%$4.'*3,.<5$.'*$3&!5$ -./$0"#1$
!#6$%$-5,>.'&,.4$.'*$545,!(&,.4$())-3$ -./$0"#1$
!#:$%$<()F5,!$!+(')25($<()9(.-$ -./$0"#1$
!#=$%$(53&*5',53$ -./$0"#1$
!#?$%$(53!())-3$.'*$,+3!)*&.4$,4)35!3$ -./$0"#1$
!#@$%$3&9'.95$ -./$0"#1$
!#1$%$3<.,5$.,,)+'!&'9$9+&*54&'53$ -./$0"#1$
!#E$%$3+3!.&'.7&4&!/$$ -./$0"#1$
!0"$%$,.-<+3$3.B5!/$.'*$35,+(&!/$3/3!5-3$ -./$0"#1$
*&2&3&)'$$""$%$<(),+(5-5'!$(5G+&(5-5'!3$ -./$0"#1$
*&2&3&)'$$"#$%$95'5(.4$(5G+&(5-5'!3$ -./$0"#1$
*&2&3&)'$$"0$%$5;&3!&'9$,)'*&!&)'3$ -./$0"#1$
*&2&3&)'$$"6$%$,)',(5!5$ -./$0"#1$
*&2&3&)'$$":$%$-.3)'(/$ -./$0"#1$
*&2&3&)'$$"=$%$-5!.43$ -./$0"#1$
*&2&3&)'$$"?$%$8))*A$<4.3!&,3A$.'*$,)-<)3&!53$ -./$0"#1$
*&2&3&)'$$"@$%$!>5(-.4$.'*$-)&3!+(5$<()!5,!&)'$ -./$0"#1$
*&2&3&)'$$"1$%$)<5'&'93$ -./$0"#1$
*&2&3&)'$$"E$%$B&'&3>53$ -./$0"#1$
*&2&3&)'$$#"$%$3<5,&.4!&53$ -./$0"#1$
*&2&3&)'$$##$%$5G+&<-5'!$ -./$0"#1$
*&2&3&)'$$#0$%$B+('&3>&'93$ -./$0"#1$
5'*$)B$!.745$)B$,)'!5'!3$
May 2018
Table of Contents
The Institute admitted its first students in 1865, four years after the approval of its founding
charter. The opening marked the culmination of an extended effort by William Barton Rogers to
establish a new kind of independent educational institution relevant to an increasingly
industrialized America.
Today MIT is a world-class educational institution. Teaching and research—with relevance to the
practical world as a guiding principle—continue to be its primary purpose. MIT is independent,
coeducational, and privately endowed. Its five schools encompass numerous academic
departments, divisions, and degree-granting programs, as well as interdisciplinary centers,
laboratories, and programs whose work cuts across traditional departmental boundaries.
The mission of MIT is to advance knowledge and educate students in science, technology, and
other areas of scholarship that will best serve the nation and the world in the 21st century. The
Institute is committed to generating, disseminating, and preserving knowledge, and to working
with others to bring this knowledge to bear on the world's great challenges. MIT is dedicated to
providing its students with an education that combines rigorous academic study and the
excitement of discovery with the support and intellectual stimulation of a diverse campus
community. The motto is Mens et Manus – Mind and Hand – which is evident in the types of
laboratories and the work displayed around the campus. The Institute seeks to develop in each
member of the MIT community the ability and passion to work wisely, creatively, and effectively
for the betterment of humankind.
MIT is an integral part of its host city of Cambridge, a diverse and vibrant community noted for
its intellectual life, history, and thriving business climate. With a campus located between Central
and Kendall Squares, and across the Charles River from Boston, the Institute has an optimal
position to engage in collaborative endeavors with its neighbors and give back to the community.
The city’s approximately 105,000 residents, including 36,000 college and university students, rub
shoulders within its 6.26 square miles. Cambridge is pedestrian and bicycle friendly, with 80
parks and playgrounds, six subway stations, a commuter rail line, 29 bus routes, multiple shuttles,
24 bike sharing stations, and numerous dedicated bicycle lanes, enabling visitors and students to
get around the city and the MIT campus without a car.
Since its founding, MIT has maintained a commitment to serving the local community as a
resource for education and technology and as a good neighbor. The Institute solidly supports
nonprofit organizations that address local challenges such as meeting the needs of underserved
populations, youth and family support, and environmental sustainability. Students, faculty, and
staff at MIT are involved in a broad range of volunteer activities in the community. The Institute's
2. MIT ORGANIZATION
The Institute's chief executive officer is the president, who is supported by the chancellor, the
provost, the executive vice president and treasurer, as well as other senior academic and
administrative officers. In addition to these officers, other senior leaders are the deans of each of
the five schools and the Vice Presidents for Human Resources, Finance, Research, Resource
Development and the General Counsel. An organization chart appears at the end of this section.
The MIT Faculty determines the Institute's educational policy. The Faculty meets monthly and
conducts much of its business through elected standing committees.
The Institute's board of trustees, known as the Corporation, includes 70 distinguished leaders in
education, industry, science, engineering, and other professions, and (ex officio) the MIT
chairman, president, executive vice president, secretary of the Corporation, president of the
Alumni Association, and three representatives of the Commonwealth of Massachusetts.
The MIT Investment Management Company (MITIMCo) reports to both the President and the
Executive Committee. MITIMCo’s mission is to provide stewardship of MIT's financial
resources. One component of the organization is the Direct Real Estate Team which develops,
owns and operates real estate as part of the MITIMCo investment portfolio. This real estate,
while owned by the Institute, is not part of the academic portfolio of buildings. Occasionally
academic or administrative functions are housed in MITIMCo properties but they are rented just
as a normal non MIT owned property would be.
MIT is located on 168 acres that extend more than a mile along the Cambridge side of the Charles
River Basin and extend into Kendall Square and the Cambridge port neighborhood. The majority
of the central group of interconnected buildings surrounding Killian Court, called the Main
Group, was dedicated in 1916 and allowed MIT to move most of its programs from Boston to the
new Cambridge campus with the School of Architecture following in 1939 when 77
Massachusetts Avenue was completed.
Despite the simplified Beaux Arts façade, the new MIT campus represented a deliberate break
from then-current concepts of collegiate design. The architect, W. Welles Bosworth (‘89),
intentionally based the campus on the best industrial design of the time, and ensured that it served
some primary pedagogical goals: vertical and horizontal connections encourage and support
interdisciplinary interaction and communication; ample natural light and fresh air brighten the
The 1916 Cambridge campus announced the Institute’s willingness to experiment with both
buildings and building systems, which continues to this day. For example, in 1938, the Alumni
Pool, designed by Lawrence Anderson (’30) and Herbert Beckwith (’26) was the first instance of
modernist architecture in the Boston area. Eero Saarinen’s Kresge Auditorium (1954) was a
departure from both architectural form and construction methods. It is one eighth of a sphere; a
thin concrete shell mounted on three ball and socket joints resting on large underground
buttresses. The Stata Center, by Frank Gehry, became one of MIT’s most iconic buildings as soon
as it opened.
Campus growth during the second half of the twentieth century saw construction of landmark
buildings by leading architects such as Alvar Aalto, I. M. Pei ('40), and Eero Saarinen. Early in
this century, several remarkable new buildings, designed by distinguished architects such as
Steven Holl, and Fumihiko Maki, were added to meet the changing needs of teaching, research,
and community.
MIT's new buildings reflect its commitment to demand and uphold the highest standards in
environmentally friendly infrastructure. Ashdown, Sloan, Building E60, Maseeh Hall, and the
Cancer Institute have received LEED Gold Certification from the US Green Building Council.
The Brain and Cognitive Sciences Complex received LEED Silver. The Sloan and Cancer
Institute buildings are among the lowest energy using buildings of their type on any college
campus.
In addition to a willingness to take architectural risks MIT has, not unexpectedly, shown the same
willingness to take engineering risks in its new buildings. Mentioned above, Kresge Auditorium
is defined by a thin-shell structure of reinforced concrete weighing only 1200 tons. Thin-shelled
concrete technology was innovative for the times and very few contractors were equipped to
complete the construction. This structure, while innovative and unusual was not MIT’s first visit
to the leading edge of structural engineering. The original 1916 buildings used reinforced
concrete instead of the more familiar masonry. The first reinforced concrete building in the US
was built in 1904 so the Main Group, designed in 1910 was a significant departure from the
accepted norm in structural design. Additionally, the use of light masonry or terra-cotta walls for
interior partitions anticipated the evolving space needs of the Institute by making renovations of
interior spaces possible without structural modifications.
At a time when most buildings were ventilated by use of operable windows the Main Group
buildings used a combination of natural and mechanical ventilation, unusual for the time. Some
years later in the mid-1960s MIT's building E53 was one of the first buildings to use the variable
air volume or VAV, HVAC system which was invented by an MIT graduate. In 2007, MIT's
PDSI project was one of the largest users of chilled beam technology in the country. The success
of this technology has led to its adoption on both the Koch Institute for Cancer Research building
In addition to the iconic buildings discussed above MIT has 21 gardens distributed throughout
the campus, 12 of these are named gardens supported by donations from alumni and others. More
information about these gardens may be found here:
http://web.mit.edu/facilities/environmental/gardens/MIT_Pocket_Gardens_map.pdf
MIT’s Percent-for-Art Program, administered by the List Visual Arts Center, allocates money to
commission art for each new major renovation or building project. The program was formally
instituted in 1968 but earlier collaborations between artists and architects can be found on the
Institute’s campus. In 1985 architect I.M. Pei and artists Scott Burton, Kenneth Noland, and
Richard Fleischner collaborated on an art program for the Wiesner Building and plaza, home to
the List Center and the Media Laboratory. Other Percent-for-Art works include a terrazzo floor
by Jackie Ferrara for the Tang Center; out-door sculptures by Mark di Suvero, Louise Nevelson,
and Tony Smith; Dan Graham’s Yin/Yang Pavilion in Simmons Hall (designed by Steven Holl
Architects); Jorge Pardo’s ceiling murals created for MIT’s Graduate Dormitory on Albany Street
designed by S/L/A/M Collaborative; and Matthew Ritchie’s Games of Chance and Skill, a three-
part map of time and space created for the Albert and Barrie Zesiger Sports and Fitness Center
designed by Kevin Roche, John Dinkeloo and Associates. Other publicly sited art includes works
by Alexander Calder, Henry Moore, Pablo Picasso, Beverly Pepper, Michael Heizer, Victor
Burgin, Jennifer Bartlett, Bernar Venet, Frank Stella, Isaac Witkin, and Jacques Lipchitz. The
MIT PM will discuss this program when it applies to a project.
The original MIT buildings referred to as the Main Group are essentially industrial loft buildings
with high floor-to-floor heights and abundant natural light. Together, they comprise a little more
than 1 .5 million square feet of mixed-use space, most of which is interconnected by a network of
corridors, stairways, elevators, and tunnels. The buildings were designed to meet a set of
principles developed by John Freeman, an MIT graduate and prominent civil engineer. These
principles were:
1. An abundance of window light and a flood of controlled ventilation and filtered air.
2. Maximum economy in energy and time of students and instructors.
3. Maximum economy in cost of efficient service in heating, ventilating, janitor service and
general maintenance.
4. Maximum resistance to fire, decay and wear.
5. Maximum economy in cost of building per square foot of useful for space.
The fact that the buildings are still at the core of the campus and still serving its main mission is
partly due to the sensibility of these principles. The 100th anniversary of the opening of the Main
Group will occur in 2016. It is the Institute's expectation that new buildings while they may be
guided by slightly different principles will also be able to celebrate 100 years of useful service to
MIT.
MIT is committed to incorporating principles of sustainable design and energy efficiency into all
of its building projects. Sustainable design seeks to design, construct and operate buildings to
reduce negative impact on the environment and the consumption of natural resources. Energy
efficiency has proven to be a cost-effective approach that reduces a buildings energy demand
without impacting its ability to support its given mission. MIT firmly believes that sustainability
and energy efficiency must be designed into the project from the beginning and should not be
treated as add-ons after the basic design is complete.
The Department of Facilities reports to the Executive Vice President and Treasurer. The
Department consists of three related organizations: Campus Construction, Campus Services and
Police, and Maintenance and Utilities. As stewards of the campus, the role of Facilities is to
develop, renew and maintain MIT’s physical assets. In the three organizations there are over 600
employees working on many types of projects. Organization charts for all three parts of Facilities
are provided at the end of this section.
The Office of Campus Planning, the Office of Sustainability and the Environment, Health and
Safety office are also integral to any project from initial feasibility through construction,
commissioning and operation. These offices also report to the Executive Vice President and
Treasurer and are part of an infrastructure Team with Facilities that ensure a collaborative
partnership on the development and implementation of projects.
The Campus Construction staff report to the Director of Campus Construction. The groups
within the departments are: Capital Projects, Contract Administration and Controls, Facility
Information Systems, Accelerated Capital Renewal Program, Renovations and Renewal, and
Systems Performance and Turnover. These groups work together to provide project delivery
services to all of the Institutes Departments, Labs and Centers (DLC’s). These projects range
from new buildings to space change projects and lab renovations.
Contracts Administration and Controls supports the work of the other departments by assisting
with preparation of contracts and purchase orders and by providing budget reports. Most large
scale projects involving design documents or construction work will be governed by a modified
AIA contract while smaller work can be done with a purchase order or an acceptance of proposal
letter.
The Facility Information Systems (FIS) team provides space accounting, archiving, and mapping
support to Facilities and other departments at the Institute. The groups Facilities CAD Guidelines
establish AutoCAD standards that must be used by architects, engineers, contractors and other
consultants working for MIT so that construction and infrastructure records are accessible. Also
useful are Survey Standards that provide data and guidelines for surveys done by architects or
contractors. The team also manages the MIT drawing archives which hold a treasury of
architectural drawings that depict MIT’s earliest buildings. In addition, the area maintains online
tools such as current building systems manuals that serve as reference material for Facilities and
outside engineers. Other services include assigning of room numbers, signs for offices, public
safety and emergency evacuation signage and dedication plaques.
The Renovations and Renewal Group manages space change and infrastructure renewal projects.
These consist of renovation projects that are initiated by various MIT Departments Labs and
Centers (DLC’s). These projects are funded by the DLCs and or the Associate Provost for Space
Office. The annual volume exceeds 60 projects valued at $50m to $60m in project costs per year.
The Capital Renewal Program, which is a major component of MIT’s 2030 Campus Master Plan,
is also managed by this group. A new prioritization model for identifying and funding capital
renewal needs campus wide was created in 2011. The “Accelerated Capital Renewal Program”
(ACR) was a three year $250m pilot of a newer, larger effort to reinvest in MIT’s campus. Based
on the successes of the ACR Program, MIT has committed to a longer and larger investment in
the campus’ physical infrastructure.
To maximize the impact of these capital renewal investments, the program will engage in projects
that have a meaningful impact on the advancement of MIT's mission. A significant amount of the
program funds will be dedicated to larger, more comprehensive building upgrades involving
major systems and substantive programmatic changes. Another large share of funding will be
committed to the replacement of targeted core building systems that are reaching the end of their
Systems Performance and Turnover is responsible for the commissioning and testing of all
building systems prior to turning them over to Repair and Maintenance. The goal is to insure
fully functioning systems that meet the design intent and conform to the contract documents and
not to burden Repair and Maintenance with the task of troubleshooting underperforming systems.
This sometimes means that a building will be turned over but that portions of a mechanical or
other system will not be until deemed to be fully functional. The group is also responsible for the
Institutes energy cost reduction program as well as the joint MIT/NSTAR energy investment
program called Efficiency Forward.
Campus Services and Police consists of the Police Department, Customer Service Center,
Custodial Services, Fleet Management, Grounds Services, Mail Services, Off Site Facilities,
Parking and Transportation, Recycling & Materials Management, Security and Emergency
Management (SEMO) and Vendor Management. Most projects will interact with a representative
from SEMO and, on occasion, other groups will also be represented on the MIT project team.
Maintenance and Utilities consists of the Comprehensive Stewardship Group, Repair and
Maintenance, Utilities and Systems Engineering.
Comprehensive Stewardship Group (CSG) is a service area within the Operations section of
Facilities. The CSG complements the Repair and Maintenance area and focuses on the new and
newly renovated buildings on campus. The group’s charge is to proactively maintain buildings so
that they will remain current with modern standards and usage thereby maximizing the impact
and return on MIT’s investment. The group’s portfolio is presently 14 buildings: 2, 6C, 18, 32,
46, 76, E14, E60, E62, NW35, W1, W35, W64, and W79. The Group is comprised of several
teams with a variety of trades that span three shifts seven days a week. While a CSG member
may attend occasional project meetings communication with CSG will largely be through the
project manager.
Repair and Maintenance (R&M) consists of a Preventive Maintenance group and a Maintenance
Mechanics group. The role of the Preventive Maintenance group is to proactively perform
periodic maintenance in order to keep building systems running reliably and efficiently. The
Maintenance Mechanic group are first line responders to customers for heat and cooling calls.
They also do some investigatory work to determine which trade should respond to a service call.
As above, an R&M team member may attend project meetings from time to time but generally,
communication will be through the project manager.
Systems Engineering advises project managers who execute renovation and expansion projects
and also provide guidance to and review of the design work of outside engineers. The
Engineering staff includes professionals from electrical, HVAC, plumbing, fire alarm, and fire
protection. The staff, working with the offices of Campus Planning and Sustainability, helps to
integrate new work in buildings with the existing infrastructure and plan for sustainable and low
energy building systems.
There is also an Administration group that provides the following services to the three
components of Facilities plus the Office of Campus Planning: Applications and Desktop
Services, Business Systems, Communications, Environment, Health and Safety, Finance and
Accounting and Human Resources. This group reports to the three Facilities directors.
The Office of Campus Planning is responsible for campus analysis and planning as wells as for
providing support to the Institute's senior leadership and key physical committees. These include
the Committee for Review of Space Planning (CRSP) and the Building Committee. This support
includes capital and space planning, capital project definition and development, designer
selection and design reviews. The office reports to the Executive Vice President and Treasurer
and collaborates closely with Campus Construction, Campus Services, Maintenance and Utilities,
EHS, the Associate Provost and the city of Cambridge. A representative from Campus Planning
will be involved in most projects and will be the lead project manager for feasibility studies,
programming, concept design and preliminary budgeting.
MIT's Environment, Health, and Safety Office (EHS) is responsible for the deployment of
resources that reduce the environmental impact of MIT's work, operations, and facilities and for
ensuring the health and safety of MIT’s community members and neighbors. The Office is also
responsible for legal compliance and reporting with respect to all Federal and state environmental
laws. The work of the office includes: Safety programs, EHS training, work area hazard
These services are provided to all of the Institutes Departments, Labs and Centers, as well as to
the Campus Construction project managers. An EHS team member will be part of most project
teams.
The Office, which reports to the Executive Vice President and Treasurer, works as a catalyst to
ensure the integration of sustainability principles across all the operational units of the Institute.
Areas of involvement include capital construction, small-project renovations, energy systems,
transportation systems, operations and maintenance, waste management, recycling, water
management, procurement and land management. The Office also examines novel opportunities
for financing, organizing and planning such projects. The Office is charged with positioning
MIT’s campus as a living and learning laboratory for sustainability. When successful, the campus
sustainability work will make direct and meaningful contributions to the core teaching and
research mission of the Institute. The opportunities range from testing new technologies being
developed in labs on campus to studying the organizational behavior that enables a sustainable
campus.
The Office works closely with departments such as Campus Construction, Campus Services and
Maintenance and Utilities to achieve its goals. A representative of the office may be involved in
larger projects.
IS&T is MIT's central IT organization, tasked with supporting MIT's core mission: "...to advance
knowledge and educate students in science, technology, and other areas of scholarship that will
best serve the nation and the world in the 21st century." IS&T reports to the Executive Vice
President.
The organization's role is to provide modern, efficient, and cost-effective IT services to the entire
MIT community. IS&T provides the technical infrastructure, services, and support to enable the
diverse work that takes place at MIT, from high speed networks and data centers supporting
faculty research collaboration, to academic software packages and teaching systems used by
MIT's over 10,000 undergraduate and graduate students. Through partnerships with other
academic and administrative units, IS&T strives to continuously streamline business processes
and lower administrative costs wherever possible.
MIT's IT environment is large and diverse. The main campus network (MITnet) provides wired
and wireless network services to all campus buildings, and consists of over 3000 network
switches and 4300 wireless access points, connected by more than 5000 miles of single-mode
In addition to end-user computing, MITnet also supports a large data center environment. IS&T
operates 6 data centers supporting academic, administrative, and research applications: email,
web publishing, learning management, academic records, financial data, and many others. These
applications are supported by over 2000 virtual servers backed by more than 1 petabytes of disk
storage. An additional 3 petabytes of near-line backup capacity provides disaster recovery
service for all data center systems and more than 5000 MIT community desktops and laptops.
Email is the lifeblood of most modern enterprises and MIT is no exception. IS&T's email system
sees a total of 1.6M inbound emails per day. Of these, roughly two-thirds (1.1 million) are spam,
with the remainder being legitimate. The MIT community sends an additional approximately
700,000 messages per day; roughly 450,000 of these are MIT-internal, with the remainder being
sent outside of MIT.
Supporting all of this is MIT’s Help Desk. Available to any member of the MIT community, the
Help Desk Call Center answers over 40,000 support call annually and replies to an additional
45,000 support requests by email. IS&T also provides additional desk side support to many
departments as well as to dormitories, fraternities, sororities and independent living groups.
Most projects will impact the IS&T infrastructure in some manner and the department will
therefore be represented by a staff member as part of the MIT project team.
The Associate Provost for Space assists the Provost in academic administration, with primary
responsibilities for space planning, space assignment and prioritizing renovations. The Associate
Provost for Space manages the Institute’s renovation budget and, with the Executive Vice
President and Treasurer and the Office of Campus Planning, coordinates long-range campus
planning and stewardship. In addition, the Associate Provost oversees MIT’s industry
engagements, the Office of Corporate Relations and Technology Licensing Office. The Associate
Provost also assists the Provost and President in strategic initiatives and other Institute affairs.
The office approves all space assignments and allocates Institute funding to those projects not
fully funded by the Department, Lab or Center. The Associate Provost also approves all signage
and all changes to public spaces. Design professionals may interact with a representative of the
Associate Provost as part of a project team or indirectly through the project manager.
MIT has been located in Cambridge for nearly 100 years, beginning in 1916. In that period the
campus has added approximately one million square feet of built space every decade. The pace of
building has been even greater in recent time, with about 2.5 million square feet being added
since 2000.
Because of its scale, MIT has many functions that are similar to those of a city, such as its own
police force, mail delivery, environmental, health and safety personnel. In addition, MIT operates
shuttle buses for transportation in and around the campus.
On the other hand, MIT is an urban institution, dependent on the City for critical infrastructure
and services, such as the city fire department, public roadways, water, sewer and most storm
drainage connections. It is subject to a wide variety of regulatory controls, such as zoning, off-
street parking, storm water controls, historic preservation, licensing for residence halls and
chemical storage. MIT is also, of course, subject to all building codes, life safety regulations and
trade permits.
MIT strives to be a good neighbor in Cambridge, not only by satisfying regulatory requirements,
but by communicating early and directly regarding its plans. The permanent nature of the
institutional relationship puts a premium on a long term approach that values mutual respect, trust
and the assumption of good faith above a more expedient approach to a single project in isolation.
A project manager (PM) has total responsibility for the project. The PM collaborates with the
user group, the necessary MIT departments, the Office of the Provost for Space, the design team,
contractors or construction managers and the City of Cambridge to ensure successful completion
of the project.
Campus Construction PM
• Coordinates with MIT departments such as Environmental Health & Safety, the Systems
Engineering Group, Repair and Maintenance, SEMO and the MIT Police.
• Creates cost estimates and manages the project budget
• Monitors project scheduling
• Provides project updates and status reports to the users and senior staff
• Coordinates project design and code compliance
• Works with contractor to manage project construction
• Secures project Certificate of Occupancy and manages turnover to the end user
• Is responsible for documenting the project in MIT financial and Facilities Information
systems
• Is responsible for post occupancy warranty issues
The MIT project team will be defined at the beginning and will be led by the MIT project
manager (PM). The team will also include a representative of the client or user group, a
representative from Engineering, the Planning Office, Campus Construction, the Sustainability
Office, Environmental Health and Safety and, where necessary Facilities Information Systems
and Utilities.
The MIT PM will direct the project from start to finish and will generally be the focal point for all
communications and decisions affecting budget and schedule. That convention does not,
however, prohibit direct communication between consultants and other MIT staff when
clarification of this document is required or design details need to be worked out. The project
manager is to be kept informed if not actually in the communication trail. As mentioned above,
MIT often enjoys a special relationship with the various components of the City of Cambridge
government. To continue to foster that relationship MIT requires that all communications with the
MIT has used the integrated design approach (referred to as integrative design by some)
successfully on several large building projects. These projects were successful from many
viewpoints, but particularly from that of energy use. The approach will not lend itself to use on
projects of all sizes and types but its adoption will be appropriate for many. The details of the
integrated approach will be familiar to all so they will not be discussed here however the reader is
encouraged to gain a better understanding of what MIT expects by studying material available on
the National Institute of Building Sciences Whole Building Design Guide website. The following
link is particularly recommended: http://www.wbdg.org/design/engage_process.php
The process will require multiple full design team meetings or charrettes. The architect may lead
these meetings but it is our experience that a specialist third party facilitator, engaged for this
purpose and for the duration of the project will yield better results. The process will also have
greater success if a broader and perhaps untraditional understanding of the design team is
accepted. This definition would include but not be limited to the lighting designer, food service
consultant, construction manager, commissioning agent and in special cases, the appropriate code
officials. There may be a sustainability charrette though it is MIT’s expectation that
sustainability will be designed into the project from the beginning and not “added on” as a
separate feature. It is also expected that specific and measurable sustainability and energy goals
will be set early in the project and that the projects progress toward those goals will be measured
at regular intervals and adjustments made as necessary. Examples of these goals are: lighting
power density in Watts/sf, building cooling demand in square feet per ton, building heating
demand in btuh per square foot. MIT has extensive data on the energy use of its building
inventory which will provide guidance in setting energy use and demand goals. Newer buildings
are sub-metered and offer detailed data on plug loads, lighting loads as well as heating and
cooling demand.
As building component and system options are developed it may be appropriate to conduct life
cycle cost analyses. MIT uses the National Institute of Building Sciences life cycle program,
BLCC. The analyses may be conducted either by MIT personnel or by the design team. If the
latter course is chosen, basic assumptions must be obtained from MIT before the analysis is
conducted.
END OF DOCUMENT
May 2018
Table of Contents
1.1 Introduction
Audiovisual systems are integral to many aspects of MIT, from classrooms, conference rooms
and performance spaces. Through advance planning and design activities, MIT Audiovisual
Services can engineer systems that meet the needs of the end users and provide a quality
experience for all program participants. An audiovisual system should be designed with end-
users as part of the facility design process to assure that all electrical, architectural and design
criteria are included and considered. Advance planning of audiovisual systems in key to a
successful system and seamless integration into the room environment.
Audiovisual design and installation practices shall comply with the following standards issued by
AVIXA (Audiovisual and Integrated Experience Association) and ANSI/INFOCOMM:
Refer to Appendix A for the MIT Audiovisual Installation Equipment Support Policy (9/17)
which includes the Supported/Serviceable Equipment List, Unsupported Equipment
Announcement Period, Options for Unsupported Equipment, Common List of Unsupported Items
and Approved Manufacturers.
In some classrooms, lecture halls and conference rooms, an audiovisual equipment booth or
closet is required to support the programmatic needs of the room. The following criteria should
be used to guide the design process:
2. A detailed AV design is required to properly configure the racks needed for the system in
advance of final architectural planning. In some cases, in-wall or above ceiling storage
systems may be needed or desired. Middle Atlantic and other manufacturers provide
solutions for non-traditional AV rack systems.
3. For rooms where AV equipment can be stored in an under counter height credenza, the
space allocated for an AV rack shall be 30 inch wide and 30 inch deep. Depending on
the AV system design complexity, more than one rack may be needed. The rack should
be accessible by the means of casters or silicone sliding strips on the base of the rack.
4. If the AV rack is mounted under a credenza countertop, the counter shall have cable pass
through capabilities by use of grommets or slots as needed by the system operation needs.
5. If the countertop is to be used for end-user devices (laptops, tablets, etc.) the placement of
duplex electrical outlets should be considered along the wall above the countertop.
6. If an AV equipment closet is planned for the space, the closet dimensions shall be at
minimum 36 inch wide by 36 inch deep. The rack should be able to be pulled out of the
closet by the means of casters on the base of the rack. Appropriate cable service lengths
must be provided to enable the rack to be pulled out for service.
7. For any AV equipment locations (credenza, AV rack closet or projection booth), proper
cooling in the space should be considered depending on the system components planned.
A heat load calculation can be performed by the AV designer to enable proper cooling for
the space. In some cases, passive cooling may be sufficient but in other areas a dedicated
cooling system (or separate AV space zone) should be provided to prevent damage to
electronics from heat generated by the AV system components.
8. Access to AV closets, cabinets rack rooms and booths shall be provided using MIT
standard Schlage locks and door hardware. The standard FA6 key and lockset must be
provided to AV cabinets and doors. Lightweight cabinet locks are not approved for AV
equipment storage locations.
9. In renovation or new construction, a card reader access to the AV room shall be provided,
along with the lockset.
10. Lighting in projection booths or closets should be operated independently of the lighting
system for the room. Fully dimmable down lights shall be provided over work areas
(LED or incandescent). Indirect dimmable florescent lights shall also be provided in 2 by
2 foot ceiling grid system.
To properly specify the electrical needs for an AV system, a full system design must be
completed with input from end users and AV system designers. Depending on the complexity of
the overall project, an electrical engineer may be required to enable the proper services for the
AV system.
This is especially true for full renovation or new construction projects. This design must be done
in advance of the final room design and pricing by general contractors to prevent change orders
related to AV system requirements.
1. Dedicated circuits must be provided for any outlets that will connect to the AV system.
This includes AV rack power, image displays (projectors and flat panels), end-user
device connection locations (power outlets for laptops, tablets or other portable devices).
These input locations may be spread around the room and final locations must be
determined with the end-users, AV designer, architect and electrical engineer.
2. All AV related power circuits must be on the same electrical phase to reduce the potential
of audio and video interference developing in the AV system. This is evident in 60 Hz
audio buzz in the sound system or rolling dark bands in video displays.
3. Isolated grounds are not required for AV equipment.
4. Electrical outlet quantities are dependent upon the size of the AV system. In general, a
quad outlet is required for AV rack closets or credenza locations. Each outlet shall be
rated at 20 amp level unless otherwise specified.
5. At image display locations, at least a duplex outlet is required. Depending on the system
components, a quad outlet is often desired to power peripheral devices at the display
location.
6. Ceiling mounted outlets shall be accessible at below ceiling level, either in a ceiling
mounting system or outlet integrated into the ceiling.
1. Conduits shall be sized appropriately to avoid over filling, based on National Electrical
Code requirements.
2. Conduit is required above any ceiling spaces that are not accessible after construction to
enable expansion in the future.
3. Conduit riser diagrams shall be developed by the AV designer and included on the
electrical drawings for construction.
4. Conduit must be used for microphone or speaker wiring, to protect them from electro-
12. To assure building code compliance, many AV systems require a connection to the
building fire alarm system. Electrical engineers must design the fire alarm system with a
connection to the AV control system (Crestron system) to enable a dry contact closure
from the fire alarm system. Once the Crestron system receives this signal, it will turn off
the AV system, raise the screens and send a signal to the lighting system (if provided) to
bring the lights up to full level. These details shall be shown on the electrical drawings
for the project and noted that a connection to the AV system is required.
13. Connection to the Lutron room lighting system will be provided through the AV control
system. The electrical engineers, in conjunction with the lighting designer and electrical
contractor, are responsible to specify, provide and wire the appropriate lighting system
interface to the AV control system as part of their scope. In addition, the Lutron
integration codes shall be provided to the Crestron AV system programmer to enable the
appropriate scene control through the AV system.
14. Location of the Lutron scene-setting controller shall be in the AV booth or in another
secure location within the room that will enable scenes to be changed while monitoring
the room lighting.
2. DISPLAY SYSTEMS
Display technologies are updated on a regular basis. The audiovisual system design process will
help determine the correct display technology for each location.
Recent developments in laser based light sources for projectors make these an attractive option
over the traditional lamp based systems commonly used in the past. There are no lamps to
purchase during the life of the projectors (rated at 20, 000 hours) and no hazardous mercury based
lamps for disposal. As laser projectors continue to improve and gain a larger market share of the
projector industry they will be specified in increasing numbers for projects at MIT.
In some cases, systems are being designed for 4K resolution content. For systems that have the
programmatic direction to include 4K or higher image quality, the AV system design will be
developed to meet this need. The remaining components of the AV system must also be 4K
capable, including switching, signal transmission devices and cabling.
As of January 2016, the following projectors are currently being recommended and installed in a
variety of locations at MIT. These projectors range in price from under $5,000-40,000,
depending on the brightness, lenses and capabilities of each display.
1. For systems that require projection screens, MIT has used Da-lite http://www.da-lite.com
and Stewart Filmscreen http://www.stewartfilmscreen.com solutions.
2. Projection screen aspect ratio shall be 16:9 for most applications.
3. For most flat floor classroom and conference room environments that call for a wall or
ceiling mounted screen, with the size of 106 inch diagonal or less, the Da-Lite Designer
Contour Electrol is specified: http://www.da-lite.com/products/electric-screens/wall-and-
ceiling-mounted-electric-screens/designer-contour-electrol
4. For ceiling recessed screens, the Da-Lite Advantage Electrol is specified: http://www.da-
lite.com/products/electric-screens/ceiling-recessed-electric-screens/advantage-deluxe-
electrol. The Advantage line of screens allow for recessing in either drop or hard ceiling
systems, with the ability to install the screen housing during the rough-in phase of
construction, followed by the screen fabric and motor once the room is in a cleaner
condition.
5. In most classrooms and lecture halls tab-tensioned screens are not used. However, for
some larger screens where edge curl over a large screen surface is a potential problem, a
tab-tensioned screen may be specified, such as the Da-Lite Tensioned Advantage
Electrol: http://www.da-lite.com/products/electric-screens/ceiling-recessed-electric-
screens/tensioned-advantage-electrol.
6. In general, MIT uses the Matte White projection surface in the Da-Lite line of screens.
Alternate screen surfaces can be selected depending on the requirements of the room
environment.
7. To integrate the projection screen into an audiovisual control system, the use of an
internal low voltage controller (LVC) device is specified.
8. In most AV systems, an electrically operated screen is recommended to assure that the
screen always stops at the correct lower limit. In some cases, a manually operated screen
is chosen. In these cases, the Da-Lite Model C with Controlled Screen Retraction (CSR)
is specified: http://www.da-lite.com/products/manual-screens/model-c-with-csr.
9. For rooms with recessed ceilings that require a manually operated screen, the Advantage
Manual with CSR is specified: http://www.da-lite.com/products/manual-
screens/advantage-manual-with-csr-ceiling-recessed
The widespread use of flat panel displays has, in some cases, enabled audiovisual systems to
become less complicated. This is due to the ability to use a large (65-90” diagonal dimension)
flat panel in rooms that had traditionally been equipped with a projection screen and projector.
In general, flat panels are chosen from a manufacturer’s line of professional equipment. These
usually have a full range of connection types and feature RS-232 control capability, which
enables integration with other professional AV system components.
Occasionally, panels from a manufacturer’s consumer line are used due to lower costs. However,
these units typically do not include warranties beyond 90 days. Sometimes extended warranties
are available for additional cost. The consumer grade equipment lines are also frequently
changing models and are sometimes difficult or impossible to control with other AV system
components.
As of January 2016, the following flat panels are currently being recommended and installed in a
variety of locations at MIT. These panels range in price from under $4,000-9,000, depending on
the size of the display.
Video wall systems are in use in several locations within MIT. Each system is uniquely designed
with the end user’s programmatic needs in mind. Specific equipment for video walls is
developed during the design process. The budget for video walls should include at least one
spare panel to enable quick swapping in case of equipment failure in the future and obsolescence
in future panel models.
In general, products from the NEC Display Technologies line of video wall packages are
specified. For further information, see http://www.necdisplay.com/solutions/video-walls/60 for
further information.
Consumer Displays:
Commercial Displays:
MIT Audiovisual Services is transitioning to an all Crestron environment to enable better long-
term support of systems. Crestron offers its A+ program to higher education institutions like
MIT. This enables the department to leverage past purchases of Crestron equipment and receive
equipment at no cost. Through this program, MIT is able to keep a stock of commonly used
Crestron components, enabling quick repair times and reducing downtime of audiovisual systems.
Crestron offers a full spectrum of technologies that enable the creation of very basic to very
complex audiovisual systems. Some of the key components currently in use on projects include:
Depending on the size of the AV system, audio requirements can be very basic or complex.
Below is a sampling of commonly used audio components for different room types.
2. Ceiling mounted speakers for speech or program audio playback, classroom or lecture
halls:
3. Large lecture hall high quality program and speech audio speakers:
a. Meyer Sound speakers have been used in 6-120, E14-Silverman Skyline and
Wong Auditorium. Each system is configured to fit the space as part of the
design. Meyer engineers will assist in the design and make site visits to assure
the proper speaker is chosen http://www.meyersound.com/index.php.
b. As part of the commissioning process a Meyer engineer is assigned to the project
to configure the system to peak operating capability.
4. Audio Amplifiers:
a. Both Crestron, QSC and Meyer brand amplifiers have been used in recent
1. MIT has standardized on the BiAmp Systems line of DSP for any systems that require
management of a large number of audio signals through the system.
http://www.biamp.com/default.aspx. Proper design of the system is required to correctly
specify the components necessary and associated programming resources necessary to
create the system.
2. Digital audio signals use the AVB (audio video bridging) standard.
1. Shure ULX-D digital microphones are specified for any new systems:
http://www.shure.com/americas/products/wireless-systems/ulxd-systems
2. A frequency scan is required before adding any new wireless systems to assure no
interference from surrounding systems is encountered with the new system.
The MIT A/V Installation Group is committed to delivering innovative, effective technology
solutions to our clients. As technologies evolve, we continue to proactively develop and shape
our solution options. The resulting new solutions and feature modifications often lead to a need
for discontinuing older hardware by both us and the equipments’ original manufacturers. MIT
A/V Services Equipment Support policy is described below.
Crestron; control systems, video processing systems, power amplifiers and loud speakers.
Additional acceptable manufacturers include: Meyer Sound, Fulcrum Acoustic, Crown Audio,
Sennheiser, Vaddio, 1Beyond, Chief Manufacturing, Peerless-AV, Middle Atlantic, Denon
Professional.
To inquire about any brands not on this list, please contact MIT Audio Visual Installation
Services.
We will no longer be able to offer support for equipment on the Unsupported Equipment list
below. If any equipment listed below was installed by MIT A/V Installations, we will continue to
support it within the one year warranty period. Some equipment is no longer supported by the
manufacturers and some is no longer up to our standards as expected by end users and the
institute.
Once a piece of equipment has been deemed “Unsupported” by MIT A/V, we can no longer offer
support of the device from either a hardware or software (programming) standpoint. This is
typically a result of the original manufacturer no longer supporting the equipment. We will still
be able to send equipment out for repair at the cost of the customer, but we cannot guarantee it
will be repairable by the manufacturer. We also cannot guarantee that a temporary fix can be
provided in the absence of the broken equipment. This could lead to rooms being non-operational
for an indeterminate amount of time.
Replace the Equipment: This can be the best option especially if the equipment is out of date.
There are constant technological advances that may provide a better experience in your space(s)
and many of these advances have become our standards on campus. But please note, most of the
older equipment utilizes older infrastructure and that too may need to be updated.
Self-Maintain the Equipment: This is typically not a good idea. This method can be something
much time and effort is wasted on and you may experience long periods of down time.
Third Party Maintenance/Service: MIT has a list of preferred vendors off-site that you are
welcome to reach out to for equipment maintenance. Please be advised that this option will
remove any on-campus help from our group as an option. For a list of preferred vendors, please
email avinstall@mit.edu.
• Composite
• S-Video
• Component (RGB)
• 5 wire RGBHV
• Biamp Nexia and Audia Series audio digital signal processors (DSP's)
• Shure SCM810 auto-mixer
• Shure SCM and M series mixers
• All Extron audio products including combiners, amplifiers and audio controllers
• Most other brands of audio DSP’s including Peavey, Gentner, ASPI, Polycom, and
BSS
• All brands of speakers that are damaged, where parts are no longer available or do not
suit the installation
• ISDN audio installations (which are no longer being offered by AT&T and Verizon)
• Wireless microphones between 600MHz and 800MHz. *(See Below)
• Video Projectors:
o NEC, Panasonic, Sony, Epson, Barco
• Flat Panel Displays (TV’s):
o NEC, Panasonic, Sharp, LG, Sony, Samsung
• Display Mounts (Video Projectors and Flat Panel Displays):
o Chief (preferred), Peerless, Middle Atlantic, Premier
• Video Switching, System Control, Video Transmission:
o Crestron
• Wireless Video Transmission:
o Barco Clickshare
• Audio DSP:
o Biamp (Preferred), Crestron, QSC
• Wireless Microphones:
o Shure (ULX-D and Axient Digital) – *See important note below
• Audio Amplifiers:
o QSC, Crestron, Biamp, Linea
• Speakers:
o QSC, Crestron, Meyer Sound, Fulcrum, Genelec
The FCC has auctioned off large portions of frequencies that fall between 600Mhz – 800Mhz. As
a result, our group will no legally longer install or support any systems that fall in this range. In
some cases, it’s already a federal violation to operate these wireless microphones as these
frequencies are dedicated to first-responder use. If you own a system that falls in this range, you
are strongly encouraged to contact us to go over options to replace these units, as there may still
be a rebate available that could save your department thousands of dollars.
Above is not a complete list. Exceptions can sometimes be made on a case by case basis. For
any equipment older than four years that is not on this list, service is on a case by case basis.
If you or your department have questions on the current support level of a piece of
equipment, please feel free to reach out to us. Thank you.
9/17
END OF DOCUMENT
May 2018
!
!
Table of Contents
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 1 of 36
1. INTRODUCTION
These guidelines are issued to promote the development of electronic drawings and models
suitable for use in the MIT Department of Facilities CAD and BIM environment. Consistency and
compatibility with existing MIT documents can only be achieved when these standards are
strictly adhered to. Electronic drawings produced and submitted in accordance with these
standards have significantly greater value to the Institute. Architects, Engineers and Contractors
delivering documentation to MIT must ensure these standards are reviewed, understood and
followed by those people responsible for preparing electronic drawings and models.
Each of the following sections contains the most essential criteria for developing electronic
drawings and models for use in the MIT CAD and BIM environment.
For typical Renovation and Space Change projects, the Designer is responsible for submitting a
complete set of construction documents (CDs) to MIT prior to the beginning of construction.
During construction, the Contractors are responsible for submitting complete As-Built
documentation to the project team as described in their contracts in electronic format and
Designers are responsible for submitting the record documents to MIT based on this As-Built
documentation. Construction Documents and Record Documents submitted to MIT need to
adhere to the criteria outlined in this document.
Designers that are not familiar with MIT's CAD requirements should meet jointly with the MIT
Project Manager and representatives from MIT’s Facility Information Systems (FIS) to discuss
specific project requirements prior to the development of any CAD documentation. Designers
should also take this opportunity to relay the project scope to FIS so MIT can furnish Designer
with existing drawings that will benefit the design team.
Milestone Deliverables:
1. For typical Renovation and Space Change projects, the following documentation shall be
delivered to MIT at the following project milestones:
Design: When the project is in the end of design phase, the Designer shall submit a
complete set of Design Documents (100% DD) in electronic and hard copy format
to MIT. These documents will be archived as a record of the project and will also
be used for initial room numbering purposes. Please refer to the MIT Space
Accounting Guidelines for information about the room numbering process.
Construction: When the project enters the construction phase, the Designer shall
submit a complete set of 100% Construction Documents (100% CD) in electronic
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 2 of 36
and hard copy format to MIT. These files will be archived as a record of the project
and will be used for room numbering verification. Please refer to the MIT Space
Accounting Guidelines for information about updating room numbers during the
construction process.
Completion: When the project has been completed, the Contractors shall submit a
complete set of As-Built (AB) Documents to the project team as described in their
contracts (electronic format). Designers are to submit the Record Drawings based
on these As-Builts and need to meet the format requirements outlined in this
document.
For typical Capital Projects, the Designer is responsible for submitting a complete set of
construction documents (CDs) to MIT prior to the beginning of construction. During
construction, the Contractors are responsible for submitting complete As-Built documentation to
the project team as described in their contracts (typically in both electronic and hardcopy formats)
and Designers are responsible for submitting the record documents to MIT based on this As-Built
documentation. Construction Documents and Record Documents submitted to MIT need to meet
the criteria outlined in this document.
Recognizing the diverse nature of capital projects, Designers shall meet jointly with the MIT
Project Manager and representatives of Facility Information Systems (FIS) to discuss specific
electronic requirements for the project in the early stages of project startup. All Designers should
also take this opportunity to relay the project scope to FIS so MIT can furnish the Designer with
existing drawings that will benefit the design team. Please request any additional documents
through the Project Manager.
Milestone Deliverables:
For typical Capital Projects, the following documentation shall be delivered to MIT at the
following project milestones:
Design: When the project is in the end of design phase, the Designer shall submit a
complete set of Design Documents (100% DD) in electronic and hard copy format
to MIT. These documents will be archived as a record of the project and will also
be used for initial room numbering purposes. Please refer to the MIT Space
Accounting Guidelines for information about the room numbering process.
Construction: When the project enters the construction phase, the Designer shall
submit a complete set of 100% Construction Documents (100% CD) in electronic
and hard copy format to MIT. These files will be archived as a record of the project
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 3 of 36
and will be used for room numbering verification. Please refer to the MIT Space
Accounting Guidelines for information about updating room numbers during the
construction process.
Completion: When the project has been completed, the Contractors shall submit a
complete set of As-Built (AB) Documents to the project team as described in their
contracts (typically in electronic and hardcopy formats). Designers are to submit the
Record Drawings based on these As-Builts and need to meet the format
requirements outlined in this document.
Construction and Record Document project drawings must be submitted in the file formats listed
below; other formats are not acceptable without the prior consent of MIT’s Facility Information
Systems (FIS).
1. All CAD drawing models shall be drafted at full scale in architectural units, such that one
drawing unit equals one inch. Tolerances for CD’s are implicit within professional
service contracts.
1. Drawings created using non-standard AutoCAD® fonts, linetypes, and hatch patterns can
result in content discrepancies in the delivered drawing set. To ensure the integrity of the
drawing set and minimize potential problems:
a. Only native AutoCAD® fonts, linetypes and hatch patterns are to be used. These
are standard support features installed as part of a standard AutoCAD® installation.
b. Custom fonts, linetypes and hatch patterns, including those provided by 3rd party
software, shall not be used.
c. Only these TrueType fonts shall be used: Arial, Courier New, Times New Roman.
d. Postscript fonts are not to be used.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 4 of 36
Blocks:
1. MIT is currently not imposing the use of any particular block definitions or block
libraries. However, MIT requires that the following general rules be employed when
handling block entities:
Object Enablers
Drawings created using standard AutoCAD® Object Enablers are not acceptable without the
prior consent of MIT’s Facility Information Systems (FIS).
Each CAD file submitted to MIT shall have only one title block. If using paper space, the title
block shall be placed with its lower left hand corner point inserted at a coordinate location of
(0,0,0). Official MIT title blocks are available in AutoCAD® format for use for project drawings
and is preferred for Record Drawings. Depending on the purpose of the drawing or facility
documentation, the drawing’s title block shall contain certain essential information that MIT
needs to store and retrieve each drawing in its library.
1. Original issue date - this date should not change once the drawing has been issued.
2. Sheet number.
3. Title - description of drawing and location information. Location information should
include all building, floor and room numbers as applicable.
4. Revision history - as applicable.
5. Drawing phase - drawings submitted as As-Builts or Record Design should clearly be
marked as such.
6. MIT Project number - if applicable.
7. A/E/C – Consultant responsible for producing the drawings should be clearly identified.
1. Drawing title - indicating the drawing content, e.g. floor plan, section, detail, etc.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 5 of 36
2. Sheet identification – must follow the Sheet Naming Convention in Section 4 of this
document
3. Date of drawing - date of final revision of the record drawing
4. Drawing Scale - representing the intended plot scale of the drawing with title block
5. North Arrow showing orientation of drawing (when applicable)
6. North Arrow showing orientation of drawing (when applicable).
1. MIT will not accept the submission of any CAD drawing deliverable which contains
unbound references to external source drawing files. All externally referenced data
sources that were used during the CAD drawing production phase should be inserted and
retained as a block within a single drawing file, including the title block, upon project
completion and prior to drawing delivery to MIT. Layers contained in XREF’s inserted as
blocks should conform to MIT guidelines. The resulting self-contained drawing file is an
acceptable deliverable to MIT.
1. MIT will not accept the submission of any CAD drawing deliverable which contains
referenced images. All images must be imbedded as OLE objects and must not be
referenced outside the DWG file. Referenced images will be discarded and therefore
might cause incomplete drawings. Please be aware of this when creating your CAD files.
1. AutoCAD® drawings created outside of MIT sometimes contain more than one drawing
sheet per file. While this may facilitate the production of construction documents, it will
impede the archival process and create content discrepancies. MIT requires that each
CAD file submitted as a project deliverable contains only one drawing model with one
title block, using either of the following setup methods. Note that some MIT clients may
express a preference for one method to be used instead of another. In this case, please
see your MIT client representative for specific preferences.
a. Method #1 Model Space Only: Both the drawing model and the drawing’s title
block are contained in the same model space environment within a single CAD file.
The paper space environment is not used. Features are drawn to 1:1 scale and title
block is scaled up to appropriate sheet size.
b. Method #2 Model Space and Paper Space Combined: Each CAD file is set up to
contain only one title block in paper space which references the building model
contained in model space. Title block shall be drawn at 1:1.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 6 of 36
Summary of Best Practices:
1. General:
a. Prior to delivery to MIT, AutoCAD® files containing multiple drawing sheets shall
be broken down into separate drawings containing single sheets.
b. AutoCAD® files delivered to MIT shall contain only one drawing and one title
block per file.
c. All AutoCAD® drawings shall be purged of empty, unused, or non-essential
drawing data prior to submittal. This includes all unused layers, linetypes, blocks,
fonts and entities.
d. AutoCAD® drawings shall not contain any frozen layers. All unused entities on
frozen layers shall be erased, and the empty layers purged.
e. Place title blocks, schedules and general notes at full-scale in paper space whenever
possible.
f. Label scaled viewports with the appropriate scale in paper space.
g. Draw all model space objects at full scale.
h. Scale objects using paper space viewports – zoom viewports to the appropriate
scale.
2. In Addition, the following practices should not be followed and using any of the
following practices will result in the rejection of the files:
a. Do not place or draw model-related blocks, tags and objects in paper space.
b. Do not dimension model space objects in paper space.
c. Do not rotate the UCS.
2.3 Layering
General: MIT has adopted the layer name and use rules recommended in the United States
National CAD Standard (NCS)- Version 6.0 for the following categories. These standards can be
found at https://www.nationalcadstandard.org/ncs6/.
1. Architectural.
2. Electrical.
3. Mechanical.
4. Plumbing.
5. Structural.
Where noted, MIT has supplemented the NCS with its own rules and standards, as necessary.
MIT’s layers listed in this guideline shall always take precedent over the NCS guidelines where
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 7 of 36
applicable. For additional detail, beyond what is outlined, please refer to the National CAD
Standard.
Exceptions to the NCS: MIT has not adopted the NCS for the following categories:
1. Civil.
2. Landscape.
3. Site.
4. Surveying.
Layering for these disciplines may be found above. Layers for land surveying can be found in the
MIT Design Standards Land Survey Thematic Folder.
1. Allow users to isolate systems and drawing elements by controlling the visibility of
objects - improving system performance and eliminating visual clutter.
2. Expedite the import process and maintenance requirements for each set of drawings upon
import into the MIT Facilities Information Systems CAD system.
3. Facilitate the sharing of information between drawings and disciplines.
4. Allow users to control display and printing characteristics such as color, line type, line
weight etc.
5. Summary of Best Practices.
6. Use only NCS and MIT standard layer names – reference the layer names provided in
this document.
7. Use the minimum number of layers necessary to adequately separate entities in each
drawing. The number of layers contained in each drawing will vary depending on the
scope and complexity of the drawing, however drawings shall not contain extraneous,
redundant, or overly detailed layer names.
8. Purge each drawing of unused layers prior to submittal. The drawing file shall contain
only those layers necessary for displaying and plotting the information and drawing
entities contained in each drawing. To ensure that subsequent prints made from each
AutoCAD® drawing match the original, unused or unnecessary layers must be purged
from the drawing prior to delivery.
1. Naming Scheme: The NCS layer naming scheme followed by MIT is organized as a
hierarchy. This structure is intuitive, easy to use and sort, and allows for expansion and
customization. Layer names are defined using characters identifying disciplines, major
groups, minor groups and modifiers. MIT disciplines are always identified by one
character. Major groups, minor groups and modifiers are always identified by four
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 8 of 36
characters and each group is separated by a hyphen and as follows:
2. Discipline Codes: The discipline code designation is a one character field with a
designator from the table below. The Discipline designators are the same for both layer
names and file names and as follows:
3. Major Groups: The major group designation is a required four-character field that
identifies the building system, such as doors, walls, windows, etc. Although most major
groups are logically associated with specific discipline codes, it is possible to combine
major group codes with any of the discipline codes.
4. Minor Groups: The minor group designation is an optional, four-character field for
further differentiation of major groups. For example, partial height walls (A-WALL-
PART) might be differentiated from full height walls (A-WALL-FULL). If necessary, the
minor group field may also be defined by the user, allowing additional layers to be added
to accommodate special project requirements. However, this should only be done after
checking the National CAD Standard to see if any of the predefined layer names in that
list would meet the special project requirements.
5. Modifiers: A modifier is an optional, four-character field that further subdivides the
minor group whenever additional clarification is necessary. Common modifiers can
delineate information categories, status or line weight elements. For example: A-WALL-
FULL-TEXT OR A-WALL-FULL-DEMO.
6. Special Modifiers: Special modifiers are used when elements from unrelated or
secondary disciplines are shown for clarity or reference on the same drawing. Drawing
elements from secondary disciplines should be placed on one layer, named with the
applicable special modifier. For example: The layer A-MECH in an architectural plan
contains mechanical elements shown for clarity or for information only in the
architectural plan. In this case, the mechanical information does not need to be separated
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 9 of 36
by layer, since the drawing is primarily architectural. In similar situations, these
modifiers may be used as needed with other major groups. Note that using these special
"group" modifiers does not preempt the proper application of appropriate layer names to
separate drawing elements within each discipline.
7. Egress Plans: For layer naming and standards for evacuation route diagrams please refer
to the MIT Design Standards Signage Thematic Folder.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 10 of 36
Attributes (Colors, Linetypes, Pens, etc.):
1. General: Many of the layers found in the Standard Layer Listing (Section 2.3.6) have
been assigned specific attribute values by MIT according to the following categories:
color, pen weight, and linetype. All attributes shall be defined on layer 0 (zero).
Attributes that have not been pre-defined by MIT may be assigned at the discretion of the
user.
2. Colors: Specific colors must be used for the layers and annotation layers most often
used to assist space documentation. The color assignment of these layers can be found in
the Standard Layer Listing. Entity colors shall be defined by layer, not by entity. Layer
colors shall fall in the range of color numbers 1-15. All other layers may have their
colors assigned at the discretion of the client.
a. As a general rule for all projects, drawing entities should assume the color property
of the layer on which they reside. This means that the color of individual entities
should be assigned ‘by layer’ as opposed to ‘by entity.’ Entities which have been
translated from other systems may fail to meet this requirement.
1. For most MIT Renovation and Space Change projects (small to medium size projects),
the MIT CAD layering standard should suffice as is. In certain cases the layering
standards may require modification to accommodate special project requirements. For
example, large MIT capital projects or facilities drawings developed for special projects
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 11 of 36
often present unique circumstances, requiring special considerations for CAD
requirements.
2. Modifications to or deviations from the layering standards as published in this document
must be pre-approved by a member of MIT’s Facility Information Systems (FIS). Any
special CAD requirements should be addressed at a joint meeting between the parties
involved, prior to the development of CAD drawings for the project; otherwise the
standards and guidelines in this document apply. Any changes need to be documented
and submitted to FIS for approval.
The following layer list is an example of commonly used NCS layer names along with additional
MIT specific layer names (marked with a * in the left hand column). Where MIT specific
layer names differ from NCS, MIT layer names shall be used. For additional detail, beyond what
is outlined herein, please refer to the National CAD Standard for guidance.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 12 of 36
* A-DOOR-EXST Existing Doors 1-red Continuous
A-DOOR-IDEN Door Identification 2-yellow Continuous
A-EQPM Equipment 6-magenta Continuous
A-EQPM-IDEN Equipment Identification 2-yellow Continuous
A-FLOR Floor Information – Finishes Continuous
A-FLOR-EVTR Elevators 2-yellow Continuous
* A-FLOR-EVTR-EXST Existing Elevators 1-red
A-FLOR-STRS Stairs and Ladders 2-yellow Continuous
* A-FLOR-STRS-EXST Existing Stairs and Ladders 1-red
A-FLOR-CSWK Casework, Cabinets, Counters 6-magenta Continuous
A-FLOR-OVHD Overhead Skylights and Overhangs Continuous
* A-FLOR-SILL Door Sills 5-blue Continuous
* A-FLOR-PATT Floor Hatching/Patterns 5-blue Continuous
* A-FLOR-TEXT-DEMO Demolition Plan Text 7-white Continuous
A-FLOR-TEXT Floor Plan Text 7-white Continuous
A-FLOR-DIMS Floor Plan Dimensions (Lines/Text) 1/7- Continuous
red/white
A-FLOR-SYMB Floor Symbols (Section, Detail, & 4-cyan Continuous
Elevation Marks)
* A-FLOR-MECH Floor Plan Mechanical Elements 9-light gray Continuous
* A-FLOR-ELEC Floor Plan Electrical Elements 9-light gray Continuous
A-FURN Furniture Layouts 5-blue Continuous
A-FURN-IDEN Furniture Identification 2-yellow Continuous
A-GLAZ Windows 2-yellow Continuous
* A-GLAZ-DEMO Demolished Windows 1-red Dashed
* A-GLAZ-EXST Existing Windows 1-red Continuous
* A-GLAZ-SILL-EXST Existing Window Sill 1-red Continuous
A-GLAZ-SILL New Window Sill 2-yellow Continuous
A-GLAZ-PRHT Partial Height Windows and Glazed 1-red Continuous
Partitions
A-GLAZ-IDEN Window Identification 2-yellow Continuous
A-WALL Full Height Walls 4-cyan Continuous
* A-WALL-DEMO Demolished Walls 1-red Dashed
* A-WALL-EXST Existing Walls 1-red Continuous
A-WALL-PRHT Partial Height Walls 2-yellow Continuous
A-WALL-MOVE Moveable Wall Partitions 2-yellow Continuous
A-WALL-HEAD Door and Window Headers 15-brown Continuous
A-WALL-JAMB Door and Window Jambs 2-yellow Continuous
A-WALL-PATT Wall Hatching/ Poché 8-gray Continuous
A-WALL-CNTR Wall Centerlines 5-blue Continuous
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 13 of 36
A-WALL-IDEN Wall Identification 2-yellow Continuous
* A-WALL-SHFT Service Shafts (hidden lines) 5-blue Hidden
* A-WALL-MATL Wall Panels or Surface Materials 5-blue Continuous
* A-ELEV-FINE Elevation Linework – Fine 5-blue Continuous
* A-ELEV-LITE Elevation Linework – Light 1-red Continuous
* A-ELEV-MEDM Elevation Linework – Medium 2-yellow Continuous
* A-ELEV-HEVY Elevation Linework – Heavy 4-cyan Continuous
* A-ELEV-TEXT Elevation Text 7-white Continuous
* A-ELEV-DIMS Elevation Dimensions 1/7- Continuous
red/white
* A-ELEV-SYMB Elevation Symbols 4-cyan Continuous
* A-SECT-FINE Section Linework – Fine 5-blue Continuous
* A-SECT-LITE Section Linework – Light 1-red Continuous
* A-SECT-MEDM Section Linework – Medium 2-yellow Continuous
* A-SECT-HEVY Section Linework – Heavy 4-cyan Continuous
* A-SECT-TEXT Section Text 7-white Continuous
* A-SECT-DIMS Section Dimensions 1/7- Continuous
red/white
* A-DETL-FINE Detail Linework – Fine 5-blue Continuous
* A-DETL-LITE Detail Linework – Light 1-red Continuous
* A-DETL-MEDM Detail Linework – Medium 2-yellow Continuous
* A-DETL-HEVY Detail Linework – Heavy 4-cyan Continuous
* A-DETL-TEXT Detail Text 7-white Continuous
* A-DETL-DIMS Detail Dimensions 1/7- Continuous
red/white
* A-SCHD-LITE Schedule Linework – Light 1-white Continuous
* A-SCHD-HEVY Schedule Linework – Heavy 4-cyan Continuous
* A-SCHD-TEXT Schedule Text 7-white Continuous
* A-XREF External References Continuous
* A-MTCH Match Lines (Polylines) 6-magenta Continuous
* A-VIEW Paper Space Viewports Continuous
* A-TEXT General Notes and Specifications 7-white Continuous
* A-SHBD Sheet Border and Title Block (Polylines) 6-magenta Continuous
* A-REVC Revision Clouds (Polylines) 6-magenta Continuous
Civil and Site
C-BLDG MIT Building Footprints
* C-BLDG-DOCK MIT Loading Docks
C- PRCH MIT Porches
C-DECK MIT Decks
C-BLDG-IDEN MIT Building Identification
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 14 of 36
* C-BLDG-OTHR Other Building Footprints
C-BLDG-OTHR-IDEN Other Building Identification
C-PRKG Parking Lots
C-PRKG-IDEN Parking Lot Identification
C-ROAD Paved Roads
C-ROAD-UPVD Dirt Roads
C-DRIV Driveways
C-ROAD-CURB Curbs
C-ROAD-EQPM Road Apparatus - Traffic Lights etc.
C-ROAD-IDEN Road Identification
C- BRDG Bridges
C- BRDG-IDEN Bridge Identification
C-RAIL Railroad Tracks
C-RAIL-EQPM Railroad Apparatus - Crossing Gates etc.
C-RAIL-IDEN Railroad Identification
C-STRM Storm Drainage Lines
* C-STRM-EQPM Storm Drainage Equipment
* C-STRM-MHOL Storm Drainage Manholes
C-STRM-CBSN Storm Drainage Catch Basins
C-STRM-IDEN Storm Drainage Identification
C-SSWR Sanitary Sewer Lines
* C-SSWR-EQPM Sanitary Sewer Equipment
C-SSWR-MHOL Sanitary Sewer Manholes
C-SSWR-IDEN Sanitary Sewer Identification
* C-CWTR Chilled Water Lines
* C-CWTR-EQPM Chilled Water Equipment
* C-CWTR-MHOL Chilled Water Manholes and Valve Boxes
* C-CWTR-IDEN Chilled Water Identification
C-STEM High Pressure Steam Lines
* C-STEM-EQPM High Pressure Steam Equipment
C-STEM-MHOL High Pressure Steam Manholes
* C-STEM-IDEN High Pressure Steam Identification
* C-STEM-COND High Pressure Condensate Lines
* C-STEM-COND-EQPM High Pressure Condensate Equipment
* C-STEM-COND-MHOL High Pressure Condensate Manholes
* C-STEM-COND-IDEN High Pressure Condensate Identification
* C-STMP Medium Pressure Steam Lines
* C-STMP-IDEN Medium Pressure Steam Identification
* C-DOMW Domestic Water Lines
* C-DOMW-EQPM Domestic Water Equipment
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 15 of 36
* C-DOMW-MHOL Domestic Water Manholes and Valve
Boxes
* C-DOMW-IDEN Domestic Water Identification
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 16 of 36
C- ESMT-IDEN Easement Identification
* C-PROP-PRCL Parcel Lines
* C-PROP-PRCL-IDEN Parcel Identification
* C-PROP-MNMT Property Monuments
* C-PROP-MNMT-IDEN Property Monument Identification
C-TOPO Contour Lines and Elevations
C-TOPO-SPOT Spot Elevations
* C-TOPO-BMRK Benchmarks
C-WALL-RTWL Retaining Wall
C-TOPO-IDEN Elevation Identification
* C-WATR Water Bodies - Rivers, Lakes, etc.
* C-WATR-IDEN Water Body Identification
C-GRID-MMIT MapMIT Grid
* C-GRID-MMIT-IDEN MapMIT Grid Identification
* C-GRID-MSCS Mass State Coordinate System
* C-GRID-MSCS-IDEN MSCS Identification
* C-ELEV Elevations
* C-ELEV-TEXT Elevation Text
* C-SECT Sections
* C-SECT-TEXT Section Text
* C-DETL Details
* C-DETL-TEXT Detail Text
* C-LGND Legend symbols
* C-LGND-TEXT Legend text
* C-SCHD Schedules
* C-SCHD-TEXT Schedule Text
* C-TEXT General Notes and Specifications
* C-XREF External References
* C-VIEW Paper Space Viewports
* C-SHBD Sheet Border and Title Block
Electrical
E-FIRE Fire Alarm Wiring and Conduit
* E-FIRE-DEVC Fire Alarm Devices - Miscellaneous
* E-FIRE-DEVC-MANL Fire Alarm Manual Devices - Pull Stations
* E-FIRE-DEVC-SGNL Fire Alarm Signal Devices - Horns and
Lights
E-FIRE-EQPM Fire Alarm Equipment - Panels and Boxes
* E-FIRE-SCHM Fire Alarm Schematic Diagrams
E-FIRE-IDEN Fire Alarm Identification
E-LITE Lighting Fixtures
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 17 of 36
* E-LITE-POWR Lighting Power
E-LITE-SWCH Light Switches
E-LITE-IDEN Lighting Identification
* E-EQPM-13_8 13.8KV Equipment
* E-EQPM-208V 120/208V Equipment - Switches, XFMRs,
Panels
* E-EQPM-2400 2400V Equipment
* E-EQPM-480V 277/480V Equipment
* E-POWR-13_8 13.8 KV Power Circuits
* E-POWR-13_8-IDEN 13.8KV Power Identification
* E-POWR-1LIN One Line Power Diagrams
* E-POWR-208V 120/208V Power Circuits
* E-POWR-208V-IDEN 120/208V Power Identification
* E-POWR-2400 2400V Power Circuits
* E-POWR-2400-IDEN 2400V Power Identification
* E-POWR-480V 277/480V Power Circuits
* E-POWR-480V-IDEN 277/480V Power Identification
E-COMM Communications Wiring and Conduit
E-COMM-EQPM Communications Devices and Equipment
E-COMM-IDEN Communications Identification
* E-SECR Security Wiring, Conduit
* E-SECR-EQPM Security Devices, Equipment
* E-SECR-IDEN Security Identification
E-LITE-EMER Emergency Lighting
* E-EMER-POWR Emergency Power
* E-EMER-EQPM Emergency Equipment
* E-EMER-IDEN Emergency Identification
E-CONT Electrical Controls
E-CONT-IDEN Electrical Controls Identification
E-GRND Ground System
E-GRND-IDEN Ground System Identification
* E-ELEV Elevations
* E-ELEV-TEXT Elevation Notes
* E-SECT Sections
* E-SECT-TEXT Section Notes
* E-DETL Details
* E-DETL-TEXT Detail Notes
* E-SCHD Schedule Lines
* E-SCHD-TEXT Schedule Text
* E-LGND Legend Symbols
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 18 of 36
* E-LGND-TEXT Legend Text
* E-TEXT General Notes and Specifications
* E-XREF External References
* E-VIEW Paper Space Viewports
* E-SHBD Sheet Border and Title Block
Landscape
L-PLNT Plants and Landscaping
L-PLNT-TREE Trees and Shrubs
L-PLNT-GCVR Ground Covers and Vines
L-PLNT-BEDS Rock, Bark and Landscaping Beds
L-PLNT-TURF Lawn Areas
L-PLNT-IDEN Plant and Landscaping Identification
L-IRRG Irrigation Piping
L-IRRG-SPKL Irrigation Sprinklers
L-IRRG-IDEN Irrigation Identification
L-SITE Site Improvements
* L-SITE-CONC Concrete Pads
L- FENC Fencing
L-SITE-STEP Steps
* L-SITE-SIGN Signs
* L-SITE-RAMP Handicap Ramps and Access
L-SITE-WALL Walls
L-SITE-SWLK Walkways
L-SITE-TRAL Dirt Paths
L-SITE-FURN Site Furnishings
L-SITE-SPRT Athletic Fields
L-SITE-IDEN Site Identification
* L-ELEV Elevations
* L-SECT Sections
* L-DETL Details
* L-SCHD Schedules
* L-SCHD-TEXT Schedule Text
* L-LGND Legend Symbols
* L-LGND-TEXT Legend text
* L-TEXT General Notes and Specifications
* L-XREF External References
* L-VIEW Paper Space Viewports
* L-SHBD Sheet Border and Title Block
Mechanical
M-CWTR Chilled Water Supply/Return Piping
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 19 of 36
M-CWTR-EQPM Chilled Water Equipment
* M-CWTR-PROC Secondary Chilled Water - Equipment
Cooling
M-CWTR-IDEN Chilled Water Identification
M-CNDW Condenser Water Supply/Return Piping
M-CNDW-EQPM Condenser Water Equipment
M-CNDW-IDEN Condenser Water Identification
* M-HWTR Heating Hot Water Supply/Return Piping
M-HWTR-EQPM Heating Hot Water Equipment
M-HWTR-IDEN Heating Hot Water Identification
M-REFG Refrigeration Piping
M-REFG-EQPM Refrigeration Equipment
M-REFG-IDEN Refrigeration Identification
M-STEM-HPIP High Pressure Steam Piping
M-STEM-HPIP-EQPM High Pressure Steam Equipment
M-STEM-HPIP-IDEN High Pressure Identification
M-STEM-HPIP-COND High Pressure Condensate Piping
M-STEM-HPIP-COND- High Pressure Condensate Identification
IDEN
M-STEM-MPIP Medium Pressure Steam Piping
M-STEM-MPIP-IDEN Medium Pressure Steam Identification
M-STEM-LPIP Low Pressure Steam Piping
M-STEM-LPIP-IDEN Low Pressure Steam Identification
M-STEM-LPIP-COND Low Pressure Condensate Piping
M-STEM-LPIP-COND- Low Pressure Condensate Identification
IDEN
M-STEM-LPIP-PROC Low Pressure Process Steam Piping
M-STEM-LPIP-PROC- Low Pressure Process Identification
IDEN
M-RCOV-PIPE Heat Recovery Piping
M-RCOV-EQPM Heat Recovery Equipment
M-RCOV-IDEN Heat Recovery Identification
M-FUEL-OGEP Fuel Oil Piping
M-FUEL-OGEP-IDEN Fuel Oil Identification
M-HVAC-SPLY-SDFF HVAC Supply Diffusers
M-HVAC-SPLY-DUCT HVAC Supply Ductwork
M-HVAC-SPLY-IDEN HVAC Supply Ductwork and Diffuser
Identification
M-HVAC-RETN-RDFF HVAC Return Diffusers
M-HVAC-RETN-DUCT HVAC Return Ductwork
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 20 of 36
M-HVAC-RETN-IDEN HVAC Return Duct and Diffuser
Identification
* M-HVAC-EXHS-EDFF HVAC Exhaust Diffusers
M-HVAC-EXHS-DUCT HVAC Exhaust Ductwork
M-HVAC-EXHS-IDEN HVAC Exhaust Duct and Diffuser
Identification
* M-HVAC-SUPP-1LIN HVAC Supply One-Line Ductwork
* M-HVAC-RETN-1LIN HVAC Return One-Line Ductwork
* M-HVAC-EXHS-1LIN HVAC Exhaust One-Line Ductwork
M-HVAC-EQPM HVAC Equipment
M-HVAC-EQPM-IDEN HVAC Equipment Identification
* M-HVAC-CONT HVAC Controls
* M-HVAC-CONT-IDEN HVAC Control Identification
M-CMPA Compressed Air – Mains
M-CMPA-EQPM Compressed Air Equipment
M-CMPA-IDEN Compressed Air Identification
* M-ELEV Elevations
* M-ELEV-TEXT Elevation Notes
* M-SECT Sections
* M-SECT-TEXT Section Notes
* M-DETL Details
* M-DETL-TEXT Detail Notes
* M-SCHD Schedule Lines
* M-SCHD-TEXT Schedule Text
* M-LGND Legend Symbols
* M-LGND-TEXT Legend Text
* M-TEXT General Notes and Specifications
* M-XREF External References
* M-VIEW Paper Space Viewports
* M-SHBD Sheet Border and Title Block
Plumbing
* P-FIRE Fire Protection Piping and Sprinkler Heads
* P-FIRE-EQPM Fire Protection Equipment
* P-FIRE-IDEN Fire Protection Identification
P-DOMW-CPIP Domestic Cold Water Piping
P-DOMW-HPIP Domestic Hot Water Piping
* P-DOMW-HOTR Domestic Hot Water Return Piping
P-DOMW-EQPM Domestic Water Equipment
P-DOMW-IDEN Domestic Water Identification
* P-PROC-COLD Process Cold Water Piping
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 21 of 36
* P-PROC-HOTS Process Hot Water Piping
* P-PROC-HOTR Process Hot Water Return Piping
* P-PROC-EQPM Process Water Equipment
* P-PROC-IDEN Process Water Identification
* P-RCVR Recovered Water Piping
* P-RCVR-EQPM Recovered Water Equipment
* P-RCVR-IDEN Recovered Water Identification
* P-CMPA Lab Air Piping
* P-CMPA-EQPM Lab Air Equipment
* P-CMPA-IDEN Lab Air Identification
* P-VACM Vacuum Piping
* P-VACM-EQPM Vacuum Equipment
* P-VACM-IDEN Vacuum Identification
* P-CO2S CO2 Piping
* P-CO2S-EQPM C02 Equipment
* P-CO2S-IDEN C02 Identification
* P-NIOX NO Piping
* P-NIOX-EQPM NO Equipment
* P-NIOX-IDEN NO Identification
* P-NO2S NO2 Piping
* P-NO2S-EQPM NO2 Equipment
* P-NO2S-IDEN NO2 Identification
* P-OXYG Oxygen Piping
* P-OXYG-EQPM Oxygen Equipment
* P-OXYG-IDEN Oxygen Identification
* P-NGAS Natural Gas Piping
* P-NGAS-EQPM Natural Gas Equipment
* P-NGAS-IDEN Natural Gas Identification
* P-PURE Pure Water Piping
* P-PURE-EQPM Pure Water Equipment
* P-PURE-IDEN Pure Water Identification
P-SSWR-PIPE Sanitary Waste Piping
P-SSWR-VENT Sanitary Vent Piping
* P-SSWR-INDR Indirect Waste Piping
* P-SSWR-LABS Lab Waste Piping
* P-SSWR-LABS-VENT Lab Vent Piping
P-SSWR-IDEN Sanitary Identification
P-STRM-PIPE Storm Drain Piping
P-STRM-IDEN Storm Drain Identification
* P-FIXT Plumbing Fixtures
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 22 of 36
* P-FIXT-IDEN Plumbing Fixture Identification
* P-ELEV Elevations
* P-ELEV-TEXT Elevation Notes
* P-SECT Sections
* P-SECT-TEXT Section Notes
* P-DETL Details
* P-DETL-TEXT Detail Notes
* P-LGND Legend Symbols
* P-LGND-TEXT Legend Text
* P-SCHD Schedule Lines
* P-SCHD-TEXT Schedule Text
* P-TEXT General Notes and Specifications
* P-XREF External References
* P-VIEW Paper Space Viewports
* P-SHBD Sheet Border and Title Block
Structural
S-COLS Columns
S-GRID Column Grid
S-GRID-DIMS Column Grid Dimensions
S-GRID-IDEN Column Grid Identification
S-WALL Structural or Bearing Walls
* S-FRAM Framing
S-BEAM Beams
S-DECK Decking
S-FNDN Foundation
S-FNDN-PILE Foundation Piles
S-FNDN-PIER Foundation Piers
S-FNDN-RBAR Foundation Reinforcement
* S-METL Miscellaneous Metal
* S-ELEV Elevations
* S-ELEV-TEXT Elevation Notes
* S-SECT Sections
* S-SECT-TEXT Section Notes
* S-DETL Details
* S-DETL-TEXT Detail Notes
* S-SCHD Schedule Lines
* S-SCHD-TEXT Schedule Text
* S-LGND Legend symbols
* S-LGND-TEXT Legend text
* S-TEXT General Notes and Specifications
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 23 of 36
* S-XREF External References
* S-VIEW Paper Space Viewports
* S-SHBD Sheet Border and Title Block
MIT recognizes that many of its vendors do not use the same version of design software to
produce plans for their projects. However, MIT requires that service providers who work with
other file formats submit DWG formatted CAD files upon project closeout that are fully
compliant with all of the standards outlined herein, and which have no significant loss of drawing
entities or project data that can result from standard CAD file translation procedures.
Projects using Building Information Modeling (BIM) software are still required to produce DWG
and PDF/TIF formats for their projects. The use of the National CAD Standard will help
facilitate the production of properly formed DWG files.
For firms translating their native CAD file format into DWG format concerned about delivering
error-free CAD files to MIT upon project closeout, it is strongly recommended that thorough file
translation testing be conducted before the drawing development phase of the project. This will
assure early detection of file conversion issues, if any, and allow for corrective measures to be
taken before the project closeout period. DXF files will not be accepted at project closeout as a
substitution for DWG file deliverables.
All DWG files and CAD drawing entities submitted at the end of a project must be able to be
manipulated using standard AutoCAD® drafting procedures. Files with proprietary features from
other AutoCAD add-ons will not be accepted. Non-compliance with this policy will result in the
rejection of DWG files submitted at project closeout in addition to delayed rendering of final
project payment.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 24 of 36
3. USE OF BUILDING INFORMATION MODELING
(BIM)
Many projects are utilizing Building Information Modeling (BIM) for design and construction
projects at MIT. While this practice is encouraged, the 2D deliverables are still required as
outlined in this guideline and as specified in MIT contracts.
Refer to the BIM Execution Plan Thematic Folder. Document is to be completed by project
teams as indicated.
Projects using BIM are required to use the MIT BIM Execution Plan to document modeling
practices. This document declares what is being modeled, the accuracy of the models, the intent
of the models, and how project teams work within the models. Software platforms and
procedures are also outlined and agreed upon in this document.
The MIT BIM Execution Plan template is available upon request to fis-request@mit.edu.
There are a number of evolving standards for the use of BIM. Since no one standard can be
applied to all types of MIT projects, it is recommended that modeling practices and standards be
declared and agreed upon in the project’s BIM Execution Plan (BEP).
Currently MIT is working on its internal BIM standards, but until the standard is
complete the use of IFC and the creation of IFC compliant models is highly
recommended. Information about IFC can be found at the BuildingSMART Alliance
website at: http://www.nibs.org/
If other BIM standard is being used for a project, for example OmniClass, it must be
declared and agreed upon in the project’s BIM Execution Plan before the start of the
project.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 25 of 36
3.4 BIM Models and Deliverables
Models turned over to MIT as a deliverable must meet the requirements of the agreed upon MIT
BIM Execution Plan. Internally, MIT has standardized its BIM environment on Autodesk’s
BIM platform and models created for projects are expected to work within MIT’s CAD/BIM
environment.
1. It is recommended that models are created in the most current versions of Autodesk Revit
or Autodesk NavisWorks. Modeling practices are declared in the project’s BIM
Execution Plan and best practices for model creation include, but are not limited to:
2. Naming conventions of models delivered to MIT should closely follow the naming
conventions outlined in File Organization and Transmittal to MIT below.
1. It is understood that different disciplines require the use of different types of software.
These software packages need to be declared in the BIM Execution Plan and their use
must result in the creation of proper 2D products and with models that can be used.
BIM Deliverables:
1. Its MIT’s philosophy that the use of BIM will assist in the creation accurate deliverables
as outlined in this document. When models are considered as part of the deliverable and
conform to the projects BIM Execution Plan, the MIT BIM Execution Plan itself is
considered a required deliverable. Models created with the use of BIM also need to be
outlined in the Electronic File Index listed in Appendix A.
The intent of requiring Archival Print Files is to receive a file of sufficient detail to recreate 100%
of the information contained in the hard copy original, without creating an excessively large
digital file. Every sheet in the record or construction drawings needs to have a corresponding
(1:1) Archival Print File. These files must be either PDF or TIF formats and they may be
produced either directly from CAD/BIM applications or from a scanned hard copy (PLT files and
other print file formats will not be accepted).
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 26 of 36
Regardless of production method, the Archive Print Files must match the content of the materials
being submitted at closeout. The names of these files must also be the same as the DWG files
they represent, therefore multipage TIF/PDF files will not be accepted. All Archival Print Files
must follow these production requirements and must be listed with their DWG counterparts in the
Electronic File Index listed in Appendix A.
1. PDF files from DWG files must mirror the color and line thickness that were represented
by the print products. To create these files, the same print settings should be used to
generate the PDF files. Unless colors are used in the files, PDF files with AutoCAD
layer colors instead of their line settings will not be accepted since this is not a true
representation of the project documentation.
1. When possible, PDF files should be in vector format to provide crisp line work for
drawings. Files needing to be rasterized or scanned may be produced in PDF format and
should be created at a resolution of 300dpi or higher. A 24 by 36 inch original at 300dpi
will result in an image 7,200 pixels by 10,800 pixels, but higher resolution can be used if
300dpi does not accurately reproduce all content in ad drawings. Do not adjust paper
settings to achieve 300dpi.
BIT Depth:
1. Images encapsulated in PDF files should be created with a bit depth that is appropriate
for the drawings they represent. Embedded images may be either compressed using
LZW lossless compression or uncompressed. The figure below shows suggested settings
for drawings with rasterized features:
Bit Depth
May not be used for images created by scanning
Black and
1-bit hard copy, only to be used in circumstances where
White
there will be no loss of information.
Grayscale 8-bit Sheets in which no color is used.
8-bit or Sheets in which color is used to differentiate
Color
greater content.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 27 of 36
4.2 TIF File Creation
1. Generating TIF files by scanning the hard copy drawing are accepted. Please refer to the
Bit Depth table above for appropriate resolutions and bit depths. JPG files will not be
accepted in place of TIF or PDF files.
1. Creation of TIF files directly from AutoCAD® is not recommended. PDF files are the
preferred file format when producing Archival Print Files from CAD/BIM software.
1. Converting to TIF from other image file formats, the format being converted from must
be a lossless format like PNG or GIF. Firms should not convert from a file format that
uses lossy compression, such as JPEG, due to degradation of the image. Images should
not be resampled in order to increase resolution to 300dpi.
MIT requires that for each sheet submitted as a project deliverable there is a corresponding DWG
and Archive Print File (PDF or TIF). The sheet and the digital files should follow the same
naming convention. Each print file’s name should have the same name as its source DWG file.
Larger Capital Projects should use the following sheet identification format. It is a consistent
format that contains five alphanumeric characters in a specific sequence conveying meaningful
information to both the drawing creator and user. The sheet identifier consists of three
components: the discipline designator, the sheet type designator, and the sheet sequence.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 28 of 36
Discipline Designators:
1. The discipline designator consists of one alphabetical character and a hyphen or two
alphabetical characters. The codes used for the discipline designator are listed in the
Layer Naming Convention. The discipline designator identifies the sheet as a member of
a particular genre of drawings and is one character. For more specific genres, such as
security (SC) or audio visual (AV) drawings, creators can use a two-character designator.
Not all type designators are required. The standard also does not prohibit combining
different types of drawings onto the same sheet. Basic discipline designators are listed
below:
1. Sheet type designators consist of one numeric character. The sheet type designator refers
to the type of information displayed in the drawing.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 29 of 36
Sheet Sequence Numbers:
1. Sheet sequence numbers consists of two numeric characters in sequential order from 00
through 99. Example: Second floor plan - A102.
In order to keep track of materials submitted to MIT, a clear catalog of information needs to
accompany the materials submitted to MIT. This includes materials on a disk, files conformation
to a naming convention, CD/DVDs produces in a orderly way, and an index sheet naming each
file and its description.
File Names:
1. MIT has its own file naming convention for archival purposes to make file easily
identifiable to users. Though this naming convention is not required, it is good to be
aware of the nomenclature used for archiving. Naming convention for MIT’s archiving
system is as follows:
a. File: MIT_MG02_02145_A_AB_A-102.DWG
b. Convention: [campus]_[building #]_[MIT project #]_[discipline]_
[phase]_[sheet #].[extension]
c. Description: From the MIT campus, Main Group building 2, project number
02145 and is an architectural as-built, sheet A-102.
2. Please refer to the MIT Archiving Guidelines for other best practices when organizing
project information.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 30 of 36
File Transmittal:
1. The content of electronic drawings must match the delivered original hard copy set
exactly. To ensure the integrity of the electronic drawing set upon delivery to MIT:
a. Ensure the drawings adhere to the guidelines presented in this document. Review
the procedures for preparing drawings for submittal as detailed in the preceding
paragraphs.
b. Include a digital copy transmittal PDF with all submittals indicating MIT Project
number, MIT Project name (if applicable) and complete listing of all filenames
and sheet numbers. Please use the “Electronic Filing Index’ template when
submitting documentation.
c. Submit Adobe PDF’s or TIF’s of the sheets, with file names corresponding to
names of DWG files.
d. Submit all digital files on thumb drive, portable hard drives, CD-ROM or DVD-
ROM to the MIT project manager. If external ftp or file transfer site is being
used, please notify FIS.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 31 of 36
APPENDIX A: BIM EXECUTION PLAN
Refer to the BIM Execution Plan Thematic Folder. Please use the MIT BIM Execution Plan for
all project utilizing building information modeling. This template can be requested at fis-
request@mit.edu.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 32 of 36
APPENDIX B: GLOSSARY OF TERMS
The definitions below have been gathered from a variety of sources including online documents,
the American Institute of Architects and MIT Staff.
As-Built Drawings:
As-built drawings are prepared by the contractor. They show, in red ink, on-site changes to the
original construction documents. This set of drawings depicts the actual conditions of the
completed construction “as it was built”.
Basis of Design:!
The basis of design is the documentation of the primary thought processes and assumptions
behind design decisions that were made to meet the Owner’s Project Requirements. The basis of
design describes the systems, components, conditions and methods chosen to meet the intent.
Some reiterating of the Owner’s Project Requirements may be included.
Bid Documents:
Documents required to be submitted in response to an Invitation To Bid (ITB). These include the
prescribed bid form, drawings, specifications, time lines, charts, price breakdowns, etc.
Commissioning Plan:!
An overall plan, developed before or after bidding, that provides the structure, schedule and
coordination planning for the commissioning process.!
Construction Drawings:
Drawings that provide all the necessary information, both graphic and written, to build the
project. These drawings provide specific, detailed information regarding walls, doors, furniture,
equipment, lighting, outlets, and so on.
Design Drawings:
Technical drawings used to fully and clearly define requirements for engineered items so that
they may conform to the design aesthetic. The purpose of such a drawing is to accurately and
unambiguously capture all the geometric features of a product or a component that will allow a
manufacturer to produce that component.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 33 of 36
A final summary report by the Commissioning Authority provided to the Owner, focusing on
evaluating commissioning process issues and identifying areas where the process could be
improved. All acquired documentation, logs, minutes, reports, deficiency lists, communications,
findings, unresolved issues, etc., are compiled in appendices and provided with the report!
O&M Manuals:
Operational and Maintenance Manuals include equipment specifications and schedules, drawings
and overall information needed to maintain installed equipment.
Record Drawings:
Record drawings are prepared by the architect and reflect on-site changes the contractor noted in
the as-built drawings. They are often compiled as a set of on-site changes made for the owner per
the owner-architect contract.
Shop Drawings:
A drawing or set of drawings produced by the contractor, supplier, manufacturer, subcontractor,
or fabricator typically required for pre-fabricated components.
Sketches:
A simple, technical drawing created to isolate a particular engineering/architectural item and
provide specific requirements related to that item.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 34 of 36
Specifications:
Specific qualitative statements of particular needs to be satisfied, or essential characteristics that a
customer requires (in a good, material, method, process, service, system, or work) and which a
vendor must deliver. They are usually written in a manner that enables all parties to measure the
degree of conformance.
Submittals:
Product data submittals, samples, and shop drawings are required primarily for the architect and
engineer to verify that the correct products will be installed on the project. This process also
gives the architect and sub-consultants the opportunity to select colors, patterns, and types of
material that were not chosen prior to completion of the construction drawings. !
Survey Drawings:
A CAD plan prepared by a licensed surveyor, which shows all essential measurements taken in
the survey. Each survey drawing will be tied into the MIT control network and be submitted in
NAD 83 feet.
!
Systems Manual:!
The Systems Manual expands the scope of the traditional operating and maintenance
documentation to include the additional information gathered during the Commissioning Process
and to provide a systems-based organization of information. The Systems Manual is intended to
be useful in the day-to-day operations of a facility. !
Working Drawings:
A complete set of plans and specifications showing and describing all phases of a project,
architectural, structural, mechanical, electrical, civil engineering, and landscaping systems to the
degree necessary for the purposes of accurate bidding by contractors and for the use of artisans in
constructing the project.
!
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 35 of 36
APPENDIX C: ELECTRONIC FILE INDEX
All electronic materials (CAD files, PDF and TIF files, index table files, etc.) must be delivered
on a CD or DVD, formatted using Windows XP or higher. Indices for files must be submitted in
both paper format and electronically in Microsoft Excel 2003 or higher. Indices must follow a
format similar to the sample shown below. This template can be requested at fis-
request@mit.edu.
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder Page 36 of 36
!
MIT
Design Standards
BIM Execution Plan
Thematic Folder
May 2018
!
!
!
!
!
!
!
"#$%&'!()$!'*'+,-)./!%&#/!#/0!1'2,)1'$'/-"!
!
$)-!%345678!/9:6!
!$)-!%345678!/;:<63!
!
!
"#$#%&'#"!()!*&%%+,&-+.(&)!/(.0!
!
!
+4=>83;78?4=!+4:@9=A!
!
#37B?8678!
!
+)"!
!
'=C?=663!
!
!
!
-#(&'!.D!+./-'/-"!
"#! $%&!'(')*+%,-!./0-!,1'21%'3! 4!
5#! .2,6')+!%-7,2&0+%,-! 8!
9#! :';!.2,6')+!),-+0)+<! =!
>#! .2,6')+!?,0/<@$%&!*<'<! A!
>#"! &06,2!$%&!?,0/<@,$6')+%1'<! A!
>#5! $%&!*<'<! A!
>#9! $%&!*<'<!0-0/;<%<!3,2:<B''+! A!
!
"G#"! ,1'20//!<+20+'?;!7,2!F*0/%+;!),-+2,/!@!F*0/%+;!),-+2,/!)B'):<! "=!
"G#5! &,E'/!0))*20);!0-E!+,/'20-)'<! "A!
!
!
EF ()$!'*'+,-)./!%&#/!.G'1G)'H!
!
"#!$%&&'$$(%))*!+,-)','./!0%+)1+.2!3.(#4,5/+#.!6#1')+.2!70368!#.!5!-4#9'&/:!/;'!-4#9'&/!/'5,!;5$!1'<')#-'1!/;+$!
1'/5+)'1!036!=4#9'&/!>?'&%/+#.!=)5.@!";'!036!=4#9'&/!>?'&%/+#.!=)5.!1'(+.'$!%$'$!(#4!036!#.!/;'!-4#9'&/!7'@2@!
1'$+2.!5%/;#4+.2:!&#$/!'$/+,5/+.2:!5.1!1'$+2.!&##41+.5/+#.8:!5)#.2!A+/;!5!1'/5+)'1!1'$+2.!#(!/;'!-4#&'$$!(#4!
'?'&%/+.2!036!/;4#%2;#%/!/;'!-4#9'&/!)+('&*&)'@!!
!!
";+$!+$!5)$#!5!-+)#/!%$'!#(!036!5/!63"!A;'4'!/;'!&)+'./!+$!'.252'1!+.!/;'!036!-4#&'$$!5)#.2$+1'!/;'!1'$+2.!5.1!
&#.$/4%&/+#.!/'5,$@!
!
";'4'!A+))!B'!$+?!+./'4)+.C'1!036!(+)'$!B*!/;'!1'$+2.!/'5,D!5.!>?+$/+.2!E#.1+/+#.$FG4&;+/'&/%45)!H'$+2.!6#1')!B*!
GIEJK!6'&;5.+&5):!=)%,B+.2:!>)'&/4+&5):!E#,,%.+&5/+#.$:!5.1!G&&'$$!E#./4#)!,#1')$!B*!>LM@K!5.1!/;'.!5!
E##41+.5/+#.!6#1')!B*!ENLO@!";'!1'$+2.!,#1')$!A+))!B'!+.!I'<+/!G4&;+/'&/%4'!PQRQ@!";'!E##41+.5/+#.!6#1')!A+))!
B'!+.!L5<+$A#4C$@!!
!
!
!
IF %1.J'+-!)/D.1$#-)./!
!
R@ =4#9'&/!NA.'4D!63"!
P@ =4#9'&/!L5,'D!63"!SR!I'.#<5/+#.!=4#9'&/!
T@ =4#9'&/!U#&5/+#.!5.1!G114'$$D!TQV!6',#4+5)!H4+<':!E5,B4+12':!6G!QPRTW:!XOG!
Y@ E#./45&/!"*-'FH')+<'4*!6'/;#1D!
V@ =4#9'&/!H'$&4+-/+#.D!65$$5&;%$'//$!3.$/+/%/'!#(!"'&;.#)#2*!0%+)1+.2!SZR!&#.$/4%&/+#.!$'4<+&'$!(#4![QQ!,+))+#.:!
RWV:QQQ!$(!1'$+2.FB%+)1!4'.#<5/+#.!5.1!4'$/#45/+#.!#(!$'<'.Z$/#4*:!;+$/#4+&!7R\QQ$8!4'$+1'.&'!;5)):!+.&)%1+.2!
&#,,#.!54'5$:!1+.+.2!4##,:!C+/&;'.:!5.1!)#BB*K!$&#-'!#(!A#4C!A+))!+.&)%1'!4'&#.(+2%45/+#.!#(!1#4,+/#4*!
4##,$:!GHG!&#,-)+5.&'!%-2451'$:!5.1!5))!.'A!)+('Z$5('/*!5.1!6F>F=!$*$/',$K!$+/'!+$!+.!5!;+2;Z-4#(+)'!)#&5/+#.!
#.!65$$5&;%$'//$!G<'.%':!4']%+4+.2!'?/'.$+<'!)#2+$/+&5)!&##41+.5/+#.K!-4#9'&/!+$!/542'/+.2!U>>H^!O+)<'4!
E'4/+(+&5/+#.!
_@ =4#9'&/!L%,B'4$!
!
.2,6')+!%-7,2&0+%,-! -*&$'2! !
63"!=4#9'&/!L%,B'4! Q`Q_T! !
!
ENLO"IXE"3NL!=4#9'&/!L%,B'4! Q\QR\T! !
GIEJ3">E"XIGU!=4#9'&/!L%,B'4! ! !
!
>LM3L>>I3LM!=4#9'&/!L%,B'4! P\VW@QY! !
!
! !
!
`@ =4#9'&/!O&;'1%)'F=;5$'F6+)'$/#.'$!
!
.2,6')+!.B0<'!@!! '<+%&0+'E! '<+%&0+'E! .2,6')+!<+0:'B,/E'2<!
&%/'<+,-'! <+02+!E0+'! ),&./'+%,-!E0+'! %-1,/1'E!
>?+$/+.2!&#.1+/+#.$!
PFRQFPQQW! RPFRFPQRQ! NA.'4:!GF>:!$%BZ&#.$%)/5./$:!E6!
1#&%,'./5/+#.!
EH!)'<')!,#1')!A+/;!,59#4!GF6>=!
WFQRFPQQW! RPFRWFPQQ\! GF>!
&##41+.5/+#.!
E#./45&/#4!&##41+.5/+#.!
_FR`FPQRQ! WFRPFPQRQ! E6:!$%B&#./45&/#4$!
+,-)','./'1!+./#!,#1')@!
3.-#45/'!5$ZB%+)/!+.(#4,5/+#.!
WFRPFPQRQ! RRFRRFPQRQ! E6:!$%B&#./45&/#4$!
+./#!,#1')!
!
! ! !
!
!
!
KF L'M!%1.J'+-!+./-#+-"!
!
2,/'! ,2?0-%D0+%,-! ),-+0)+!-0&'! /,)0+%,-! 'H&0%/! .B,-'!
=4#245,!65.52'4! 63"!!!!!!!!!!!!!! !O#.+5!I+&;541$! L>Y\! ! !
=4#9'&/!65.52'4! ENLO! a#'!O,+/;! 0#$/#.! ! !
O'.+#4!G$$#&+5/'! GIEJ! a5,'$!O,+/;! 0#$/#.! ! !
65.52'4!b3O! 63"! 6+&;5')!=54C+.! L>Y\! ,-54C+.c-)5./@,+/@'1%! _R`@PVP@RVYY!
d+4/%5)!E6! ENLO! a5.'!O,+/;! 0#$/#.! ! !
! >LM! a#;.!O,+/;! 0#$/#.! ! !
! >LM! a'.!O,+/;! 0#$/#.! ! !!!!!
! ! ! ! ! !
!
!
NF %1.J'+-!O.#&"P()$!,"'"!
NFE $#J.1!()$!O.#&"P.(J'+-)G'"!
!
.2%,2%+;!?,0/!E'<)2%.+%,-! .,+'-+%0/!$%&!*<'<!
J+2;! O/4'5,)+.'!6>=Fb=!&##41+.5/+#.! E)5$;!(4''!036!
6'1+%,!
>?-)#4'!;#A!$-5&'$!5.1!#B9'&/$!+.!/;'!,#1')!&5.!B'!'.4+&;'1!A+/;!15/5!+.!5!
7N-'.Z !
(5$;+#.!/;5/!1#<'/5+)$!A+/;!EGb6!5.1!EN0+'Z&#,-)+5./!15/5!&#.<'4$+#.!
>.1'18!
U#A! ! !
! ! !
!
NFI ()$!,"'"!
!
(! ./0-! (! E'<%?-! (! ),-<+2*)+! (! ,.'20+'!
O3">!X"3U3eG"3NL! 0X3UH3LM!6G3L">LGLE>!
! =INMIG663LM! (! H>O3ML!GX"JNI3LM! (! !
=UGLL3LM! OEJ>HXU3LM!
ENLO"IXE"3NL!
! O3">!GLGUfO3O! (! H>O3ML!I>d3>SO! (! ! 0X3UH3LM!OfO">6!GLGUfO3O!
OfO">6!H>O3ML!
! ! (! TH!ENNIH3LG"3NL! (! TH!ENNIH3LG"3NL! (! GOO>"!6GLGM>6>L"!
O=GE>!6GLGM>6>L"!F!
! ! ! O"IXE"XIGU!GLGUfO3O! ! H3M3"GU!bG0I3EG"3NL! !
"IGEg3LM!
U3MJ"3LMFO;51+.2! TH!ENL"INU!GLH!
! ! ! ! ! H3OGO">I!=UGLL3LM!
GLGUfO3O! =UGLL3LM!
! ! ! >L>IMfF6>=!GLGUfO3O! (! I>ENIH!6NH>U3LM! (! I>ENIH!6NH>U3LM!
EN66XL3EG"3NL!AF!
! ! (! J3O"NI3E!EN663OO3NL! (! d+4/%5)!6#&C%-! ! !
5.1!63"!EN66XL3"f!
ENH>:!U>>H!
! ! ! ! ! ! !
>dGUXG"3NL!
! YH!6NH>U3LM! (! YH!6NH>U3LM! (! YH!6NH>U3LM! ! YH!6NH>U3LM!
! ENO"!>O"36G"3NL! ! ENO"!>O"36G"3NL! ! ENO"!>O"36G"3NL! ! ENO"!>O"36G"3NL!
>h3O"3LM!ENLH3"3NLO! >h3O"3LM!ENLH3"3NLO! >h3O"3LM!ENLH3"3NLO! >h3O"3LM!ENLH3"3NLO!
! (! (! (!
6NH>U3LM! 6NH>U3LM! 6NH>U3LM! 6NH>U3LM!
!
NFK ()$!,"'"!#/#&M")"!H.1L"Q''-!
!
";'!036!X$'$!G.5)*$+$!S#4C$;''/!A+))!$-'&+(+&5))*!+1'./+(*!+,-#4/5./!+.(#4,5/+#.!(#4!/;'!1'<')#-,'./!#(!
/;'!&;#$'.!036!X$'$!+.!5.!#425.+i'1!A5*!/#!+.&4'5$'!'((+&+'.&*!5.1!&#))5B#45/+#.@!!";'!A#4C$;''/!&5.!
!
B'!(#%.1!+.!G--'.1+?!jj@
!
!
RF .1O#/)S#-)./#&!1.&'"P"-#DD)/O!
!
! ! ! ! !
!
jG4&;+/'&/%45)!5.1!6>=!,#1')$!54'!$'-545/'!B%/!)+.C'1@!
!
!
-*&$'2!,7!
'<+%&0+'E!
$%&!*<'! ,2?0-%D0+%,-! +,+0/!<+077! /,)0+%,-I<J! /'0E!),-+0)+!
<+077!B,*2<!
7,2!$%&!*<'!
>?+$/+.2!6#1')! E#./45&/#4!G! ! ! ! !
! ! ! ! ! !
! ! ! ! ! !
!
!
!
TF $.0'&!-1#/")-)./!%1.+'""!0)#O1#$!
!
=4#<+1'!,#1')!/45.$+/+#.!-4#&'$$!1+5245,!(#4!'5&;!036!,#1')@!";+$!-4#&'$$!1+5245,!A+))!-4#<+1'!5!1'/5+)'1!-)5.!(#4!
'?'&%/+#.!#(!'5&;!036!,#1'):!B%+)1+.2!/;'!(#%.15/+#.!(#4!/;'!'./+4'!'?'&%/+#.!-)5.@!G!$5,-)'!1+5245,!7$''!B')#A8!
+$!5<5+)5B)'!(#4!1#A.)#51!5/!;//-DFF(+$@,+/@'1%F4'$#%4&'$F2%+1')+.'$@;/,)@!7=)'5$'!.#/'!/;5/!/;+$!+$!5!$5,-)'!
1+5245,!5.1!$;#%)1!B'!,#1+(+'1!B5$'1!#.!-4#9'&/!$-'&+(+&!+.(#4,5/+#.!5.1!4']%+4','./$8@!
TFE .G'1G)'H!0)#O1#$!!
!
!
UF ()$!)/D.1$#-)./!'*+Q#/O'"!
!
6#1')!')','./$!B*!1+$&+-)+.':!)'<')!#(!1'/5+):!5.1!5.*!$-'&+(+&!5//4+B%/'$!+,-#4/5./!/#!/;'!-4#9'&/!54'!1#&%,'./'1!
%$+.2!+.(#4,5/+#.!'?&;5.2'!A#4C$;''/@!O''!E;5-/'4!b#%4D!H'(+.+.2!/;'!I']%+4','./$!(#4!3.(#4,5/+#.!>?&;5.2'$!+.!
/;'!036!=4#9'&/!>?'&%/+#.!=)5..+.2!M%+1'!(#4!1'/5+)$!#.!&#,-)'/+.2!/;+$!/',-)5/'@!
UFE &)"-!.D!)/D.1$#-)./!'*+Q#/O'!H.1L"Q''-"!!
!
";'!(#))#A+.2!+$!5!)+$/!#(!/;'!3.(#4,5/+#.!>?&;5.2'!S#4C$;''/$!/;5/!&5.!B'!(#%.1!+.!G--'.1+?!jj@!
!
";'!(#))#A+.2!54'!'?5,-)'$@!6#1+(*!(#4!$-'&+(+&!-4#9'&/@!O#,'!3.(#4,5/+#.!>?&;5.2'$!,5*!.''1!/#!B'!4',#<'1:!
A;+)'!$#,'!3.(#4,5/+#.!>?&;5.2'$!,5*!.''1!/#!B'!511'1@!!
!
• >?+$/+.2!E#.1+/+#.$!6#1')+.2!
• E#$/!>$/+,5/+#.!
• YH!6#1')+.2!
• =4#245,,+.2!
• O+/'!G.5)*$+$!
• H'$+2.!I'<+'A$!
• H'$+2.!G%/;#4+.2!
• >.'42*!G.5)*$+$!
• O/4%&/%45)!G.5)*$+$!
• U+2;/+.2!G.5)*$+$!
• TH!E##41+.5/+#.!
• O+/'!X/+)+i5/+#.!=)5..+.2!
• TH!E#./4#)!5.1!=)5..+.2!
• I')!6#1')+.2!
• 65+./'.5.&'!O&;'1%)+.2!
• 0%+)1+.2!O*$/',!G.5)*$+$!
!
UFI $.0'&!0'D)/)-)./!H.1L"Q''-!
!
7G//5&;!6#1')!H'(+.+/+#.!S#4C$;''/8!
!
!
!
VF ()$!#/0!D#+)&)-M!0#-#!1'2,)1'$'/-"!
!
63"!$''C$!/#!%$'!/;+$!,#1')!-4#&'$$!/#!'?-)#4'!;#A!63"!O-5&'!G&&#%./+.2!15/5!&5.!B'!+./'245/'1!+./#!/;'!,#1')@!
O-5&'$!$;#%)1!(#))#A!63"!$/5.1541$!5$!1'$&4+B'1!+.!/;'!63"!O-5&'!G&&#%./+.2!M%+1')+.'$!dT@Q:!5.1!15/5!$;#%)1!B'!
&4'5/'1!$#!/;5/!+/!&5.!'?-#4/!<+5!NH0E!5.1!#/;'4!$/5.1541!&#..'&/+<+/*!$/5.1541$:!$%&;!5$!5!.'A)*!','42+.2!l)+/'m!
(#4,!#(!EN0+'@!";'!63"!O-5&'!G&&#%./+.2!M%+1')+.'$!&5.!B'!(#%.1!5/!jj@!
!
";'!(#))#A+.2!+$!5!)+$/!#(!+/',$!/;5/!$;#%)1!B'!+.&)%1'1!+.!/;'!,#1')!(#4!b5&+)+/+'$!65.52','./!%$'D!
!
j!3.&)%1'!)+$/!#(!+/',$!/#!B'!+.&)%1'1!+.!/;'!,#1')!(4#,!b6!$/5.1-#+./!
!
!
WF +.&&#(.1#-)./!%1.+'0,1'"!
!
WFE +.&&#(.1#-)./!"-1#-'OM!
!
";'!-4#9'&/!/'5,!A+))!%$'!5.!b"=!$+/'!5$!5!/##)!(#4!&#,,%.+&5/+#.:!1#&%,'./!,5.52','./!5.1!/45.$('4@!!!!
WFI $''-)/O!%1.+'0,1'"!
!
.2,6')+!
&''+%-?!+;.'! 72'F*'-);! .02+%)%.0-+<! /,)0+%,-!
<+0?'!
036!I>nX3I>6>L"O!g3EgZNbb! ! ! ! 63"!
H>O3ML!ENNIH3LG"3NL! ! ! ! 63"!
ENLO"IXE"3NL!=INMI>OO!
! S''C)*:!5$!.''1'1! ! 63"!
I>d3>SO!
"#!/'5,K!"#!
)'51'4$;+-!#(!
036!H>6NLO"IG"3NL!G"!
63"!b5&+)+/+'$K! "0H! ! 63"!
EUNO>NX"!
/#!#/;'4!
5%1+'.&'$!
! ! ! ! !
!
WFK $.0'&!0'&)G'1M!"+Q'0,&'!.D!)/D.1$#-)./!'*+Q#/O'!D.1!",($)"")./!
#/0!#%%1.G#&!
!
E*'!E0+'@! -0+%1'! 7%/'!
%-7,2&0+%,-! 7%/'! 7%/'! ,-'H+%&'!@! &,E'/! &,E'/!
<+02+! 7%/'! '()B0-?'!
'()B0-?'! <'-E'2! 2')'%1'2! 72'F*'-);! 7%/'! <,7+302'!
E0+'! +;.'! +;.'!
6HO!!
7b"=!=NO"8!
I'<+/!G4&;!
>?+$/+.2!6#1')!! GIEJ! 7ENNIH3L S>>gUf! oHG">p! G4&;! @4</! @4</!
PQRQ!
G"3NL!
U>GH8!
ISO!
7b"=!=NO"8!
>.2+.''4+.2!! S>>gUf!NI! I'<+/!G4&;!
>LM! 7ENNIH3L oHG">p! 6>=! @4</! @4</!
6#1')$! ONNL>I!"0H! PQRQ!
G"3NL!
U>GH8!
OHE!
E##41+.5/+#.!
ENLO! 7b"=!=NO"8! S>>gUf! oHG">p! GF6>=! L5<+$A#4C$! @.A1! @.A1!
6#1')!
7ENNIH3L
!
G"3NL!
U>GH8!
!
WFN )/-'1#+-)G'!H.1L"%#+'!
!
";'!-4#9'&/!/'5,!$;#%)1!&#.$+1'4!/;'!-;*$+&5)!'.<+4#.,'./!+/!A+))!.''1!/;4#%2;#%/!/;'!)+('&*&)'!#(!/;'!-4#9'&/!/#!
5&&#,,#15/'!/;'!.'&'$$54*!&#))5B#45/+#.:!&#,,%.+&5/+#.:!5.1!4'<+'A$!/;5/!A+))!+,-4#<'!/;'!036!=)5.!1'&+$+#.!
,5C+.2!-4#&'$$@!H'$&4+B'!;#A!/;'!-4#9'&/!/'5,!A+))!B'!)#&5/'1@!E#.$+1'4!]%'$/+#.$!)+C'!qA+))!/;'!/'5,!B'!
&#))#&5/'1rk!3(!$#:!A;'4'!+$!/;'!)#&5/+#.!5.1!A;5/!A+))!B'!+.!/;5/!$-5&'r!S+))!/;'4'!B'!5!036!"45+)'4r!3(!*'$:!A;'4'!
A+))!+/!B'!)#&5/'1!5.1!A;5/!A+))!B'!+.!/;'!$-5&'!$%&;!5$!&#,-%/'4$:!-4#9'&/#4$:!/5B)'$:!/5B)'!&#.(+2%45/+#.r!3.&)%1'!
5.*!511+/+#.5)!+.(#4,5/+#.!.'&'$$54*!5B#%/!A#4C$-5&'$!#.!/;'!-4#9'&/@!
WFR '&'+-1./)+!+.$$,/)+#-)./!%1.+'0,1'"X!!
!
!
!
EYF 2,#&)-M!+./-1.&!
!
EYFE .G'1#&&!"-1#-'OM!D.1!2,#&)-M!+./-1.&!P!2,#&)-M!+./-1.&!+Q'+L"!
!
";'!(#))#A+.2!&;'&C$!A+))!B'!-'4(#4,'1!/#!5$$%4'!]%5)+/*!5.1!A'!A+))!$''C!/#!&5-/%4'!/;'!-4#&'$$!5$!A'!-4#&''1!
/;4#%2;!/;'!-4#9'&/@!!
!
2'<.,-<%$/'! <,7+302'!
)B'):<! E'7%-%+%,-! 72'F*'-);!!
.02+;! .2,?20&I<J!
>.$%4'!/;'4'!54'!.#!%.+./'.1'1!,#1')!
ENLO!5.1!
d3OXGU!EJ>Eg! &#,-#.'./$!5.1!/;'!1'$+2.!+./'./!;5$!B''.! I'<+/:!GHI! G/!$%B,+//5)$!
GIEJ!5.1!63"!
(#))#A'1!
H'/'&/!-4#B)',$!+.!/;'!,#1')!A;'4'!/A#!B%+)1+.2!
3L">Ib>I>LE>! &#,-#.'./$!54'!&)5$;+.2!+.&)%1+.2!$#(/!5.1!;541K! ENLO!5.1!
I'<+/:!GHI! G/!$%B,+//5)$!
EJ>Eg! /;+$!+$!)+,+/'1!+.!$&#-'!(#4!/;+$!-4#9'&/!B%/!A+))! GIEJ!5.1!63"!
,5+.)*!+.<#)<'!+./'4('4'.&'!A+/;!B%+)/!$%4(5&'$@!
>.$%4'!/;5/!/;'!036!5.1!G>E!EGHH!O/5.1541!;5<'!
O"GLHGIHO! ENLO!!5.1!
B''.!(#))#A'1!7(#./$:!1+,'.$+#.$:!)+.'!$/*)'$:! I'<+/:!GHI! G/!$%B,+//5)$!
EJ>Eg! GIEJ!5.1!63"!
)'<')$F)5*'4$:!'/&8!
H'$&4+B'!/;'!nE!<5)+15/+#.!-4#&'$$!%$'1!/#!'.$%4'!
6NH>U!
/;5/!/;'!=4#9'&/!b5&+)+/*!H5/5!$'/!;5$!.#!
3L">MI3"f! ENLO!!5.1!
%.1'(+.'1:!+.,'&/)*!1'(+.'1!#4!1%-)+&5/'1! I'<+/:!GHI! G/!$%B,+//5)$!
EJ>EgO! GIEJ!!5.1!63"!
')','./$!5.1!/;'!4'-#4/+.2!-4#&'$$!#.!.#.Z
!
&#,-)+5./!')','./$!5.1!,'&/+<'!5&/+#.!-)5.$!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
EYFI $.0'&!#++,1#+M!#/0!-.&'1#/+'"!
!
6#1')$!$;#%)1!+.&)%1'!5))!5--4#-4+5/'!1+,'.$+#.+.2!5$!.''1'1!(#4!1'$+2.!+./'./:!5.5)*$+$:!5.1!&#.$/4%&/+#.@!!U'<')!
#(!1'/5+)!5.1!+.&)%1'1!,#1')!')','./$!54'!-4#<+1'1!+.!/;'!3.(#4,5/+#.!>?&;5.2'!S#4C$;''/!+.!G--'.1+?!jj@!!
!
!
.B0<'! E%<)%./%-'! +,/'20-)'!
>?+$/+.2!$/4%&/%45)!&#)%,.$!5.1!B'5,$!A'4'!,#1')'1!#.!5.!5$!
.''1'1!B5$+$!(4#,!O"=!&#./45&/!145A+.2$!5.1!#4+2+.5)!$/4%&/%45)!
145A+.2$@!
!
b##/-4+./!#(!/;'!,5$#.4*!$/4%&/%4'!+$!5--4#?+,5/'!B5$'1!#.!$%4<'*:!
>?+$/+.2!6#1')! G4&;!
(+')1!,'5$%4','./$!5.1!#4+2+.5)!145A+.2$@!
!
U+2;/!(+?/%4'$:!-)%,B+.2!(+?/%4'$!5.1!/#+)'/!5&&'$$#4+'$!54'!
5&&%45/')*!)#&5/'1!B%/!/;'!#B9'&/$!54'!.#/!4'-4'$'./5/+<'!#(!/;'!
5&/%5)!(+?/%4'$@!!!
G))!6>=!$*$/',!&#,-#.'./$!$;5))!B'!(%))*!&##41+.5/'1!B*!/;'!
&#./45&/#4m$!-4+#4!/#!+.$/5))5/+#.@!!S;5/!+$!$-'&+(+'1!5.1!$;#A.!+.!
/;'!,#1')!+$!.#/!.'&'$$54+)*!A;5/!A+))!B'!$%B,+//'1:!5--4#<'1:!5.1!
#4!+.$/5))'1@!!H%'!/#!/;'!$&5)'!#(!/;'!145A+.2$!B+1FEH!145A+.2$!54'!
1+5245,,5/+&!+.!.5/%4'@!!";'!&4'5/+#.!#(!5!TH!,#1')!+.!I>d3"!+$!
H'$+2.!6#1')$! 6>=!
1#.'!/#!5$$%4'!/;5/!/;'!,59#4!&##41+.5/+#.!+$$%'$!&5.!B'!4'$#)<'1!
-4+#4!/#!+.$/5))5/+#.K!/;'!TH!,#1')!A+))!/;'.!B'!-5$$'1!#./#!/;'!
&#./45&/#4$!(#4!/;'+4!%$'!+.!&4'5/+.2!/;'!5$ZB%+)/!,#1')!A+/;!
%-15/'1!+.(#4,5/+#.!5.1!&#./'./:!5/!5!$&5)'!$%+/5B)'!/#!4'()'&/!/;'!
+.$/5))5/+#.!&)'54)*!#.!5!-4+./'1!$;''/@!
!
!
EEF -'+Q/.&.O)+#&!)/D1#"-1,+-,1'!/''0"!
EEFE ".D-H#1'!
!
E%<)%./%-'!
$%&!*<'! <,7+302'!! 1'2<%,-!
IKL!MNNOKPMQORJ!
>?+$/+.2!6#1')!
GIEJ! I>d3"! PQRQ!
G%/;#4+.2!
6'&;@!H'$+2.!6#1')$!
>LM! I>d3"! PQRQ!
G%/;#4+.2!
E##41+.5/+#.!6#1')!
ENLO! LGd3O! PQRQ!
G%/;#4+.2!
!
!
EEFI +.$%,-'1"!P!Q#10H#1'!
!
,3-'2!,7!
$%&!*<'! B02E302'!! <.')%7%)0+%,-<!
B02E302'!
=INE>OONI:!N=>IG"3LM!
OfO">6:!6>6NIf!O"NIGM>:!
H>O3ML!GX"JNI3LM! hhh!EN6=X">I!OfO">6! GIEJ3">E"!h!
MIG=J3EO:!L>"SNIg!EGIH:!
>"E@!
!
!
EEFK $.0'&)/O!+./-'/-!#/0!1'D'1'/+'!)/D.1$#-)./!
!
E%<)%./%-'! &,E'/%-?!),-+'-+!@!
$%&!*<'! 1'2<%,-!
IKL!MNNOKPMQORJ! 2'7'2'-)'!%-7,2&0+%,-!
"#!B'!1'/'4,+.'1!(%4/;'4!+./#!
H>O3ML!GX"JNI3LM! GIEJ! !
/;'!-4#&'$$!
!
!
!
EIF $.0'&!"-1,+-,1'!
!
EIFE D)&'!/#$)/O!"-1,+-,1'!
!
7%/'!-0&'<!7,2!&,E'/<!<B,*/E!$'!7,2&0++'E!0<S!
EG6=XOt0X3UH3LMt63"!=INa>E"!ut6NH>ULG6>tHG">@?*i!
>h3O"3LM!6NH>U! 63"tSRtQ`Q_Tt>h3O"Z!66HHff!@4</!
JdGE!6NH>U! 63"tSRtQ`Q_TtJdGEZ!66HHff!@4</!
=UX603LM!6NH>U! 63"tSRtQ`Q_Tt=UX60Z!66HHff!!@4</!
>U>E"I3EGU!6NH>U! 63"tSRtQ`Q_Tt>U>EZ!66HHff!!@4</!
EN66XL3EG"3NLO!6NH>U! 63"tSRtQ`Q_TtEN66Z!66HHff!!@4</!
GEE>OO!ENL"INU!6NH>U! 63"tSRtQ`Q_TtGEE>OOZ!66HHff!!@4</!
>L>IMf!6NH>U! L#/!G--)+&5B)'!%.)'$$!1'&+1'1!#/;'4A+$'!B*!&)+'./!
ENLO"IXE"3NL!UNM3O"3EO!
63"tSRtQ`Q_TtENLO"Z!66HHff!@4</!
6NH>U!
H3OE3=U3L>!ENNIH3LG"3NL!
63"tSRtQ`Q_TtENNIHZ!66HHff!!@4</!
6NH>U!
!
EIFI $.0'&!"-1,+-,1'!
!
";'!,#1')!A+))!B'!#425.+i'1!B*!)'<')!7()##4!Q:R:P:T:Y:'/&@8@!
!
&,E'/%-?!<+0-E02E<!
H45(/!/#!B'!1'<')#-'1!(4#,!)+$/!B')#A!5.1!5%2,'./'1!/;4#%2;#%/!/;'!,#1')+.2!-4#&'$$!
6#1')+.2!$;#%)1!5<#+1D! 6#1')+.2!O;#%)1D!
O/5&C'1!A5))$! X$'!/;'!#<'45))!&##41+.5/'!$*$/',!-4#<+1'1!B*!63"!!
6#1')!1+(('4'./!&#.$/4%&/+#.!')','./$!$'-545/')*!
U#&C+.2!1+,'.$+#.$!+.!/;'!-4#9'&/! '<'.!+(!/;'*!54'!5195&'./!7'@2@:!$+))$!$'-545/'!(4#,!
A+.1#A$8!
E4'5/+.2!%..'&'$$54*!-545,'/'4$!+.!/;'!-4#9'&/! X$'!/;'!$;5(/!#-'.+.2!/##)!(#4!$;5(/$!5.1!')'<5/#4$!
E4'5/'!<+'A$!#425.+i'1!B*!$;''/!$'/!#4!%$'!7S#4C+.2:!
H##4$!5$!&%4/5+.!-5.')$!
H#&%,'./5/+#.:!=4'$'./5/+#.8!
E4'5/'!$'/!#(!'?+$/+.2!-)5.$!%.1'4!/;'!A#4C+.2!(#)1'4:!
G//5&;+.2!A5))$!/#!()##4$!5.1!4##($!
A+/;!1+,'.$+#.$@!
X$+.2!,5$$!(5,+)+'$!(#4!5.*/;+.2!'?&'-/!#<'45))! X$'!1'-'.1'./!<+'A$!A;'4'<'4!/;'*!B4'5C!%-!-)5.$!
B%+)1+.2!,5$$+.2! /#!(+/!#.!5!$;''/@!
N-'.+.2$!+.!A5))$!5.1!#-'.+.2$!5$!A5*$!#(!A+.1#A$!
X$'!X.+(#4,5/!(#4!A#4C$'/$!!
/#!&%/!A5))$!7%$'!<#+1$!+.$/'518!
b#))#A!.5,+.2!&#.<'./+#.!(#4!5.*!.'A!(5,+)+'$!
!
&4'5/'1!
! X.+(#4,5/!(#4!T1!&#,-#.'./$!!
!
! EO3!(#4!P1!&#,-#.'./$!
!
EIFK '*+&,")./"!!
!
";'!(#))#A+.2!/5B)'$!-4#<+1'!)+$/$!#(!#B9'&/$!/;5/!54'!/#!B'!'?&)%1'1!(4#,!/;'!,#1')7$8@!
!
O''!G--'.1+?!jj!(#4!UNH!'?;+B+/@!
!
%+'&<!+,!$'!'()/*E'E!72,&!+B'!02)B%+')+*20/!&,E'/!
H##4!;541A54'!
b##1!O'4<+&'!>]%+-,'./!5.1!&5$'A#4C!
G--)+5.&'$!
OC*)+2;/$!
U#BB*!4'&'-/+#.!1'$C!
J5.145+)$!
b+.+$;'$:!A##1!/4+,!7.#/!&#.$+$/'./)*8:!$+2.52':!A+.1#A!!/4'5/,'./$:!5&#%$/+&!A5))!-5.')$!
%+'&<!+,!$'!'()/*E'E!72,&!+B'!B10)!E'<%?-!&,E'/!
LN">D!/;'!+/',$!#,+//'1F.#/!&#..'&/'1!54'!(#4!145A+.2!&)54+/*!4'5$#.$!#4!/;'!$*$/',$!A'4'!145(/'1!+.!EGH@!
!
G))!4']%+4'1!#(($'/$!1%'!/#!$/4%&/%45)!5.1!#/;'4!#B$/4%&/+#.$@!
";'!(%))!'?/'./!#(!-+-+.2!5.1!5&&'$$#4+'$!5$$#&+5/'1!A+/;!,'&;5.+&5)!']%+-,'./@!
b+.5)!&#..'&/+#.$!/#!,'&;5.+&5)!']%+-,'./!7dGd:!XJ:!bEX:!'/&@8@!
E#..'&/+#.$!B'/A''.!;#4+i#./5)!5.1!<'4/+&5)!1%&/A#4C!5/!$;5(/$@!
=+-'!5.&;#4$@!
I'(4+2'45./!U+]%+1!5.1!O%&/+#.!)+.'$!B'/A''.!GEm$!5.1!J=$!
!
d54+#%$!$;%/Z#((!<5)<'$:!25%2'$:!145+.!<5)<'$:!'/&@!4']%+4'1!/;4#%2;#%/!/;'!B%+)1+.2@!!7O''!1'/5+)$!5.1!1+5245,$8!
J5.2'4$:!$'+$,+&!B45&+.2:!<+B45/+#.!+$#)5/+#.!
%+'&<!+,!$'!'()/*E'E!72,&!+B'!./*&$%-?!E'<%?-!&,E'/!
LN">D!/;'!+/',$!#,+//'1F.#/!&#..'&/'1!54'!(#4!145A+.2!&)54+/*!4'5$#.$!#4!/;'!$*$/',$!A'4'!145(/'1!+.!EGH@!
!
J#4+i#./5)!-+-+.2!5.1!&#..'&/+#.$!+.!(+?/%4'!&;5$'$:!#/;'4!/;5.!,5+.!4+$'4$!5.1!$/5&C$@!
J5.2'4$:!$'+$,+&!B45&+.2:!<+B45/+#.!+$#)5/+#.!
=+-+.2!+.!/;'!A'$/!A+.2!#.!/;'!24#%.1!()##4!+.&)%1+.2!/;'!C+/&;'.!54'5!
=+-+.2!+.!/;'!O'4<'4*!54'5!#(!/;'!(+4$/!()##4!7A'$/!A+.28!
X.1'424#%.1!-+-+.2!+.&)%1+.2!()##4!&)'5.#%/$!
";'!(%))!'?/'./!#(!-+-+.2!5.1!5&&'$$#4+'$!5$$#&+5/'1!A+/;!/;'!;#/!A5/'4!;'5/'4$:!/;'4,#$/5/+&!,+?+.2!<5)<'$!5.1!
B5)5.&+.2!<5)<'$!
>?5&/!)#&5/+#.$!#(!-)%,B+.2!(+?/%4'$!
"*-+&5)!B5/;4##,!-+-+.2!)5*#%/!5.1!-+-'!$+i'$!7$''.!#.!B5/;4##,!-54/!-)5.$8!$;#A.!#.!5))!()##4$!
b+.5)!E#..'&/+#.$!/#!']%+-,'./!7J#/!S5/'4!J'5/'4$:!O'A52'!>9'&/#4:!O%,-!=%,-$:!H4*'4$:!O/#<'$:!'/&@8!,5*!
.#/!B'!,51'!(#4!145A+.2!&)54+/*@!
G))!4']%+4'1!-+-+.2!#(($'/$!1%'!/#!$/4%&/%45)!5.1!#/;'4!#B$/4%&/+#.$!
d54+#%$!$;%/Z#((!<5)<'$:!25%2'$:!145+.!<5)<'$:!'/&@!4']%+4'1!/;4#%2;#%/!/;'!B%+)1+.2!
!
!
!
%+'&<!+,!$'!'()/*E'E!72,&!+B'!'/')+2%)0/!E'<%?-!&,E'/!
!
>)'&/4+&5)!&#.1%+/$!;5<'!.#/!B''.!,#1')'1@!=)'5$'!4'('4!/#!>)'&/4+&5)!$&;'1%)'$!(#4!&#.1%+/!$+i+.2@!!
E#.1%&/#4!$+i'$!;5<'!.#/!B''.!+.&)%1'1!A+/;+.!/;'!,#1')@!X.)'$$!#/;'4A+$'!.#/'1!#.!-)5.$:!-)'5$'!4'('4!/#!
>)'&/4+&5)!$&;'1%)'$!(#4!&#.1%&/#4!$+i+.2@!
>]%+-,'./!B*!#/;'4!/451'$!;5<'!.#/!B''.!+.&)%1'1!+.!/;'!,#1')@!>)'&/4+&5)!$'4<+&'$!(#4!']%+-,'./!;5$!B''.!
-4#<+1'1@!
65+.!$'4<+&'!']%+-,'./!7+@'@!RVCd!OA+/&;'$:!O%B$/5/+#.:!M'.'45/#4:!'/&@8!;5<'!.#/!B''.!+.&)%1'1!+.!/;'!,#1')@!
U+2;/+.2!E#./4#)!O*$/',!(#4!O'4<'4*FH+.+.2!G4'5!;5$!.#/!B''.!,#1')'1@!
H'/5+)$:!O*,B#)!U'2'.1:!M'.'45)!L#/'$:!I+$'4!H+5245,$:!O&;'1%)'$!;5<'!.#/!B''.!,#1')'1@!
!
!
%+'&<!+,!$'!'()/*E'E!72,&!+B'!),&&*-%)0+%,-<!E'<%?-!&,E'/!
E#,,%.+&5/+#.$!&#.1%+/$!;5<'!.#/!B''.!,#1')'1@!
E#,,%.+&5/+#.$!A+4+.2!;5<'!.#/!B''.!,#1')'1!
=54/!=)5.$!(#4!"')'&#,,%.+&5/+#.$!4##,$!;5<'!.#/!B''.!,#1')'1!
H'/5+)$:!O*,B#)!U'2'.1:!M'.'45)!L#/'$:!b5&'-)5/'!1'/5+)$:!I+$'4!H+5245,$!;5<'!.#/!B''.!,#1')'1@!
E#,,%.+&5/+#.$!A#4C!54'5!#%/)'/$!;5<'!.#/!B''.!,#1')'1!&#,-)'/')*!#.!,'&/!')'<5/+#.!;'+2;/!
!
!
!
%+'&<!+,!$'!'()/*E'E!72,&!+B'!0))'<<!),-+2,/!E'<%?-!&,E'/!
G&&'$$!&#./4#)$!&#.1%+/$!;5<'!.#/!B''.!,#1')'1@!
G&&'$$!&#./4#)$!!A+4+.2!;5<'!.#/!B''.!,#1')'1!
=54/!=)5.$!(#4!"')'&#,,%.+&5/+#.$!4##,$!;5<'!.#/!B''.!,#1')'1!
!
H'/5+)$:!O*,B#)!U'2'.1:!M'.'45)!L#/'$:!I+$'4!H+5245,$!;5<'!.#/!B''.!,#1')'1@!
G&&'$$!&#./4#)!-#+./$:!&#./4#)!-5.')!5.1!1'<+&'!)#&5/+#.$!;5<'!.#/!B''.!,#1')'1!&#,-)'/')*@!O#,'!1'<+&'$!
$;#A.!5$!)+.'!A#4C!#.)*@!
EIFN 1'G)-!.(J'+-!+#-'O.1)'"!!
!
";'!(#))#A+.2!/5B)'!2+<'$!/;'!$/5/%$!#(!'5&;!#B9'&/!&5/'2#4*!4']%+4'1!+.!/;'!,#1')7$8@!!
!
,$6')+!)0+'?,2;! <+0+*<!
G4'5$! L#/!+.!6#1')!
E5$'A#4C! L#/!+.!6#1')!
E'+)+.2$! %T!'UKVWKTX!&YZRO:!$%$-'.1'1!<$!5//5&;'1!1+(('4'./+5/'1!
E#)%,.$! %T!'UKVWKTX!&YZRO!
E%4/5+.!O*$/',$! L#/!+.!6#1'):!,5*!B'!%$'1!+.!1'$+2.!,#1')!
H'/5+)!3/',$! %T!MOO!&YZROV!MV!TRRZRZ!
H##4$! %T!'UKVWKTX!&YZRO:!(#4!)#&5/+#.!5.1!#<'45))!$+i':!.#/!1'/5+)!#(!-5.')$!
>)'&/4+&5)!>]%+-@! %T!'UKVWKTX!&YZRO:!#.)*!5$!.''1'1!
>)'&/4+&5)!b+?/%4'$! %T!'UKVWKTX!&YZRO:!#.)*!5$!.''1'1!
>./#%452'! LG!
b)##4$! %T!'UKVWKTX!&YZRO!
b%4.+/%4'FO*$/',$! L#/!+.!6#1')!
M'.!6#1')$! L#/!+.!6#1')!
U+2;/+.2! %T!'UKVWKTX!&YZRO:!/#!B'!1+$&%$$'1!5$!-'4!1'$+2.!$&#-'!
U+.'$! G4'!5.*!.''1'1!(#4!63"!2'#4'('4'.&+.2r!
65$$! "#!B'!1+$&%$$'1!
6'&;5.+&5)!>]%+-@! %T!'UKVWKTX!&YZRO:!#.)*!5$!.''1'1!
=54C+.2! LG!
=)5./+.2! %T!'UKVWKTX!&YZRO:!#.)*!5$!.''1'1!
=)%,B+.2! %T!'UKVWKTX!&YZRO:!#.)*!5$!.''1'1!
I5+)+.2$! %T!'UKVWKTX!&YZRO:!$&#-'!5/!$/5+4$!/#!B'!1+$&%$$'1!
I5,-$! LG!
I5$/'4! O%4<'*!+,52'$:!/#!B'!1+$&%$$'1!
I#51$! %T!'UKVWKTX!&YZRO:!#.)*!5$!.''1'1!
I##($! %T!'UKVWKTX!&YZRO:!-+/&;!$&#-'!/#!B'!1+$&%$$'1!
I##,$! %T!'UKVWKTX!&YZRO:!.''1!15/5!$/5.1541$!(4#,!63"!
O;5(/$! %T!'UKVWKTX!&YZRO:!#.)*!5$!.''1'1!
O+/'! N.)*!+,,'1+5/'!54'5:!.#/!(%))!/#-#245-;+'$!
O-'&@!>]%+-@! LG!
O/4@!0'5,! %T!'UKVWKTX!&YZRO!
O/4@!E#)%,.$! %T!'UKVWKTX!&YZRO!
O/4@!b#%.1@! "#!B'!145A.:!.#/!,#1')'1!75))!$%B/'445.'5.!A#4C8!
!
O/4@!b45,+.2! "#!B'!1+$&%$$'1!
"#-#245-;*! O''!$+/'!
S5))$! %T!'UKVWKTX!&YZRO!
S+.1#A$! %T!'UKVWKTX!&YZRO:!%.;#$/'1:!AF#!#-'.+.2$!7#.)*!<#+1$8:!/#!B'!4'(+.'1!'?/'.$+<')*!
+.!1'$+2.!,#1')!
!
!!
EIFR $'#",1'$'/-!#/0!+..10)/#-'!"M"-'$"!
!
3,-'4+5)!X.+/$K!M'#4'('4'.&'1!E##41+.5/'$!-4#<+1'1!B*!63"@!
!
EIFT ()$!#/0!+#0!"-#/0#10"!
!
<+0-E02E! 1'2<%,-! $%&!*<'<!0../%)0$/'! ,2?0-%D0+%,-<!0../%)0$/'!
SNIgO>"!GLH!bG63Uf!
XL3bNI6G"! ! GIEJF>LM!
NIMGL3eG"3NL!
!
!
EKF %1.J'+-!0'&)G'1#(&'"!
!
3.!/;+$!$'&/+#.:!)+$/!/;'!036!1')+<'45B)'$!(#4!/;'!-4#9'&/!5.1!/;'!(#4,5/!+.!A;+&;!/;'!+.(#4,5/+#.!A+))!B'!1')+<'4'1@!!
0..2,(%&0+'!
$%&!<*$&%++0/!%+'&! <+0?'! 7,2&0+! -,+'<!
E*'!E0+'!
! ! ! #E3?! !
! ! ! #21+! !
! ! ! #21+! !
! ! ! #.E7!@!#E3?! !
! ! ! #21+! !
! ! ! #21+! !
! ! ! #21+! !
#21+!
! ! ! !
#-3E!
!
!
ENF 0'&)G'1M!"-1#-'OMP+./-1#+-!
ENFE 0'&)G'1M!#/0!+./-1#+-)/O!"-1#-'OM!D.1!-Q'!%1.J'+-!
!
S;5/!511+/+#.5)!,'5$%4'$!.''1!/#!B'!/5C'.!/#!$%&&'$$(%))*!%$'!036!A+/;!/;'!$')'&/'1!1')+<'4*!,'/;#1!
5.1!&#./45&/!/*-'r!
ENFI -'#$!"'&'+-)./!%1.+'0,1'!
!
J#A!A+))!*#%!$')'&/!(%/%4'!/'5,!,',B'4$!+.!4'2541$!/#!/;'!5B#<'!1')+<'4*!$/45/'2*!5.1!&#./45&/!/*-'r!
ENFK ()$!+./-1#+-)/O!%1.+'0,1'!
!
J#A!$;#%)1!036!B'!A4+//'.!+./#!/;'!(%/%4'!&#./45&/$r!!
!
!
#%%'/0)+'"!
#F ()$!O.#&!#/0!,"'!H.1L"Q''-!
!
!
(F $.0'&!%1.+'""!0)#O1#$!!
!
!
!
!
+F )/D.1$#-)./!'*+Q#/O'!H.1L"Q''-
!
!
0F $.0'&!0'D)/)-)./!H.1L"Q''-!
!
MIT
Design Standards
Child Care Centers
Thematic Folder
May 2018
Table of Contents
/#"! 5.067'(*%)!38*$543%&###################################################################################################################### 9!
1.1 Introduction
Before beginning any planning or design for a new or renovated childcare facility on the MIT
campus, the project manager should schedule a meeting with the director of child care at MIT’s
Work Life Center to establish the current standards and regulations that should be utilized in the
childcare centers at MIT. MIT utilizes a third party to manage and operate the Childcare Centers.
At this point in time, the operator is Bright Horizons and they have their own set of standards that
must be utilized in design. Childcare Standards and Regulations change frequently so MIT
requires that the project team met with the Work-Life Center before starting the project to ensure
compliance with the most current regulations.
2. PLAYGROUND MATERIALS
This document was authored by EHS to standardize requirements for MIT facilities where child
care centers are located at MIT owned and/or leased locations. Standards are provided for soils,
sand and wood mulch or articles.
2.1 Soils
Acenaphtene 0.5
Acenaphthylene 0.5
Anthracene 1
Aluminum 10,000
Antimony 1
Barium 50
Benzo(a)anthracene 2
Benzo(a)pyrene 2
Benzo(b)flouranthene 2
Benzo(g,h,i)perylene 1
Benzo(k)fluoranthene 1
Beryllium 0.4
Cadmium 2
Chromium (Total) 30
Chromium(III) 30
Chromium(IV) 30
Chrysene 2
Cobalt 4
Copper 40
Dibenzo(a,h)anthracene 0.5
Fluoranthene 4
Fluorene 1
Indeno(1,2,3-cd)pyrene 1
Iron 20,000
Lead 100
Magnesium 5,000
Manganese 300
Methylnaphthalene, 2- 0.5
Naphthalene 0.5
Nickel 20
Phenanthrene 3
Pyrene 4
Selenium 0.5
Silver 0.6
Thallium 0.6
Vanadium 30
Zinc 100
2.3 Sand
Sand box sand is recommended for any sandbox located within a MIT owned and/or leased Child
Care Center Playgrounds. Specified sand shall not contain dye or added colors. Washed sandbox
sand meeting US Consumer Product Safety Commission and National Association for Education
of Young Children recommendations
2.3 Wood
Chromate copper arsenate (CCA)-treated wood products are NOT allowed either in mulch or
wood play structures. CCA treated wood products are also referred to as pressure treated wood.
Mulch is recommended to be an engineered wood fiber such as a Fibar - this type of mulch is
made of virgin wood fiber. Allowable preservative treatment include ACQ preservative or MCA
(micronized copper azole).
Products that have been used on recent projects include the following
1. ACQ treated southern yellow pine No. 2 beams, joists and posts for structure of decking.
2. White or red cedar slats for fencing.
3. Composite lumber decking and cap for cubby walls, from reclaimed wood and plastic
with integral coloring, free from toxic chemicals and preservatives.
3. PLAYGROUND EQUIPMENT
END OF DOCUMENT
May 2018
Table of Contents
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 1 of 22
@#D! ?'4E(:1& ##################################################################################################################################### $@!
@#7! &*!-,,1!+,**0+)&?&)/ ###################################################################################################################### $@!
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 2 of 22
1. GENERAL
These design standards apply to all classroom and lecture halls, for new construction and
renovations. If clarification is required, contact the MIT Project Manager for your project.
2. CHALKBOARDS
Each classroom should have two to three sets of vertical sliding, wall-mounted chalkboards. The
preferred manufacturer for non-motorized chalkboards is Educational Equipment
http://www.educationalequipment.com/. No substitutions will be considered.
Wall mounted (without pocket) is preferred. Each panel should be no greater than 11’-6” wide.
Maximize the height and the width of the writing surface of the sliding panels. Take note: handle
on bottom of sliding panel needs to be accessible when raised to the highest position. Chalkboard
system to be satin or black anodized aluminum. Reference 2-190, 6-120 and 35-225 for black
anodized aluminum. Avoid having the styles and rails of the chalkboard system custom painted to
prevent future chipping. Color of writing surface to be black.
If a pocket system is chosen, THE WRITING SURFACE OF EACH SLIDING PANEL NEEDS
TO BE FULLY EXPOSED when both panels are displayed. Be sure the sliding panels are at the
same height as the kick panel when lowered into the pocket (see 6-120). Handles on sliding
panels need to be staggered. The chalkboard tray shall be no higher than approximately 36” AFF.
All aluminum styles and rails of chalkboard system should be fully accessible and not covered
with decorative wood trim. All screws on trim need to be visible. If chalkboard system is not
recessed into the wall, screws to remove access panels can be located on sides of styles.
Whenever possible, the chalkboard tray should be one continuous piece. Chalkboard trays are
manufactured in 24’ lengths maximum. If a seam is required, it should occur where the vertical
sections of the chalkboard systems meet. Classroom chalkboards are washed each evening with a
generous amount of water. Over time, excess water will damage the surface of the kick wall
immediately below the chalkboards. To reduce damage from excess water running down the wall
below the chalkboards, an overlapping piece of aluminum is required to direct water away from
the wall. See chalkboard tray detail.
If there is ample ceiling height and approval from faculty to have three vertical sections of sliding
boards, then the chalkboards must be motorized. The preferred manufacturer for motorized
boards is Claridge. However, Educational Equipment can be considered as well.
http://www.claridgeproducts.com/
MIT Faculty prefer chalkboards over whiteboards. Whiteboards or glass boards can be used when
specifically requested by a department (see 4-152, 4-158 and 4-162).
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 3 of 22
Non-sliding chalkboards for side and rear walls with tack strip and map hooks. To prevent chalk
and water damage to neighboring wood trim, painted GWB and fabric walls, provide a physical
barrier such as a vertical aluminum strip to separate chalkboard from other surfaces.
3. LIGHTING
Auto-Off, Manual-On vacancy sensors shall be utilized. Sensors shall be set to 15 minute
timeouts. These are to be coupled with momentary wall mounted dimmer switches. These
spaces shall also be provided with dimming controls.
All local room level personal dimming controls must be Lutron or Sensor Switch. Lutron is the
preferred manufacturer of these local room level personal dimming controls.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 4 of 22
Daylight sensors shall be installed to provide daylight dimming in all applicable areas. Lighting
fixtures coupled with daylight sensors must dim up and down as opposed to turning off and on.
All network lighting controls systems must be Lutron or Crestron. Lutron is the preferred
manufacturer of these network lighting control systems.
Basic lighting environment (for a flat floor classroom with single video projector) will not require
a lighting control system such as the Lutron Grafik Eye. Simple room-level light control is best.
Specify switches to control chalkboard and general classroom lighting that is dimmable. Light
fixtures above student seating will have dimming to achieve an adjustable range from high to low
lighting output. If dimmable LED lighting is specified, a switch with a dimming function is
required. IMPORTANT: confirm selected switch is compatible with LED lighting drivers (see 5-
232 and 36-372 for switch example). LED drivers shall have dimming range down to 1 %.
Preferred LED drivers are Lutron for compatibility and reliability. Gangs of light switches
require custom engraved stainless steel switch plate(s). Switches to include: all on/off, chalkboard
left, chalkboard right, and first row of lights on/off, general lighting high and general lighting
low. All SS engraved plates (electrical and av) coordinated through architect. Final approval of
SS plates by Registrar’s Office.
Complex lighting environment (for a flat floor classroom with two or more video projectors or a
tiered lecture space) specify a Lutron Grafik Eye control system. Lutron is the standard lighting
control system on campus. Crestron will also be considered. An illuminated ON/OFF switch is
required at each entrance. A second, single gang, multi-button switch plate is also required. The
buttons on the multi-button plate to be engraved as follows: High, AV1, AV2, AV3 and Off. The
buttons on the two button plate(s) at the entrances engraved as follows: High and Off. Preorder
engraved buttons from Lutron to coincide with system installation. Coordinate with Crestron
programmer so Lutron button text matches text on Crestron touch panel. If multi-button station is
standalone, use white plastic plate cover with vinyl letters along top of plate to read: LIGHTS.
Otherwise, all SS plates approved by Registrar’s Office. See image B
Consider mounting liner chalkboard lighting behind the projection screens to avoid light spill on
adjacent projection screen. Reference 35-225
One continuous linear fixture seems to work best. Choose a fixture designed specifically for
chalkboard lighting such as Peerless[LED] wall-wash model or similar fixture from Elliptipar.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 5 of 22
Review options for LED lighting. Fixtures can be flush mounted in a soffit, ceiling mounted or
wall mounted via pendants. Avoid fixtures with a housing that is reflective and would create
hotspots on the boards. Note size and placement of chalkboard lighting to avoid blocking the
projected image along the top of the screen. Review elevations of chalkboards, projected image
on screens and chalkboard lighting fixtures. THIS IS IMPORTANT
General Classroom lighting. Lighting in seating area needs to be indirect and dimmable. Choose
energy efficient fixtures with lLED lamps that are easily accessible for re-lamping and for
changing of LED drivers and replaceable boards. LED technology is preferred especially over
fixed seating installations.. Architect and MIT (Registrar’s Office, MIT AV Services, Office of
Digital Learning (ODL) and av consultant) to review scope with lighting consultant. Review
design and product cut sheets. Review design before plan is issued to electrical engineer
Be sure there is adequate light control during video projection and for note taking. Note location
and height of light fixtures in relation to pole mounted video projector. THIS IS IMPORTANT
A light dimming system is required. . Identify and confirm locations of Lutron On/OFF, 5 preset
light stations and Lutron Grafik Eye dimming panels with MIT. Coordinate lighting scenes and
presets with Lutron field rep, lighting consultant and AV integrator so system is fully
programmed and operational when installed. THIS IS IMPORTANT
Additional lighting required for lecture capture technology as needed (see AV system below).
Source 4 LED light fixtures are the preferred option. Reference Lecture Halls 4-270, 4-370, 6-
120 and 35-225. Ideal lighting range for lecture capture is 3200 – 4600 Kelvin
Lighting system should include fixtures to highlight podium and panel discussion locations with
or without video projection
Sunshade to be (2-3%) transparency and a blackout shade. PVC free fabric only. Mecho Whisper
Shade/IQ system is the current standard (Lutron shades will be installed in 1-190 in 2018). Shade
control through the Crestron Touch Panel requires a low voltage cable from the window shades to
the MNI (Mecho Network Interface) mounted at or near the av rack. In lieu of RS232/MNI, a dry
contact connection can be used to control the shades via the Crestron touch panel. Window blinds
are not recommended.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 6 of 22
In classrooms equipped with a Crestron touch panel, motorized window shades to be controlled
from Crestron touch panel with redundant wall switch by Mecho Shades IQ Decorator switch or
Lutron shade switch. Use IQ Decorator switch or Lutron shade switch for classrooms without
Crestron touch panel control. All sun shades shall be controlled by one switch and all blackout
shades controlled by another switch. Eliminate manufacturer aluminum side and sill channels.
Build wood pockets at window sides. See examples in Buildings 4-270, 4-370 and 35-225. Sun
shades: ThermoVeil Dense Vertical Weave 1000 series 2-3% open. Blackout shades: ThermoVeil
0700 Series opaque. IQ Decorator switch by Mecho Shades. See image following:
4.1 Acoustics
Background noise levels should be NC -20 to NC-25 to support lecture capture audio (see lecture
capture technology below under Audio Visual System). If room does not support lecture capture
audio, NC-25 to NC-30 is the target number. THIS IS IMPORTANT. ARCHITECT,
ACOUSTIC ENGINEER AND HVAC ENGINGEER MUST COORDINATE.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 7 of 22
4.2 Power and Data
Ample power required to support room capacity. Combination of perimeter wall and floor box
locations works best
Data is wireless. No hardwired data at student seats unless specified. Limited number of
hardwired data ports for instructor at wall and floor box locations at front of room. Provide data
to first row of seats in rooms with fixed seating
Coordinate with Information Services & Technology (IS&T) to identify locations and number of
required WAPs (wireless access points). Estimate 1 WAP for every 25 students. WAPs cannot be
installed on ceilings. Antennas on WAPs to be white to match body of WAP. Must specify all
white with IS&T
Network jack(s) required in av booth or av closet for remote management of av system. Note:
rooms may not have av booth or av closet
Lights, window shades and projection screens to be controlled by lighted on/off switches.
Multiple switches to be mounted in engraved stainless steel wall plate(s). All SS plates
coordinated through architect. Provide actual switches to plate manufacturer for accurate
dimensional cutouts. Line voltage switches cannot be attached to stainless steel wall plates.
Provide blocking to accommodate location of wall plate screws. Countersink holes for screws and
bevel edges of wall plate. Stainless steel wall plate to be 1/8” thick. See image following.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 8 of 22
Fasteners: Specify Phillips oval head sheet metal screws to attach plate to wall. See image
following.
4.4 Controls for Audiovisual, Lighting, Window Shades and Projection Screens
Specify wall mounted Crestron touch panel to control AV system, lights, window shades &
projection screens. Angle touch panel wall unit for easy reading
Provide redundant switches to control lights, window shades & projection screens. Locate
switches adjacent to wall mounted touch panel. Multiple switches to be mounted in engraved
stainless steel wall plate. Provide actual switches to plate manufacturer for accurate dimensional
cutouts. Line voltage switches cannot be attached to SS wall plate. Low voltage switches can be
mounted directly to SS wall plates via soldered posts on rear of plate. Provide blocking to
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 9 of 22
accommodate location of wall plate screws. Countersink holes and bevel edges of wall plate. See
image following.
5. SEATING
The Concerto seat by KI is the preferred seat for lecture halls on campus. The Concerto is a fixed,
tablet armchair (for fixed tables and chairs see Navetta Symmetra Plus table with Lovano chair or
KI Torsion or Strive). Recent Concerto installations include maple seat backs with black frames.
Reference 2-105, 2-190, 3-333, 4-270, 4-370, 6-120, 10-250, 26-100 & E25-111. Maximize the
number of seats while not comprising seat width. Each seat should have the largest tablet
possible. Tablet arms should have an exposed laminate edge with a clear lacquer finish. AVOID
PAINTED EDGES on tablets. Power is required at each student seat. Power and data housing is
located under right armrest on Concerto seat. Hardwired data for first row of student seating only.
Add ~10% left hand tablets. Review attic stock with Registrar’s Office.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 10 of 22
Jacqueline McGuire Jacqueline.McGuire@ki.com is MIT rep in KI Boston Office.
http://www.ki.com/.
Reference state and national code requirements for distance between rows of fixed seating with
tablet arms. Provide a minimum of 12” from edge of open tablet to back of forward seat (if
possible, maximize this distance to 14”). If long rows of seats are proposed, this spacing will
allow unencumbered access to all seats in the row. THIS IS IMPORTANT
Preferred flooring for fixed seating is an epoxy or other hard, low maintenance surface. Linoleum
such as Marmoleum is an option for smaller spaces. Avoid carpeting in seating area if possible.
Acoustical engineer is required for analysis of the correct mixture of room finishes. See
consultant under Acoustics section. See 2-105, 2-190, 4-270, 4-370, 6-120 and 35-225 for
examples of rooms with hard flooring
Fabric wrapped acoustical panels located ~6’ or less AFF should be impact resistant
Fabric wrapped acoustical panels should sit above wood and gypsum surfaces to avoid street level
wear and tear.
All seats should have excellent sightlines to chalkboards and projection screens. Avoid center
aisle in center section of seating if possible.
Note professor/student connection. Allow approximately 10-11’ between front row of student
seating and chalkboards
Fixed jury-base student seating is preferred for rooms with fixed student tables. Review the KI
Torsion and Strive chairs. Reference Rooms 9-354 (Torsion) and 4-231 (Strive).
High-density seating with fixed tables achieved with fixed swing out seating. Review the Navetta
Symmetra Plus with Lovano chair. Navettadesign.com Reference Rooms E52-164 and 35-225.
Drew Strong strongsales@comcast.net
Locate wheelchair positions at front of room by positioning fixed seats either forward or back in a
row to line up with adjacent companion seat. This will provide a wheelchair location without
losing a seat.
Preferred table size is 18”D x 54”L x 29”H (this table will accommodate two students). If
classroom layout permits, use 18” x 60”. Plastic laminate for surface with durable vinyl edge.
Flip top as needed. Good examples are Herman Miller Everywhere table, Versteel Brattice and KI
Barron table (one end of table has hidden casters for mobility). Note table height for classrooms
with a chair rail
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 11 of 22
Preferred chair is Caper by Herman Miller without arms. Four legs with glides for hard surfaces.
Height of chair is 32.5”. Note chair height for classrooms with a chair rail
All seats should have excellent sightlines to chalkboards and projection screens
Note professor/student connection. Allow approximately 8-10’ between front row of student
tables or tablet armchairs and chalkboards
Allow minimum of 3’ from back edge of student table to front edge of following student table
American Seating Nima tablet armchair is a standard (see 1-135 and 1-242). Herman Miller
Caper tablet armchair is another option (see 13-3101)
Node chair by Steelcase is another tablet armchair to consider (see 14E-310). However, the Node
requires additional square feet per chair.
Tablet edges should be natural with a clear coating. NO PAINTED EDGES on tablets (paint
wears off after a few years of use). Add ~10% left hand tablets. Review attic stock with
Registrar’s Office.
Erik Booth ebooth@cop-inc.com is the MIT rep for Herman Miller products, Brattice table in
Boston at Creative Office Pavilion. http://www.cop-inc.com/
Negri (Ferstler), Beth BNegri@red-thread.com in Boston at Red Thread for Node chair and
Brattice table
Matt Hodge matt@ritzinc.com in Boston at Ritz Inc for American Seating Nima chair.
1-2 movable tables for instructor at front of room. Table size and manufacturer must match
student table size so they are interchangeable. Good examples are Everywhere table by Herman
Miller, Brattice by Versteel (Erik Booth ebooth@cop-inc.com or Negri (Ferstler), Beth
BNegri@red-thread.com and KI Barron tables (Jacqueline McGuire
Jacqueline.McGuire@ki.com ).
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 12 of 22
Stand-alone lectern for lecture halls. As required for classrooms. See Izzy Dewey Lectern
(without storage cabinet). Reference 2-190, 4-270, 4-370, 6-120, 35-225 and E25-111. Erik Booth
ebooth@cop-inc.com
Vitra Visavis Visitor Chair (Erik Booth ebooth@cop-inc.com). Plastic Backrest with round
perforations. Chrome frame. Upholstered seat with Alta treated fabric at 100,000+double rubs.
Vitra offers a small tablet version for the Visavis chair that can be used around a conference table.
All chairs in the conference room would be outfitted with a tablet. Reference 66-148
6. FLOORING
Linoleum such as Marmoleum for classroom flooring. Incorporate contrasting borders with
welded seams. Avoid carpeting whenever possible. Acoustical engineer is required for analysis of
the correct mixture of room finishes and HVAC. See consultant under Acoustics section.
Reference 4-159 & 4-163.
Preferred flooring for fixed seating is an epoxy or other hard, low maintenance surface. Linoleum
such as Marmoleum is an option for smaller lecture rooms. See 4-163 for example. Avoid
carpeting in seating area if possible. Acoustical engineer is required for analysis of the correct
mixture of room finishes. See consultant under acoustics section. Reference 2-105, 2-190, 4-
270, 4-370, 6-120 and 35-225.
Preferred flooring throughout lecture hall is resilient urethane floor. Stontec TRF resilient
urethane floor, by Stonhard, with 1/4" flakes, flat finish, Shenandoah Buff Color or approved
equivalent. Completed thickness to be between 1/8" and 3/16" above concrete substrate. Apply
to existing concrete, plus new vertical and horizontal concrete tiers. System consists of: Urethane
Mortar (4 component high-solids urethane mortar); TRF Undercoat (two component high-solids,
epoxy-bonding coat followed by application of 1/4" flakes); Stonseal GS7 Clear Flat: two part
non-reflective, waterborne, aliphatic polyurethane coating. Coordinate work with embedded
items: stair nosing, railing sleeves, return registers on face of risers, escutcheon at handrail and
seat bases.
Provide fire alarm integration of AV controlled lighting and speakers. Provide manual pull
stations where required by Massachusetts Building Code.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 13 of 22
Provide emergency lighting and exits signs where required for egress illumination.
Acoustical panels located ~6’ or less AFF along walls should be impact resistant
Acoustical fabric wrapped wall panels. Snap-Tex system provides an excellent finished product
with crisp edges and long seamless panels. Custom made panels can be considered, but have size
limitations. A white liner may be required between the yellow Fiberglass insulation and the
fabric. For examples see 4-159 & 4-163
Hooks for laptop cables: http://www.sugatsune.com/hooks. Large utility hook, JF-70. Mounted to
stainless steel plate or on wall for laptop cables.
Doors to classroom must have narrow vision panel. See 2-131 and 2-190. Larger door glazing
with film to restrict visibility. Reference 3-270, 3-333, 35-225 and E25-111
Digital wall clock visible to instructor. Clock must have internal transformer and an infrared
remote option (IRR option) with short electrical cord. Clock secured to wall to prevent theft.
Enlarged frame around clock to hide cord may be required. Mounting location on rear wall of
classroom. http://www.digitaldisplay.com/digital-clocks/digital-clocks/stand-alone-digital-clocks/
Choose model BSA-41240 for the 4” size numerals
All doors to have kick plates (coordinate finishes for all door hardware)
Hallway wall flag sign(s) identifying classroom entrance. Reference 3-333, 1-132
Lecture hall room number to be metal. Reference 3-270, 4-270, 4-370, 10-250 and E25-111
Provide stainless steel engraved “Please No Food or Drink” signs for all classrooms and lecture
halls
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 14 of 22
Location for panic/duress button (as required)
Locate trash and recycling bins outside of classroom or lecture hall. Consider built-in counter for
bins. Reference 2-190 and 35-225
Integrate hallway seating such as benches near clusters of classrooms and entrances to lecture
halls. Provide electrical outlets and robust wireless connectivity
Integrate hallway chalkboards near classrooms to support faculty/student interaction before and
after class
Chair rail on all walls in classrooms to prevent wall damage from tables and chairs. NOTE
TABLE AND CHAIR HEIGHTS
Refer to the MIT Design Standards Audio Visual Thematic Folder for audiovisual systems and
the following.
Ceiling mounted video projector(s) with two forms of theft prevention integrated into the mount
hardware. Utilize projector security bar when available in conjunction with cable and lock.
Use a ceiling mounted equipment storage box above projector, brands to consider include Premier
and FSR
In rooms without a ceiling equipment storage box, install quad electrical outlet for projector flush
mounted in ceiling tile facing inside of classroom.
Conduit required between projector location(s) at ceiling, control panel on wall, interface(s), wall
or ceiling mounted speakers and equipment rack. Minimum diameter 1.25”.
Wall mounted Crestron touch panel control system for all video projector installations
Sound system for program audio, typically left and right of projection wall
Distributed speech for microphone use (as required for room size). One lapel (cardioid
microphone) and one handheld (SM58) Shure brand, specific model and frequency to be
coordinated at time of design.
Wireless microphones require a wireless access antenna mounted in the room over presentation
area. Conduit to each access antenna 1.00” minimum diameter. Reference 2-190.
Coordinate frequency of microphones with adjacent rooms to avoid interference between rooms.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 15 of 22
Assistive listening system (as required for room size). Hearing assist receivers shall have both
earpieces and inductive loops provided. Listen Technologies RF72 transmitter/receiver is the
specified product line. https://www.listentech.com/assistive-listening/listenrf/
Connection points for laptops (VGA & HDMI) and aux video input. All signals to the displays
should follow a digital signal path (Crestron DM platform). Conduits minimum diameter 1.5”
Power required at any av connection location shall be on the same electrical phase. This includes
power for projectors, laptops adjacent to connection plate(s), floor boxes and AV racks.
Floor box location for laptop connections, power and data: FSR600-6-P-B floor box. The cover
should be Style 5, hinged, and be made of quarter inch solid in anodized aluminum finish. The lid
installation will have the hinge on the audience side. When opening the cover, it should flip
towards the audience. Coordinate installation of floor box lid with flooring contractor to ensure
floor box is flush with floor covering. Reference 35-225.
At least one dual port network jack installed in the floor box.
The AV connections will use the continuous six-gang side of the box. Install the six-gang side so
that it faces the front of house (chalkboard) side of the room. Power and data installed on opposite
side of floor box.
Stainless steel wall plate for laptop connections, power and data. Plate to be 1/8” thick. Attach
hooks to lower corners of plate to hang computer cables. All plates to be brushed stainless steel,
bevel full perimeter of plate edges. Engraved lettering on plate to be black. Provide blocking in
wall for devices and for oval head screws for attaching plate to wall. 1/4" high letters and
HELVETICA FONT. All SS plates coordinated through architect. See Image B
Rack plate for audio record output, laptop/device input (HDMI), line level input, microphone
input
Rooms with AV closets sized for easy rack movement. Provide adequate service loop cabling
length to allow for service behind AV rack. AV racks for lecture halls sized appropriately to
house equipment. Middle Atlantic MRK-4426 typically used for lecture halls. Reference 35-225.
AV Rack rooms shall have two quad AC outlets adjacent to the AV rack (s). Final location to be
determined with design team.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 16 of 22
AV Rack rooms shall have doors high enough to enable installation of AV racks and associated
equipment.
Rack mounted touch panel for AV tech to operate within rack room. Rack touch panel should
emulate the in-room unit and have all the same functionality.
Cooling and ventilation for av booth and av closet based on heat load of equipment installed
within the space. Provide heat load to HVAC engineer for proper sizing of cooling systems.
AV booth and av closet requires card reader access. All av booth, av closet and av cabinet doors
to be keyed to FA6
Four Network jacks required in av booth or av closet at rack location. One jack assigned to
Crestron Fusion for remote management of av system. Note: rooms may not have av booth or av
closet
9. LECTURE CAPTURE
9.1 General
At the heart of the system should be a central routing system which will feed into a lecture
capture device (make and model to be determined). Potential sources into the router will include
computer signals using both analog and digital systems (VGA and HDMI with associated audio
and video information) and presenter lapel and audience handheld microphone signals.
A video camera for presentation capture will need to be installed in the back of the classroom in
order to capture the presenter and any chalkboard work that they do while teaching. These
cameras should be mounted as close to center on the back wall as is possible, given architectural
constraints.
The routing system should also contain all the capabilities to display and amplify signals to the
local audience through the traditional classroom AV destinations (projectors, flat panels, speaker
system, etc.).
Special attention should be paid to the following areas of the system following.
9.2 Video
A high-resolution (1080i/p) capable camera(s) must be installed in the center wall at the back of
the room for lecture capture. The camera(s) can either be used in a wide shot or can have
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 17 of 22
tracking capability similar to the installations in E25-111 and E25-117 (Vaddio camera with IR
tracking which allows the camera to follow movement at the front of the lecture hall in the room).
Ideally, this camera would also have the ability to recall specific presets for chalkboard capture as
well.
One possible way the tracking could work is as follows: if a professor were standing in a central
location, the tracking technology would allow for movement, but if they stood in front of a
chalkboard, it would go to a pre-framed preset, which would allow the camera to capture the
writing on the chalkboard
There should be control on the Crestron touch panel to allow the disabling of tracking by those
presenters who do not wish to be tracked, or to disable video completely and capture audio over a
computer driven presentation. The camera tracking capability should be activated only when the
lecture capture system is initiated.
When a lecture capture session is completed, the tracking capability should be disabled to allow
for non- lecture capture classes to proceed without the disruption of the tracking cameras.
There should be an LCD panel at the rack, which can monitor video signals from the rear of room
camera. A duplex electrical outlet and dual port Ethernet drop should also be installed at the
camera location for local power and control.
9.4 Audio
Audio should contain all in-room sources through a digital signal processor (DSP) device that
will allow for a program output to a lecture capture device. Please provide both balanced and
unbalanced line and microphone outputs at the rack for encoding by a lecture capture device. In
general, audio systems should provide for left/right speakers on the front wall for program audio
and a distributed sound system for speech audio. An associated hearing assistance system should
also be integrated into the system.
Additional lighting required for lecture capture technology as needed (see AV system). Office of
Digital Learning to approve light fixture and light fixture location. Source 4 LED light fixtures
are the preferred option. Reference Rooms 4-270, 6-120 and 35-225. Ideal lighting range for
lecture capture is 3200 – 4600 Kelvin.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 18 of 22
9.6 VGA/HDMI
System must be capable of transmitting a computer image source (up to WUXGA) for lecture
capture. In-room sources such as a built-in computer (if installed), in-room document camera and
other presentation materials should be routable to a device, which will allow for lecture capture.
Provide a wall plate sized to accommodate video from camera, presentation source output,
microphone and program audio mounted on the rear wall for possible DIY recording. It would
also be ideal if a secondary video input and balanced audio inputs could be added to this plate for
additional camera connectivity for MIT Video Productions, as well as a connection for manual
control of the in room camera for local recording.
Non-MIT network Cat6 Ethernet should be run from points in back of classroom to AV rack for
future connectivity (i.e., additional audio connections by MIT AV for Q&A pick up if desired in
future installation work.)
Motorized projection screens centered over each section of chalkboards. Non tab-tension screens
with a 16 x 9 aspect ratio http://www.da-lite.com/
Matte white surface with black borders, built-in LVC (low voltage controller) vs. external
controller to allow for integration into control systems
Design GWB pocket to conceal projection screen boxes (installer will use floating brackets to
position screen boxes)
Review height of projected image, hanging chalkboard lighting and chalkboards. Coordinate
elevations (projected image needs to be at a MINIMUM of 48” off the floor in flat-floor
classrooms to ensure good sightlines)
Review if room layout permits building two wing walls (flanking chalkboards) for video
projection screens. This layout will free up all chalkboards for writing. Correct angle of wing
walls is critical for excellent sightlines. Determine if wing walls can support an appropriate size
screen for the size of the room. Reference 10-250 and 4-163 for examples, Da-Lite Contour
Electrol (Reference 4-231 and 4-237), Da-Lite Advantage Electrol. Reference Rooms 3-333 and
35-225.
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 19 of 22
11. CONSULTANTS
The following consultants have experience with MIT standards and requirements:
Acoustics
Audio Visual
Design/Build AV Integrator
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 20 of 22
Lighting Consultant
Tables/Chairs/Tablet Armchairs/Podiums
Epoxy Flooring
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 21 of 22
Chalkboard Vendor and Installation
END OF DOCUMENT
MIT Design Standards | Classrooms and Lecture Halls Thematic Folder Page 22 of 22
MIT
Design Standards
Commissioning
Thematic Folder
May 2018
Table of Contents
"#"! $%&'()*!)&++,--,&.,./!+0.102######################################################################################################### 3!
END OF DOCUMENT
TABLE OF CONTENTS
1.0! GENERAL ....................................................................................................................................... 3!
1.1! RESPONSIBLE PERSONNEL....................................................................................................................... 3!
1.2! DESCRIPTION ............................................................................................................................................... 3!
1.3! DEFINITIONS ................................................................................................................................................ 7!
1.4! COORDINATION .......................................................................................................................................... 9!
1.5! COMMISSIONING PROCESS ...................................................................................................................... 9!
1.6! RELATED WORK........................................................................................................................................ 11!
1.7! COMMISSIONING COMPLETION............................................................................................................ 11!
1.8! SYSTEMS TO BE COMMISSIONED......................................................................................................... 12!
1.9! RESPONSIBILITIES .................................................................................................................................... 15!
1.10! MEETINGS................................................................................................................................................... 25!
1.11! REPORTING................................................................................................................................................. 25!
1.12! SUBMITTALS .............................................................................................................................................. 25!
1.13! TESTING REQUIREMENTS....................................................................................................................... 26!
1.14! TESTING PREREQUISITES ....................................................................................................................... 26!
1.15! TEST METHODS AND MONITORING..................................................................................................... 27!
1.16! TEST EQUIPMENT ..................................................................................................................................... 27!
1.17! PREFUNCTIONAL CHECKLISTS, START-UP AND INITIAL CHECKOUT........................................ 27!
1.18! FUNCTIONAL PERFORMANCE TESTING & INTEGRATED SYSTEMS TESTING .......................... 29!
1.19! BUILDING ENVELOPE MOCK-UPS AND TESTING ............................................................................. 33!
1.20! BAS EVALUATION .................................................................................................................................... 33!
1.21! DOCUMENTATION, NON-CONFORMANCE AND APPROVAL OF TESTS....................................... 33!
1.22! DEFERRED TESTING................................................................................................................................. 35!
1.23! WRITTEN WORK PRODUCTS .................................................................................................................. 36!
2.0! MECHANICAL (HVAC) TESTING REQUIREMENTS ............................................................ 36!
2.1! AIR HANDLING UNITS – RECIRCULATING ......................................................................................... 37!
2.2! AIR HANDLING UNITS – 100% OUTSIDE AIR AND EXHAUST......................................................... 38!
2.3! EXHAUST FANS ......................................................................................................................................... 39!
2.4! SUPPLY AND EXHAUST FANS................................................................................................................ 40!
2.5! TERMINAL UNITS TEST ........................................................................................................................... 41!
2.6! HYDRONIC (CHILLED WATER) SYSTEM TEST................................................................................... 44!
2.7! HYDRONIC (HOT WATER) SYSTEM ...................................................................................................... 45!
2.8! STEAM SYSTEM TEST .............................................................................................................................. 47!
2.9! FUEL OIL SYSTEM..................................................................................................................................... 48!
2.10! CONTROL SYSTEMS TEST....................................................................................................................... 49!
2.11! TEST AND BALANCE WORK (TAB) TEST............................................................................................. 51!
3.0! PLUMBING TESTING REQUIREMENTS ................................................................................. 53!
3.1! PLUMBING WATER SYSTEM .................................................................................................................. 53!
3.2! LAB WASTE PUMPS .................................................................................................................................. 54!
4.0! FIRE PROTECTION TESTING REQUIREMENTS ................................................................... 55!
4.1! SPRINKLER SYSTEMS .............................................................................................................................. 55!
5.0! ELECTRICAL TESTING REQUIREMENTS.............................................................................. 56!
5.1! PROTECTIVE DEVICE SETTING ............................................................................................................. 56!
5.2! EMERGENCY GENERATOR TEST .......................................................................................................... 57!
5.3! AUTOMATIC TRANSFER SWITCH(ES) TEST ....................................................................................... 58!
5.4! EMERGENCY LIGHTING TEST................................................................................................................ 58!
5.5! FIRE ALARM SYSTEM TEST.................................................................................................................... 59!
5.6! LIGHTING CONTROL SYSTEM TEST..................................................................................................... 60!
6.0! OPERATION AND MAINTENANCE MANUALS .................................................................... 61!
7.0! TRAINING OF OWNER PERSONNEL ...................................................................................... 61!
1.0 GENERAL
B. Responsibility of Disciplines: The parties listed below are part of the commissioning team
and are required to participate in the commissioning process. The responsibilities
relative to commissioning for each of these parties are defined in this section in addition
to those required elsewhere in the contract documents.
1. Architect
2. Engineer
3. Owner
4. Construction Manager
5. General Contractor
6. Mechanical Contractor
7. Plumbing Contractor
8. Electrical Contractor
9. Controls Contractor
10. Testing, Adjusting and Balancing Contractor
11. All subcontractors, vendors and suppliers that are associated with the above
disciplines
1.2 DESCRIPTION
IF PROJECT IS FOLLOWING LEED RATING PROGRAM, REVISE PARAGRAPHS 1.2.B & 1.2.C
BELOW AS APPROPRIATE TO MEET PROJECT REQUIREMENTS
B. This project has a goal of achieving a gold rating using LEED Version 4 and has
implemented the commissioning program to meet the specific requirements of the EA
Fundamental Commissioning and Verification Prerequisite and the EA Enhanced
Commissioning Credit.
• T'#+$.&)(4&)21"#&.$1&0)*'.)%&*0$1&%&'()2"-'(0)-')(4&)#"%%-00-"'-'/)2+*'6)
@..1&00)(4&),"++"5-'/9)
• J"+&0)*'.)1&02"'0-:-+-(-&0<)
• W&*0$1&%&'()1&8$-1&%&'(0)E%&(&10C)2"-'(0C)%&(&1-'/)030(&%0C).*(*)
*##&00G<)
• ;4&)2"-'(0)("):&)(1*#D&.C)5-(4),1&8$&'#3)*'.).$1*(-"'),"1)(1&'.)
%"'-("1-'/<)
• ;4&)+-%-(0)",)*##&2(*:+&)B*+$&0),"1)(1*#D&.)2"-'(0)*'.)%&(&1&.)B*+$&0)
E54&1&)*221"21-*(&C)21&.-#(-B&)*+/"1-(4%0)%*3):&)$0&.)(")#"%2*1&)-.&*+)
B*+$&0)5-(4)*#($*+)B*+$&0G<)
• ;4&)&+&%&'(0)$0&.)(")&B*+$*(&)2&1,"1%*'#&C)-'#+$.-'/)#"',+-#():&(5&&')
030(&%0C)"$(=",=0&8$&'#&)"2&1*(-"')",)030(&%0)#"%2"'&'(0C)*'.)&'&1/3)
*'.)5*(&1)$0*/&)21",-+&0<)
• @')*#(-"')2+*'),"1)-.&'(-,3-'/)*'.)#"11&#(-'/)"2&1*(-"'*+)&11"10)*'.)
.&,-#-&'#-&0<)
• ;1*-'-'/)(")21&B&'()&11"10<)
• 7+*''-'/),"1)1&2*-10)'&&.&.)(")%*-'(*-')2&1,"1%*'#&<)*'.)
• ;4&),1&8$&'#3)",)*'*+30&0)-')(4&),-10()3&*1)",)"##$2*'#3)E*()+&*0()8$*1(&1+3G6)
• X2.*(&)(4&)030(&%0)%*'$*+)5-(4)*'3)%".-,-#*(-"'0)"1)'&5)0&((-'/0C)*'.)/-B&)
(4&)1&*0"'),"1)*'3)%".-,-#*(-"'0),1"%)(4&)"1-/-'*+).&0-/')
AND/OR
71"\&#(0)(4*()0&+&#()U2(-"')Q)%$0()#"%2+&(&)(4&),"++"5-'/)#"%%-00-"'-'/)21"#&006)
H"1)0%*++)21"\&#(0)5-(4)2&*D)#""+-'/)+"*.0)+&00)(4*')OCMMMCMMM)V($]4)E^MM)D_GC)"1)*)("(*+)
#"%2$(&1) 1""%) 2&*D) #""+-'/) +"*.) +&00) (4*') ^MMCMMM) V($]4) EQRP) D_GC) (4&) AF@) %$0()
2&1,"1%)(4&),"++"5-'/)*#(-B-(-&09)
• A"'.$#()*()+&*0()"'&)#"%%-00-"'-'/)B&1-,-#*(-"')1&B-&5)",)(4&)"5'&1Y0)21"\&#()
1&8$-1&%&'(0C):*0-0)",).&0-/'C)*'.).&0-/')."#$%&'(0):&,"1&)%-.=#"'0(1$#(-"')
."#$%&'(0).&B&+"2%&'(<)
• V*#D=#4&#D)(4&)1&B-&5)#"%%&'(0)-')*++)0$:0&8$&'().&0-/')0$:%-00-"'0<)*'.)
• A"'.$#()*')*..-(-"'*+),$++)B&1-,-#*(-"')1&B-&5)*()aP`)#"%2+&(-"')",)(4&).&0-/')
."#$%&'(0)*'.):*0-0)",).&0-/'6)
)
C. In additional to the requirements outlined by the LEED program, commissioning during
the construction phase shall as a minimum, achieve the following specific objectives in
concert with the contract documents:
1. Verify that applicable equipment and systems are installed according to the
manufacturer’s recommendations, to industry accepted minimum standards, per
the contract documents and that they receive adequate operational checkout and
testing by installing contractors and suppliers.
4. Verify that the equipment and systems comply with the contract documents.
Identify non-complying items.
D. The commissioning process does not negate, take away from or reduce the responsibility
of the system designers or installing contractors to provide a finished and fully functioning
product as required by their contracts.
E. This project will have selected building systems commissioned. The Commissioning
Authority will coordinate the commissioning process. All correspondence will flow through
the Construction Manager with copies to the Owner’s Project Manager.
F. Abbreviations: The following are common abbreviations used in the Specifications and in
the commissioning process.
1.3 DEFINITIONS
A. Acceptance Phase - Phase of construction after startup and initial checkout when
functional performance tests, O&M documentation review and training occur.
B. Basis of Design - The basis of design is the documentation of the primary thought
processes and assumptions behind design decisions that were made to meet the design
intent. The basis of design describes the systems, components, conditions and methods
chosen to meet the intent.
E. Data logging - Monitoring flows, currents, status, pressures, etc. of equipment using
stand-alone data loggers separate from the control system.
F. Deferred Functional Tests - FPTs that are performed later, after substantial completion,
due to partial occupancy, equipment, seasonal requirements, design or other site
conditions that disallow the test from being performed.
H. Design Intent - A dynamic document that provides the explanation of the ideas, concepts
and criteria that are considered to be very important to the owner. It is initially the
outcome of the programming and conceptual design phases.
I. Design Narrative or Design Documentation - Sections of either the Design Intent or Basis
of Design.
K. Functional Performance Test (FPT) - Test of the dynamic function and operation of
equipment and systems using manual (direct observation) or monitoring methods.
Functional testing is the dynamic testing of systems (rather than just components) under
full operation. Systems are tested under various modes, such as during cooling or
heating loads, component failures, unoccupied, varying outside air temperatures, fire
alarm, power failure, emergency power, etc. The systems are run through all the control
system’s sequences of operation and components are verified to be responding as the
sequences state. The commissioning authority develops the functional test procedures in
a sequential written form, coordinates, observes and documents the actual testing, which
is performed by the installing contractor or vendor. FPTs are performed after pre
functional checklists and startups are complete.
M. Integrated Systems Test (IST) - Integrated testing verifies the performance of systems
operating in conjunction with one another under various modes of operation conform with
design documents. Final acceptance phase testing of systems interactively, using failure
analysis and "what if" scenarios to determine the ability of systems to provide continuous
and safe operation. ISTs follow successful completion of FPTs.
N. Manual Test - Using hand-held instruments, immediate control system readouts or direct
observation to verify performance (contrasted to analyzing monitored data taken over
time to make the “observation”).
R. Over-written Value - Writing over a sensor value in the control system to see the
response of a system (e.g., changing the outside air temperature value from 50F to 75F
to verify economizer operation). See also “Simulated Signal.”
S. Owner-Contracted Tests - Tests paid for by the Owner outside the contractor’s contract
and for which the CA does not observe. These tests will not be repeated during
functional tests if properly documented.
U. Pre Functional Checklist (PFC) - A list of items to inspect and component tests to conduct
to verify proper installation of equipment, by the contractor. Pre functional checklists are
primarily static inspections and procedures to prepare the equipment or system for initial
operation (e.g., belt tension, oil levels OK, labels affixed, gages in place, sensors
calibrated, etc.). Some pre functional checklist items may entail simple testing of the
function of a component, a piece of equipment or system. The word pre functional refers
to before functional testing. Pre functional checklists augment and are combined with the
manufacturer’s start-up checklist. The commissioning authority only requires that the
procedures be documented in writing, and does not witness the pre functional check
listing.
V. Sampling - Functionally testing only a fraction of the total number of identical or near
identical pieces of equipment.
W. Seasonal Performance Tests - FPT that are deferred until the system(s) will experience
conditions closer to their design conditions.
X. Simulated Condition - Condition that is created for the purpose of testing the response of
a system (e.g., applying a hair blower to a space sensor to see the response in a VAV
box).
Z. Startup - The initial starting or activating of equipment, including executing pre functional
checklists.
AA. Systems Manual – The Systems Manual is intended to be useful in the day-to-day
operations of a facility. The Systems Manual expands the scope of the traditional
operating and maintenance documentation to include the additional information gathered
during the Commissioning Process and to provide a systems-based organization of
information.
BB. Test Procedures - The step-by-step process, which must be executed to fulfill the test
requirements. The CA develops the test procedures.
CC. Test Requirements - Requirements specifying what modes and functions, etc. shall be
tested. The test requirements are not the detailed test procedures.
1.4 COORDINATION
A. Management. The CM will coordinate the efforts of the contractors and vendors so that
the commissioning process is coordinated and completed in advance of substantial
completion except for deferred tests.
6. The Subcontractors shall execute and document the pre functional checklists and
perform prior to startup and initial checkout. The CA may witness start-up of
selected equipment at his option.
7. The CA shall develop specific equipment and system functional performance test
and integrated system test procedures. The Subcontractors shall review the
procedures and plans.
10. The CA shall review the O&M documentation for completeness as prepared by
the subcontractors and vendors.
13. Seasonal testing shall be conducted in the opposite season from functional tests.
B. Building Envelope Review Process. The following narrative provides a brief overview of
the typical building envelope review tasks during construction and the general order in
which they occur.
5. The CA works with the Subs in developing the mock-up program for building
envelope including which configurations should have mock-ups, when they should
be completed, notification requirements of completion, tests to be performed and
who shall witness and evaluate each mock-up.
7. The Subs, under their own direction, will complete mock-ups in accordance with
the building envelope mock-up program and notifies the building envelope team
that the mock-ups are ready for evaluation. The CA evaluates the mock-ups and
documents observations and test results as applicable.
8. The mock-up test procedures are created and executed by the Subs and
witnessed by the CA. Items of non-compliance in material, configuration or
installation are corrected at the Sub’s expense and the system retested.
9. Between the installation of each building envelope component, the CA will perform
a periodic inspection and final punch list inspection of each building envelope
component and document items of non-compliance in material, configuration or
installation.
1. All TAB work and commissioning activities must be complete prior to Functional
Completion, unless approved in writing by the Owner. This includes for all
systems, but is not limited to:
B. Commissioning activities are non-compensable and cannot be a cause for delay claims.
A. The following systems as a minimum shall be commissioned in this project. The matrix
below provides a listing of the systems along with an indication of the responsibility for
each. Preliminary testing requirements are part of this section. Each member of the
commissioning team shall review all test procedures in this section to determine if his/her
presence is required for each test. Certain tests of mechanical equipment may require
the support of electrical personnel and vice versa.
NOTE: Testing listed below does not reduce or eliminate other testing requirements called
for in any other section of this specification document.
1.9 RESPONSIBILITIES
A. All Parties:
1. Attend commissioning meetings.
2. The Contractors that have been awarded this project will be required to use
Facility Grid for the purpose of completion of pre-functional checklists and
for responding to commissioning issues. MIT will provide the Contractors
with access to Facility Grid and required training for effective use of the
software at no cost.
4. These do not take the place or diminish other labeling requirements, such
as BMS designator or P&ID.
B. Architect:
1. Construction Phase
2. Acceptance Phase
C. Design Engineer:
1. Construction Phase
2. Acceptance Phase
3. Turnover Phase
1. Bidding Phase
2. Construction Phase
3. Acceptance Phase
4. Turnover Phase
1. Construction Phase
2. Acceptance Phase
a. Verify that any seasonal or deferred testing and any deficiency issues
are addressed.
1. Construction Phases
l. Address current A/E punch list items before functional testing. Air and
water TAB shall be completed with discrepancies and problems
remedied before functional testing of the respective air- or water-
related systems.
2. Acceptance Phase
G. Mechanical Contractor:
1. Provide start-up for all HVAC equipment, except for the building automation
control system.
3. Install a P/T plug at each water sensor that is an input point to the control system.
4. List and clearly identify on the as-built drawings the locations of all airflow stations.
5. Notify the CM with adequate notice (>= 5 days), who will notify the CA, of time and
date for start-up of each piece of equipment. Be responsible to notify the CM
ahead of time, when commissioning activities not yet performed or not yet
scheduled will delay construction.
H. Controls Contractor:
5) Start-up sequences.
9) Shutdown sequences.
16) Initial and recommended values for all adjustable settings, set
points and parameters that are typically set or adjusted by
operating staff; and any other control settings or fixed values,
delays, etc. that will be useful during testing and operating the
equipment.
c. The schematics will include the system and component layout of any
equipment that the control system monitors, enables or controls, even
if the equipment is primarily controlled by packaged or integral
controls.
d. Provide a full points list with at least the following included for each
point:
1) Controlled system
2) Point abbreviation
3) Point description
4) Display unit
5) Control point or set point (Yes / No)
6) Monitoring point (Yes / No)
7) Intermediate point (Yes / No)
8) Calculated point (Yes / No)
e. Key:
4. The Controls Contractor shall keep the CA informed of all changes to the point list
during programming and setup.
6. Assist and cooperate with the TAB contractor in the following manner:
a. Meet with the TAB contractor prior to beginning TAB and review the
TAB plan to determine the capabilities of the control system toward
completing TAB. Provide the TAB any needed unique instruments for
setting terminal unit boxes and instruct TAB in their use (handheld
control system interface for use around the building during TAB, etc.).
a. System name.
b. List of devices.
4) Plan and process for calibrating valve and damper actuators and
all sensors.
d. A copy of the log and field checkout sheets that will document the
process. This log must include a place for initial and final read values
during calibration of each point and clearly indicate when a sensor or
controller has “passed” and is operating within the contract
parameters.
9. Provide a signed and dated certification to the CM who will forward to the CA
upon completion of the checkout of all controlled devices, equipment and system
prior to functional testing for each piece of equipment or system, that all system
programming is complete as to all respects of the Contract Documents, except
functional testing requirements.
10. Beyond the control points necessary to execute all documented control
sequences, provide monitoring, control and virtual points as requested by the CA
to demonstrate system operation.
11. List and clearly identify on the as-built duct and piping drawings the locations of all
static and differential pressure sensors (air, water and building pressure).
I. TAB Contractor:
2. Three months prior to starting TAB, submit to the CA the qualifications of the site
technician for the project, including the name of the contractors and facility
managers of recent projects on which the technician was lead. The Owner will
approve the site technician’s qualifications for this project.
3. Submit the outline of the TAB plan and approach for each system and component
to the CA and the controls contractor six weeks prior to starting the TAB. This
plan will be developed after the TAB has some familiarity with the control system.
b. All field checkout sheets and logs to be used that list each piece of
equipment to be tested, adjusted and balanced with the data cells to
be gathered for each.
e. Detailed step-by-step procedures for TAB work for each system and
issue: terminal flow calibration (for each terminal type), diffuser
proportioning, branch/sub main proportioning, total flow calculations,
rechecking, diversity issues, expected problems and solutions, etc.
f. List of all airflow, water flow, sound level, system capacity and
efficiency measurements to be performed and a description of specific
test procedures, parameters, formulas to be used.
g. Details of how total flow will be determined (Air: sum of terminal flows
via BAS calibrated readings or via hood readings of all terminals,
supply (SA) and return air (RA) pitot traverse, SA or RA flow stations.
Water: pump curves, circuit setter, flow station, ultrasonic, etc.).
i. Specific procedures that will ensure that both air and water side are
operating at the lowest possible pressures and provide methods to
verify this.
k. Details of whether and how minimum outside air cfm will be verified
and set, and for what level (total building, zone, etc.).
m. Details of methods for making any specified coil or other system plant
capacity measurements.
5. The TAB field technicians shall keep a running log of events and issues. Submit
hand-written reports of discrepancies, deficient or uncompleted work by others,
contract interpretation requests and lists of completed tests to the CA and CM at
least twice a week.
6. Communicate in writing to the controls contractor all set point and parameter
changes made or problems and discrepancies identified during TAB that affect the
control system setup and operation.
7. Provide a draft TAB report within two weeks of completion. A copy will be
provided to the CA. The report will contain a full explanation of the methodology,
assumptions and the results in a clear format with designations of all uncommon
abbreviations and column headings. The report should follow the latest and most
rigorous reporting recommendations by AABC, NEBB or ASHRAE Standard 111.
8. Provide CA with any requested data gathered, but not shown on the draft reports.
9. Provide a final TAB report for the CA with details, as in the draft.
10. Conduct functional performance tests and checks on the original TAB as
specified.
1.10 MEETINGS
A. Kick-Off Meeting:
B. Miscellaneous Meetings:
1.11 REPORTING
A. The CA will provide regular reports to the CM, with increasing frequency as construction
and commissioning progresses.
B. The CA will regularly communicate with all members of the commissioning team, keeping
them apprised of commissioning progress and scheduling changes through memos,
progress reports, etc.
C. Testing or review approvals and non-conformance and deficiency reports are made
regularly with the review and testing as described in later sections.
1.12 SUBMITTALS
A. The CA will review submittals related to the commissioned equipment as it relates to the
commissioning process, to the functional performance of the equipment and adequacy
for developing test procedures. This review is intended primarily to aid in the
development of functional testing procedures.
B. The CA may request additional design narrative from the A/E and Controls Contractor,
depending on the completeness of the design intent documentation and sequences
provided with the Specifications.
C. The O&M manuals and as-builts are the responsibility of the Contractor, though the CA
will review.
A. Specific functional testing requirements are provided for a majority of systems found in
the project. From these requirements, the CA will develop step-by-step procedures to be
executed by the Subs. Additional testing requirements shall be provided by the CA for
those systems not detailed herein. The test requirements for each piece of equipment or
system contain the following:
B. The testing requirements specified for commissioning are in addition to and do not
replace any testing requirements specified elsewhere.
A. The following applicable generic prerequisite checklist items are required to be completed
and checked off by the contractors prior to functional testing.
1. All related equipment has been started up and start-up reports and pre functional
checklists submitted and approved.
3. All control system functions for this and all interlocking systems are programmed
and operable per contract documents, including final set points and schedules
with debugging, loop tuning and sensor calibrations completed. Controls
contractor to sign and date when ready.
4. Test and balance (TAB) complete and approved for the HVAC air and water
systems.
1. Manual test method is a method of testing that requires visual inspection of the
device performing as intended.
A. The Division contractor shall provide all testing equipment required to perform startup,
initial checkout and functional performance testing.
B. Special equipment, tools and instruments (only available from vendor, specific to a piece
of equipment) required for testing equipment, according to these Contract Documents
shall be included in the base bid price to the Contractor and left on site.
C. All testing equipment shall be of sufficient quality and accuracy to test and/or measure
system performance with the tolerances specified in the Specifications.
1. Pre-Functional Checklists (PFCs) are required to verify that the equipment and
systems are hooked up and operational. It ensures that functional performance
testing may proceed without unnecessary delays. Each piece of equipment shall
receive full pre functional checkout. No sampling strategies are to be used. The
PFCs for a given system must be successfully completed prior to formal functional
performance testing of equipment or subsystems of the given system.
2. Prior to startup, the execution of the PFCs are directed and executed by the Subs.
3. Only individuals that have direct knowledge of the piece of equipment for which
the PFC is being filled shall initial or check off items on that sheet. It is not
acceptable for witnessing supervisors to fill out these forms.
2. The primary role of the CA in this process is to verify that there is written
documentation that each of the manufacturer-recommended procedures have
been completed. Parties responsible for pre functional checklists and startup are
identified in the commissioning scoping meeting and in the checklist forms.
Parties responsible for executing functional performance tests are identified in the
testing requirements for each system.
3. The subcontractor responsible for the purchase of the equipment shall develop
the full start-up plan by combining the manufacturer’s detailed start-up and
checkout procedures from the O&M manual and the normally used field checkout
sheets. The plan shall include checklists and procedures with specific boxes or
lines for recording and documenting the checking and inspections of each
procedure and a summary statement with a signature block at the end of the plan.
5. The subcontractor shall submit the full startup plan to the CA for review.
6. The CA will review the procedures and the format for documenting them.
1. All field-installed temperature, relative humidity, CO, CO2 and pressure sensors
and gages, and all actuators (dampers and valves) on all equipment shall be
calibrated using approved methods. Sensors provided with calibration certification
need not be field calibrated.
2. All procedures used shall be fully documented on the pre functional checklists or
other suitable forms, clearly referencing the procedures followed and written
documentation of initial, intermediate and final results.
1. For all valve and damper actuator positions checked, verify the actual position
against the BAS readout.
F. Execution of Startup:
1. The Subs and vendors shall execute startup, complete the start-up checklist(s),
and provide the materials to the prime Contractor. The prime Contractor will
provide the CA with a signed and dated copy of the completed start-up checklists.
2. Only individuals that have direct knowledge and witnessed that a line item task on
the start-up checklist was actually performed shall initial or check that item off. It
is not acceptable for witnessing supervisors to fill out these forms.
1. The Subs shall clearly list any outstanding items of the initial start-up and pre
functional procedures that were not completed successfully, at the bottom of the
procedures form or on an attached sheet. The procedures form and any
outstanding deficiencies are provided to the CA within two days of checklist
completion.
2. The CA will review the report. When satisfactorily completed, the CA will
recommend approval of the execution of the checklists and startup of each system
to the CM using a standard form.
3. Items left incomplete, which later cause deficiencies or delays during functional
testing may result in back charges to the responsible party.
B. The parties responsible to execute each test are listed with each test.
1. The Functional Performance Testing (FPT) shall demonstrate that each system is
operating according to the design intent and Contract Documents. Functional
testing facilitates bringing the systems from a state of substantial completion to full
dynamic operation. Additionally, during the testing process, areas of deficient
performance shall be identified and corrected, improving the operation and
functioning of the systems.
1. Before test procedures are written, the CA shall obtain all requested
documentation and a current list of change orders affecting equipment or systems,
including an updated points list, program code, control sequences and
parameters.
2. The CA shall develop specific test procedures and forms to verify and document
proper operation of each piece of equipment and system. Each Sub or vendor
responsible to execute a test shall provide assistance to the CA in developing the
procedures (answering questions about equipment, operation, sequences, etc.).
Prior to execution, the CA shall provide a copy of the test procedures to the
Sub(s) who shall review the tests for feasibility, safety, equipment and warranty
protection.
4. The test procedure forms developed shall include (but not be limited to) the
following information:
E. Test Methods:
2. Simulated Conditions:
3. Overwritten Values:
5. Setup:
6. Sampling:
3) If 10% of the units in the second sample fail, test all remaining
units in the whole group.
1. The Subs shall provide sufficient notice to the CA and CM regarding their
completion schedule for the startup of all equipment and systems. The CA will
schedule FPTs through the CM and affected Subs. The CA shall direct, witness
and document the FPTs and ISTs of all equipment and systems. The Subs shall
execute the tests.
2. In general, FPTs are conducted after PFCs and startups have been satisfactorily
completed. The control system is sufficiently tested and approved by the CA
before it is used for TAB or to verify performance of other components or systems.
G. Problem Solving:
b. Prerequisites
1) All equipment and systems testing per Divisions 21, 22, 23, 25
and 26 are complete and approved.
2) The BAS will be used to record the system data and the dynamic
step response data. Where BAS points are not available
manually recorded parameters will be acceptable.
3) The balancing of all related components and installed systems
will be complete and test results shall be available.
c. Procedure
1) Conduct testing as described in the final test report.
2) The effects on the systems relating to the various operational
and failure conditions will be monitored, recorded and response
times noted. The variables will be measured on a real time basis
and utilizing the collected data fine tuning adjustments to the
systems will be implemented.
3) All test results will be presented in both graphic form and trend
printout and provided in two electronic data file formats (CSV
and PDF). The controls contractor will provide the trending data
from their system.
A. The CA shall review all BAS graphic screens for correctness and completeness. This
includes verifying, but is not limited to, the following:
1. Accuracy of graphics to installed system. (Does it accurately depict the system
and operation as provided?)
2. Accuracy of sensor readings. (I.e. Do the readings correspond to the correct
sensor in the field and are those readings accurate?)
3. Existence of active alarms or errors on the system. (Verify alarm delays)
4. Consistency of graphic pages and links. (Are there the same points/ links on
similar pages?)
5. Correctness and completeness of page links. (Links take you to correct location
and that location has all the required information.)
A. Documentation:
1. The CA shall witness and document the results of all FPTs using the specific
procedural forms developed for that purpose. Prior to testing, these forms are
provided to the CM and Subs for review.
B. Non-Conformance:
1. The CA will record the results of the FPT on the procedure or test form. All
deficiencies or non-conformance issues shall be noted and reported to the CM on
an agreed upon non-compliance form. This form may be the CA’s master
deficiency and resolution log.
2. Corrections of minor deficiencies identified may be made during the tests at the
discretion of the CA. In such cases the deficiency and resolution will be
documented on the procedure form.
3. Every effort will be made to expedite the testing process and minimize
unnecessary delays, while not compromising the integrity of the procedures.
However, the CA will not be pressured into overlooking deficient work or loosening
acceptance criteria to satisfy scheduling or cost issues.
4. As tests progress and a deficiency is identified, the CA discusses the issue with
the executing contractor.
3) If the deficiency is identified during the retest, the cost for that
retest, as well as any other retest effort, will be as indicated below in
Item 8 – Cost of Retesting.
6. The CA retains the original non-conformance forms until the end of the project.
7. Any required retesting by any contractor shall not be considered a justified reason
for a claim of delay or for a time extension by the prime contractor.
8. Cost of Retesting:
a. The cost for the Sub to retest a pre functional or functional test, if they
are responsible for the deficiency, shall be theirs. If they are not
responsible, any cost recovery for retesting costs shall be negotiated
with the CM.
b. The added time for the CA and CM to direct any retesting required
because a specific start-up test item, reported to have been
successfully completed by the installing contractor, but determined
during FPTs or ISTs to be faulty, may be back charged to the
contractor responsible for the misinformation or deficiency.
C. Approval:
1. The CA notes each satisfactorily demonstrated function on the test form. Formal
approval of the functional test is made later after review by the CA and by the CM,
if necessary. The CA recommends acceptance of each test to the CM using a
standard form. The CM gives final approval on each test using the same form,
providing a signed copy to the CA and the Contractor.
1. If any check or test cannot be completed due to the building structure, required
occupancy condition or other deficiency, execution of checklists and functional
testing may be delayed upon approval of the PM. These tests will be conducted
in the same manner as the seasonal tests as soon as possible. Services of
necessary parties will be negotiated.
B. Seasonal Testing:
1. During the Acceptance Phase, seasonal testing (tests delayed until weather
conditions are closer to the system’s design) shall be completed as part of this
contract. The CA shall coordinate this activity. Tests will be executed,
documented and deficiencies corrected by the appropriate Subs, with facilities
staff and the CA witnessing. Any final adjustments to the O&M manuals and as-
builts due to the testing will be made.
“design” is indicated in the procedure, it means that the season is within 5°F of the
ASHRAE 2-1/2% design criteria or 95% of the loading design.
Product Developed By
1. Commissioning meeting minutes CA
2. Commissioning schedules CM with input from the CA
3. Complete commissioning plan CA
4. Equipment documentation submittals Subcontractors and vendors
5. Sequence clarifications Subcontractors and A/E as needed
6. Basis of design documentation A/E
7. Equipment startup and initial checkout plan Subcontractors and vendors, review
by CA
8. Write PFCs CA with primary input from
subcontractors
9. Executed PFCs Subs
10. TAB plan TAB subcontractor with verification
by CA and Owner
11. Final TAB report TAB with verification by CA and Owner
12. Certificates of Readiness GC and Installing Subs
13. Write functional performance tests CA with primary input from
subcontractors
14. Executed functional performance tests Subcontractors with verification by CA
15. Write integrated systems testing protocols CA with input from subcontractors and
A/E
16. Executed integrated systems testing Subcontractors with verification by CA
17. Corrective action tracking log (deficiencies) CA
18. Commissioning progress record CA
19. Deficiency reports CA
20. Owner Training Plan Subcontractors approved by CA
21. O&M manuals Subcontractors approved by CA
22. Warranty List Subcontractors approved by CA
23. Systems Manual CA
24. Final commissioning report CA
The following sections depict minimum requirements for the functional performance and
integrated system testing executed for this facility. It is up to the CA to determine how the
following is accomplished and whether additional testing is required based on the final design.
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
C. Prerequisites:
1. The applicable prerequisite checklist shall be signed off prior to functional testing.
The commissioning agent may also spot-check misc. items and calibrations on the
pre functional checklists before the beginning of functional testing.
E. Special Procedures (other equipment to test with, etc.; reference to function ID): None
1. For the conditions, sequences and modes tested, the system, integral
components and related equipment respond to varying loads and changing
conditions and parameters appropriately as expected, as specified and according
to acceptable operating practice.
B. Integral Components or Related Equipment Being Tested: Pre functional checklists must
be complete for all of the components listed below prior to performing this functional test.
C. Prerequisites:
1. The applicable pre functional checklist items shall be signed off prior to functional
testing. The commissioning agent may spot-check misc. items and calibrations on
the pre functional checklists before the beginning of functional testing.
E. Special Procedures (other equipment to test with, etc.; reference to function ID): None
OR Verify ventilation balancing and relative pressurization of spaces.
1. For the conditions, sequences and modes tested, the system, integral
components and related equipment respond to varying loads and changing
conditions and parameters appropriately as expected, as specified and according
to acceptable operating practice.
1. Hood exhaust
2. Specialty exhaust
3. Miscellaneous exhaust
C. Integral Components or Related Equipment Being Tested: Pre functional checklists must
be complete for all of the components listed below prior to performing this functional test.
1. Controls
2. Terminal equipment
D. Prerequisites The applicable prerequisite checklist items shall be signed off prior to
functional testing. The commissioning agent may spot-check misc. items and calibrations
on the pre functional checklists before the beginning of functional testing.
F. Special Procedures (other equipment to test with, etc.; reference to function ID)
1. None.
1. For the conditions, sequences and modes tested, the fans, integral components
and related equipment respond to changing conditions and parameters
appropriately as expected, as specified and according to acceptable operating
practice.
H. Sampling Strategy: Test all hood and specialty exhaust (as applicable)
Test 25% minimum of miscellaneous exhaust units.
C. Integral Components or Related Equipment Being Tested: Pre functional checklists must
be complete for all of the components listed below prior to performing this functional test.
1. None
D. Prerequisites: The applicable prerequisite checklist items shall be signed off prior to
functional testing. The commissioning agent may spot-check misc. items and calibrations
on the pre functional checklists before the beginning of functional testing.
F. Special Procedures (other equipment to test with, etc.; reference to function ID)
1. None
1. For the conditions, sequences and modes tested, the fans, integral components
and related equipment respond to changing conditions and parameters
appropriately as expected, as specified and according to acceptable operating
practice.
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
1. Constant volume and VAV boxes w/and w/o reheat coils (supply and exhaust)
2. Laboratory supply and exhaust flow controls
3. Fan coil units (FCU, FCW, FCH, FCA)
4. Radiation (FTR)
5. Chilled Beams
6. Unit heaters (UH, CUH, RR, PR)
7. In duct heating coils (RHC)
8. Return air systems
9. Heat Exchanger and Pumps (HW)
C. Prerequisites:
1. The applicable prerequisite checklist items shall be signed off prior to functional
testing. The commissioning agent may also spot-check misc. items and
calibrations on the pre functional checklists before the beginning of functional
testing.
E. Special Procedures (other equipment to test with, etc.; reference to function ID):
1. For the conditions, sequences and modes tested, the TU, integral components
and related equipment respond to varying loads and changing conditions and
parameters appropriately as expected, as specified and according to acceptable
operating practice.
2. Space temperature during occupied modes shall average within +/- 1°F of set
point and always remain within 1°F of the ends of the dead band without
excessive hunting of the coil valve or complaints of drafts or stuffiness from
occupants.
2. For all other terminal units of the same type and function, but different in size, are
considered identical for sampling purposes.
a. Testing:
b. Monitoring:
1. Electrical Contractor
2. Controls Contractor: Operate the controls, as needed
3. HVAC mechanical contractor or vendor: Assist in testing sequences
4. CA: To witness and document testing
5. Balancing Contractor to verify flows
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
a. Chilled water
b. Chilled Beam active and passive systems
c. Chilled Beam water/pumps
d. Distribution Equipment (AHU, AC, FCU, FCW, FCH, FCA)
C. Prerequisites:
E. Special Procedures (other equipment to test with, etc.; reference to function ID):
1. None.
1. For the conditions, sequences and modes tested, integral components and related
equipment respond to varying loads and changing conditions and parameters
appropriately as expected, as specified and according to acceptable operating
practice.
2. Heat exchanger shall maintain the water set point to within +/- 3.0F of set point
dead band without excessive hunting.
3. Pumping system and controls shall maintain the current desired pressure set point
to within an amount equal to 10% of the set point value either side of the dead
band without excessive hunting.
a. Lab heating
b. Radiation heating
2. Heat exchangers
3. Pumps, AD, ET
4. VFD
E. Special Procedures (Other equipment to test with, etc.; reference to function ID)
1. For the conditions, sequences and modes tested, the heat exchangers, integral
components and related equipment respond to varying loads and changing
conditions and parameters appropriately as expected, as specified and according
to acceptable operating practice.
2. Maintain the supply water set point to within +/- 3.0F of set point dead band
without excessive hunting.
3. Pumping system and controls shall maintain the current desired pressure set point
to within an amount equal to 10% of the set point value either side of the dead
band without excessive hunting.
1. Electrical Contractor
2. Controls Contractor: Operate the controls, as needed
3. HVAC mechanical contractor or vendor: Assist in testing sequences
4. CA: To witness and document testing
5. Balancing Contractor to verify flows
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
C. Prerequisites:
E. Special Procedures (other equipment to test with, etc.; reference to function ID):
1. For the conditions, sequences and modes tested, integral components and related
equipment respond to varying loads and changing conditions and parameters
appropriately as expected, as specified and according to acceptable operating
practice.
2. Heat exchanger shall maintain the supply water set point to within +/- 3.0F of set
point dead band without excessive hunting.
3. Pumping system and controls shall maintain the current desired pressure set point
to within an amount equal to 10% of the set point value either side of the dead
band without excessive hunting.
C. Prerequisites:
E. Special Procedures (other equipment to test with, etc.; reference to function ID): None.
1. For the conditions, sequences and modes tested, the system, integral
components and related equipment respond to varying loads and changing
conditions and parameters appropriately as expected, as specified and according
to acceptable operating practice.
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
C. Prerequisites:
1. The applicable prerequisite checklist shall be listed checked off prior to functional
testing. The commissioning agent may also spot-check misc. items and
calibrations on the pre functional checklists previously completed by the installer,
before the beginning of functional testing.
D. A significant part of the BAS functional testing requirements is the successful completion
of the functional tests of equipment the BAS controls or interlocks with. Uncompleted
equipment functional tests or outstanding deficiencies in those tests lend the required
BAS functional testing incomplete.
E. Integral or stand-alone controls are functionally tested with the equipment they are
attached to, including any interlocks with other equipment or systems and thus are not
covered under the BAS testing requirements, except for any integrated functions or
interlocks listed below.
F. In addition to the controlled equipment testing, the following tests are required for the
BAS, where features have been specified.
G. Special Procedures (other equipment to test with, etc.; reference to function ID): None
OR Process line equipment is not fully defined at this time, additional testing of that
equipment may be required at a later date and will be done using an hourly rate or by a
fixed price should the scope be clearly defined.
1. For the conditions, sequences and modes tested, the BAS, integral components
and related equipment respond to changing conditions and parameters
appropriately as expected, as specified and according to acceptable operating
practice.
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
1. TAB water-side
2. TAB air-side
3. TAB equipment and systems
4. TAB electrical
C. Prerequisites
1. The applicable prerequisite checklist items shall be checked off prior to functional
testing. The commissioning agent may also spot-check misc. items and
calibrations on the pre functional checklists previously completed by the installer,
before the beginning of functional testing.
D. Purpose:
1. The purpose of this test is to spot check the TAB work to verify that it was done in
accordance with the contract documents and acceptable practice and that the
TAB report is accurate.
E. The following tests and checks will be conducted. The following testing requirements are
in addition to and do not replace any testing requirements elsewhere in this Specification.
F. Special Procedures (other equipment to test with, etc.; reference to function ID): None
a. For air flow of supply and return: a deviation of more than 10% of
instrument reading
b. For minimum outside air flow: 20% of instrument reading (30% for
reading at intermediate supply flow for inlet vane or VFD OSA
compensation system using linear proportional control)
d. For air and water pressures: a deviation of more than 10% of full
scale of test instrument reading
The following sections depict minimum requirements for the functional performance and
integrated system testing executed for this facility. It is up to the CA to determine how the
following is accomplished and whether additional testing is required based on the final design.
b. Recirculating pumps
C. Prerequisites: The applicable prerequisite checklist items shall be checked off prior to
functional testing. The commissioning agent may also spot-check misc. items and
calibrations on the pre functional checklists previously completed by the installer, before
the beginning of functional testing.
E. Special Procedures (other equipment to test with, etc.; reference to function ID)
1. None
F. Required Monitoring
1. None
C. Prerequisites: The applicable prerequisite checklist items shall be checked off prior to
functional testing. The commissioning agent may also spot-check misc. items and
calibrations on the pre functional checklists previously completed by the installer, before
the beginning of functional testing.
E. Special Procedures (other equipment to test with, etc.; reference to function ID)
1. None
F. Required Monitoring
1. None
The following sections depict minimum requirements for the functional performance and
integrated system testing executed for this facility. It is up to the CA to determine how the
following is accomplished and whether additional testing is required based on the final design.
B. Prerequisites: The applicable prerequisite checklist items shall be checked off prior to
testing. The commissioning agent may also spot-check misc. items and calibrations on
the checklists previously completed by the installer, before the beginning of testing.
D. Special Procedures (other equipment to test with, etc.; reference to function ID)
E. Required Monitoring
1. None
The following sections depict minimum requirements for the functional performance and
integrated system testing executed for this facility. It is up to the CA to determine how the
following is accomplished and whether additional testing is required based on the final design.
1. Electrical Contractor
2. CA: To witness and document testing
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
C. Prerequisites:
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
1. Generator Motor
2. Generator Cooling System
3. Generator Fuel System
4. Phase Rotation
C. Prerequisites:
1. For the conditions, sequences and modes tested, the generator, integral
components and related equipment respond to varying loads and changing
conditions and parameters appropriately as expected, as specified and according
to acceptable operating practice.
F. Sampling Strategy
1. No sampling.
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
C. Prerequisites:
E. Acceptance Criteria
1. Acceptance is achieved when all functions of the specified system have been
demonstrated.
1. Electrical Contractor
2. CA: To witness and document testing
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
C. Prerequisites:
E. Acceptance Criteria
1. Acceptance is achieved when all functions of the specified system have been
demonstrated.
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
C. Prerequisites:
1. Acceptance is achieved when all requirements of NFPA 72.B&20 met and test
reports provided.
B. Integral Components or Related Equipment Being Tested: Pre functional tests must be
complete for all of the components listed below prior to performing this functional test.
1. Occupancy sensors
C. Prerequisites:
1. Units of the same type and function, but different in size, are considered identical
for sampling purposes.
2. Testing:
1. The specific content and format requirements for the standard O&M manuals are
detailed in each Section.
2. CA Review:
A. The CA shall be responsible for overseeing and coordination the training of Owner
personnel for commissioned equipment including the content and adequacy of the
training. The CM shall be responsible for training execution and scheduling and
ultimately for ensuring that training is completed.
C. No later than 30 days in advance of the scheduled training, building tours shall be given
to Owner’s personnel. CM representative, knowledgeable with the systems, shall be
available to accompany the tours. These tours will include the following systems at a
minimum:
i. 2 tours for HVAC / Mechanical Technicians
ii. Create a preliminary training plan that includes scheduling, training agenda
requirements and other pertinent information.
1. Each Sub and vendor responsible for training will submit a written
training agenda to the CA for review and approval prior to training. The
agenda will cover the following elements (as applicable):
i. Diagnostic instructions.
iii. Trainers must be well versed in the systems and equipment in which they are
providing training, as well as be familiar with the installation and operation of
those on this particular project. (Note: If factory representatives are used for
equipment training, but they did not install the equipment, the session shall be
supplemented by a representative of the installing contractor.)
iv. Each discipline shall receive a minimum of 4 training sessions. They shall be
as follows:
st rd
1. 2 sessions for 1 /3 shift personnel (to start at 7:30am)
v. At least one session of each training topic shall be digitally recorded for
Owner’s use after the completion of the training program. These training
videos shall be turned over with the O&M documents.
2. Video files that contain more than one training session (I.e. all HVAC
related equipment and systems are in one file), the file is to be
electronically indexed (tabbed) so each individual session can be found
easily and immediately accessed.
3. If multiple videos are taken during a single training session, the video
files are to be combined into a single video file. Multiple files per
equipment/system are not acceptable.
c. The design engineer shall assist in training for the Owner. At the
beginning of each discipline training session, the design
engineer shall present an overall system design concept
overview and shall include a review of all systems using the
simplified system schematics (one-line drawings) including boiler
water systems, AHU systems, heating systems, fuel gas supply
systems, supply air systems, exhaust system and outside air
strategies, dust collection and BAS system.
May 2018
Table of Contents
2.! SAFETY..................................................................................................................... 3!
+#"! ,'-./-)0!($1,)(################################################################################################################################# *!
+#+! .122!3141&0(###################################################################################################################################### 5!
+#*! ./6)0!2100)&( ##################################################################################################################################### 7!
+#8! (9:2/;3<( ########################################################################################################################################### 7!
+#=! >/-0'>!>1(3/-; ############################################################################################################################## ?!
+#@! )A)&;)-,:!):)>1(3)(!1-0!(3'>)&( ################################################################################################### ?!
+#5! ./&)!$&'<),</'-!1-0!2/.)!(1.)<:!.)1<%&)( ########################################################################################## "8!
+#7! .21AA1B2)!C!,'AB%(</B2)!2/D%/0!1-0!,3)A/,12!(<'&1;) #################################################################### "8!
+#?! ./&)!)6</-;%/(3)&( ############################################################################################################################ "?!
+#"E! 3'/(<(!1-0!2/.</-;!)D%/$A)-<######################################################################################################### +E!
+#""!! .2''&!0&1/-( ################################################################################################################################ +E!
+#"+!! 0)(/;-!'.!A),31-/,12!&''A(C($1,)( ############################################################################################ +"!
)-0!
1.1 Purpose
The purpose of these guidelines is to provide specific MIT requirements and background on
design issues that relate to Environment, Health and Safety (EHS). MIT expects Architects,
Engineers, and Designers to design campus buildings and renovations that meet building codes
and regulatory standards while providing safe and healthy environments for occupants and
maintenance personnel.
2. SAFETY
1. OSHA 29 CFR1910.146.
All structures shall be designed to eliminate or minimize the number of confined spaces. A
confined space is an area that meets the following three requirements:
1. The space is large enough for an employee to enter and perform assigned work;
2. The space has limited or restricted means for entry or exit; and
3. The space is not designed for continuous employee occupancy.
A confined space can have hazards that make them significantly more dangerous to enter. These
spaces are considered “permit required” confined spaces, which means one or more of the
following characteristics exist:
When the creation of a permit required confined space is unavoidable, one or more of the
following actions should be taken to reduce the hazards associated with the space.
a. Allow workers to enter without having to contort their bodies, crawl, or use their
hands to climb in or out.
b. Provide large access openings, such as standard doorways, through which
workers can pass easily and quickly.
c. Provide standard overhead clearances so that workers can stand in the space
whenever possible.
d. Install standard steps with handrails in lieu of ladders or spiral staircases. Steps
allow safer, unrestricted entry and exit from the space.
e. Provide sufficient aisle clearances within the space and provide clear access to
openings and exits.
f. Locate pipes, ducts and other equipment so workers do not have to climb over,
under or around them.
g. Provide multiple access openings at regular intervals in long spaces, such as
crawl spaces and tunnels, to ensure that employees’ ability to exit the space is not
restricted by distance.
h. House equipment in buildings above ground with a standard doorway for access
rather than placing equipment in a vault below grade.
1. Install critical equipment (valves, gauges, etc.) that require periodic operation, inspection,
or maintenance outside the space so that entry will not be necessary.
2. Extend valve handles so they can be operated from outside the confined space.
3. Use flexible components and install retrieval systems for items that are located at the
bottom of the confined space (e.g., sump pump) so they can be removed and serviced
without entry.
4. Install extension tubes and fittings to make lubrication possible from outside the confined
space.
5. Install catch baskets at the bottoms of tanks or other spaces that can be raised to retrieve
fallen parts to prevent the need to enter the confined space.
6. Use remote monitoring systems (cameras, gas detection, leak detection, wireless meter
readers, etc.) to obtain information while outside the space.
7. Select mechanical equipment for maximum service life and minimal maintenance
requirements to reduce the number of entries required. Over the long term, the additional
cost of such equipment may pale in comparison to the cost of routine confined space
entry.
8. Install viewing and cleaning ports in tanks and other equipment so that the interiors can
be seen and cleaned without entering the space.
1. If entry into a particular confined space will never be required, modify the space to make
entry impossible.
2. Make access openings too small for a person to fit through.
3. If existing access openings are large enough to pass through, seal the openings using
security locks, weld openings shut and so on, or block openings by installing grating
across the opening.
a. Prevent entry and accumulation of organic debris that could decompose and lead
to oxygen deficiency or the generation of toxic gases.
b. Prevent moisture and water intrusion that could cause rusting and lead to oxygen
deficiency. If this is not possible, use materials that do not rust or seal materials
with a rust preventer.
c. Eliminate the placement of piping or conduit containing hazardous materials,
gases, chemicals, or sewage in the confined space. Where pipes do enter the
space, provide means to drain, purge, and blank any piping. Use welded joints on
any piping that will carry hazardous materials to prevent leakage.
1. If confined spaces cannot be eliminated, the space should be designed to facilitate non-
entry rescue to the extent feasible.
Structures should be designed to eliminate fall hazards during routine and non-routine use,
maintenance, repairs, and all other purposes. Where exposure to fall hazards are unavoidable, the
hazards involved in working at heights above 4 feet, including roof tops and loading docks,
should be minimized by incorporating the following into the building design:
1. Eliminate the hazard: Avoid work at height where possible or locate plant and equipment
in safe locations where there is no risk of a fall.
2. Guard the hazard: When working at height is essential, ensure that workers are not
exposed to unnecessary risks, consider providing a parapet or guardrail to eliminate the
fall hazard.
3. Protect the worker: Where it is not possible to eliminate the risk of falling, use a suitable
fall protection system to minimize the consequences of a fall. This can be achieved with a
fall arrest or fall restraint system–two completely different entities, as long as it provides
protection along entire route.
a. Fall Restraint:
i. These systems allow a person access to conduct their duties but prevent
them from reaching a point where a fall could occur.
ii. Fall Restraint systems are generally suitable if the person needs to work
at the edge of a hazard. For example, where there is a need to maintain
gutters along the edge of a roof, or if there are other potential fall hazards
such as a fragile roof, roof lights or air vents.
iii. If fitting a fall restraint system, it is recommended that the system should
be tested to fall arrest loads to ensure a person’s safety in situations
where the system may be misused (i.e. when the person using it wears an
over-length lanyard to enable access to the edge of a roof).
iv. Restraint systems are generally positioned more than 6 feet from the
hazard. This is because common practice is for the worker to be
connected to the system by a fixed length 4 foot lanyard.
b. Fall Arrest:
ii. Where guardrails are not feasible, install permanent fall arrest anchor
points for the use of personal fall protection equipment. Anchorages to
which personal fall arrest equipment is attached shall be capable of
supporting at least 5,000 pounds per employee.
Where it is necessary to install a fixed ladder, it shall comply with the OSHA standard 29 CFR
1910.27. It shall also be constructed in accordance with ANSI standard A14.3-2002. These
standards prescribe minimum requirements for design, construction, and use of fixed ladders. It
also sets forth requirements for cages, wells, and ladder safety systems used with fixed ladders, in
order to minimize personal injuries. Where cages or wells are not feasible, fall arrest anchors
shall be designed to protect against falls.
2.4 Skylights
Skylights shall be designed to prevent people from falling through them. OSHA concludes that,
“a skylight shall be regarded as a hatchway, i.e., an opening in the roof of a building through
which persons may fall.” (29 CFR 1910.23(a)(4)). Therefore, OSHA regulations require that
skylights shall be guarded by a standard skylight screen, skylight that has the same load
requirements of a screen or a fixed standard railing on all exposed sides.
Roof anchors are to be installed on all new buildings that require windows to be washed by
suspended scaffolds, boatswain’s chair, rope descent system or other suspended system. An
engineered drawing showing anchors, and their weight limits must be provided.
All anchors must be pull tested and commissioned by a qualified party as part of the installation.
Meet or Exceed the Following Standards. Refer also to the Plumbing Division - 22 and the
Lab Design Thematic Folder of the MIT Design Standards.
Introduction
Emergency eyewashes and showers are to be installed in all laboratories and other types of non-
lab work areas, which have hazards that include but are not limited to those listed below. In lab
buildings, if the current hazards do not trigger the need for this equipment, piping shall be
installed during the current renovation (left capped at either end to avoid “dead legs” and labeled
for future use). This is to facilitate installation of eyewashes and/or showers when hazards
change (often before the renovation is completed or soon after) or during a future space change.
The goal is to reduce the cost of, time involved, and impact of the installation on the users.
This covers almost every lab, lab support space, and maker space and workshop at MIT.
Coordinate location of emergency eyewashes and showers with fume hoods and with floor
drains, to minimize the potential for spills from fume hoods entering drains.
Equipment Specifications
1. The lever that is pushed, pulled or squeezed to activate the eyewash/ shower should be
designed to remain on without requiring the use of the operator’s hands. It should be
easy to operate in an emergency.
2. The water or fluid should flow until intentionally shut off or until the specified amount
has been discharged.
Eyewashes
1. Fluid should be provided to both eyes simultaneously via two nozzles or other means.
2. Nozzle protection should automatically come off when the water/ fluid starts to flow.
3. Eyewashes must be located where they can be effectively used hands free once the unit is
engaged. Provide accessible clearances and heights for users with disabilities.
4. There are access limitations with some sink-mounted eyewashes for individuals who
Showers
A water flow sensor reporting to the BMS shall be installed on all emergency showers located in
public hallways or in remote locations such as mechanical rooms where hazardous chemicals are
used and stored such as pH neutralization spaces.
If an emergency shower is chosen that is activated by a handle that hangs down, the end of the
long shower handle should hang as close to the wall and as far away from the path of travel as
possible to prevent inadvertent activation and head injuries. Acceptable Options:
Some of the Specifications for the Water or Fluid Supply are Described Below.
527 CMR
10.02 248
CMR 10.13
Water/Fluid Potable water, preserved water, saline solution or any medically acceptable solution
Quality (ANSI) potable water (527 CMR 10.02, 248 CMR 10.13)
Control valve Valve should be the on/off type designed to remain activated until intentionally shut off
Prevent Installing equipment in a manner that prevents the stagnation of water in the piping 248
stagnation CMR 10 section (l) 5
Select location that is adjacent to the hazard but there must be enough room so that the victim and
emergency responders will be safe. For example, installing an eyewash/ shower “immediately
adjacent” to an exhaust hood is not recommended. The emergency shower and eyewash unit must
be located on the same level of the hazard and the path of travel must be free of obstructions that
would inhibit the immediate use of the equipment. Doors to the eyewash or shower must swing in
that direction. For strong acid and strong caustic hazards the eyewash unit should be immediately
adjacent to the hazard.
The ANSI standard for Emergency Eyewash and Shower Equipment specifies the distance of the
unit from the standing surface and the wall (or the nearest obstruction). This is to ensure that the
unit will be reachable by any user and that the user will not be injured.
Emergency showers should be located within the laboratory as close to the main door as possible.
This minimizes water possibly being sprayed on to electrical equipment that may be in the lab
and it is less likely that items will block access to the shower.
No obstructions, protrusions, or sharp objects shall be located within 16 inches from the center of
the spray pattern of the emergency shower. Electrical apparatus, telephones, thermostats or
power outlets should not be located within 18 inches of either side of the emergency shower or
eyewash.
In specific limited cases where the equipment is to be installed outside the lab, the lab door must
swing out and the doorway must be recessed so pedestrians will not be hit by the door. The
emergency shower and eyewash unit must be located on the same level of the hazard and the path
of travel must be free of obstructions that would inhibit the immediate use of the equipment.
Code/Regulatory Citations
29CFR
1910.151(c)
ANSI In accessible locations that require no more than 10 seconds to reach (…), on the same
level as hazard (i.e. on the same floor). The path of travel (to the safety equipment) should
Z358.1-2009 be free of obstructions (i.e. locked doors, boxes, etc.). It is acceptable to go through an
7.7.4 and 4.6.1 unlocked door.
For a strong acid or caustic, (it) should be immediately adjacent to the hazard.
527 CMR Should not be located greater than 50’from an experimental area
10.02 (2)
248 CMR
10.13
Emergency wash equipment that meets the ADA requirements should be installed when new
buildings are constructed or when the building is renovated. Designers of new labs should refer to
the Massachusetts Access Architectural Board (MAAB) guidelines for approach and reach.
Typical Solution: One sink is at the regular height and the eyewash is installed there. One
shallow sink is at the lower height required by ADA with nothing underneath it. The sink is
Each emergency shower or eyewash location “should be identified with a highly visible sign and
the area around the equipment should be well lighted”. (ANSI Z358.1). The signs must have
contrasting color of green and white and be at least 70 square inches in area (527 CMR 10.02
(2)). (Refer also to the Signage Thematic Folder in the MIT Design Standards).
The wall sign for the equipment shall be visible from most points within the lab or work area.
The area under the shower shall be clearly identified to ensure that the lab users do not block
access to the shower. For example, this can be done with a “keep area clear” graphic, contrasting
colored flooring or other demarcation on the floor. The marking chosen should be permanent, slip
resistant and resistant to wear.
Exit Corridors
1. Comply with MAAB, ADA and all Massachusetts Building and Fire Code requirements.
Do not design fixed obstructions in corridors. Do not plan for storage of equipment in
corridors, proper egress cannot be obstructed.
Control Areas
1. Control areas are spaces within a building, where quantities of hazardous materials not
exceeding exempt amounts are stored, dispensed, used or handled.
2. Whether new construction or renovation, project team must identify and maintain
separations and ensure planned storage amounts fit within the control areas for that
building/complex and for the floor within the building.
3. Where exempt amounts are not exceeded, control areas shall be used to store flammable
and combustible liquids inside buildings. The design, construction, location and number
of control areas shall meet the requirements of the Massachusetts State Building Code
780 CMR, and shall not exceed allowable amounts of hazardous materials per control
area (as specified in 780 CMR). Maximum quantities may be increased under the
following conditions:
a. When storage is in a building equipped throughout with automatic sprinklers in
accordance with 780 CMR.
b. If flammable materials are stored in approved cabinets, gas cabinets, fume hoods
or ventilated cabinets.
2. Location: If desired design criteria amounts of stored flammable and combustible liquids
exceed allowed amounts per control area, an inside liquid storage or cut off rooms (a
room including one or two outside walls) is required. Inside storage rooms would be
considered have to meet all the requirements of H-2 or H-3 occupancy and cannot be
constructed in basements.
3. Design: Inside storage rooms shall be constructed to meet the applicable requirements of
780 CMR and the Massachusetts Comprehensive Fire Safety Code and NFPA 30,
Flammable and Combustible Liquids Code, 2015. Inside storage area shall not exceed
500 square feet. Cut off rooms exceeding 500 square feet shall have at least one exterior
door approved for Fire Department access.
4. Fire Resistance Ratings: Fire resistance ratings for inside storage areas shall meet the
minimum requirements of NFPA 30. In mixed use groups fire separation shall meet the
14. Explosion Venting: Where Class IB liquids are in open use or being dispensed in excess
of maximum allowable quantities, explosion venting shall be provided in accordance with
780 CMR.
Flammable storage cabinets must meet NFPA 30, Flammable and Combustible Liquids Code and
527 CMR 14.00. These cabinets are used for storage of flammable and combustible liquids, and
must have leak proof pans at the base of the cabinet to contain spills. These cabinets can be under
fume hood cabinets or free standing. Cabinets must be labeled “Flammable - Keep Fire Away”.
Flammable storage cabinets are not required to be vented for fire protection purposes. Venting a
cabinet could compromise the ability of the cabinet to adequately protect its contents from
involvement in a fire because cabinets are not generally tested with any venting. Therefore,
venting of flammable storage cabinets used exclusively for non-highly toxic or non-highly
noxious/odiferous flammable liquids is not recommended.
The ventilation rate should not be less than 50 air changes per hour based on the volume of the
cabinet.
If vented, the cabinet should be vented from the bottom with make-up air supplied to the top.
Also, mechanical exhaust ventilation is preferred and should comply with the Massachusetts
Building Code, 780 CMR.
References: Flammable and Combustible Liquids Code, NFPA 30; Massachusetts Building
Code, 780 CMR
Refrigerators: All refrigerators designated to store flammable liquids must comply with NFPA 45
and be UL listed for the appropriate electrical classification such as Class 1, Group C and D.
Cold Rooms: Flammable and combustible liquids cannot be stored or used in cold rooms unless
the electrical and refrigeration equipment is specifically designed as explosion proof and
mechanically ventilated with an exhaust rate of 6 air changes per hour.
Grounding System: For dispensing of flammable and combustible liquids of more than one gallon
from metal containers, grounding bars, cables and clamps shall be provided.
1. Acid storage cabinets have corrosion resistant liners (powder-coated cabinets and
cabinets with corrosion resistant liners) and for under fume hood cabinets are vented into
the hood using acid resistant pipes which lead to the interior of the hood. This is typically
behind the baffle in a location where good air volume will be drawn into cabinet.
2. Acid storage cabinets are used to store non-flammable materials that are toxic or
odiferous. These cabinets can be under fume hood cabinets or free standing, exhausted
cabinets. See section Chemical Storage for more information.
3. MIT EHS does not recommend cabinets with metal standards, clips, etc. because the
metal will corrode. Molded plastic standards are an acceptable option for this
application. The design of cabinet adjustable shelving should allow researchers to
properly secure and level shelves. The supporting system should be stable and easy to
readjust to another stable setting.
Portable fire extinguishers shall be installed as part of a space change renovations and/or new
building construction. The type, location and size (capacity) of portable fire extinguishers are
based on the specific fire hazard(s) present in the work area.
Massachusetts Comprehensive Fire Safety Code, 527 CMR 1.00, 2015, Paragraph 13.6, Portable
Fire Extinguishers, NFPA 10, OSHA 1910.157 outline requirements for the selection and
placement of portable fire extinguishers in the work place. Key points include:
For most occupancies at MIT, a multi-purpose, dry chemical (ABC) type portable fire
extinguisher (50 foot travel distance spacing) will provide adequate protection. The suggested UL
rating is 4A:80BC. This is preferred over carbon dioxide and pressurized water extinguishers.
1. Exception 1: certain high hazard laboratory operations may need special protection.
2. Exception 2: multi-purpose dry chemical (ABC) type extinguishes, containing ammonia
compounds, are prohibited for use on oxidizers containing chlorine and bromine. Water
type extinguishers should be used for these areas.
Portable fire extinguishers for kitchens within offices and commercial kitchens (utilizing grease
producing equipment such as fryolators etc.) shall use “Class K” extinguishing agent. The travel
distance from the hazard shall be a maximum of 30 feet.
Portable fire extinguishers for areas that have combustible metals shall use “Class D”
extinguishing agent. The travel distance from the hazard shall be a maximum of 30 feet.
Whenever hoists or related equipment are installed as part of a project or modified including -
hoisting machinery, derricks, cableways, machinery used for discharging cargoes, and temporary
elevator cars used on excavation work or used for hoisting building material, lattice cranes, cranes
with or without wire rope, overhead hoists (underhung), overhead cranes, underhung cranes,
monorail cranes, overhead bridge cranes, electric or air driven hoists, pendant controlled hoists,
lifting devices, powered platforms and any other equipment that has the minimum capability of
hoisting the load higher than 10 feet or that has the capability of lifting loads greater than 500
pounds must include the following criteria:
Requirements:
General
Per 360 CMR 10.023, the following items are specifically prohibited from discharge to the
MWRA sewer system via the floor drain system:
1. Groundwater, storm water, surface water, roof or surface runoff, tidewater, or subsurface
drainage, except construction site dewatering in a combined sewer area when permitted
by the authority and municipality.
2. Non-contact cooling water, non-contact industrial process water, uncontaminated contact
cooling water, and uncontaminated industrial process water, and cooling tower blow
down. (Small volumes of chilled water from small leaks may go to floor drain/sewer.)
3. Fuel oil, crude oil, lubricating oil, or any other oil or grease of hydrocarbon or petroleum
origin unless an approved and appropriate gas/oil separator that is in compliance with 360
CMR 10.016 is used.
4. Any liquid, solid, or gas, including, but not limited to, gasoline, kerosene, naphtha,
benzene, toluene, xylene, ethers, alcohols, ketones, aldehydes, peroxides and methyl
ethyl ketone, which by reason of its nature or quantity or by interaction with other
substances, may create a fire or explosion hazard.
5. Any noxious or malodorous liquid, gas, or solid or any other pollutant which either singly
or by interaction with any other Waste causes or contributes to the creation of a public
Research Laboratories,
Refer to the MIT Lab Design Thematic Folder: Section 8.3
Refer to the Plumbing Division 22 of the MIT Design Standards for the requirements in these
areas.
Where the Massachusetts Plumbing Code requires connection of floor drains to grease traps or
oil-water separators these devices must meet the requirements outlined in the codes and the
Plumbing Division 22.
. Refer also to Division 23 - HVAC for EHS related HVAC design guidelines.
Chemicals requiring eye washes and safety showers: Many chemicals may be present in the
mechanical rooms. Most common are water treatment chemicals for cooling tower, chilled water
ad hot water systems and chemicals to manufacture RODI water. It is necessary that safe storage
handling and disposing methods be employed including eyewash and safety showers where
needed.
Proper access to higher equipment: By nature several equipment installed in the mechanical
rooms are high with components requiring maintenance also high. It is necessary that access
ladders, platforms and other devices be provided. Without proper maintenance access,
maintenance may not be performed. For instance his access may include chain operation
capability on valves located high.
Noise
Multiple equipment running together add to the noise level. Where multiple pieces of equipment
are used, the PWLs must be added logarithmically. Hearing protection may be required
Safety guards: The mechanical room layout should include that all guards on moving parts are
not obstructed.
Electrical Layout: The National Electric Code (NFPA 70) and Mass electric code in genera
prohibit installation of incoming electric service or emergency generators in mechanical rooms.
They are installed in separate 2 hour rated rooms.
Noise: Loud noise outside mechanical room due to mechanical equipment may even be more
objectionable.
Vibration: Excessive vibration outside mechanical room can similarly be deleterious to teaching,
research or other work. It is critical that vibration isolation be provided on any moving
equipment.
1. MIT periodically installs storage tanks for the storage of flammable or combustible
materials. In most cases these are fuel oil tanks used in conjunction with diesel driven
emergency generators or fire pumps, but could also include tanks installed for storage of
other types of flammable or combustible liquids including but not limited to electrical
insulating oils, lubricating fluids etc.
2. The regulations covering the installation, use, permitting and licensing of storage tanks
are from a variety of agencies including federal, state and local. For instance, there are
local permitting requirements for specific tank installations, licensing requirements for
the amount of flammable materials stored on the particular property and MassDEP tank
registration requirements (UST’s only.) In most cases, tanks installed as part of
construction and renovation projects only require approval from the local authorities. To
Lab staff must leave the laboratory in a clean and safe condition for construction crews. Prior to
vacating the laboratory; laboratory staff must remove all chemical, biological, and radiological
materials and they must decontaminate all work surfaces and equipment. This can be done by the
laboratory personnel or a hired environmental contractor (at the expense of the lab or Dept.).
They must also arrange for removal of all equipment (unless arrangements have been made
otherwise) and any garbage or other items that will not be wanted by the new occupants, or items
that need to be out of the way of renovation activities.
EHS works directly with the lab vacating a space to ensure the associated hazards are removed or
identified. Depending on the scope of work, EHS assesses the following locations within a lab for
hazards and documents the findings for the incoming renovation project team. EHS provides the
project manager a summary report documenting the work completed either by the lab or
environmental vendor, along with the remaining hazards in the lab, should they exist. EHS also
posts the Notice of Laboratory Decontamination form on the doors of the associated spaces.
Must verify that the laboratory is clean and decontaminated prior to demolition or construction of
a lab to help prevent unexpected delays or unsafe working conditions. It is strongly encouraged
that the project manager or representative visit with the laboratory safety representative,
department EHS coordinator or a member of the central EHS office, to verify that the laboratory
is clean before construction begins.
Polychlorinated biphenyls, or PCBs, refer to a class of compounds that were used in a variety of
industrial applications, including as dielectric fluid in transformers and capacitors. PCBs were
added to caulking and sealants to improve their plasticity. In 1976, the United States
Environmental Protection Agency (US EPA) banned the manufacture and continued use of PCBs
in concentrations above 50 parts per million (ppm). The most common sources of PCBs
impacting building renovations and demolition are in electrical equipment, namely transformers
and capacitors, building materials such as caulking and sealants, and hydraulic oils pre-dating
1976. The EHS Office is responsible for ensuring that MIT complies with proper PCB
management practices as identified under the Toxic Substances Control Act (TSCA), 40 CFR
761.
At the project outset, building age and repair/renovation history shall be used as a guide for
determining whether sampling is required. Buildings constructed after 1980 are not expected to
require sampling. Buildings constructed or renovated between 1950 and 1980 require sampling if
engineering data is not available to rule out the presence of PCBs.
Relative to sampling for PCBs, MIT’s PCB management program distinguishes between
individual window repairs or small scale renovation projects (1-2 rooms) versus building
demolition or large scale renovation.
If the building was built and/or renovated between 1950 and 1980, any caulking removed shall be
presumed to potentially contain PCBs and the waste handled accordingly. If the building was
constructed after 1980, it can be assumed that PCBs are not present. If the building was built
before 1950, PCBs are likely not present.
If the building was built and/or renovated between 1950 and 1980, and engineering data is not
available to rule out the presence of PCBs, then caulking and sealants must be sampled. If
sampling reveals PCB concentrations in excess of 50 ppm, then additional sampling of masonry
may also be required. The EHS Office provides direction to the Project Manager and the
contractor on sampling protocol, including analytical method. In the event a remediation plan is
required, the Project Manager shall work with the EHS Office and a technically qualified
Contractor to develop and execute the plan.
Transformers and capacitors pre-dating 1980 must be evaluated for date of manufacture and
presence of oil. Oil containing equipment must be tested prior to removal from MIT campus.
In as much as feasible, implement the following pest management recommendations in the new
construction projects, renovation projects and demolition projects. Emphasis should be placed on
the grade floor(s), all building entrances and exits, building connections, and additional support
structures as piping and ventilation. Design considerations include:
a. Playgrounds
! Exterior fencing around playgrounds and park like settings should have a
smooth vertical surface to prevent pests from climbing, and a top that
prevents rodents from getting over the top of fence, for example a T-cap.
! Exterior fencing should have 24 inch metal extension below grade and
have holes no greater than 1/4 inch in any dimension to prevent rodent
burrowing.
! Below grade metal fence extensions, preferably constructed from
stainless steel or other resilient material, shall be contiguous and where
2. Building Exteriors
a. All access points into a building (exterior doors, mechanical doors, garages,
loading docks, windows) should be assessed from an Integrated Pest
Management (IPM) perspective.
b. Exterior doors must make use of door sweeps and self-closers. The doors sweeps
should be constituted of a rodent proof material, and the placement of door
sweeps and self-closers should ensure gaps are less than 1/8 of an inch in length
or height. Further, door sweeps and self-closers should be easily maintained or
replaced.
c. The exterior building envelope should be tight with no gaps larger than 1/8 inch
to prevent pest access (for example bees, mice, rats).
d. Exterior ledges, particularly over entrances, should be eliminated. Smooth,
sloped (45 degree angle) surfaces work best. The goal is to prevent birds from
resting or nesting. Additional anti-bird/pigeon measures include netting.
e. Sidewalks, parking lots, and ground level surfaces surrounding buildings should
3. Building Interiors
a. Provide tightly sealed access panels to all “dead spaces” such as pipe chases and
ceilings other than drop ceilings.
b. Perforations and other spaces through which pipes and cables are laid throughout
the facility shall be properly sealed and fire stopped. Typically fire stopping will
provide a barrier that will prevent pest/rodent travel but individual systems
should be reviewed to these criteria before use.
c. Overhead rolling doors shall be flush and tight with no gaps larger than 1/8 inch
and preferred to be motion detection enabled, automatically closing when no
activity is present.
d. Provide door sweeps on all interior mechanical spaces, food service, loading
docks and “back of the house” doors.
e. Custodial closets and storage spaces should have finished floors and door
sweeps. Sinks in closets must be properly caulked and sealed to the floor and
wall. Drain cover should not allow large particles into drain. See more details in
the MIT Design Standards – Plumbing Division 22.
f. Provide sealed hatches or coverings for sewage ejector pits.
g. If raised floors with utilities below are used, means of pest control and regular
inspection must be considered and addressed in the design.
h. Floor mounted heating and cooling vents shall be screened to a less than 1/8 inch
diameter opening, and have the ability to be regularly cleaned and maintained.
4. Kitchens
a. Food service counters, benches, cabinets, etc. should be flush with floors and
walls to prevent nesting opportunities underneath and behind.
b. Flooring materials for commercial kitchens shall be commercial kitchen grade
such as quarry tile or epoxy and resistant to hot water and grease. Kitchens in
office areas are typically resilient tile.
c. Baseboard moldings shall include coved corners, be at least 4 inches high and
allow for water containment, cleaning and protection of walls. All breaches,
holes and penetrations in flooring must be sealed.
d. Cabinets in kitchens and cabinets designed for food storage must seal tightly,
with full back panels and kick plates. Once installed, any holes in cabinets for
utilities or factory provided accessories must be tightly and properly sealed.
e. Bulk food storage rooms shall have rodent proof features incorporated. The
5. Waste Management
a. Waste compactors shall be self-contained, water tight, and sealed between the
ram and the container.
b. Animal bedding waste containers (dumpsters/compactors), must be sealed
between the ram and container.
c. Compactor doors shall be self-closing and latching.
d. Surfaces where compactors are placed shall be level, well drained, sealed or
painted, concrete or asphalt surface.
e. Design dumpster locations, water sources, and floor drains for proper
housekeeping practices. Alternative dumpster locations and types need to be
considered if the building site interferes with trash and recycling removal from
surrounding buildings.
f. Exterior trash and recycling receptacles should be covered and rodent proof. Big
Belly solar compactors or equivalent are the standard for any new exterior
receptacles.
g. Buildings shall have easy access to a trash/recycling wash room. These wash
rooms shall have water resistant walls and flooring, sanitary floor drains, a warm
water source and be sized for cleaning collection receptacles.
h. Consider power and mounting capabilities for fly lights in waste areas.
i. Where commercial kitchens are present, the waste area for facility must allow for
consolidation, storage and disposal of compostable food wastes from kitchens.
The MIT construction Project Manager or selected contractor shall contract with MIT's pest
control provider for any pest control services provided to projects to better coordinate integrated
pest management efforts Institute-wide.
Occupants of neighboring buildings or areas should be notified prior to work starting of potential
impact of increased pest activity due to demolition/construction activities. Communication shall
remind occupants how to report pest problems. Design considerations include:
1. Demolition Sites
2. Construction Sites
a. Appropriate rodent control actions must be taken along the perimeter and
surrounding areas of construction sites.
b. Construction dumpsters shall not be used for food waste disposal and must be
emptied on a regular basis.
c. The dumpster location shall be kept clean to prevent harborage and food sources.
d. A City of Cambridge Ordinance that requires all dumpsters, including
construction dumpsters be licensed and maintained.
e. Pest proof, covered exterior and site trash receptacles are required where needed
for use by construction personnel and catering trucks.
f. Pest sightings or evidence of pest activity should be immediately reported to the
MIT Project Manager and pest control vendor for immediate action.
g. Access points on the perimeter of project areas to neighboring spaces should be
sealed and door sweeps installed wherever possible.
h. Doors leading to and from renovation areas must be kept closed at all times,
particularly exterior doors. This includes before or after deliveries of materials to
the job site.
i. Construction dumpsters shall be emptied on a regular basis and the dumpster
location kept clean to prevent harborage and food sources.
j. Construction waste dumpsters must not be used for the disposal of food or food
packaging related wastes.
k. Staging areas are required to be clean at all times to prevent harborage and food
sources.
6. CONSTRUCTION MITIGATION
Mitigation concerns to MIT Community include: vibrations, noise, dust, odors, debris, vehicle
and pedestrian traffic, fire exiting during construction, and crane operations.
7. WASTE HANDLING
Waste is generated through all phases of a project and a building’s life span including demolition,
construction, and operations. The project management team should work with the EHS Office to
ensure demolition debris from laboratories is assessed and managed properly.
Existing buildings slated for demolition or renovation should be assessed by EHS prior to the
project’s demolition phase to ensure potential hazards are identified and/or removed. All
radioactive, biological and chemical materials and wastes must be removed from a space before
work can begin by the project, as indicated in these guidelines.
Many of the waste streams generated during building demolition and construction projects are
recyclable. Construction and Demolition (C&D) Wastes have been identified as a major target for
reuse and recycling because this material typically represents a large volume of material.
The Commonwealth of Massachusetts has banned the landfill disposal of C&D debris. This
means that asphalt pavement, brick and concrete (ABC) rubble, as well as other waste materials
(see list below) must be handled in accordance with Massachusetts Solid Waste Regulations.
Contractors are required to obtain a dumpster permit through the City of Cambridge. In addition,
the contractor should review the location of the proposed dumpster with the Recycling and
Materials Management Office prior to the delivery of the dumpster.
In addition, contractors shall be aware that the Commonwealth of Massachusetts has banned the
following waste streams from incineration or landfill disposal. These MIT waste materials may
not be included in shipments destined for incineration or landfills. These include:
General Contractors hired for new building construction, renovations or demolition projects
should submit a Waste Management Plan to the MIT Project Manager. The Plan should include
the following:
The Waste Management Plan shall include provisions for periodic reporting to MIT, including
types and quantities of waste materials hauled off-site. In this way, the MIT Project Team can
demonstrate the waste management and recycling efforts through-out the course of the project as
opposed to attempting to collect, analyze, and report the data at the end of the project.
For new building construction and full building renovations, consideration should be given to the
staging areas within the building and at the loading dock level for general waste management,
which includes recycling. MIT Recycling and Materials Management Office, Custodial Services,
and the EHS Office should be contacted for review of these locations. Locations at each floor
level should be provided for occupants or service staff to bring the following materials:
If floor level kitchenettes are available, organic food waste collection should be provided near the
trash and recycling bins. Signage should accompany containers for all streams generated.
If a café or food venue is in the space, proper container placement and signage should be included
for recycling, organic food waste, and trash.
At the loading dock level, ample space should be provided for collection and removal of bulk
streams mentioned above.
8. VALUE ENGINEERING
8.1 Standards
The EHS Office is available to comment during VE initiatives. Value Engineering Change
Proposals (VECP) should be reviewed by EHS in those situations where the VE analysis results
in a direct (or indirect) effect on safety. The role of the EHS Office is to conduct a hazard and risk
assessment to assist the project team with decision-making and if necessary, identify possible
alternatives to the VECP.
9. FURNITURE
9.1 Flammability
When purchasing new furniture for renovation or new building, comply with current regulations
for flammability.
Note :In most cases the Massachusetts Fire Code allows furnishings in public spaces within
sprinklered buildings to have seating that meets California standard TB 117-2013.
Computer workstation ergonomic design principles need to be considered to give the user the best
overall positioning and the adjustability required to improve worker comfort and productivity
while preventing workplace injuries including musculoskeletal disorders and repetitive strain
injuries.
The purpose is to adapt the workplace to the worker, dependent on the job description, required
tasks, duration and physical make-up of the employee performing those tasks.
One of the best ways to prevent and control injuries and illnesses is to "design out" or minimize
risks early in the design process and to build in/plan for adjustability. Workstations may be used
by multiple persons of a wide variation of sizes, either by being shared or over time. Newer work
styles which require sit/stand positioning as well as use of voice transcription should be
accommodated. By addressing safety and health needs in the design process, the goal, to prevent
or minimize work-related hazards and risks associated with workstations can be achieved.
Many ergonomic factors are involved in the design of a computer workstation such as:
1. Chair design/adjustability.
2. Keyboard placement/adjustability/articulating keyboard tray.
3. Workspace adjustability.
4. Work environment/heating and cooling.
5. Adjustable work surface/desk.
6. Ambient office and task lighting.
7. Sit to stand stations.
8. Ease of adjustability.
9. Adequate space.
10. Location of other components/telephone/headsets.
11. ADA accommodations.
12. Type/location of input devices.
13. Anti-glare screens.
14. Foot rests.
15. Monitor adjustability and monitor arms.
All of the above issues when properly addressed in the design process may reduce or eliminate
musculoskeletal disorders associated with poor ergonomic design or equipment. It is important
that designers meet with those that will be using or have knowledge of the work to understand the
job function in order to apply appropriate design principles. All workstations should be
adjustable, for areas with many users, adjustability is an even more important consideration and
these workstations should be suitable for users of many sizes.
Or visit:
11.1 Standards
11.2 Equipment
MIT periodically installs combustion equipment in the buildings such as emergency generators,
boilers, hot water heaters, etc. A process or piece of equipment (emission source) at MIT has the
potential to be included in the campus-wide Title V Operating Permit if it uses and/or emits any
of the following substances above threshold levels. Notify EHS if these are being considered.:
Massachusetts Department of Environmental Protection (Mass DEP) and US EPA regulate the
installation, use, and permitting of all combustion sources. Particular care is required when
locating these emission sources so as to avoid causing a localized health or nuisance problem
from emissions or sound impacts.
If emission unit has an outside stack, that stack shall be configured to discharge the combustion
gases vertically and cannot be equipped with any part or device that restricts the vertical exhaust
flow of the emitted combustion gases, including rain protection devices “shanty caps” and “egg
beaters”. Any emission impacts of exhaust stacks must be minimized by employing good
engineering practices. Such practices might include:
Emission unit should be located so as to avoid the creation of a noise nuisance. Units located
outside should be housed in enclosures specifically designed to attenuate sound.
Emission sources, including those that are exempt from permitting requirements, are registered
with Mass DEP in the next required Source Registration (the annual air emissions report) so EHS
needs to be notified prior to the installation.
However, permits are required for many activities that result in air pollutant emissions. Air
permits identify what pollutants are emitted, how much can be released according to standards,
and what controls are implemented to reduce emissions, including plans to monitor the pollution
at the site.
1. Emergency generator, fire pump or other similar engine rated at 37 kilowatts and up, or
2. Non-emergency engine rated at 50 kilowatts and up.
All engines must comply with EPA emission standards and have a stack that exhausts vertically.
EHS will submit the certification for these units.
12.1 Standards
12.2 Introduction
A significant portion of the MIT Cambridge campus is located on soil known as urban fill. This
material often contains materials from burning of fires and wastes from the early industrial
revolution which includes significant amounts of coal ash. These soils and possibly, groundwater,
may also be contaminated by years of vehicle emissions from leaded gasoline internal
combustion engines, and in some cases from factories or service stations formerly located in the
area. As a result, excavated soil may contain metals such as lead or arsenic, hydrocarbon
compounds considered hazardous materials and organic contaminants.
Projects with excavation or underground utility work that disturb soils should consult with EHS
during project planning to determine scope of soils work and applicability of soils and
groundwater contamination regulations. For utility work located on City of Cambridge property
for MIT projects, contact EHS early in the project to discuss the stringent City soils pre-
characterization requirements.
During excavation should any unusual odors or discolored soil conditions be found, stop the
excavation and contact EHS as soon as possible to determine whether the site has potential
contamination. This type of contamination may require the contractor to report to MIT a
condition where MA DEP must be notified within 2 hours by MIT EHS.
Project Managers should review the MIT GIS system to ascertain whether the project site is listed
as having an Activity Use Limitation (AUL) from a past project and require certain procedures
for future work as required by the MCP. Contact EHS when working on an MIT site that is a
listed AUL.
On excavation projects, analytical testing of soils is required for MCP site classification and off-
site disposal. An LSP is required to supervise this work and make any required notifications to
MA DEP, on behalf of MIT.
13.1 Introduction
Maker spaces/Shops, and other locations where material fabrication and assembly work
occurs are important resources at MIT. Whether curricular or non-curricular, for students
and faculty or employee use only, these spaces provide the equipment and
instrumentation through which our educational, research, and infrastructure maintenance
goals are met.
The purpose of this section is to outline design guidance from an EHS perspective
location, attributes, layout, and other features of maker space/shops on campus.
Size
Accessibility
Consider material in- and outflows, loading dock. Consider the size of the largest materials to be
used or assembled. May require large / expandable door systems, and freight elevator access.
Where such features are needed but unavailable, identify alternate method(s) for managing
material and equipment transport and movement. For new maker space/shops or substantial
renovations of existing maker space/shops, the project should include the procurement of any
necessary lifts, powered industrial trucks, or other special means of material transport or
handling.
Utility Hook-ups
Ensure space has or can readily accommodate necessary mechanical service requirements. These
include but are not limited to basic 120/220 V electrical power, 3-phase electrical power, water,
wastewater discharge, ventilation systems, data / internet connectivity, compressed air, and
hydraulics.
Neighbors
Consider and actively work to mitigate potential impacts from shop operations on all adjacent
neighbors, whether MIT or non-MIT. Potential impacts include noise, vibration, dust, chemicals,
spills, off-hours deliveries and material transport, and pedestrian and vehicular traffic.
Access Control
Shop Entryways
1. Shop entryway areas shall provide visual accessibility into the shop, using clear glass
door view panels, sidelights, windows, or window walls. All clear openings must be of
impact-resistant construction and meet applicable fire rating
2. Main shop entryways must be furnished with standard MIT room door safety
identification sign holders and any additional hazard warning signage applicable to the
materials or operations inside the shop
Establish and demarcate clear separation(s) between the shop proper and any break, eating
locations, meeting, classroom, desk, or other non-tool areas. Depending upon the nature of the
shop, this demarcation may be a painted line or other symbol on the floor, area signage, chains,
bollards, cones, gates, or doors.
Offices
Any interior office(s) for shop manager(s) or instructor(s) should be sited in a central or otherwise
readily accessible location, with high visibility onto the shop floor through unobstructed
doorways, windows, window walls, or other design elements.
Design Goal: Design and layout maker space/shops to optimize space utilization and storage,
enhance the learning experience, promote safety, and ensure accessibility for future service and
maintenance.
Existing and proposed new maker space/shops must meet basic fire and life safety rules,
including appropriate number and sizing of emergency egress pathways, fire-rated separations
between shop and surrounding non-shop spaces, maximum occupancy and assembly limits, and
applicable building designations.
Egress
All egress routes and exit doors must be posted and their routes kept clear.
1. Specific fire alarm considerations may include hard-wired, battery back-up smoke / heat
rise detection systems with local audible alarm(s). In spaces anticipated to generate
significant amounts of dust, humidity, or mists, consider avoiding photoelectric style
smoke detectors and instead rely upon heat rise detection
2. All occupied spaces must be protected by MIT standard fire sprinkler systems. Within
the maker space/shop consider installing protective caging on all sprinkler heads
3. Provide one or more prominently located and labeled portable fire extinguishers
(reference MIT standard here), typically as a 10 pound Class ABC dry chemical
extinguisher. Where laser, electronic, optical, or other sensitive equipment could be
damaged by dry powder, carbon dioxide extinguishers may generally be substituted. If
fine combustibles present, provide class d extinguisher
1. Hot work tools and operations must adhere to applicable MIT and City of Cambridge
requirements, including safe work distances for open flames, non-combustible surfacing,
compressed gas cylinder storage, and limits on maximum quantities of flammable
materials
2. Welding, cutting torches, brazing, and related high temperature “hot work” operations
can produce hazardous fumes, sparks and other hot particles, and create ocular hazards to
nearby persons. Hot work areas must be physically segregated from other tools and
operations by distance and shielding. Non-combustible opaque solid shields or welding
curtains must be provided to prevent inadvertent ocular exposure and provide protection
against sparks and other hot particles
3. All working surfaces in or around hot work areas much be of non-combustible
construction
4. Supplemental dedicated portable fire extinguishers must be provided for hot work areas
5. Depending upon the nature and frequency of the hot work, local exhaust ventilation or
portable “fume extractors” may be required
6. Provide storage areas for welding helmets, gloves, and fire resistant coats or aprons.
Provide adequate capacity and means to safely transport and store the anticipated range and size
of raw materials, finished products, and shop equipment and supplies.
1. Consider needs for any overhead trolleys, hoists, cranes, and other lifts. (See guidelines
on Hoists and Overhead Lifting Equipment for additional information)
2. Ensure that shop aisles and walkways have sufficient width for anticipated material
transport, including the use of hand-carts, rolling carts, lifts, or powered industrial trucks
Storage
1. Determine the preferred method(s) for storage in the shop, ranging from the creation of
formal tool and materials “cribs” to the use of open, decentralized storage. Final
decisions will be dependent upon shop type, user base, staffing, and value or hazards of
stored materials and tooling
2. Minimize footprint loss by using vertical or stacking storage systems where feasible, or
co-locating storage areas in adjacent spaces. Design should consider safe and easy access
to materials.
3. Rolling carts and parts bins often provide maximum flexibility for varied work projects
Compressed gases and flammable chemicals require special storage arrangements. Cylinders of
any compressed gases must be secured against tipping and falls by wall chains or another
approved restraint system. Flammable materials, including liquid chemicals, most aerosol spray
can products, and flammable compressed gases are subject to MIT and Cambridge quantity limits
flammable materials should be stored in a rated flammable storage cabinet.
Electrical
1. Following the Massachusetts Building and Electrical Code, maximize the number of
separate circuits to avoid overloads, ensure circuit breaker boxes and individual circuits
are well-marked and coded, and centrally located for quick access
2. All equipment must be certified by UL or have other NRTL certification.
3. Special Electrical Needs
a. Identify any special electrical service requirements (i.e., 3-phase power,
uncommon line voltage equipment) during planning and design
b. Avoid floor-level electrical outlet service; instead, use overhead electrical busses
to provide maximum accessibility for future tool installations and / or re-
orientation of existing tools
c. Provide an adequate number and distribution of common 120 and 240 V outlets
d. Consider installing overhead retractable cord and reel units for larger open
assembly areas and for flexible multi-function shop spaces
4. Emergency Power Shut-Offs
a. In addition to emergency shut-off buttons on all fixed location power tools, room-
level under-voltage trip/relay should be provided in all shops. These can be simple
shunt-trip circuit disconnects or full-room electrical controller switches. Where
installed, they must be prominently labeled. Strong consideration should also be
given to also using a button style that requires a key or ID card to reset power in
order to force a review of the cause for the emergency shut-off event
b. Room-level electrical control switches can also be used to affirmatively depower
some or all of the tools in a shop, manually or by a time-of-day clock. This approach
can serve as a reliable means to “de-rate” the hazard classification of a shop to enable
its broader use or to simply ensure that no work can occur in that space without
specific on-site supervision
c. In dusty or wet shops, consider installing emergency power shut-off buttons inside
clear weather-proof covers
Lighting
1. Location
a. Compressors, vacuum pumps, and hydraulic control pumps are noisy and a
source of significant vibration. Select the lowest noise emitting units possible
when procuring new equipment
b. Locate these system components in either a separate space or within a special
enclosure in the shop
c. Wherever placed, use isolation mounts to minimize vibration and provide ready
access for routine service and maintenance
2. Distribution
a. Shut-off valves should be located to facilitate routine service needs, and pipes
located on walls or ceilings.
b. Pipes should be prominently labeled by service
Reference
The overall approach is to provide adequate general ventilation to provide overall air quality
supplemented by local exhaust and local filtration systems that limit control contaminants at their
source and limit their spread. It is also desirable to be able to where possible have local exhaust
systems operate with the tool or work station and may be turned on/off or controlled by users.
Filtration of local exhaust may also be necessary before discharge to the outside or in some cases
re-circulated in the space. Hood design, placement, and exhaust quantity are critical for effective
capture. Manufacturers of tools and filtration systems may also have specifications and guidance
on ventilation volumes, pressure drops, etc. The Industrial Hygiene Program (IHP) staff in the
EHS office should be consulted for review of shop ventilation systems.
Ventilation
1. Good general ventilation should be provided for maker space/shops since odors may be
produced from machining and storage or use of cutting fluids. ASHRAE provides
guidance of 6 air changes per hour of ventilation. Both local and general exhaust can be
included in this number
2. General exhaust grills should allow for good mixing and be accessible for cleaning. It is
preferable if general exhaust can be single pass air if supply air is not the only means of
heating and cooling. BMS controls should be provided to set back the general ventilation
when the shop is not in use
System Determination
1. Both the types of materials being machined and the particle size generated by the
machine tool must be considered when determining if local ventilation will be needed for
a given tool. Band saws and drill presses produce large chips and generally do not need
local ventilation unless the metals being machined contain beryllium, lead or other toxic
metals
2. Metal working lathes and mills can produce smoke from cutting fluids and some
potentially metal fume (depending on process). Some process will generate aerosols of
cutting fluids, mist eliminators can be used to capture these locally. Consider adding a
snorkel to mills and lathes that will be heavily used or used w/metals containing toxic
Machining of Plastics
Local exhaust discharged to outdoors is recommended for large volume machining of plastics
where significant odors are generated.
1. Local exhaust with filtration (dust collection) is required for most tools. Recirculation
back to the shop is usually acceptable if the collection efficiency of the dust collection is
high and general ventilation is also provided. Exhaust or filtration ports are needed at/on
each tool
2. If multiple tools are used simultaneously or regularly should consider appropriately sized
dust collection system with primary (typically a cyclone) and secondary (high efficiency
bag filter or paper filter) collectors. The system can be located in the shop or outside. If
outside, weatherproofing and other fire related codes will need to be addressed
Laser Cutters
Laser cutters require local exhaust vented to the outside. These may be high static pressure
systems which tend to be noisy and best designed to be turned off following use and when the
piece has cooled sufficiently to not produce odors. If multiple parts are made a ventilated rack or
cabinet can be used to exhaust cooling parts.
3D Printers
Required ventilation for 3D printing will depend upon the printing technology and materials,
manufacturer recommendations, number and size of machines and room configuration. Since the
ventilation requirements are variable an understanding of planned and future 3D printing needs is
critical. At a minimum, good general exhaust ventilation is required in all 3D printing areas.
Locating the 3D printing area to take advantage of room airflow patterns to quickly exhaust odors
and fine particles should be considered. Some 3D printers come with enclosures and in some
CNC equipment with enclosures may have ports for ventilation to be exhausted to the outside or
connected to a mist eliminator/smoke eliminator and re-circulated in the shop. The machine
specifications, materials to be machined, cutting fluid and volume should be reviewed to
determine if ventilation is necessary and the type to be installed.
Many maker space/shops, studios, and assembly areas may require a small hood for odors
produced from this type of work. These odors must be exhausted from the building via a non-
recirculating system (100% exhausted to the outside), and should be equipped with a paint mist
filter (installation of large spray booths should be evaluated for additional safety and
infrastructure measures). These hoods should be on/off with an exhaust flow monitor that can be
muted when the hood is off. Controls may include occupancy sensors, timers or other
technology.
Local exhaust vented to the outside will be required for all welding operations.
System Controls
Where feasible, tool-based local exhaust ventilation systems should be connected to the tool
power control and / or room ventilation system. This ensures that contaminant capture is actuated
when the tool is turned on, and turned back off again upon completion of the task. Under certain
circumstances, shut-off time delays may be needed to provide additional ventilation time.
Identify special water consumption, quality and quantity needs, and wastewater- generating
activities during planning and design to ensure suitability of the intended shop location and
Municipal Water
1. City water may not be used for single use, pass-through cooling of mechanical systems
or tools; instead, use house chilled water, process chilled water, or a stand-alone point-
of-use recirculating water chiller
2. For equipment or operations that generate wastewater special permitting and / or pre-
discharge treatment systems may be required. Consult MIT EHS for assistance)
Sinks
Emergency shower needed in Maker Space/shop if flammable or corrosive liquids will be used.
Eye wash recommended for dusty (wood) environments as opposed to particulates (e.g.
metal/plastic particles).
Adequate space and collection devices for safe, compliant disposal of all waste materials
generated in the shop.
Best Practices
1. Dedicate one or more areas to the collection of regular trash, recyclable materials,
special shop-generated wastes, and any hazardous and other regulated wastes
2. Locate waste storage areas in readily-accessible parts of the shop to encourage use and
facilitate routine pick-up and removal
3. For any hazardous chemical wastes, additional collection area features are generally
required, including secondary containment, special signage, and training
Consistent, readily-identifiable access to safety equipment and other safety features in all shops.
Provide the following at or near the main entry point or other common area of each shop:
1. Safety glasses, goggles, face shields, hearing protection, etc., as appropriate to shop
operations
2. Hair and beard tie-back accessories (e.g., hats, head bands, ponytail ties, hair and beard
nets)
3. Any other personal protective equipment required for the shop
4. Basic first aid kit
5. SDS station and binder (as applicable)
6. Small tool out-of-service / mini-LOTO (lock-out/tag-out) kit
Telephones
Each shop must have one or more landline telephone(s) with posted campus emergency contact
numbers, including building number and street address to aid emergency responders.
Remote Monitoring
Although largely tool-specific, several general concepts guide the safeguarding of all shop tools
and machines. Consult MIT EHS prior to ordering any new or replacement shop tools or
equipment.
1. Tool Safeguarding
a. For each tool, provide safeguarding that meets regulatory (e.g., OSHA),
advisory organization (e.g., ANSI), and Institute requirements, regardless of
manufacturer-provided guarding and controls. Refer to the MIT EHS
Machine and Woodworking Shop Safety SOP (EHS-0076) for details.
1. Non-Lab Areas:
a. When designing a shop space, the needs for chemical storage should be factored
in. All shops are required to maintain a chemical list, and this list can be used in
evaluating storage needs.
b. When large numbers of spray cans are used, or other flammables, space should
be planned for flammable storage cabinets, perhaps the biggest chemical storage
need in a shop. In some cases, it may be desirable to vent the flammable cabinet.
In rare cases, it might be appropriate to design a flammable storage room with
appropriate diking and fire protection
d. If drums of chemicals are used, sufficient space for such storage needs to be
15.1 Standards
Meet or Exceed the Following Standards - Refer also to Lab Design Thematic Folder
15.2 Introduction
Gas monitoring may be required when highly toxic, toxic, flammable, or pyrophoric
(spontaneously combustible in air) gas use is planned. Under some conditions oxygen monitoring
is required in locations with compressed and liquefied inert gases and LEL (Lower Explosive
Limit) monitoring in locations such as storage areas for flammable gases and chemicals. This
section applies to Lab and Non-Lab areas.
1. Monitor type, alarm set points, automated actions and notifications for monitoring
systems are determined by the project design review team based on MIT EHS and
Facilities specifications, code requirements, building infrastructure and research needs.
2. All monitoring systems must report alarm details back to a continuously monitored
station (e.g. the Facilities Operations Center and if available, a department response
team.).
Certain gases with very high toxicity and/or pyrophoric properties (e.g., silane, arsine, and
phosphine) require continuous 24 hour air monitoring in the work area and ventilated
equipment/enclosures and possibly duck work. Automatic gas shutdown at the gas source and
tool shutdown in the event of ventilation failure or gas detection may also be required. An
automatic fire detection system must be installed in rooms or areas where highly toxic
compressed gases are stored or used. Flame detection is required for pyrophoric gases.
Toxic gas alarm set points are based on the American Conference of Industrial Hygienist
Threshold Limit Values (ACGIH TLVs). Typically monitors are set to alarm at half of the TLV
and the TLV. For detection inside of ventilated enclosures (e.g., gas cabinet or tool enclosure) the
lab should be evacuated and gas source automatically shut down. For highly toxic and pyrophoric
gas detection at the TLV level or higher in ambient/breathing air, the building is evacuated.
The monitoring system shall be equipped with an audible and visual alarm indicator. The audible
signal shall be at least 15 dB above the ambient sound level. The visual alarm beacons shall be
While toxic gas use may not require the same monitoring and controls as very toxic gases, each
planned use of toxic gas requires some level of engineering controls and/or monitoring.
Especially of concern are toxic gases that may not provide adequate warning below the TLV due
to high or no odor thresholds and olfactory fatigue (e.g., carbon monoxide, hydrogen sulfide or
hydrogen chloride).
Highly toxic, toxic and pyrophoric gas monitoring requires that sensing ports be located in the gas
cabinet, tool/equipment enclosure, and lab area.
Compressed gas cylinders containing highly toxic, toxic and pyrophoric gases shall be stored in a
fire suppression system (also, see Section 3.5). The cabinet shall be equipped with an excess flow
control valve and flow restrictor in cylinder and exhaust monitor/interlock for gas flow shutdown
upon exhaust loss. There should be a manual emergency shutoff at the gas cabinet. For high
hazard group H occupancies, the exhaust ventilation system serving gas cabinets, as well as any
tool enclosures, shall be provided with emergency power. The local authority having jurisdiction
may require additional safeguards.
1. Note: SEMI and Massachusetts Building Code define a highly toxic gas as having an LC
50 of 200 ppm or less and a toxic gas as having an LC50 of greater than 200 ppm and less
than or equal to 2000 ppm for a one hour exposure to albino rats between 200 and 300
grams. [SEMI F6-92]. NFPA 704 uses an LC50 of less than or equal to 1000 ppm for its
highest health hazard rating of 4 and an LC50 of 1000 to 3000 ppm for a hazard level of 3
Small returnable cylinders (lecture bottles) containing less than 10 cubic feet of gas by volume
that are kept inside gas cabinets or fume hoods:
Some research laboratories use compressed and liquefied gases in locations where the potential
for a low oxygen, <19.5% O2, atmosphere exists. These areas are required to have oxygen
sensors. Examples include liquid helium cooled magnets or dilution refrigerators, MRI rooms,
EHS with assistance from the project design group will review the proposed research, location
and gas quantities to determine whether oxygen level monitoring may be required. In some cases
provisions for emergency exhaust triggered by an alarm may be required. Positioning of sensors
should be based on gas density at the time of release relative to ambient conditions. Sensors for
MRI and MEG rooms should be designed for these rooms to eliminate interference with the
image quality.
The signage shall include appropriate hazard warnings, as well as response instructions (e.g.,
“Warning! Low Oxygen Alarm”) contact information and emergency phone numbers. Refer to a
template sign for consistency. Response protocols should also be developed and distributed as
outlined above in the toxic gas section.
The purpose of the lower explosive limit (LEL) monitoring of gases within a laboratory space or
gas storage room is to give early warning to personnel of a potentially hazardous condition.
When a gas is both toxic and flammable or pyrophoric, the more stringent (sensitive) monitoring
requirement shall be used. Both monitors are not required.
The monitoring system shall be equipped with an audible and visual alarm indicator. The audible
signal shall be at least 15 dB above the ambient sound level. The visual alarm beacons shall be
labeled.
The location of gas sensors shall be determined based on the properties of the gas.
Flammable gases should be monitored by a continuous monitor in the lab room and any non-toxic
flammable gas cylinders outside a gas cabinet should have an excess flow valve. For non-toxic
flammable gas, sensors are required in the gas cabinet, equipment/tool enclosure and lab area.
Exceptions:
1. When the cylinder contains less than or equal to 10 cubic feet of non-toxic flammable gas
Any non-toxic flammable gas cylinder containing greater than 33 cubic feet of gas must be
contained in a gas cabinet if sprinkler protection is not provided in the lab.
The local authority having jurisdiction may require additional safeguards. Response protocols
should also be developed and distributed as outlined above in the toxic gas section.
The purpose of the lower explosive limit (LEL) monitoring of flammable liquid vapors within a
laboratory space or flammable liquid storage room (FLSR) is to give early warning to personnel
of a potentially hazardous condition. In the case of an FLSR, these areas are normally
unoccupied; thus, it is possible that a leak or spill could result in high concentrations of
flammable vapors that could go undetected.
LEL monitoring may be required in locations designed as flammable liquid storage rooms
(FLSR) where dispensing will occur. Requirements include:
1. The LEL alarm system shall activate on a single alarm point set at 20 %. This set-point
may need to be lower for liquids that are also toxic
2. The monitoring systems shall be equipped with an audible and visual alarm indicator.
The alarm signal shall be transmitted to a constantly attended station. The audible alarm
shall exceed background ambient levels by 15db. The visual alarm shall be labeled
3. The alarm sensors shall be located no higher than 12 inches above the floor
4. Signage shall be posted outside the FLSR. The signage shall include appropriate hazard
warnings, as well as response instructions (e.g. “Do Not Enter if the Alarm has been
Activated”) contact information and emergency phone numbers
5. When the flammable liquid dispensing involves use of an automatic pumping system (as
opposed to manual,) the pump shall shut-down upon LEL alarm activation (or line
leakage detection) to stop the flow of liquid
Response protocols should also be developed and distributed as outlined above in the toxic gas
section. See Table 1 for suggested sequence of operations.
Carbon monoxide monitoring is required in all residential areas, commercial kitchens, Ice Rink
and garages (to start ventilation fans only). Natural gas monitoring is required in commercial
kitchens. Where there is an assumed high hazard to occupants from the natural gas/carbon
monoxide exposure in other non-lab buildings, a discussion will take place between the designers
and EHS to determine the appropriate monitoring in these areas. Response protocols should also
be developed and distributed as outlined above in the toxic gas section.
END OF DOCUMENT
May 2018
Table of Contents
1.1 General
With over 160 buildings on the Cambridge campus, MIT has a number of buildings that are
historically significant and are considered iconic works of architecture. These buildings require
an additional level of attention and care when contemplating renovation and renewal projects.
Since 1916, when MIT moved to the original Main Group buildings designed by architect
William Welles Bosworth and engineer John Freeman in Cambridge, until today, MIT has had a
tradition of hiring innovative architects and engineers to design the campus buildings. Many of
these buildings are visited by architects, design professionals and tourists from all over the world
as they were iconic works of architecture and engineering at the time of construction and remain
so today.
Buildings 1 to 8, 10, 11, 14, 50, E1 and E2 are part of a historic district nominated to the National
Register of Historic Places by the National Park Service in 1986. Other buildings that were
nominated separately are the MIT Chapel (W15) and Kresge Auditorium (W16), W31 (the former
Cambridge Armory), Metropolitan Storage Warehouse (W41), Baker House (W7) and the Arthur
D. Little Building (E60). In 2012, MIT had Building E52 Determined eligible for the National
Register.
MIT declined to have any of the nominated buildings listed on the National Register. By
Commonwealth of Massachusetts statute, these buildings have a Determination of Eligibility for
the National Register and are listed on the State Register of Historic Buildings. When work on
these buildings requires a State permit or the renovation project is funded by the Commonwealth
of Massachusetts bond funding, the Massachusetts Historic Commission reviews exterior
alterations.
In 2015, MIT signed a protocol agreement with the Cambridge Historical Commission (CHC)
that ensured that MIT would review all exterior alteration to buildings considered significant with
the staff of the CHC. In 2017, MIT completed a historic survey and evaluation of campus
buildings 45 years or older and three campus landscapes. The evaluation utilized the Secretary
for Interior Standards for Historic Preservation evaluation criteria and a team consisting of MIT
staff, the Cambridge Historical Commission staff and the project consultant, Public Archaeology
Lab from Pawtucket RI evaluated the historic resources.. The attached campus map indicates the
buildings and landscapes that require consultation with the Office of Campus Planning before a
design team engages in alterations and additions.
Since 2000, a number of iconic buildings have been constructed on campus which do not require
any regulatory review but are significant enough to require internal design review for
compatibility with the original building design. These buildings include Simmons Hall, Stata
Center, Brain and Cognitive Sciences, the Media Lab (E14) and the Sloan Building E62. The
Office of Campus Planning works with the Comprehensive Stewardship Group, Repair and
Maintenance and Campus Construction to review proposed modifications to those buildings to
ensure that the design intent remains intact.
Buildings:
1. The attached campus map indicates buildings and landscapes of historic significance.
2. All renovations and alterations should be done with particular care to ensure high quality
workmanship and historic appropriateness.
3. When working on all these buildings, any exterior alterations should be reviewed with the
staff of Office of Campus Planning.
4. If the proposal warrants, there will be an informal review with the staff of the Cambridge
Historical Commission.
5. If there are any issues that cannot be resolved between MIT and the Cambridge Historical
Commission staff, the proposal will be brought to the Cambridge Historical Commission
for review.
Location:
1. First Floor entry lobbies, rest rooms and other public areas of historic or iconic buildings
should be constructed with high quality durable finishes and materials. For example:
2. Exterior features and the exterior envelope should be respectfully restored using materials
and assemblies expected to have a long life span. For example:
a. The new replicated steel windows in the Main Group have an anticipated life
span of 75 to 100 years. Their design uses new technology and maintains the
historic and iconic character of the Main Group buildings.
b. The successful long-term restoration of building envelopes is dependent upon
4. Materials:
Ma
Be
t
ss a
nS
nt
S t
rso
chu
Less than 50 Years Old
lke
sett
Fu
sA
NE83
ve
NE123A
N57
t
hSt
Six
St
nd
rtla
Po
N50
St
Br
St Te
th
oa
ch
Gre
ney
Fif
no
NE48
dw
Sid log
en
ay
y Sq
Fra
t S
nkli
Ma
NW61 N51 in NE46
n
N52 St
St
NW98
NE49
NE47 Bin
ne
yS
t
St
e St
rn
Lan dsdown NE45
bo
Os
Cro
NW86
ss
St
eS
t Purringto n St NW10
n
ok li
Bro
NW22
Erie
Albany St
NW17 NW16 N4
Pa
NW23 46
St
c
ific
N16A
S
N10 N9
t
N16C
N16B 48
NW35 N16
Alb any
St
NW12 44
NW13
NW14 42
NW12A
41 43
NW32 NW21 NW15 St
Vassar
He
NW30 36 76 St
NW20
nry
d
3r
St
WW15 W41 38 32
35 37 39 34
W45
ly S
t
W56 33 E19 Ma
ver
W57
W31 31 in
St
Wa W59 W57A 24
17 26
WW25 W64 W36 W33 57 68
W55 W32
St E18 NE18
W79 Vassar 9
13 E17 E38
W34 12
W35 W20 16 56 66 E25 E39
7A E70
W89 7 11 10
E48
8
W97 W85FG
St
54
St
ard
W85DE 18 E15
ton
yw
6C E23
St
rle
5B
Ha
W85HJK
Ames St
o rth
Ca
W92 W16 5A 62 64
W53G
5
5C
3 4 6
w
W15 E55
ds
W53F
W85ABC 5D
5E 6B
Wa
W53E
W53 E14
W98 W53D
Amesbury St
W11 E40
Ave
W85 W53C
W53A
W83
W53B
Amherst Alley Amherst St
W91
Amherst Alley E2 E53
W84 W1 1 2
W61 14 50 E62
Fowler St
Endicott St
W70 W51 E51
W71 W51D W7 W5 E52
W51C
W4 W2 E1 E60
Memorial Dr Memorial Dr
51
W8
[ 500
Feet
May 2018
Table of Contents
"#"! $%&'(!)*!+,-(###################################################################################################################################### .!
"#/! +,-!0'(123!($,30,40( ######################################################################################################################## .!
1. Baseline
2. Life Science/Bio
3. Optical
4. Engineering/Physical Sciences
5. Maker Space/ Machine Shop
6. Chemistry
7. BL1
8. BL2
9. BL2+
10. BL3 (place holder)
11. Radioactive
12. Clinical Lab (place holder)
13. Animal/ Survival Surgery
14. ABSL-2
15. ABSL-2+
The general design and construction of laboratory fume hoods should conform to applicable
guidelines in the current editions of:
Planning
Laboratory means a facility where the "laboratory use of hazardous chemicals” occurs. It is a
workplace where relatively small quantities of hazardous chemicals are used on a non-production
basis.
*BSL2 laboratories are the most commonly found biological research laboratories at MIT, please
refer to the BSL-2 section below for the requirements in ADDITION to the requirements listed in
this section.
1. Eating and drinking are not permitted in laboratories. Laboratory design should
incorporate areas outside the labs to store food and a safe place to eat. When laboratories
place write-up areas inside the laboratory zone, storage solutions for drink vessels should
be provided for outside of the laboratory.
2. Mechanisms for controlling laboratory access must be in place. All laboratories must
have doors for separation from public areas. The doors must be self-closing and lockable
in order to control access to the laboratory and to research materials and information.
Locking mechanisms on doors may include a standard keyed entry, a punch-code lock, a
card reader, or a combination of these measures. Card readers may be preferred for
laboratories of specific types/ use.
3. Clearly identify and label the Building Occupancy Classification and Chemical Control
Areas in the life safety documentation — Occupancy classification and control areas
should be based upon an assessment of the projected chemical inventory of the building.
Most teaching and research buildings should not require an H occupancy classification;
however, individual H occupancy rooms may be necessary.
4. Each laboratory using hazardous materials, whether chemical, biological, or radioactive,
should contain a sink for hand washing. Sinks for hand washing are required in each
biological research lab as well as eye wash stations. The following considerations should
be made when choosing a sink:
a. Hands-free sinks (foot-pedal operated) are preferred since this reduces spread of
contaminants from handles. Otherwise, consider use of paddle handles to
minimize need to touch handles to turn water on and off.
b. Sink screen strainers (fine mesh) should be considered to prevent sharps, i.e.
needles, small pipette tips from going down the drain.
c. Sink material should be compatible with chemical decontaminants commonly
used in biological laboratories. They should be easy to clean and disinfect.
5. There must be adequate in-laboratory storage cabinets to store reagents and chemicals
and to provide segregation of incompatible materials. Storage design should be based on
projected quantities and waste management practices. MIT has successfully utilized a
ventilated sliding cabinet design adjacent to certain fume hoods as an option to achieve
these goals.
6. All laboratories should have access to phone communication. An evaluation of the
building and the hazards in the space will result in the recommendation of specific types
of phones and locations. Consult with MIT EHS and MIT IST..
1. Because the handling and storage of hazardous materials inherently carries a high risk of
exposure and injury, segregate laboratory and non-laboratory activities to the extent
possible. A possible example of this is to separate the offices and write up areas from the
chemical usage areas. This separation can take the form of a glass wall that provides a
direct line of sight into the laboratory, while still separating the HVAC, Plumbing, and
finish requirements of the differing space types. For example, this physical separation
would allow the HVAC system to be tailored to each hazard area, with the 100%
exhausted air system utilized in the higher hazard laboratories, while a more efficient
recirculated system could be utilized in the office, conference, and collaboration areas.
This strategy also has the added benefit of reducing prohibited food and drink within the
higher hazard laboratory zone when connected to the public circulation.
2. If possible, a separation of corridors servicing laboratory operations and general public
circulation through the building is desired to enhance the safety of all building
inhabitants.
3. Be aware that while a typical new construction general laboratory requires a maximum
vibration velocity of 50 (!m/s) and a structural criterion of 6,400 (kips/in-sec, with
specialty sciences requiring more stringent criteria, please review with specific
researchers their vibration requirements.
4. If multiple laboratories will need nitrogen, carbon dioxide, or other specific gasses in
large volumes, the project team should analyze merits of bulk tank(s) and distribution
system.
Dimensions
Modular design is seen to be an advantage to the Institute, by rationalizing the “kit of parts” users
and administrators utilize to fulfill their programmatic needs. Rational and repetitive sizing of
laboratory bench components and shelving is encouraged. Here are some more specific
dimensional goals:
Design laboratory workstations to accommodate the range of body dimensions that may be using
the workstations. For example, computer and microscopes workstations may require height-
adjustable work surfaces and chairs.
In specialized spaces with equipment such as roll-in Autoclaves & Glass Wash, special attention
has to be spent coordinating any required slab depressions, an/or ramping required within the
space.
Aisles
Aisles are to be a minimum of 5’-0” clear in width, and free from obstructions. The design team
should allow for hazardous waste and trash receptacles within the bench design, allowing for the
aisles to remain free of clutter and hazardous obstacles.
Fume Hoods
(Refer to Section 5.9 in this document)
Finishes
Certain finishes are recommended for certain laboratory environments in order to maintain clean-
ability and safety.
1. All work surfaces (e.g., bench tops, counters, etc.) should be impervious to the chemicals
and materials used in the laboratory. Bench tops must be impervious to water and
resistant to acids, alkalis, organic solvents and moderate heat.
2. The laboratories shall be designed so that they can be easily cleaned. This includes built-
in components as well as furniture.
3. Laboratory furniture should be sturdy and easily cleanable, including upholstered
materials. Hard, non-porous surfaces, like plastic are preferred because they are more
All wastewater from laboratory sinks, floor drains, and other areas within MIT buildings that
enters the public sanitary sewerage system MUST meet the MWRA limits on contaminants and
pollutants within the waste water. Any new laboratory waste water site would require either a
new permit, or be added to MIT’s discharge permit.
Laboratory waste water is to be treated by the MIT EHS approved waste water treatment system.
(An acid neutralization system being the most common). Chip Tank waste water treatment
systems are NOT permitted at MIT.
MIT Design Guidelines section on plumbing for specific information and alternatives for
acceptable cooling water options. EHS prohibits the once-through or single-pass cooling
techniques.
Questions about these policies should be directed to the Environmental Management Program
(452-EHSS or (617) 452-3477).
References:
NIH Guidelines for Research Involving Recombinant or Synthetic Nucleic Acid Molecules, 2013.
CDC/NIH Biosafety in Microbiological and Biomedical Laboratories, latest edition
Planning
All BSL-1 Laboratory spaces should be designed to a BSL-2 standard. Please refer to “Section
2.3: BSL-2 Laboratory” below.
BSL2 laboratories are the most commonly found biological research laboratories at MIT. Design
of biological research laboratories at MIT must comply with the NIH Guidelines for Research
1. Biological research laboratories must have net directional inward airflow (be under
negative pressure) with air moving from public spaces into the laboratory towards the
most contaminated or high risk areas. This allows for control of exposures in case of a
spill in the laboratory. Laboratory air may not be re-circulated to any other building
spaces outside of the laboratory. It must be exhausted to the outside. Please refer to
section 3.2 Ventilation (section 16.2 EHS) within this document.
2. Insect and Rodent control: Laboratories should be designed to prevent insect and/or
rodent penetration, including sealing holes to prevent intrusion. If laboratory windows
are operable, they must be fitted with fly screens.
3. Depending on the research and safety needs, laboratories may require the following
equipment:
Planning
Facility design, procedures and practices must fulfill all requirements of a BSL-2 laboratory with
the addition of specific BSL-3 design components, practices and procedures, as outlined in
Biosafety in Microbiological and Biomedical Laboratories and the NIH Guidelines for Research
Involving Recombinant or Synthetic Nucleic Acid Molecules.
The following design guidelines are for common BSL-2+ laboratories. Occasionally, highly
specific, customized requirements will be needed based on unique experimental needs. Unique
laboratory designs may require Committee on the Assessment of Biohazards/Embryonic Stem
Cell Research Oversight (CAB/ESCRO) review in addition to Biosafety Program (BSP) review.
• Laboratory Design
1. The laboratory plan must meet all requirements for BSL-2 laboratories as described in the
previous section.
2. A door must physically separate the BSL-2+ laboratory from other research and public
areas. In other words, the BSL-2+ laboratory must be a separate room. The entry door
must be self-closing and the door should have a window so that personnel working at
BSL-2+ can be seen (safety issue).
• Equipment
• Signage
1. It is preferred to have access to utilities serving a BSL 2+ lab outside the lab. Signage
indicating the location of shutoff valves for gas, water, vacuum, and electricity serving
the BSL-2+ facility should be posted on the entry door to the facility so that services may
be shut down as needed without having to enter the research laboratory.
References:
NIH Guidelines for Research Involving Recombinant or Synthetic Nucleic Acid Molecules, 2013.
CDC/NIH Biosafety in Microbiological and Biomedical Laboratories, latest edition
2.5 BSL-3
All BSL-3 projects require very significant upgrades to the architectural and MEP systems over a
BSL-2 plus laboratory standard. Any such project must be coordinated directly with MIT EHS,
SEG, and Campus Construction for exact design requirements.
2.8 Chemistry
Planning
Organic and inorganic chemistry laboratory activities include mixing, heating, cooling, distilling,
evaporating diluting, and reacting chemicals for testing and research experiments. Many
analytical procedures call for handling moderate amounts of hazardous chemicals, usually
petroleum solvents, explosive gases, and all types of toxic substances. Usually this type of
laboratory will be co-located within a building containing multiple laboratory. A Chemistry
Laboratory must meet the criteria set out in Section 2.1 for a “Baseline” laboratory, along with
these additional considerations.
Design Considerations:
1. It is extremely important to follow the fume hood placement guidelines outlined in the
MIT placement criteria requirements, Section 5.9, in this document. The outlined
clearances in this section are essential to maintain fume hood contaminant containment.
2. Allow for a high concentration of fume hoods, and utilize a Variable Volume ventilation
system to vary supply and exhaust air based on use.
3. Install digital signs at the lab entrance displaying the laboratories exhaust airflow
volume to inform and encourage users to close fume hood sashes for energy
conservation.
4. Allow for deeper and taller fume hoods than standard, so as to accommodate a variety of
required rig set ups within the hood.
5. Effluent gases from some analytical equipment (ex. gas chromatographs, absorption
spectrometers, etc.) must be exhausted to the exterior of the building via non-
recirculating (100% outside air) laboratory exhaust system. This may be a manifolded
system within a fire control area. Effluent gases should be captured and exhausted from
the laboratory via various methods such as canopy hoods, enclosures, duct drops, etc..
Note: Perchloric acid use requires dedicated hoods with the appropriate construction,
materials, and internal wash-down capability. Please refer to Section 5.4. of this
document for information on Perchloric fume hoods.
6. The heat load of each of the analytical instruments and auxiliary equipment should be
evaluated when estimating heating and air conditioning requirements.
7. When high voltage equipment is installed in analytical chemistry laboratories, individual
disconnects and emergency shut-off switches to equipment should be located beside and
near equipment (within reach of all laboratory workers). Plan adequate space between
equipment to allow for disconnect access, service, and cleaning.
Introduction
This section describes requirements for labs that will use radioactive material(s) /radiation
producing equipment. The goal in the design and construction of these facilities are to keep
radiation doses As Low as Reasonably Achievable (ALARA). The MIT Radiation Protection
Program shall be consulted for further information regarding the design of radiation facilities.
All laboratories utilizing radiation sources, both ionizing and non-ionizing, such as radioactive
sources, radiation producing equipment such as analytical x-ray, lasers, superconducting magnets,
etc, must meet all federal and/or local regulatory requirements for licensing/registration. These
regulations and standards also can have facility design and construction requirements.
Consideration should be given to having all laboratory door access controlled by card proximity
readers. The doors would remain locked at all times and access would be granted only to person
associated with the lab space who have completed the required EHS training. Lab doors should
have auto-closing mechanisms. Access control and security monitoring is required for high
activity irradiator labs.
The following list is a summary of the radiation facilities that have specific requirements:
2.9.1 Radioactive Material Facilities (105 CMR 120.200 Standards for Protection
against Radiation)
Background
Radioactive materials are material composed or unstable radioactive atoms which spontaneously
decay to reach a more stable state. During the decay process they release excess energy in the
form of radioactive particles (beta, alpha, neutrons) or electromagnetic waves/photons (gamma
rays, X-rays). These radioactive materials are used as a tool in various research applications at the
Access Control
All facilities that plan to use radioactive material (RAM) must be equipped with adequate access
control to prevent unauthorized access to the facilities. Laboratory doors should be equipped with
an access control system to allow access to only authorized persons.
Stock Storage such as cabinets, drawers, refrigerators, freezers, etc… shall be equipped with a
locking mechanism to prevent unauthorized access to radioactive materials. Examples are
padlocks, combinations locks, and punch codes. Depending on the amounts of radioactive and
particular isotopes involved access control requirements can vary.
It is preferred to use materials that can be easily decontaminated in the construction of RAM
facilities.
Flooring material shall be non-porous and is recommended to be seamless. Many facilities have
tiles floors which are adequate; however, tiles may have to be removed in the event of a spill.
Bench tops shall be non-porous and seamless where possible. Typical laboratory bench top
materials are generally adequate.
Fume hoods are required when using volatile radioactive materials and powders. Specialized
ventilation is required if work will involve volatile radioactive material. This hood should
probably be located in the multi-use “hot” lab and would be equipped with the appropriate
filtration system (activated carbon or HEPA). Fume hoods shall be constructed of a surface that
can be easily decontaminated such as stainless-steel.
A multi-user “hot lab” where the bulk of the radioactive material experiments will be performed
and the stock radioactive material will be securely stored. This lab would be shared by many
researchers for initial labeling experiments. Only lower activity samples would be taken to the
individual labs for further experimentation. The floor in this lab should be rolled, seamless vinyl
for ease of decontamination. Bench surfaces should be impervious to allow for ease in
decontamination.
Fume hoods should have a stainless steel interior for ease of decontamination. Exhaust ductwork
shall be resistant to corrosion or degradation by chemicals used.
Sink for disposal of aqueous, biological, soluble liquid waste that meet regulatory requirements.
Sink should be able to be operated hands free (such as foot pedals) to prevent further
contamination.
Shielding: Radiation shielding may need to be incorporated into a facilities design depending on
the quantity and isotopes used. This radiation dose can affect radiation users if unshielded and
may extend into adjacent spaces affecting other facility occupants. The following examples of
shielding equipment should be discussed during design as necessary:
Various types of laboratory safety equipment need to be incorporated into a facility’s design to
keep occupants mitigate radiation contamination, injury or other emergency events.
Personal Protective Equipment (PPE) Storage should be located by the entrance to the facility
so that it can be donned prior to entering a potentially hazardous area. Adequate space should be
allotted for laboratory coats so that they are easily accessible, and the possibility of cross
contamination is reduced.
Radiation Survey Equipment Space should be allotted for the storage of this equipment to
avoid damage and contamination.
Lab signage holder at entrance for required regulatory warning postings and emergency
response information.
Physical Form: Solid, Liquid, Sharps, Mixed Hazardous Waste, Animal Carcasses, Liquid
Scintillation Vials (LSV)
When designing a RAM facility adequate space must be provided for the waste containers so that
they can be in close proximity to the work being performed whether small bench top containers or
large floor containers are used. Liquid waste containers may need to be provided with secondary
containment which will require a larger footprint.
Background
PET scans use radioactive tracers to collect in an area of interest in the body that have high levels
of chemical activity which correspond to areas affected by disease. When a PET scan is
performed these areas are show up as highlighted regions. The isotopes used typically have high
specific activities (leading to high dose rates) and a relatively short half-life.
All items listed under the RAM Facilities must be implemented in the design of PET/CT
facilities. More stringent requirements may be necessary due to the high dose rates from the
isotopes used in these procedures.
Shielding calculations will need to be performed for walls, ceiling, and possibly the floor. Lead is
the most commonly used shielding material for these facilities.
Layout of the space will need to be reviewed by the RPP to ensure that radiation exposures
comply with the ALARA principle. Certain areas need to be in place for holding of radioactive
animals, storage of waste, and sample preparation.
2.9.4 Irradiator Facilities (105 CMR 120.620: Licensing and Radiation Safety
Requirements for Irradiators)
Background
Irradiators are device which contain a sealed gamma emitting radiation source to irradiate (deliver
radiation dose) a material, object, or device. At the institute irradiators are often used for animal
studies and for testing electronic components specifically for space applications.
1. Consideration for floor loading as these units can weigh between 6000-9,000 pounds.
2. Typically higher voltage electric supply.
3. The room should have floor to ceiling fully grouted masonry walls, not sheetrock.
4. Room supply/exhaust air system ductwork should be less than 12 inches in diameter.
5. Room must have access control system utilizing both proximity card access and
biometric validation for unescorted use. The access control system will be alarmed to
detect any unauthorized/forced entry or a door held open for a defined period of time.
6. Room will be supplied with motion detectors.
7. Room equipped with radiation dose rate level monitors directly connected to security to
alarm the detection of abnormal radiation levels.
8. Panic buttons connected to security.
9. Cameras/video system to allow security to triage alarm conditions and report to
emergency first responders the conditions within the room.
10. Cameras/video in the corridors leading to the irradiator facility to monitor entrance/exit.
11. A telephone within the room to allow for communication with security.
12. A 24/7 facility security monitoring station (dispatch) to monitor alarms from the
irradiator facility to enable appropriate emergency response depending on the alarm
conditions.
13. Secure transmission of security communications between the facility and the security
monitoring station.
14. Lab signage holder at entrance for required regulatory warning postings and emergency
response information.
X-Ray Irradiators
1. Consideration for floor loading as these units can weigh between 6000-9,000 pounds.
2. Typically higher voltage electric supply.
3. Lab signage holder at entrance for required regulatory warning postings and emergency
response information.
4. Room shall have access control system. Utilizing proximity card access is highly
recommended.
1. Consideration for floor loading as these units can weigh thousands of pounds.
2. Typically higher voltage electric supply.
3. Analytical x-ray machines with an open beam configuration, consideration must be given
to either integral shielding within the facility walls, doors, and/ or isolation barriers.
4. Fully enclosed or cabinet type analytical x-ray equipment that does not emit any
increased radiation levels outside the enclosure requires only standard lab design.
Standard laboratory design with a few additional considerations. The MIT Radiation
Protection Program shall be consulted during the design and review process.
2.9.7 Medical X-ray Facilities (105 CMR 120.400: X-Rays in the Healing Arts)
Background: X-rays are used as a diagnostic tool in medical and veterinary applications. Due to
the fact that X-rays are very penetrating they pass though less dense tissues such as skin, and are
absorbed by more dense tissue such as bones and teeth. The X-rays that penetrate completely
though the tissue are collected on a film on detection device this shows up as the white areas on
an X-ray and the darker areas represent the dense tissue. Medical and dental x-ray facilities need
to be designed in a way to protect the operator as well as other occupants of the facility.
Standard medical room design with additional considerations. The MIT Radiation
Protection Program shall be consulted during the design and review process.
2.9.8 Dental X-ray Rooms (105 CMR 120.400 “X-Rays in the Healing Arts)
Background: X-rays are used as a diagnostic tool in medical and veterinary applications. Due to
the fact that X-rays are very penetrating they pass though less dense tissues such as skin, and are
absorbed by more dense tissue such as bones and teeth. The X-rays that penetrate completely
though the tissue are collected on a film on detection device this shows up as the white areas on
an X-ray and the darker areas represent the dense tissue. Medical and dental x-ray facilities need
to be designed in a way to protect the operator as well as other occupants of the facility.
Standard dental room design with additional considerations. The MIT Radiation Protection
Program shall be consulted during the design and review process.
1. See 105 CMR 120.400 “X-Rays in the Healing Arts” for additional requirements set forth
by the Massachusetts Department of Public Health Radiation Control Program.
2. See NCRP Report No. 145: Radiation Protection in Dentistry of additional requirements.
3. Prior to construction a shielding plan shall be submitted to the Radiation Control Program
for review and approval.
Background: PET and CT images provide the researcher with extraordinary functional and
anatomic views of live animals. PET and CT images are made by detecting the emitted gamma
rays or x-rays and using a mathematical algorithm calculating the origin of this radiation Whether
the gamma rays emitted by radioactive (PET) isotopes or the x-rays being emitting by the CT
tube, these energetic rays require extra shielding in order to minimize the radiation dose to
workers and visitors both in the use area and also the adjacent areas. Researchers compounding
pharmaceuticals may need specialized shielding equipment when manipulating the highly
radioactive material.
1. Facilities that require the use of PET-CT equipment (typically in the vivarium),
consideration must be given to assess the necessary shielding required in the lab to
minimize worker and adjacent room public exposures. Portable and fixed lead shielding
may be necessary depending on the types and amounts of PET isotopes to be used.
Integral wall-door shielding may also be necessary.
Note: If the facility is considering installation a cyclotron to produce their own PET
isotopes, there are many considerations/requirements for the appropriate shielding,
delivery systems, ventilation and security systems that must be designed into the cyclotron.
Laser radiation emitted from Class 3B and 4 lasers is considered to be potentially hazardous.
Proper lab design can mitigate this hazard. This section is divided into two parts, covering both
the exterior and interior design of a laser lab.
A visual overview of the safety requirements for a laser lab are provided in
This section provides requirements and recommendations for the exterior of laser labs.
Class 3B and 4 laser labs require access control. The three most common controls are:
• Door interlock systems
• Electronic lock (keypad / RFID)
• Hazard posting
An MIT Laser Safety Officer from EHS Radiation Protection shall be consulted to determine the
required access control system for an individual lab. If a laser interlock system is required, it must
be such that the interlock must be armed first to allow the laser to be turned on. An interlocked
system is not always the best solution. Interlock systems must only cause the laser beam to
become safe when tripped. This is often achieved by dropping a shutter or causing the laser to
lose power (least favored approach).
RFID card access or Cipher lock with key override: this approach provides secure access but has
no effect on laser operation. The key override is for first responders only, not housekeeping.
Sign Conditions
• Posted at eye level (60” above the floor) to the side of the entryway, not above the door
frame
• LED light source
• A red light or non-descriptive sign is not sufficient
• The illuminated sign is required for each doorway that is accessible
• Illuminated whenever the laser is energized and capable of producing a beam
• Automatic light, light turn off/on based on when the laser is on/off
• If light manually controlled, light switch shall be located in a convenient position near the
laser control
Laser Eyewear Storage
A critical element of laser safety is laser protective eyewear; hence, the storage and protection of
that eyewear is very important. Laser eyewear can be stored inside or outside of the laser use area
or at both locations. Storage shelf or rack must protect the physical integrity of the eyewear and
be easily accessible to the users.
Storage Considerations: If multiple lasers are present, store in a way to avoid confusing different
types of eyewear
Windows
In general, windows should be avoided as they will need to be covered. If doors are equipped
with windows, the following needs to be considered:
• Window panels in doors should be covered with a permanent opaque material.
• If windows are required for non-laser use periods, then shades or removable covers for
laser operation need to be available.
• Electronic shutter windows can be used in some circumstances
• Windows can be covered with optical density acrylics to provide protection and viewing.
Such acrylics must be labeled with wavelength and optical density.
• Portals/viewing windows must be designed to prevent any exposure above the maximum
permissible exposure value. Contact EHS Radiation Protection for support with this
evaluation.
• Wall windows should be treated the same as door windows.
Walls/Enclosures/Barriers
Walls should be painted a non-reflective color such as a matte black. There should be no
reflective materials in the lab such as corner protectors on walls.
For open beam, class 4 labs without any localized barriers such as laser curtains or laser table
barriers, the design of a laser-safe entry area must be considered to prevent contact with a stray
laser beam upon entrance to the lab. A laser safety eyewear storage rack should be included of
this area.
The purpose of a curtain area is to protect the doorway and/or eye-safe areas of the room. These
curtains should have the following properties:
Work Station
When a computer workstation exists within the lab and laser protective eyewear needs to be
removed to see the screen:
• Take steps to ensure there are partitions, perimeter guards, or equivalent means to allow
safe viewing of computer screens
• Workstation screen should not be at the same level as any open laser beams
If the facility will require the use of equipment that may generate large magnetic fields such as
MRI/NMR/EPR, consideration must be given to assess the necessary magnetic field shielding
requirements in the walls, ceilings, and doors. The MIT Radiation Protection Program shall be
consulted during the design and review process. There are numerous and detailed considerations
to be accounted for in the design of MRI’s that need to be discussed and taken into consideration
with the end user, MRI vendor, shielding vendor, EHS, and the design team.
The above should take into account the location and strength of the magnetic fringe fields with
respect to exposure to individuals with pacemakers and other regulatory requirements.
A lab entrance posting receptacle for required regulatory warning postings and emergency
response information will be required and if needed area and/or floor postings of fringe fields
needs to be considered. A receptacle inside of the lab door for lab occupants to place credit cards,
watches, cell phones, etc. may need to be considered depending on the strength of the magnet.
Limits for personnel exposure can be found in the American Conference of Governmental
Industrial Hygienists (ACGIH) “Threshold Limiting Values (TLV) guidance on Static Magnetic
Fields” and/or the International Commission on Nonionizing Radiation (ICNIRP) “Guidelines on
Limits of Exposure to Static Magnetic Fields”. In addition magnetic resonance imaging systems
for human subjects should follow the American College of Radiology Guidance for Safe MR
Practices.
Additional Notes
1. Weight 12-18,000lbs.
2. Need for Magnetic shielding in addition to the standard RF shielding.
Low level radioactive waste typically falls into the following categories:
Solid radioactive waste (paper, plastic, glass): Will be segregated by half-life in appropriate
containers at the lab level to ensure proper disposal management. Short half-lived waste should
be managed by decay-in-storage and ultimate disposal when the waste is no longer radioactive.
Long half lived solid waste will be packaged for ultimate off-site disposal.
Aqueous liquid radioactive waste: May be disposed via the sanitary sewer system in accordance
with local regulations or license conditions or collected and stored for off-site disposal.
Mixed chemical-radioactive waste: Must be stored for ultimate off-site disposal. If short half-
lived, the waste may be stored until no longer radioactive and disposed as chemical waste.
Animal carcass waste: Stored frozen until ultimate off-site disposal.
Collect the waste from the laboratories in containers that can be transported offsite for
processing/disposal.
Provide autoclaves for each lab area and have the researcher’s process and manage their own
non-sharp biological waste. The disinfected (autoclaved) waste can be disposed as regular trash.
Separate containers for sharp biological waste would need to be provided. This waste would be
collected and treated as #2 or #3 below.
Collect the waste from the laboratories and transport to a central processing facility for treatment
and disposal as non-regulated waste. The central facility would need to be equipped with a large
scale autoclave and trash grinder prior to the disposal of treated waste as regular trash.
Note: Do not short change the amount of space required to have a well-functioning
hazardous waste management program. This includes:
• Designated areas in the lab for waste collection containers, in cabinets, bench space and
floor space
• Temporary consolidation storage spaces for waste near the point of generation, and
• A state of the art central waste processing/storage facility.
2.9.13 Accelerator Facilities (105 CMR 120.700: Radiation Safety Requirements for
Particle Accelerators)
Background
Accelerators are machines capable of accelerating electrons, protons, deuterons, or other
charged particles in a vacuum and of discharging the resultant particulate or other radiation into
a medium at energies usually in excess of 1 MeV. For purposes of this definition, "particle
accelerator" is an equivalent term.
Accelerator facilities range from simple to very complex systems. The requirements of
105CMR120.700 and 105CMR120.200 shall be met and the Radiation Protection Program must
be contacted in the early design considerations to ensure shielding designs are appropriate for the
facility. In addition the ANSI N43.1, Radiation Safety for the Design and Operation of Particle
Accelerators should be consulted in the design phase. Consult MIT RPP with any questions
regarding accelerator facilities.
Introduction
Systems that emit radiofrequency (RF) energy as an intentional emitter need to be reviewed by
MIT EHS if system power is in excess of 5W Effective Isotropic Rated Power (EIRP) to ensure
that exposure levels meet the requirements of the MDPH 105CMR122.000 and those of the IEEE
C95.1. Unintentional emitters shall be shielded to preclude exposures in excess of the limits in
the regulations and standards as noted above. All systems shall be designed to operate in a non-
interference mode in accordance with 47CFR15 which may require the use of RF shielding.
Limit center bay vibration velocity to 2,000 microinches/second due to building resonances and
footfall induced vibration including slow walking speed within labs and moderate walking speeds
in adjacent corridors. Regions within 5 feet of columns shall be restricted to a vibration velocity
of 600 microinches / second with inducer located at center of bay. This will provide a laboratory
environment where approximately 45% of the lab are 500 and 1,000 micro-inches/second;
approximately 10% are between 1,000 and 1,500 micro-inches/second; and only 20% are between
1,500 and 2,000 micro-inches/second. For vibrations induced by mechanical equipment,
structural slabs between lab and mechanical spaces shall be constructed to a minimum mass of
350 Kg/M2 in order to provide an appropriate base for equipment isolators to work against. The
design approach will then be to provide equipment isolation to preclude vibrations from being
transferred into the structure.
Tables may be designed for up to 4000 lbs. gross load capacity. Therefore, PM needs to have an
expert evaluate if the floors may need reinforcement to handle this equipment depending on the
table and application. Most vibration damping tables require compressed gas. Therefore, secure
cylinder storage or house supplied air must be available. Granite tables offer some damping but
are typically no longer used.
If the table will be used for in vitro electrophysiology, an electrical ground connection and
vacuum supply should be available. Additional room shielding may be recommended. Typically,
a Faraday cage will be placed on the anti-vibration table. Surgical platforms for in vivo
electrophysiology may also require vibration damping tables. For both in vivo and in vitro
Several disciplines, particularly those associated with biological research, may require vibration
damping for microscopy. Vibration damping tables may be required for surgical stations,
confocal imaging technology, scanning electron microscopy, scanning probe microscopy and
conventional optical microscopy.
Planning
The layout of a clinical laboratory will be determined by its size and by the nature and number of
clinical tests that will be performed as well as by the number of staff, number of shifts, and
number of automated instruments. Clinical laboratories resemble a combination of analytical
chemistry and biological laboratory. Special requirements may be imposed by the Joint
Commission on Accreditation of Health Care Organizations (JCAHO, 2001). In addition, special
process workstations, laboratory benches, and seating should be carefully designed to aid the
ergonomic safeguards of workers, because clinical laboratory activities are highly repetitive and
many have the potential to cause repetitive stress injuries. A Clinical Laboratory must meet the
criteria set out in Section 2.1 for a “Baseline” laboratory, along with these additional
considerations.
Design Considerations
1. The clinical laboratory must meet the same criteria as the BSL-2 laboratory, with similar
emergency shower, eyewash, autoclave, BSC, and flammable storage requirements.
2. Due to the evolving trends in Clinical Laboratory design, the following zone flexibility
is recommended:
a. Least flexible: offices, bathrooms, lockers, etc.
b. Semi flexible: blood bank, outpatient area.
c. Highly flexible: all testing areas.
3. Storage facilities and refrigeration for reagents, standards, supplies, and stained glass
specimen microscope slides shall conform to applicable NFPA standards.
4. A specimen collection facility may be located outside the laboratory suite, and will
require the following:
a. The blood collection area should have counter space, patient seating, and hand
wash facilities.
b. Specimen collection room should be equipped with water closet and lavatory.
5. If radioactive materials are employed, facilities must be available for long-term storage
and disposal while meeting all applicable MIT EHS, City, State, and Federal regulations
and guidelines.
6. Potential requirements:
a. Glove box/ BSC (Biological Safety Cabinets).
Location Criteria
All laboratory construction shall include one or more of these strategies for the storage and use of
Compressed Gas.
Cylinder brackets for gas cylinders, and alcoves for cylinders and cryogenic dewars shall not
remain or be installed in exit or public corridors. Any existing cylinder brackets in exit or public
corridor(s) must be removed.
Gases should not be used in spaces such as cold rooms, warm rooms, and other areas which may
not have adequate fresh air ventilation. If gases must be used in such areas, A/E team will contact
the MIT CC Project Manager to engage MIT EHS for assistance in determining if oxygen
monitoring or other monitoring is required and/or for help in selecting a monitoring system with
local alarms.
Gases that are toxic (NFPA health rating 3 or 4), pyrophoric gases, and nitrous oxide gas should
be stored in a ventilated area secured from unauthorized access (i.e. a locked storage room or
Care should be given to calculate the total volume of flammable gas to be used and stored in a
given laboratory/ control area in order to ensure compliance with the building code.
Cylinders should be located away from boilers, radiators, heaters and other heat producing
equipment. Storage area temperatures should not exceed 125 °F, or below 0 °F. (Compressed
Gas Association).
1. The following options should only be accessible via a secure non-public circulation/
corridor or laboratory suite:
a. Build/install a specialized lab gas distribution manifold that can progressively
switch (automatically or manually) supply between cylinders or dewars to meet
demand, and are hard piped to distribution turrets or equipment throughout the
laboratory. These manifolds can usually range from a 3 to 18 tank manifold,
with the tanks being staked single or double file. Dependent on the orientation,
the tanks can be safely secured via straps, chain, or steel tube frame tank
restraints. Such manifolds can be housed in rooms or closets that are centrally
located within the service zone outside of the laboratory, to allow for the least
disruptive delivery and replacement process possible. Include fire rated doors
where required, and fire sprinklers, gas monitoring, and lab exhaust ventilation in
the design of the room/closet. This space must be negatively pressurized to the
adjacent corridor. Based on the hazards of the gases in this room/closet,
determine if this area should not be used for anything else or if other lab
equipment can be installed. Depending on gas cylinder/dewar type, distribution
manifolds could also be located within open alcoves with the approved gases
piped into the lab from that location. This strategy can be applied building wide.
b. If a multi-tank specialty gas tank manifold cannot be located outside of the
laboratory zone, then alternate locations can include adjacent support spaces, or
low hazard areas of the lab where service and delivery of the manifold will not
interfere with the operation of the laboratory, such as near the entrance
(preferred).
2. If a (non-public, non-exit) service corridor is a minimum of 9’-0” wide, it can be
reconfigured to create a service “linear equipment” room, with end-walls defining
“equipment zones”. All Linear Equipment rooms must still meet all building code
requirements.
3. The review of possible exterior bulk storage of liquid nitrogen, carbon dioxide, etc.
should be an overall design consideration for projects where large volumes are intended
to be used.
4. If direct source (no manifold) gas cylinders need to be set up in the lab next to equipment,
fume hood, etc. to serve specific scientific needs, then dedicate wall space for an
1. Include a suitable pressure relief device to protect a system using a compressed gas if
the system has a pressure rating less than the compressed gas supply source and if, due
to the gas capacity of the supply source or for any other reason, the system pressure
rating may be exceeded.
2. Cylinders containing gases that pose health hazards and pyrophoric gases shall be
housed in mechanically ventilated gas cylinder cabinets or fume hoods; Highly toxic,
toxic and pyrophoric gases must be stored in ventilated, gas cylinder cabinets with a
sprinkler head connected to the building sprinkler system. Check FM Global
requirements for pyrophoric gases.
3. Include Gas Monitors /Interlocks / Alarms: Cylinder cabinets, fume hoods or other
locally ventilated enclosures are required to be equipped with a continuous gas
monitoring system with gas and ventilation alarm when used to store gases with NFPA
health hazard rating =4 or =3, or when used to store gases that do not possess adequate
warning properties or flammability rating =4. The alarm should warn of the presence of
gases at or below the ACGIH TLV.. See Gas or Vapor Monitoring section.
Consideration should be given to providing monitoring, alarms and automatic shut off of
gas flow upon other events besides gas detection, such as loss of power, high process
pressure, loss of vacuum or loss of cooling.
4. Gas Cabinets shall be ventilated according to manufacturers recommendations. The
cabinet window should be labeled “Hazardous – Keep Fire Away”.
5. Review need for scrubbing / treating of process and purge effluent from highly toxic
gases prior to exhausting to the outside or capture catastrophic release of cylinder
contents with the MIT EHS office.
Consult the MIT EHS Office Industrial Hygiene and Safety Programs if further assistance is
needed.
Electrical
Include the following electrical features to control compressed gases within the laboratory:
1. Consider including an ‘Emergency Gas Shut-Off’ button to terminate the gas flow and
shut off any research equipment. Consider locating the electrical gas shut-off button
adjacent to the laboratory exit.
2. Provide emergency backup power for hazardous gas cabinet enclosure exhaust fans,
alarms, and other system components.
3. Confirm that electrical fixtures in flammable and pyrophoric gas storage rooms conform
to NEC Class I division 2 requirements
4. Cylinders and piping containing flammable or pyrophoric gases should be grounded if
the buildup of static electricity could present an ignition hazard.
1. Before use, systems should be evacuated, vacuum tested, and pressure checked with
inert gas at pressures two to three times anticipated working pressures. Systems using
hydrogen should be leak tested with helium, other systems can be tested with nitrogen.
2. Testing certifications should be performed by a qualified vendor.
1. When designing a lab space, it is important to factor in the needs of the lab with respect
to storage of chemicals. Their needs will depend, in part, on the extent of their chemical
use
2. Labs are required to maintain a chemical inventory. The lab’s chemical inventory is used
to make sure the labs are within exempt quantities for the lab’s building code
classification and floor location
3. The chemical inventory can also be used to get an initial idea of what the lab’s chemical
storage needs might be
5. In addition, the materials of construction for chemical storage areas should be compatible
with materials to be stored, corrosion resistant, when needed, moisture proof, when
needed, and easy to keep clean
Control Areas:
1. Control areas are spaces within a building, which are enclosed and bounded by exterior
walls, fire walls, fire separation assemblies and roofs, or a combination thereof, where
quantities of hazardous materials not exceeding exempt amounts are stored, dispensed,
used or handled.
2. Where exempt amounts are not exceeded, control areas shall be used to store flammable
and combustible liquids inside buildings. The design, construction, location and number
of control areas shall meet the requirements of the Massachusetts State Building Code
780 CMR, and shall not exceed allowable amounts of hazardous materials per control
area (as specified in 780 CMR). Maximum quantities may be increased under the
following conditions:
a. When storage is in a building equipped throughout with automatic sprinklers in
accordance with 780 CMR.
b. If flammable materials are stored in approved cabinets, gas cabinets, fume hoods
or ventilated cabinets.
3. The City of Cambridge requires that flammable liquid storage and Class I flammable
liquids are not permitted below the first floor.
4. The number of permitted control areas per floor, the percent of allowable exempt
quantities per control area, and the degree of vertical fire separation shall meet the
requirements of 780 CMR.
5. Fire separation assemblies shall be in accordance with 780 CMR. Control areas are not
permitted more than two levels below grade.
Specific considerations:
1. Flammable Materials: should be stored in flammable storage cabinets. Many labs are
designed with space under the fume hoods for storage of flammables. A lab with a large
quantity of flammable materials may need additional cabinets for flammable storage, and
the lab space will need to be designed to accommodate these cabinets. In some cases, it
may be necessary to vent the cabinets. NFPA 30 provides guidance on how to correctly
vent
2. Storage of Volatile Toxics and Stench Chemicals: Ventilated storage should be provided
for volatile toxic materials and/or stench agents. One option is vented flammable storage
cabinets, or vented storage under fume hoods. Ventilation should be sufficient to prevent
build-up of odor, but a large amount is not required
3. Storage of Acids: Ventilated, corrosion resistant storage should be provided for acids. In
addition, organic acids need to be stored separately from oxidizing acids. There should
be sufficient ventilated storage space to accommodate the specific needs for acid storage
4. Refrigerated Storage: In some cases labs may need appropriate space designed to
accommodate refrigerated storage of some lab chemicals. There may be a need for
special refrigeration equipment, and space will need to be designed to accommodate it,
and electric utility needs should be factored in (appropriate outlets in good locations for
equipment). Refrigerators and freezers for storing flammable liquids must be designed,
constructed, approved, and labeled for that purpose
5. Shelving: Hazardous liquids need to be stored at eye level or lower. Shelving should be
sufficient to accommodate such storage. Dry chemicals should be stored separately from
liquids. Shelving should be sufficient to address this need as well
6. Under Sink Storage: Many times disinfectants and cleaning products are stored under
sinks. Sink areas should be constructed of materials not likely to be damaged by storage
of such products
7. Hazardous Waste Collection Areas: Ideally, waste collection areas should be ventilated,
and be located in close proximity to lab hoods, where such waste is most likely to be
generated. It is preferable not to have the hazardous waste storage occupying space in the
lab hood. See above for more information
10. Cold Rooms: Cold rooms should not be used for volatile toxic or flammable chemical
use or storage unless they are designed for such use. Careful attention should be given to
current activities in cold rooms when designing for chemical storage
11. Weigh Stations: It may be important to design space for location of dry chemical
weighing areas that can be vented, either by air filtration or to the exhaust system.
2. Location: If desired design criteria amounts of stored flammable and combustible liquids
exceed allowed amounts per control area, an inside liquid storage or cut off rooms (a
room including one or two outside walls) is required. Inside storage rooms would be
considered have to meet all the requirements of H-2 or H-3 occupancy and cannot be
constructed in basements.
3. Design: Inside storage rooms shall be constructed to meet the applicable requirements of
780 CMR and the Massachusetts Comprehensive Fire Safety Code and NFPA 30,
Flammable and Combustible Liquids Code. Inside storage area shall not exceed 500
a. Mechanical ventilation systems shall provide at least one cubic foot per minute of
exhaust per square foot of floor area, but not less than 150 CFM (at least 6 air
changes per hour).
b. The mechanical ventilation system shall be equipped with an airflow switch or
other reliable method which is interlocked to sound an audible alarm upon failure
of the ventilation system and connected to BMS.
c. The proportion of the exhaust ventilation shall be taken from the ceiling and the
floor will depend on the density of the vapors expected from a spill.
d. The location of both the exhaust and inlet air openings shall be arranged to
provide, as far as possible, air movement across all portions of the floor to
prevent the accumulation of flammable vapors.
e. Exhaust from the room shall be vented directly to the exterior of the building
without recirculation.
f. All ducts shall comply with Massachusetts Building Code, 780 CMR.
9. Storage: In every flammable storage room, an aisle of at least 3 feet wide shall be
maintained. Containers over 30 gallons capable of storing Class I or Class II liquids shall
not be stored more than one container high.
a. Flammable liquid storage rooms, where open use, dispensing or pouring will
occur, shall be monitored for Lower Explosive Limit (LEL).
b. The LEL alarm system shall activate on alarm points of 20% and 50% of the
LEL. These set-points may need to be lower for liquids that are also toxic.
c. The monitoring system shall be equipped with an audible and visual alarm
indicator.
d. The alarm signal shall be transmitted to a constantly attended station. The audible
alarm shall exceed background ambient levels by 15db.
e. The visual alarm shall be labeled.
f. The alarm sensors shall be located no higher than 12 inches above the floor.
g. Signage shall be posted outside the room. The signage shall include appropriate
hazard warnings, as well as response instructions (e.g., “Do Not Enter if the
alarm has been activated.”) contact information and emergency phone numbers.
h. When the flammable liquid dispensing involves use of an automatic pumping
system (as opposed to manual), the pump shall shut-down upon LEL alarm
activation (or line leakage detection) to stop the flow of liquid.
i. The local authority having jurisdiction may require additional safeguards.
j. Exception: flammable liquid storage rooms where dispensing or pouring will not
be conducted or when pouring/dispensing is done in fume hood in storage room.
14. Explosion Venting: Where Class IB liquids are in open use or being dispensed in excess
of maximum allowable quantities, explosion venting shall be provided in accordance with
780 CMR.
Flammable storage cabinets must meet NFPA 30, Flammable and Combustible Liquids Code and
. These cabinets are used for storage of flammable and combustible liquids, and must have leak
proof pans at the base of the cabinet to contain spills. These cabinets can be under fume hood
cabinets or free standing. Cabinets must be labeled “Flammable - Keep Fire Away”.
Flammable storage cabinets are not required to be vented for fire protection purposes. Venting a
cabinet could compromise the ability of the cabinet to adequately protect its contents from
involvement in a fire because cabinets are not generally tested with any venting. Therefore,
However, it is recognized that venting can be needed for other reasons, such as health and safety.
Storage of highly toxic or highly noxious/odiferous flammable materials should be in a vented
flammable storage cabinet. If a storage cabinet is vented for any reason, the cabinet should be
vented directly to outdoors in such a manner that will not compromise the specified performance
of the cabinet and in a manner that is acceptable to the Fire Department. In such cases, the
venting system should be installed so as to not affect substantially the desired performance of the
cabinet during a fire. Means of accomplishing this can include thermally actuated dampers on the
vent openings or sufficiently insulating the vent piping system to prevent the internal temperature
of the cabinet from rising. Any make-up air to the cabinet should also be arranged in a similar
manner.
If vented, the cabinet should be vented from the bottom with make-up air supplied to the top.
Also, mechanical exhaust ventilation is preferred and must comply with the Massachusetts
Building Code, 780 CMR. Manifolding the vents of multiple storage cabinets should be avoided.
References:
Flammable Liquid Approved Refrigerators: Any refrigerators to be used for storing flammable
materials must be designed for such storage, with no internal electrical components.
Cold Rooms: Flammable, toxic, and combustible liquids that are volatile cannot be stored or used
in cold rooms.
Grounding System: For dispensing of flammable and combustible liquids of more than one gallon
from metal containers, grounding bars, cables and clamps shall be provided.
1. Acid storage cabinets have corrosion resistant liners (powder-coated cabinets and
cabinets with corrosion resistant liners) or are constructed from acid resistant materials
like polypropylene. Under fume hood cabinets are vented into the hood using acid
resistant pipes which lead to the interior of the hood. This is typically behind the baffle
terminating in a location where good air volume will be drawn into the cabinet.
2. Acid storage cabinets can also be used to store non-flammable materials that are toxic or
odiferous. These cabinets can be under fume hood cabinets or free standing, exhausted
cabinets. See section Chemical Storage for more information.
3. MIT EHS does not recommend cabinets with metal standards, clips, etc. because the
metal will corrode. Molded plastic standards are an acceptable option for this
Three types of hazardous wastes may be generated in research buildings: radiological, biological
and/or chemical. All are regulated by the Federal Environmental Protection Agency (EPA), the
Massachusetts Department of Public Health (DPH) or Department of Environmental Protection
(DEP). The requirements for handling these wastes are described below:
3. Chemicals
Plan & Elevation: TYP. Single Fume Hood Chemical Waste Collection
3.4 Accessibility
Emergency eyewash and shower equipment that meets the ADA requirements should be installed
when new buildings are constructed or when the building is renovated. Designers of new labs
should refer to the Massachusetts Access Architectural Board (MAAB) guidelines for approach
and reach. 521 CMR 6 and 521 CMR 12.00 Educational Facilities
Any laboratory serving the undergraduate student population shall be provided with at least one
(1) ADA accessible fume hood and sink.
The following areas should be reviewed with the project design team and occupants of the lab
space to determine opportunities for sustainable design in an effort to increase long term cost
savings and efficiencies once the space is occupied:
1. Energy:
a. Efforts should be made to reduce the number of fume hoods and bio safety
cabinets where possible.
b. Fume hoods with lower face velocity and sash restriction are preferred by the
EHS Office, refer to Section 3.2, Laboratory Chemical Hoods, of the EHS
Design Guidelines for specific requirements.
c. In situations where variable volume fume hoods may be considered for
hibernation (shutting them off for periods of time), the correct corresponding
HVAC valves and controls must be installed.
2. Water:
a. Consider the use of foot pedals at sinks to ensure water is not left running when
the user walks away from the sink. Also consider the installation of low-flow
aerators on faucets to control water flow and reduce water consumption.
b. Energy efficient autoclaves and water mizers for autoclaves should be reviewed
for use within a lab to reduce the amount of water consumed by this type of
equipment. A water mizer is a device used on sterilizers or autoclaves to monitor
the temperature of the system and apply cold water only when needed. Using this
type of device can save 40-50 gallons of water per hour. Consolidated Sterilizer
Systems offers a WaterEco Series sterilizing system or autoclave that can save
over 1000 gallons of water per day.
c. EHS prohibits the once-through or single-pass cooling technique. Refer to MIT
3. Equipment:
a. Reduce the depth of chemical storage and shelving units in order to increase the
visibility of the lab’s chemical inventory. This will enable better chemical
inventory management practices, which save the lab time and money.
b. During design, discuss the option of a shared chemical stockroom that can be
safely accessed by lab and departmental members.
5. Waste Management:
Integrated pest management for lab design is complex. In spaces where biological or animal
work will take place attention to pest management must be a priority. Before starting work a pest
inspection of the space should be conducted, by the pest management vendor and design team, to
control or eliminate any pest and to seal any pest access points in to the space.
After the work is concluded a follow up a pest inspection of the space should be conducted, by
the pest management vendor and design team to ensure all pest access points have been blocked
with suitable materials.
4.1 Controls
Temperature Control
As sustainable energy targets become more and more stringent, designers are looking for alternate
methods to reduce energy use. Building on the individual user defined temperature control that is
becoming standard practice in today’s science buildings, a re-evaluation of acceptable
temperature variances and ranges are under discussion. From an EHS point of view, the science
my demand a tighter tolerance in laboratory spaces than in more office, conference, and
collaborative spaces. These low risk spaces may become opportunities for wider temperature
variations, or possibly natural ventilation under specific conditions.
Air Changes
All air change rates are to be determined by the use and hazard level, in association with MIT
EHS. Laboratory ventilation systems designs are to ensure that chemical fumes, vapors, or gases
originating from the laboratory are not recirculated. The design should ensure that air pressures
in the laboratory work areas are negative with respect to corridors and non-laboratory areas of the
laboratory spaces except for positive pressure cleanrooms, when doors are opened, fume hood
sash positions are changed, and other short-term temporary activities that would affect static
pressures. (The other exception is in a designated electrically classified hazardous area with a
positive air pressure system as described in NFPA 496: Standard for Purged and Pressurized
Enclosures for Electrical Equipment.) NFPA 45: Standard on Fire Protection for Laboratories
does not specify an ACH rate, but rather provides the general statement that "laboratory
Special local exhaust ventilation systems, such as snorkels, are to have sufficient capture
velocities to entrain the chemical being released. It is important to not underestimate what is
required to provide proper capture velocities. These calculations are in the ACGIH Industrial
Ventilation guide and can range from 75 to 2000 fpm, depending on the configuration and
process.
a. MIT EHS and Department of Facilities agreed back in the late 1980’s on a minimum
of 6 air changes per hour for laboratories with chemical, biological, or radiological
hazards.
b. EHS can require a higher air change rate if they believe the hazard level requires it.
c. EHS’s approach, generally, however is to first try to eliminate or reduce the hazard,
and then capture airborne hazards with local exhaust controls (chemical hoods,
biosafety cabinets, enclosures, capture hood) and not rely on general exhaust
ventilation rates to control hazards.
d. Designers should work with researchers and EHS to determine local exhaust
requirements, then determine if energy conservation measures like variable air
volume hoods are feasible and appropriate, and then finally calculate air change rates
provided by the lab ventilation system.
e. In most labs, MIT has not made a distinction between air change rates for occupied
and unoccupied labs The Koch Institute uses occupancy sensors to reduce air change
rates to 4 ACH when the lab is unoccupied. It is best to handle heat load with a
recirculating system like a fan coil or chilled beam rather than single pass air. The
unit only recirculates within the local lab environment.
f. If air change rates for the lab are high (greater than 15 ACH), special air supply
distribution systems may be necessary to ensure hood containment is not adversely
effected by cross drafts.
g. Designers should ensure that densely populated fume hoods, as in various forms of
chemistry, do not experience air starvation and loss of containment in the event of a
power failure. This fume hood make-up air starvation can be exacerbated if the
supply air handlers supplying these fume hood dense spaces are not on standby
power. Two typical methods of addressing this make up air starvation are:
1. Place the part of the system supplying these hood dense spaces on standby
2. Calculation Guideline:
a. In general, the 6 air changes per hour ventilation rate does not apply to areas where
chemical, biological, or radiological hazards do not exist.
b. Sometimes these facilities are still considered a laboratory but ventilation rates
should be based on 20 cfm of outside air per person (based on number of people
routinely in the space) unless other considerations in the space (heat load or other
equipment requirements) dictate a higher rate.
a. When designing ventilation systems for machine shops, studios, and other types of
non-lab areas with hazards, consult EHS on the HVAC system approach rather than
relying on a standard ACH approach. EHS will need to work with users of the space
to determine if local exhaust is required and if air cleaning is necessary. If general
exhaust only is provided for these areas, EHS may need to articulate the restrictions
on work or required work practices that exist for the area.
In an overall building design it is appropriate to keep the building at a slightly positive pressure.
This eliminates unwanted infiltration.
However specific laboratories may requires pressure control requirements with respect to other
spaces (e.g. corridors). For example it may be positive pressure for clean rooms, or negative
pressure for most laboratories, HVAC systems must be designed to satisfy space pressure needs
under all conditions of operation.
In general a 10% difference between supply and exhaust air is recommended to maintain a lab
under negative pressure. In special cases there may be more stringent requirements requiring
pressure control strategies.
There are following pressure control strategies that can be used. A/E team should review specific
application with MIT EHS department.
Detailed description is provided in chapter 29 of Guidelines for Laboratory Design, John Wiley &
Sons (DiBerardinis et. al. 2010)
Air Flow/Diffusion
Airflow distribution within laboratories need to consider several factors that can directly impact
the safety and comfort of the occupants. While energy efficiency is a prime factor in the design
of the ventilation systems within the laboratory, the following are examples of additional
considerations vital to the successful design of a laboratory environment.
1. Fume Hood placement within the laboratory. Please refer to the “Fume Hood” section in
section 7.1 of this document.
2. The location of supply air diffusers should also be taken into consideration.
Directional airflow must be sustained by drawing air into the laboratory from “clean” areas
toward ‘potentially contaminated areas’. The laboratory shall be designed such that under failure
conditions the airflow will not be reversed.
If certain EHS parameters are met regarding signage identifying the current state of the laboratory
ventilation systems, motion detectors can be utilized to activate full active laboratory ventilation
by zone during off hour “turn-down” periods. This methodology can counteract the tendency to
run all laboratories 24hrs/ day 7 days a week in order to allow for the work flexibility of the users.
In order to enhance the sustainable goals of the institution, using smart technology to allow for
MIT Design Standards | Lab Design Thematic Folder Page 56 of 87
reduced ventilation rates during periods when the laboratory is unoccupied, can realize significant
energy savings. If this strategy is pursued, clearly identifiable signage displaying the ventilation
status of the lab is required to allow for off hour laboratory users to confirm that the system has
detected them and has increased the ventilation rate to full occupied levels before beginning work
in the laboratory.
Other than CO2 monitoring in classrooms and conference spaces, NO other “facility system air
monitoring” (contaminant sensing) system is to have demand control over the HVAC system in a
laboratory environment.
Specialty local exhaust ventilation is exhaust ventilation that is designed for a specialized
laboratory process. There are many types of SLEV that may be needed in laboratories
depending upon the nature of the chemicals, and processes in use in the lab. Because of this
large variety, it is imperative that the EHS Office be consulted during design review to
specify air flow, face velocity at openings, and physical design. It is important that the final
design be adequate to control contaminants but not waste energy by incorporating excessive
or unnecessary air flow.
MIT currently has 2000 separate pieces of local exhaust ventilation serving laboratory
equipment (in addition to fume hoods). The EHS Office measures the performance of the
ventilation annually for high priority SLEVs and every 3 years for regular priority SLEVs.
1. Chemical storage cabinets for flammables and for corrosives are discussed in above in
Flammable Storage Cabinets and Chemical Storage Cabinets
2. Snorkel exhaust with small diameter plastic canopies can be used for work will small
amounts of low toxicity solvents and adhesives on the open lab bench
3. Plain open ducts are can be used to exhaust a variety of lab processes such as vacuum
pumps, pressurized glove boxes using nitrogen or argon, and exhaust from laboratory
analytical instrumentation. For vacuum pumps, a typical design airflow is 50 cfm (a
minimum of 25 cfm above the maximum pump down airflow of the pump). Vacuum
pumps containing oil should have an oil filter in place (available from the manufacturer)
to prevent oil mist from being drawn into the exhaust system. It is recommended that the
4. Small canopies in the lab can be used to exhaust heat from glassware dryers, solvent
vapor from gas chromatography autosamplers, and heat and gas emissions from atomic
absorption furnaces. The size of the canopy will depend on the dimensions of the
equipment and should be designed according to the guidelines of the ACGIH Industrial
Ventilation Manual (see References below). Large canopies require a large amount of
exhaust to be effective and often an enclosure is a more efficient capture method and
requires lower airflow cfm. Stacked ovens should have bottom shelf to keep lower oven
off the floor and shelves should be perforated to allow heat to rise to capture hood above
5. Gas cabinets are required for toxic gasses with an NFPA Health Rating of 3 or 4. In
general, the flow rate provided to the cabinet should be specified by the manufacturer. A
typical flow rate for a two cylinder cabinet is about 275 cfm. At minimum the
Semiconductor Industry and NFPA require 200 feet per minute face velocity at the open
access port.
7. Other specialty equipment enclosures may be designed in house through the Central
Machine Shop or local vendors. EHS will evaluate designs with respect to containment,
airflow, materials of construction, physical dimensions, and location of access ports. For
enclosures for processes using highly toxic materials, some guidelines include an airflow
of ten air changes per minute with 100 fpm face velocity at any opening. Openings for
air to enter the enclosure (of roughly the same area as the exhaust duct) must be provided
so that there is continuous air flow through the enclosure to allow purging of any
contaminants
8. Slot exhausts are used in animal areas for the administration of anesthesia and other
procedures. A convenient size is 3 feet in width containing 3 slots having slot velocities
of 750 to 1000 fpm. Total airflow is typically 300 cfm. Exact physical dimensions can
be obtained from the units in DCM in the Koch Building. Plastic sides must be installed
on each slot unit. Sometimes a top is installed also depending upon the procedures being
performed
9. Machine shop and welding area local exhaust ventilation should be designed using the
templates provided in the ACGIH Industrial Ventilation Manual
In situations that require the exhausting of contaminants from pieces of equipment with variable
flow rates (ex. vacuum pumps), the following detail may be applicable:
1. Note: the following detail is conceptual, and any application must be designed and vetted
by the project’s HVAC engineer, and MIT’s EHS/ Facilities departments for the specific
location in question.
4.4 Lighting
Lighting Amount
If the design team chooses to light the aisles in lieu of the bench edge in the interests of lighting
efficiency, the design team is to ensure that 70fc can be achieved at the benchtop (typical 36”
a.f.f.) without shadows being cast by the user of the benchtop. The use of task lighting and
alternate reagent rack designs are acceptable alternate solutions to eliminating shadows.
Lighting Control
Controlling the light quality, intensity, color, and schedule are all potential variables when
designing lighting in laboratories. While sustainable features can be somewhat automated to
1. Basic Bio-Laboratory Bench lighting controls can utilize daylight harvesting techniques
in order to save energy and reduce glare at the work surface while maintaining at least
70-75 FC.
2. Electrophysiology: A locally controlled, non-ballasted (ex. LED), dimmable fixture at the
rig site within the light darkened zone with multi-zoned switchable general lighting. (the
ballast interferes with the RF shielding)
3. Imaging: The same as Electrophysiology except without the RF frequency restrictions on
the dimmable fixture.
4. Vivarium holding room: a programmable multi-bulb fixture that can be switched
between standard white light and “rose chocolate” red light. The white lighting should be
capable of offering 2 levels of light, 30-35 FC at 3’-0” and 70-75 FC at 3’-0”
Electrical failure:
MIT enjoys a very reliable electrical system. Loss of normal power is not frequent. However,
there may well be situations where back up or emergency power is needed. This is generally only
warranted in the case of unusually high hazards. In some cases, it may be impractical to provide
emergency power to run fans at their normal capacity and a reduced capacity may be considered.
The most common source of backup power at MIT are diesel generators. The following items
should be considered:
1. Support systems to generator like fuel pump must also be connected to emergency or
back up power.
3. The amount of fuel storage should be carefully evaluated to ensure it meets the required
backup time.
1. When possible running laboratory exhaust systems at reduced capacity is preferred. Areas
of greatest risk will need to be prioritized to ensure lab personnel safety during the power
enforced suspension of building operations. Within laboratories, priority should be given
to maintaining containment at the fume hoods. Additional priority should also be placed
on the maintenance of containment within hazardous gas, solvent, and chemical storage
1. To decrease energy use in laboratories on the MIT campus, EHS recommends high
performance fume hoods be considered for installation in new and renovated laboratories.
2. The general design and construction of laboratory chemical hoods should conform to
applicable guidelines (see current editions of the ACGIH Industrial Ventilation: A
Manual of Recommended Practices, ANSI Z9.5 Laboratory Ventilation standard and
SEFA Recommended Practices for Laboratory Fume Hoods).
3. High performance hoods have design features such as improved aerodynamic airfoils and
greater depth that optimize contaminant capture efficiency at lower face velocities than
the traditional fume hoods models from the same manufacturers and therefore require less
airflow.
4. For most applications, high performance hoods are preferred. In limited instances, a
higher hood exhaust volume could be required for dilution and this may limit energy
savings, but using a high performance hood will allow for future flexibility. Note that for
some applications, e.g., acid digestions, operating a fume hood at a reduced face velocity
may not be appropriate.
5. Approved Manufacturers/Models (As of December 2015). The following high
performance hoods are recommended by EHS. The use of any other hood must be
approved by EHS:
1. The construction of floor-mounted fume hoods should be in accordance with ANSI Z9.5-
latest version.
2. Floor-mounted type fume hoods are generally not recommended as they consume
significantly more energy than a standard bench-mounted hood. These hoods are
designed for use when a standard hood is inadequate to contain larger equipment. They
are generally intended to be used with the lower doors in place during normal operations
since opening the lower door can result in a loss of containment.
3. Modifications to the hood maybe necessary if the lower doors are required to opened
during the normal course of work.
4. The face velocity of the hood should be 100 fpm with the lower doors in place and the
upper doors at 18 inches.
5. EHS should be contacted to evaluate all designs involving the installation of floor-
mounted hoods.
1. Laminar flow exhausted hoods are designed to provide protection to the researcher and
also provide a clean environment within the hood for the research material.
2. Like walk-in hoods, laminar flow hoods consume significantly more energy than standard
fume hood and should be installed only when absolutely necessary. Air enters through the
sash opening and is immediately drawn through a grill in the front before it comes into
contact with the research sample. At the same time, room air is drawn through a HEPA
filter at the top of the hood which blows down over the research sample. The proportion
of room air entering the sash and room air entering through the HEPA filter is critical and
should be set by the manufacturer.
3. EHS should be contacted to evaluate all designs involving the installation of laminar flow
hoods.
1. The use of heated perchloric acid requires a special hood designed specifically for it. The
hood should be on its own separate fan and not manifolded or joined to other non-
perchloric acid exhaust systems.
2. The hood should be designed with a wash-down system for the hood and associated duct
work. Fans should be induction type so that no moving parts are exposed to perchloric
acid vapors. The hood surfaces and ductwork must be constructed of materials that will
not react with perchloric acid.
3. There are additional requirements for perchloric acid hood installations. See the current
edition of Industrial Ventilation: A Manual of Recommended Practice for Design and
MIT Design Standards | Lab Design Thematic Folder Page 62 of 87
ANSI/AIHA Z9.5 Laboratory Ventilation for more information.
4. Perchloric acid hoods should meet the same containment performance as the MIT
standard chemical fume hoods. In addition, they should be constructed of stainless steel
and have welded seams throughout. No taped seams, joints, putties, or sealers can be
used in the fabrication of the entire hood duct system. The perchloric acid hood also
requires an internal water-wash system to eliminate the buildup of perchlorates. The
water wash system should consist of a water spray head located in the rear discharge
plenum of the hood, plus as many more heads as are required to ensure a complete wash
down of all internal surfaces of the ductwork. This includes the run from the work
surface fan to the discharge stack on the roof. To facilitate satisfactory water drainage of
the ducts internal surfaces the route from the fume hood to the exhaust fan should be
vertical, with no horizontal runs.
5. Perchloric acid hoods often represent a significant financial investment and there may be
additional options for using this material. EHS should be contacted to evaluate all designs
that involve its use.
1. Depending on the quantity and process , the use of some concentrated mineral acids can
cause corrosion and deterioration of hood surfaces, ductwork, control valves, and fans
(this is particularly notable in the case of aqua-regia and especially boiling aqua-regia).
2. In some cases, the use of hoods with Teflon coated metal parts and acid resistant
ductwork may be appropriate.
3. In more extreme cases hoods designed with built in scrubbers may be appropriate. These
hoods generally use a water mist to dissolve the acid vapor. The mist is then collected
and either neutralized at the hood or using the building neutralization system.
4. It should also be noted that hydrofluoric acid (HF) can damage glass hood sashes. Some
manufacturers offer sash material that is resistant to HF.
5. EHS should be contacted to evaluate all fume hood designs that involve the use of acids.
1. Design sash height at 18 inch unless researcher and EHS agree on another height.
2. Sash stop required if operating height less than full open.
3. Tissue screen for bottom slot is required.
4. All fume hoods are required to have audible and visual alarms that are capable of
indicating when the fume hood flow rate drops below 20% of the design criteria. In
Variable Air Volume hoods the manufacturer of the VAV valve should supply a
corresponding controller with a digital readout of face velocity and alarm. For Constant
Air Volume Hoods an airflow monitor with digital readout of face velocity such as the
TEL AFA 1000 or MIT approved equivalent is required.
5. Exhaust and supply control devices need to be of laboratory grade for appropriate
response times for laboratory hoods or SLEV.
6. No cup sinks unless allowed by EHS.
1. The MIT face velocity criteria for the traditional fume hoods still in use on most of the
MIT campus remains an average of 100 feet per minute (fpm) with an acceptable range
of 90 to 110 fpm.
2. For high performance fume hoods EHS recommends an average design face velocity of
80 fpm at the maximum design opening. A tighter tolerance for average face velocity is
required for high performance hoods.
3. The measured average face velocity of high performance hoods shall not be less than 75
fpm. An exception to these criteria is the Mott RFV-2 hood which can be operated at 70
fpm at the maximum design opening. The measured average face velocity for this hood
shall not be less than 65 fpm.
1. Variable Air Volume (VAV) systems should be considered for all laboratories, including
those with high performance hoods, where their use could result in reduced energy
consumption.
2. Other energy conservation measures related to fume hoods such as proximity sensors and
automatic sash closure devices require approval by EHS.
The location of fume hoods within laboratories is critical to hood performance and safety of the
occupants. In general, the far end of the lab away from supply air diffusers and low traffic areas
are best. Specifically:
1. Hoods should be located away from laboratory exits so the occupants do not have to pass
in front of the hood to evacuate the lab.
2. The location of supply air diffusers should also be taken into consideration. Diffusers that
emit supply air with a significant directional component and velocity in front of the hood
can have a serious effect on hood performance. Ideally laboratory diffusers should be
large with a significant number of perforations to allow for the gentle introduction of air
into the lab. The recommendations outlined in ANSI/AIHA Z9.5 Laboratory Ventilation
should be followed; specifically, 5.3.2 Supply Air Distribution.
MIT Design Standards | Lab Design Thematic Folder Page 64 of 87
3. Partially enclosed alcove locations should be avoided as they may affect hood
performance.
Due to the possibility that disturbances in the air adjacent to a fume hood can lead to a loss of
containment, the following fume hood placement guidelines are recommended. The dimensions
listed in items 1-10 do correspond (where dimensioned) to the NIH DRM Appendix I guidelines.
2. Maintain a distance of 120” between opposing fume hood open faces (180°).
3. Maintain 80” clear from the face of the fume hood to opposing wall surfaces.
5. Maintain 40” clear from the side of a fume hood and a perpendicular (90°) bench top to
avoid placing Fume Hoods inside adjacent lab bench work areas, in which the work zone
of the fume hood and lab bench overlap.
7. Maintain 48” clear to the inside corner when fume hoods are placed on adjacent
perpendicular walls (90°).
10. Supply air distribution systems shall be designed to minimize turbulence and avoid
impacts to the containment and performance of Fume Hoods, with exhaust grilles and
registers located away from supply air diffusers in a manner that creates a uniform, low
velocity airflow across the room. The distance from a fume hood to a diffuser depends
on the type of diffuser, throw pattern and terminal velocities that result over the range of
temperature and supply volume. Unless otherwise justified through further investigation
(CFD or mockup), the minimum distance between a diffuser and the plane of the sash
shall be 5 feet.
The spatial relationship of a supply diffuser to the fume hood is critical to optimizing it's
performance with zone 1 being the best and zone 3 being adequate, Lab designers should
use caution when locating diffusers in Zone 3 in front of a hood opening, as air directed
MIT Design Standards | Lab Design Thematic Folder Page 70 of 87
perpendicular to the plane of the sash can be more detrimental to hood performance than
cross drafts of similar velocity directed parallel to the opening. If diffusers must be
located within this nominal 5'-0"/ 60" 'No Diffuser Zone' or NDZ, CFD may be necessary
to evaluate potential problems and modified ASHRAE 110 compliance. In addition, the
terminal velocity of the supply air should not exceed " of face velocity of the fume hood.
6. BIOSAFETY CABINETS
Biological Safety Cabinets (BSCs) can be exhausted into the lab with the exception of BSL-2+
spaces. In very limited circumstances, an assessment of the materials or conditions of use may
lead to a need to have a canopy or loose connection to the lab exhaust system. Please contact the
EHS Biosafety Program for more details
There are three classes of BSC. NSF International Standard 49 details the regulatory
requirements for testing and certifying a Class II BSC, the most common type of BSC currently
in use. There are different types of Class II BSC, including A1, A2, B1 and B2.
The majority of BSC units on campus are Class II Type A1/A2 which produces a clean working
environment for product protection as well as personnel and environmental protection via laminar
air flow. Air is drawn into the cabinet, circulates via internal blower through a HEPA filter which
pushes clean air down onto the working surface. 70 percent of the air is exhausted and 30 percent
is re-circulated into the BSC. This produces a protective air curtain which provides containment
with in the cabinet.
Location of BSC is important due to the fact that the air curtain created by the laminar flow is
easily disturbed, which can compromise containment of the materials, as well as introduce
environmental contaminants into the working area. Please refer to Section 5.9 for BSC
placement criteria.
Class II Type B1 cabinets must be hard ducted, and Class II Type B2 cabinets are total exhaust.
MIT BSP does not recommend installation of Type B1 or B2 cabinets unless absolutely required.
Class I BSC is a directional air flow unit that offers environmental and personnel protection only.
There is no product protection in this model as it functions similar to a chemical fume hood.
Since this cabinet does not offer protection of material from contamination their use in research
has declined.
The MIT CAB/ESCRO Policy recommends investigators do NOT use Bunsen burners, including
the “touch type”, or other heat sources while working in a BSC. Any point-source of heat may
disrupt the protective laminar air flow pattern of a BSC. Therefore gas lines shall not be plumbed
to BSCs.
Class II Type A2 Biosafety Cabinet (BSC) installations after must comply with requirements for
design, construction, and performance contained in NSF/ANSI 49- latest version.
BSCs purchased for MIT laboratories should be NSF/ANSI 49 certified by the manufacturer.
BSCs are often reused after renovations of existing biological research laboratories. As part of
the renovation, BSCs must be brought into compliance with NSF/ANSI 49.
For older model BSCs that cannot accept a canopy connection, and the research involves the use
of volatile reagents in the cabinet, cabinet replacement should be considered. Alternatively, with
MIT EHS approval, cabinets may be unducted and used as free standing cabinets.
All cabinets must be NSF/ANSI 49 field recertified prior to and after relocation since during a
move it is possible to damage the cabinet and or shift the seating of the cabinet HEPA filters.
Recertification ensures the proper functioning of the cabinet in the new location.
Please note content also included in Section 2.6 EHS Thematic Folder
Introduction
Emergency eyewashes and showers are to be installed in all laboratories and other types of non-
lab work areas, which have hazards that include but are not limited to those listed below. If the
current hazards do not trigger the need for this equipment, piping shall be installed during the
current renovation (left capped at either end to avoid “dead legs” and labeled for future use).
This is to facilitate installation of eyewashes and/or showers when hazards change (often before
the renovation is completed or soon after) or during a future space change. The goal is to reduce
the cost of, time involved, and impact of the installation on the users.
Equipment Specification
1. The lever that is pushed, pulled or squeezed to activate the eyewash/ shower should be
designed to remain on without requiring the use of the operator’s hands. It should be
easy to operate in an emergency.
2. The water or fluid should flow until intentionally shut off or until the specified amount
has been discharged.
Eyewash
1. Fluid should be provided to both eyes simultaneously via two nozzles or other means.
2. Nozzle protection should automatically come off when the water/ fluid starts to flow.
3. Eyewashes must be located where they can be effectively used hands free by all
researchers, once the unit is engaged. Provide accessible clearances and heights for users
with disabilities.
4. There are access limitations with some sink-mounted eyewashes for individuals who
might need them at a lower height due to disability or short stature. Lower eyewash
stations may be required in areas where needs have been identified.
5. MIT researchers prefer eyewashes that are activated by pulling one vertical arm
downward. These have a much smaller footprint compared to the swing activated
(horizontal) type, which spray water on the bench during testing.
6. The endpoint of the eyewash arm shall be 14 inches or less from the leading edge of the
lab bench. Users of all heights must be able to lean over the sink to reach the water
stream. Install longer arm eyewashes if necessary. If the PI agrees, units may be panel
mounted (at a 45-degree angle outward).
7. Eyewash units should be installed at sinks for proper draining to allow for required
weekly testing of the units. If there isn’t a sink in the room and a sink can’t be installed,
then appropriate provisions must be made in the plumbing design to allow for capture and
drainage of one minute’s flow of water from the unit to allow for the required testing.
(cup sinks are not adequate due to insufficient flow capacity)
8. Eyewashes should not be installed in the wall unless the unit is connected to the lab waste
system and the wall is protected from water damage/ mold growth.
9. Do not install new drench-hose type eyewashes in new labs or during renovations or
repairs as primary, fixed-eyewash stations. Hose-types can only be installed as
supplementary equipment and cannot serve as approved eyewashes, per the State
Plumbing Board and for accessibility limitations. If the lab only has room for one
eyewash, then only install the approved type of eyewash.
10. Where the tempered water supply exceeds 45 psig, provide pressure reducing valve(s) to
control delivery pressure to 45 psig static and not less than 30 psig during unit activation.
11. Faucet-mounted eyewashes are prohibited.
DOF has a new requirement to connect a water flow sensor to the BMS. (VERIFY w/ DOF)
The end of the long handle should hang as close to the wall and as far away from the path of
travel as possible. This is to prevent inadvertent activation and to prevent head injuries.
Acceptable Options: A handle that is wall mounted. A handle that can be adjusted in length
based on the needs of the current lab users. A long chain with eye hooks so the chain hangs along
the wall. A handle that is behind the smaller panel of a double leaf door.
Some of the specifications for the water or fluid supply are described below.
Select location that is adjacent to the hazard but there must be enough room so that the victim and
emergency responders will be safe. (For example, installing an eyewash/ shower “immediately
adjacent” to an exhaust hood is not recommended.) The emergency shower and eyewash unit
must be located on the same level of the hazard and the path of travel must be free of obstructions
that would inhibit the immediate use of the equipment. Doors to the eyewash or shower must
MIT Design Standards | Lab Design Thematic Folder Page 75 of 87
swing in that direction. For strong acid and strong caustic hazards the eyewash unit should be
immediately adjacent to the hazard.
The ANSI standard for Emergency Eyewash and Shower Equipment specifies the distance of the
unit from the standing surface and the wall (or the nearest obstruction). This is to ensure that the
unit will be reachable by any user and that the user will not be injured.
Emergency showers should be located within the laboratory as close to the main door as possible.
This minimizes water possibly being sprayed on to electrical equipment that may be in the lab
and it is less likely that items will block access to the shower. Do not wedge shower between the
wall and the door when it is in the open position.
No obstructions, protrusions, or sharp objects shall be located within 16 inches from the center of
the spray pattern of the emergency shower. Electrical apparatus, telephones, thermostats or
power outlets should not be located within 18 inches of either side of the emergency shower or
eyewash.
If the equipment is installed outside the lab, then the lab door must swing out and the doorway
must be recessed so pedestrians will not be hit by the door. Most lab doors swing into the lab to
comply with the Building Code. The emergency shower and eyewash unit must be located on the
same level of the hazard and the path of travel must be free of obstructions* that would inhibit the
immediate use of the equipment. *The Cambridge Plumbing Inspector will not issue a permit to
install an eyewash or a shower if the door that does not swing in the direction of the path of travel
because he considers this to be an obstruction.
ANSI In accessible locations that require no more than 10 seconds to reach (…), on the same
Z358.1-1998 level as hazard (i.e. on the same floor). The path of travel (to the safety equipment) should
7.7.4 and 4.6.1 be free of obstructions (i.e. locked doors, boxes, etc.). It is acceptable to go through an
unlocked door.
For a strong acid or caustic, (it) should be immediately adjacent to the hazard.
527 CMR Should not be located greater than 50’from an experimental area
10.02 (2)
248 CMR
10.13
Emergency wash equipment that meets the ADA requirements should be installed when new
buildings are constructed or when the building is renovated. Designers of new labs should refer to
the Massachusetts Access Architectural Board (MAAB) guidelines for approach and reach.
Typical Solution: One sink is at the regular height and the eyewash is installed there. One
shallow sink is at the lower height required by ADA with nothing underneath it. The sink is
equipped with a tight fitting cover so the lab bench can be used until it is needed. Alternatively,
install the piping in such a way that the lower sink could be installed quickly when the person,
who actually needs it, starts working.
Each emergency shower or Eyewash location “should be identified with a highly visible sign and
the area around the equipment should be well lighted”. (according to ANSI Z358.1). The signs
must have contrasting color of green and white and be at least 70 square inches in area (527 CMR
10.02 (2)). Refer also to the Signage Thematic Folder in the MIT Design Standards.
The wall sign that comes with the equipment shall be visible from most points within the lab or
work area.
The area under the shower shall be clearly identified to ensure that the lab users do not block
access to the shower by using a “keep area clear” slip resistant graphic demarcation on the floor.
This graphic should be permanent and resistant to wear. Refer also to the Signage Thematic
Folder in the MIT Design Standards.
Gas monitoring may be required when highly toxic, toxic, flammable, or pyrophoric
(spontaneously combustible in air) gas use is planned. Under some conditions oxygen monitoring
is required in locations with compressed and liquefied inert gases and LEL (Lower Explosive
Limit) monitoring in locations such as storage areas for flammable gases and chemicals. This
section applies to Lab and Non-Lab areas.
1. Monitor type, alarm set points, automated actions and notifications for monitoring
systems are determined by the project design review team based on MIT EHS and
Facilities specifications, code requirements, building infrastructure and research needs
2. All monitoring systems must report alarm details back to a continuously monitored
station (e.g. the Facilities Operations Center and if available, a department response
team.).
3. A visual and audible alarm must be present inside and outside of the lab with the ability
by emergency responders to silence the alarm. Alarm details in a display panel (alarm
type, level, etc.) must be available inside and immediately outside of the monitored area
4. A remote monitor is required in the Fire Command Room or near the main building Fire
Alarm Panel. Signage should indicate the warning signal intent. The signage shall include
appropriate hazard warnings, as well as response instructions (e.g., “Do Not enter the
laboratory if the alarm has been activated”) contact information and emergency phone
numbers. The researcher is responsible for writing a response procedure that is reviewed
by EHS which they are posted at the lab including alarm levels and contact information
that the DLC, Operations Center and EHS would follow in case of an alarm. The
response protocol would be distributed to Operations Center, EHS and be covered as part
of the lab specific training. The response procedures and any other supporting
documentation will be kept in a secure location such as in the Fire Command Room or
blue locked box mounted outside the lab entry
5. The location of gas sensors will be based on the properties of the gas and potential leak
points. Sensors shall be located within 12 inches of the floor for gases heavier than air
and near the ceiling for gases lighter than air. Ambient air sensors for toxic gas
monitoring will be located near breathing zone height
6. Monitoring equipment make/models should be standardized as much as possible to
facilitate maintenance requirements. Contact Facilities and EHS to ensure that an
acceptable monitor is purchased
7. Emergency power, battery backup (24 hours) must be provided for monitoring systems.
The monitoring system should continue to operate without interruption
Certain gases with very high toxicity and/or pyrophoric properties (e.g., silane, arsine, and
phosphine) require continuous 24 hour air monitoring in the work area and ventilated
equipment/enclosures and possibly duck work. Automatic gas shutdown at the gas source and
MIT Design Standards | Lab Design Thematic Folder Page 78 of 87
tool shutdown in the event of ventilation failure or gas detection may also be required. An
automatic fire detection system must be installed in rooms or areas where highly toxic
compressed gases are stored or used. Flame detection is required for pyrophoric gases.
Toxic gas alarm set points are based on the American Conference of Industrial Hygienist
Threshold Limit Values (ACGIH TLVs). Typically monitors are set to alarm at half of the TLV
and the TLV. For detection inside of ventilated enclosures (e.g., gas cabinet or tool enclosure) the
lab should be evacuated and gas source automatically shut down. For highly toxic and pyrophoric
gas detection at the TLV level or higher in ambient/breathing air, the building is evacuated.
The monitoring system shall be equipped with an audible and visual alarm indicator. The audible
signal shall be at least 15 dB above the ambient sound level. The visual alarm beacons shall be
amber for equipment and gas cabinet/enclosure alarms and blue for ambient alarms. The visual
alarm beacons shall be labeled.
While toxic gas use may not require the same monitoring and controls as very toxic gases, each
planned use of toxic gas requires some level of engineering controls and/or monitoring.
Especially of concern are toxic gases that may not provide adequate warning below the TLV due
to high or no odor thresholds and olfactory fatigue (e.g., carbon monoxide, hydrogen sulfide or
hydrogen chloride).
Highly toxic, toxic and pyrophoric gas monitoring requires that sensing ports be located in the gas
cabinet, tool/equipment enclosure, and lab area.
Compressed gas cylinders containing highly toxic, toxic and pyrophoric gases shall be stored in a
fire suppression system (also, see Section 3.5). The cabinet shall be equipped with an excess flow
control valve and flow restrictor in cylinder and exhaust monitor/interlock for gas flow shutdown
upon exhaust loss. There should be a manual emergency shutoff at the gas cabinet. For high
hazard group H occupancies, the exhaust ventilation system serving gas cabinets, as well as any
tool enclosures, shall be provided with emergency power. The local authority having jurisdiction
may require additional safeguards.
1. Note: SEMI and Massachusetts Building Code define a highly toxic gas as having an LC
50 of 200 ppm or less and a toxic gas as having an LC50 of greater than 200 ppm and less
than or equal to 2000 ppm for a one hour exposure to albino rats between 200 and 300
grams. [SEMI F6-92]. NFPA 704 uses an LC50 of less than or equal to 1000 ppm for its
highest health hazard rating of 4 and an LC50 of 1000 to 3000 ppm for a hazard level of 3
Small returnable cylinders (lecture bottles) containing less than 10 cubic feet of gas by volume
that are kept inside gas cabinets or fume hoods:
Inert Gases
Some research laboratories use compressed and liquefied gases in locations where the potential
for a low oxygen, <19.5% O2, atmosphere exists. These areas are required to have oxygen
sensors. Examples include liquid helium cooled magnets or dilution refrigerators, MRI rooms,
MEG rooms, nitrogen generator rooms, nitrogen filling stations and storage areas for inert gases.
Where there is potential for high level oxygen, the set point would be 23.5%.
EHS with assistance from the project design group will review the proposed research, location
and gas quantities to determine whether oxygen level monitoring may be required. In some cases
provisions for emergency exhaust triggered by an alarm may be required. Positioning of sensors
should be based on gas density at the time of release relative to ambient conditions. Sensors for
MRI and MEG rooms should be designed for these rooms to eliminate interference with the
image quality.
The signage shall include appropriate hazard warnings, as well as response instructions (e.g.,
“Warning! Low Oxygen Alarm”) contact information and emergency phone numbers. Refer to a
template sign for consistency. Response protocols should also be developed and distributed as
outlined above in the toxic gas section.
Flammable Gases
The purpose of the lower explosive limit (LEL) monitoring of gases within a laboratory space or
gas storage room is to give early warning to personnel of a potentially hazardous condition.
When a gas is both toxic and flammable or pyrophoric, the more stringent (sensitive) monitoring
requirement shall be used. Both monitors are not required.
The monitoring system shall be equipped with an audible and visual alarm indicator. The audible
signal shall be at least 15 dB above the ambient sound level. The visual alarm beacons shall be
labeled.
The location of gas sensors shall be determined based on the properties of the gas.
Exceptions:
1. When the cylinder contains less than or equal to 10 cubic feet of non-toxic flammable gas
by volume (lecture bottle)
2. Natural gas plumbed as a “house gas” to labs need not be monitored
3. For experiments using a small cylinder of flammable gas (Airgas size 35, approximately
33 cubic feet of gas)
4. If ventilation in the space is adequate and the release risk is not higher than normal,
continuous monitoring may not be required but is still a best practice
5. If monitoring is used, hand-held or local alarm is acceptable
6. When gas is flowing, the experiment should be continuously attended
7. All other flammable gas controls apply: flashback arrestor, adequate piping/tubing,
restricted flow orifice, excess flow valves
Any non-toxic flammable gas cylinder containing greater than 33 cubic feet of gas must be
contained in a gas cabinet if sprinkler protection is not provided in the lab.
The local authority having jurisdiction may require additional safeguards. Response protocols
should also be developed and distributed as outlined above in the toxic gas section.
The purpose of the lower explosive limit (LEL) monitoring of flammable liquid vapors within a
laboratory space or flammable liquid storage room (FLSR) is to give early warning to personnel
of a potentially hazardous condition. In the case of an FLSR, these areas are normally
unoccupied; thus, it is possible that a leak or spill could result in high concentrations of
flammable vapors that could go undetected.
LEL monitoring may be required in locations designed as flammable liquid storage rooms
(FLSR) where dispensing will occur. Requirements include:
1. The LEL alarm system shall activate on a single alarm point set at 20 %. This set-point
may need to be lower for liquids that are also toxic
2. The monitoring systems shall be equipped with an audible and visual alarm indicator.
The alarm signal shall be transmitted to a constantly attended station. The audible alarm
shall exceed background ambient levels by 15db. The visual alarm shall be labeled
3. The alarm sensors shall be located no higher than 12 inches above the floor
4. Signage shall be posted outside the FLSR. The signage shall include appropriate hazard
warnings, as well as response instructions (e.g. “Do Not Enter if the Alarm has been
Response protocols should also be developed and distributed as outlined above in the toxic gas
section. See Table 1 for suggested sequence of operations.
Carbon monoxide monitoring is required in all residential areas, commercial kitchens, Ice Rink
and garages (to start ventilation fans only). Natural gas monitoring is required in commercial
kitchens. Where there is an assumed high hazard to occupants from the natural gas/carbon
monoxide exposure in other non-lab buildings, a discussion will take place between the designers
and EHS to determine the appropriate monitoring in these areas. Response protocols should also
be developed and distributed as outlined above in the toxic gas section.
General
Per 360 CMR 10.023, the following items are specifically prohibited from discharge to the
MWRA sewer system via the floor drain system:
1. Groundwater, storm water, surface water, roof or surface runoff, tidewater, or subsurface
drainage, except construction site dewatering in a combined sewer area when permitted
by the authority and municipality.
2. Non-contact cooling water, non-contact industrial process water, uncontaminated contact
cooling water, and uncontaminated industrial process water, and cooling tower blow
down.
3. Fuel oil, crude oil, lubricating oil, or any other oil or grease of hydrocarbon or petroleum
origin unless an approved and appropriate gas/oil separator that is in compliance with 360
CMR 10.016 is used.
4. Any liquid, solid, or gas, including, but not limited to, gasoline, kerosene, naphtha,
benzene, toluene, xylene, ethers, alcohols, ketones, aldehydes, peroxides and methyl
ethyl ketone, which by reason of its nature or quantity or by interaction with other
substances, may create a fire or explosion hazard.
5. Any noxious or malodorous liquid, gas, or solid or any other pollutant which either singly
or by interaction with any other Waste causes or contributes to the creation of a public
nuisance, makes it dangerous for personnel or equipment to enter the Sewer for purposes
of maintenance, repair, inspection, sampling, or any other similar activity, or which
results in the presence of toxic gases, vapors, or fumes within the sewer system in a
quantity that may cause acute worker health and safety problems.
6. The Massachusetts Uniform Plumbing Code requires connection of floor drains to grease
traps or oil-water separators in food preparation/service areas, motor vehicle storage
maintenance areas, or other areas where floor drains and other plumbing fixtures
(including floor sinks, automatic dishwashers, pre-rinse sinks
7. Per 248 CMR 10.00, Uniform State Plumbing Code, floor drains located in areas where
motor vehicles are being serviced, or where there is the potential for oil to be spilled must
Research Laboratories
Do not locate floor drains next to laboratory hoods or chemical storage cabinets. Floor drains are
not typically part of new laboratory construction or renovation. The decision to install floor drains
in a particular research area shall be on a case-by-case basis, such as protecting extremely
sensitive and valuable assets on the floors below the area in question due to emergency shower
usage (Examples: Clean Rooms, Electron microscope imaging, Etc.) Floor drains from the
laboratory should be routed exclusively to the building lab waste/ acid neutralization system. The
project team must therefore design their lab waste/ acid neutralization system to account for the
maximum additional flow originating from any emergency showers within the catchment area.
ANSI Z358.1-2009 states a flow rate at 20 gallons of water per minute for 15 minutes, Section
4.1.2, 4.5.5) The project design team will consult MIT EHS Department if such floor drains are
considered. If floor drains are installed for any reasons, they must have provision to prevent off
gassing of sewer gas. Trap primers or seals must be installed.
Example:
http://www.rectorseal.com/index.php/sureseal/
Ensure that the floor drain shall be equipped with an approved sediment and sand control basket,
or the floor drain shall discharge through a sand interceptor. Discharge of multiple floor drains
into one sand interceptor is acceptable.
7.4 Autoclaves
Autoclaves should be located in or near biological research laboratories for both treatment of
biohazardous solid waste and for sterilization of research materials. Autoclaves come in two
basic varieties: gravity displacement and pre-vacuum autoclaves. Both gravity and pre-vacuum
autoclaves are acceptable options for MIT laboratories. Autoclaves typically either have a rotary
style door handle or hydraulic powered vertical door. Hydraulic-powered vertical doors on
autoclaves tend to malfunction more often. BSP recommends the rotary style doors for durability
and reliability.
Local exhaust is required to take care of odors as well as heat and moisture. A canopy hood
should be fitted above the autoclave and exhausted outside in accordance with NFPA 91. Care
should be taken to prevent heat & steam from triggering sprinkler systems. A location for storage
of logbooks as well as additional safety equipment, bins, carts, etc. should be available near the
autoclave. Autoclaves should be located such that researchers can transport materials to and from
the autoclave without passing through high traffic public areas. Special attention should be paid
to providing the users with clear and visible system monitoring and notification.
References
All new laboratory construction is to accommodate a “Safety Station” adjacent to the laboratory
entrance/ exit. The intent of a “safety station” is to consolidate all the life safety equipment in an
easily understood and recognizable location that can be accessed without drama or difficulty
during an emergency situation. The station can include the following items as approved by MIT
EHS:
In addition, these “Safety Station” locations can be great locations to post hazard signage,
laboratory SOPs (Standard Operating Procedure), and other vital information. This
communication can be accommodated via either digital, or analog media displays.
Code Requirements
All electrical outlets within 6’-0” of any sink/ water source should be GFI (by code), although
certain AHJ’s can increase this requirement dependent on use and perceived adjacency of work
surfaces.
Emergency gas shut offs – location relative to locked door (discuss future code applicability of
IFGC in MA, as well as current NFPA 54 with group)
MIT Design Standards | Lab Design Thematic Folder Page 86 of 87
(IFGC) International Fuel Gas Code. (Where provided with two or more fuel gas outlets,
including table-, bench- and hood-mounted outlets, each laboratory space in educational,
research, commercial and industrial occupancies shall be provided with a single dedicated shutoff
valve through which all such gas outlets shall be supplied. The dedicated shutoff valve shall be
readily accessible, located within the laboratory space served, located adjacent to the egress door
from the space and shall be identified by approved signage stating “Gas Shutoff”.)
The placement of the panel should not enable accidental or malicious de-activation.
Please provide a spill kit as part of the “safety station” in instances of high chemical uses, per the
direction of MIT EHS.
Food/ Drink
It is within the power of the design team to create environments that promote safe behavior by
offering viable and attractive alternatives to the smuggling of food and drink into laboratory
environments. Bringing food and drink into the laboratory environment not only puts the
particular offender at risk of poisoning, but also risks the institution’s reputation and liability.
Examples:
1. Placing write-up desks or offices directly adjacent to the laboratory, allowing for direct
line-of-sight access, but separating the different hazard levels with a full height glass
partition. (This also allows for a more sustainable and energy efficient HVAC solution)
2. Creating collaborative work zones outside of the high hazard laboratory areas, with
access to food and drink. These spaces do need to be very conveniently placed to the
laboratory area to be effective.
3. Allow for remote observation of equipment within the laboratory from outside (either
digitally or through adjacency)
END OF DOCUMENT
!
!
!
May 2018
!
!
Table of Contents
This guide is intended to promote consistency for all surveys performed on MIT’s Cambridge
campus, regardless of the surveyor performing each survey. The main objective of the MIT
Survey Guidelines is to create and maintain composite master files, which can be updated as more
recent surveys are completed. As the landscape of this campus is ever changing, the need for this
type of consistent base map is critical for future planning.
The survey requirements outlined in this guide shall act as the minimum requirements for all
survey work prepared for MIT throughout the Cambridge Campus. As each project will have its
own specific needs, a project briefing shall be performed and, if possible, a site meeting between
the project surveyor and appropriate MIT staff prior to preparing a proposal for the work. The
surveyor shall develop a scope that is appropriate for the project after the project briefing and
shall provide recommendations for survey items, including ones not listed in this guide.
The MIT Survey Control Network has been established in order to provide consistent and
uniform survey information throughout the campus and must be used by all surveyors performing
work for MIT. The base control network is a starting point for the campus and allows for
supplemental control to be set and used, in order to complete each project.
2.1 Datums
MIT’s Control Network references Massachusetts (Mainland) State Plane Coordinate System
(NAD 83) and Cambridge City Base Vertical Datum. These datum references must be used for
all survey information within the MIT campus in Cambridge.
Prior to the commencement of any field survey, MIT will provide a current plan, coordinates, and
elevations of the previously established control surrounding the project area. The surveyor is
responsible for properly checking and tying into the control. No less than 3 existing points shall
be confirmed by angle and distance observations for horizontal control prior to beginning the
field survey, and a minimum of two vertical control points (if necessary) shall be leveled through
to confirm their respective positions.
The surveyor should also complete and fill out the Control Point Recovery Sheet found in
Appendix A, for all existing controls used or not found, and submit it to MIT at the completion of
the project. Should there be a discrepancy between the field observed angles and distances
greater than standard survey tolerances, those discrepancies should be noted in the notes section
of the recovery sheet, including which points were occupied with the distance observed from each
location.
Setting Supplemental Control: As necessary to perform each field survey, additional control may
be set by the surveyor using the following guidelines:
1. The surveyor must inform MIT of their intention to set additional control and provide
properly adjusted coordinates and recovery tie cards for each point set, which will be
included in the updated control network for all points set as part of a closed loop traverse.
2. A closed loop traverse is required when two or more points are set in order to perform the
field survey.
3. A spur point is allowable, as long as the point is set by turning a complete set in direct
and reverse observations.
4. A spur points set will not be included into the MIT Control Network and it is not required
to submit coordinates or tie sketches for these points.
Consult with MIT’s Facility Information Systems (FIS) for a list of available control point
numbers to be used for your project.
1. Perform a closed traverse, turning a minimum of two sets of angles using both direct and
reverse observations for each new point established.
2. Perform a closed loop level run to all newly established control points and properly adjust
level run.
3. Perform traverse adjustment by applying angular balance and compass rule adjustment or
a properly weighted least squares adjustment.
4. Prepare a sketch of all new point sets with finder ties and adjusted northing, easting and
elevation values. Use MIT’s ‘Control Tie Sketch Card’, found in Appendix B, for
recording this data.
5. Provide MIT with a ‘Control Recovery Data Sheet’, found in Appendix A, for each
existing control used.
6. Provide MIT with traverse adjustment print outs including pre and post adjustment
coordinates.
1. Network Points shall have the prefix ‘MIT-’, followed by a number, and must be a
suitable point. Items such as stone or concrete bounds, survey disks, pk nails, mag nails,
iron rods with caps, drill holes, and pin in lead will be acceptable. Do not use hub and
tacks or scribe marks for any point to be included in the MIT Control Network. Establish
new control within MIT property wherever possible.
1. All horizontal control which is set and which will be incorporated into the MIT Control
Network shall be part of a closed traverse. This traverse shall have a minimum closure of
1 part in 20,000 and minimum angular closure of 10 seconds multiplied by the square
root of the number of sides.
1. All vertical control points set shall be part of a closed differential level loop and have a
minimum closure of 0.05 feet multiplied by the square root of the length of the level run
in miles, as per Commonwealth of Massachusetts Regulations Chapter 250, Section 6.02.
2. Should the above control not be within the specified tolerances, the surveyor will re-run
the traverse or level loop in order to meet these specifications.
3. SURVEY TYPES
All property line surveys performed for MIT shall adhere to the following subsections for each
parcel or roadway retraced. The surveyor’s scope, unless otherwise noted by MIT, will include
performing research for locus, abutting roadways, and all abutting properties at the appropriate
Assessor’s Office, Registry of Deeds, Engineering Department, Massachusetts Highway
Department (if applicable), and Massachusetts Land Court.
1. Locations for all property monuments shall be performed from a closed traverse and the
linear precision or positional tolerance of said traverse shall be noted on the plan and
shall be in conformance with 250 CMR, Section 6.01, with a minimum precision of 1 part
in 12,000. Locations may also be performed from previously established MIT control
which has been properly adjusted; as long as the surveyor verifies the points by
measurements to no less than 3 known points.
1. Monumentation found that has been used to retrace the property shall be clearly shown
and labeled on the final plan with notations of held or the offsets from record location.
Any monumentation used, which is outside of the plan limits, shall show bearing and
distance ties to such monumentation.
2. Note any encroachments protruding from or onto the surveyed property.
3. Show any easements uncovered in the research.
4. Final property plans shall:
5. Label the northing and easting values for at least 2 property corners of the retraced parcel
to the nearest 0.01 foot and any additional monuments set.
1. Upon completion of the survey project, the surveyor shall provide the following to MIT
in the format described herein including:
The base property line survey shall be performed in the same manner as outlined in the Property
Line Survey section of this manual, unless there is a previously recorded plan on file at the
Registry of Deeds. In the case of an existing plan, the surveyor may tie into that plan and will not
be required to perform a full retracement survey. The surveyor is expected to work in tandem
with MIT and the environmental consultant in order to delineate the AUL area. The surveyor’s
scope, unless otherwise noted by MIT, will include performing research at the City of Cambridge
Assessors, Middlesex County Registry of Deeds, City of Cambridge Engineering Department,
and Massachusetts Land Court at a minimum. The surveyor will be required to adhere to the
guidelines set forth in the following subsections.
1. All distances shall be reported to the nearest 0.01 foot, unless the course is tied to a water
body, in which case a tie bearing and distance must be provided in order for future
surveyors to be able to mathematically close the plan.
1. Prepare written requests to utility companies in the area for underground utilities which
fall within public roadways. Utilities to be requested in the research shall include: water,
sewer, drain, gas, telephone, electric, telecom, steam systems, Massachusetts Water
Resources Authority (MWRA) lines, and Massachusetts Bay Transportation Authority
(MBTA) lines and tunnels.
2. Obtain MIT underground utility information from the MIT Facilities Department.
3. Determine with MIT personnel if Ground Penetrating Radar (GPR) services are going to
be performed for the project prior to the survey and coordinate accordingly. The
surveyor may be requested to provide control for the GPR services and should also
budget for incorporating the GPR located utilities into the topographic survey file.
4. Obtain spot grades suitable to prepare one-foot contours, unless otherwise specified by
MIT prior to the project. In all cases spot grades should be no more than 40-feet apart.
5. Locate major features such as: walks, curbing, walls, steps, fencing, buildings, manholes,
gate valves, trees, landscaped area, pads, etc.
6. Obtain tree diameter for all located trees at 3-feet above ground level and note by text or
symbol whether the tree is deciduous or coniferous.
7. Obtain threshold elevations at all building entrances which abut the survey.
8. Obtain locations and elevations of surface utility structures, as well as any evidence of
underground utilities. Evidence will include painted lines by outside companies and
patches in paved areas. Note underground lines on the plan which are a result of painted
lines.
9. Compile underground utilities on the plan as obtained from MIT and the various utility
1. Upon completion of the survey project, the surveyor shall provide the following to MIT
in the format described herein including:
The base property line survey shall be performed in the same manner as outlined in the Property
Line Survey section of this thematic folder, unless there is a previously recorded plan on file at
the Registry of Deeds. In the case of an existing plan, the surveyor may tie into that plan and will
not be required to perform a full retracement survey. The surveyor is expected to work in tandem
with MIT and the environmental consultant in order to delineate the AUL area. The surveyor’s
scope, unless otherwise noted by MIT, will include performing research at the City of Cambridge
Assessors, Middlesex County Registry of Deeds, City of Cambridge Engineering Department,
and Massachusetts Land Court at a minimum. The surveyor will be required to adhere to the
guidelines set forth in the following subsections.
1. All distances shall be reported to the nearest 0.01 foot, unless the course is tied to a water
body, in which case a tie bearing and distance must be provided in order for future
surveyors to be able to mathematically close the plan.
a. All monumentation found that has been used to retrace the property shall be clearly
shown and labeled on the final plan with notations of held or the offsets from
record location. Any monumentation used, which is outside of the plan limits,
shall show bearing and distance ties to such monumentation.
b. Locations for all property monuments shall be performed from a closed traverse
and the linear precision or positional tolerance of said traverse shall be noted on the
plan and shall be in conformance with 250 CMR. Locations may also be
performed from previously established MIT control which has been properly
adjusted; as long as the surveyor verifies the points by measurements to no less
than three known points. The plan shall be noted if existing MIT controls are
utilized in the property retracement.
c. Locate the limits of the AUL area to be established by the environmental consultant
for the project.
d. Locate any major physical features which fall within the AUL area, including but
not limited to paving, walls, fencing, curbs, above ground tanks, buildings, planting
areas, steps, etc.
e. Show any easements uncovered in the research.
f. Prepare a boundary description for both the affected property and the AUL area.
Should an existing plan be on record at the Registry of Deeds or the Massachusetts
Land Court, the description may recite the plan used. The AUL description must
include a point of beginning that is tied to the main property.
AUL Deliverables:
1. Upon completion of the survey project, the surveyor shall provide the following to MIT
in the format described herein including:
a. Two copies of deeds, record plans, and certificates of title pertaining to MIT
property shall be submitted in DWG format and, TIFF or PDF format, noting
which parcel the deed pertains to.
b. The surveyor shall anticipate preparing four separate plans for submission. The
plan set will include: one 36 by 48 inch MIT Standard Plan, one 24 by 36 inch plan
suitable for recording at the Registry of Deeds, one Exhibit A Plan on 8-1/2 by 11
inch sheet, and one Exhibit B Sketch Plan on 8-1/2 by 11 inch sheet.
1. Locations for all property monuments shall be performed from a closed traverse and the
linear precision or positional tolerance of said traverse shall be noted on the plan and
1. Monumentation found that has been used to retrace the property shall be clearly shown
and labeled on the final plan with notations of held or the offsets from record location.
Any monumentation used, which is outside of the plan limits, shall show bearing and
distance ties to such monumentation.
2. Locations for all property monuments shall be performed from a closed traverse and the
linear precision or positional tolerance of said traverse shall be noted on the plan and
shall be in conformance with 250 CMR. Locations may also be performed from
previously established MIT control which has been properly adjusted; as long as the
surveyor verifies the points by measurements to no less than three known points. The
plan shall be noted if existing MIT controls are utilized in the property retracement.
3. Note any encroachments protruding from or onto the surveyed property.
4. Show any easements uncovered in the research.
5. Final property plans shall:
a. Show all bearing and distances related to NAD 83.
b. Note the discrepancies between record and calculated dimensions.
c. Show all monumentation, including record building offsets used.
d. Show all abutting owners with deed information.
e. Show deed information for the surveyed parcel.
f. List other deed and plan references used for the survey.
g. The property lines shall be a closed polyline when applicable.
6. Label the northing and easting values for at least 2 property corners of the retraced parcel
to the nearest 0.01 foot and any additional monuments set.
1. Upon completion of the survey project, the surveyor shall provide the following to MIT
in the format described herein including:
This section is to supplement the existing MIT CAD and Digital File Guidelines for surveying
only. The surveyor must review and adhere to the existing MIT CAD and Digital File Guidelines
unless otherwise specified herein.
All survey work must be performed in Massachusetts (Mainland) State Plane Coordinate System
(NAD 83) and Cambridge City Base, utilizing existing MIT Campus Control and be drawn in this
correct coordinate space.
All survey plans created for MIT must follow the same criteria and show the same information.
For reference, all topographic surveys shall be entitled either “Topographic Plan of Land for
Design” or “Existing Conditions Survey”; this is important to the maintenance and updating of
the MIT master files.
In addition, the appropriate Subsurface Utility Engineering (SUE) quality level must be indicated
at the end of each layer name. A description of these SUE designators are found in the scale
section below. Each survey drawing will be incorporated into MIT’s master files, which will be
the responsibility of MIT personnel at the completion of each project.
General Requirements:
a. North arrow.
b. Reference to the NAD 83 datum.
c. Graphic scale.
d. Date of the survey.
e. Pertinent notes related to the specific project.
f. Deed and plan references (if applicable).
CAD Requirements:
1. MIT requires all surveys to be in compliance with the layering standards and drafting
practices set forth in this document as well as in the MIT CAD and Digital File
Guidelines for all AutoCAD® plans. Layering conventions for surveying are found in
MIT Layering Standards for Surveys below.
4.2 Scale
In an effort to remain consistent, a scale of 1”=20’ is preferred for all topographic surveys, unless
site conditions dictate that a scale of 1”=10’ is more advantageous and appropriate. The surveyor
must request permission from MIT to prepare a topographic plan at a scale other than 1”=20’
prior to the commencement of any work.
Property Line surveys, Easement surveys, and Activity and Use Limitation Plans may be
produced at any scale as long as the property fits on one sheet and is legible.
1. MIT implements the same layer name formatting standard as the United States National
CAD Standard (USNCS) for all of its surveying layers. In addition, MIT requires that the
last letter of every underground utility layer name must indicate the standard Subsurface
Utility Engineering (SUE) quality level (A, B, C or D) for the information on that layer.
Please refer to Standard SUE Quality Levels.
2. Surveying layers are named according to the following system with the discipline
designator always being ‘SURV’.
1. The ‘Standard Guideline for the Collection and Depiction of Existing Subsurface Utility
Data’ defines the Subsurface Utility Engineering (SUE) quality levels used for all surveys
at MIT. This document was published in 2003 and last updated in 2015 by the American
a. Quality Level ‘A’ is also known as ‘locating’. It is the highest level of accuracy
presently available and involves the full use of the subsurface utility engineering
services. It provides information for the precise plan and profile mapping of
underground utilities through the nondestructive exposure of underground utilities,
and also provides the type, size, condition, material and other characteristics of
underground features.
c. Quality Level ‘C’ is probably the most commonly used level of information. It
involves surveying visible utility facilities (e.g., manholes, valve boxes, etc.) and
correlating this information with existing utility records (Quality Level ‘D’
information). When using this information, it is not unusual to find that many
underground utilities have been either omitted or erroneously plotted. Its usefulness,
therefore, is primarily on rural projects where utilities are not prevalent, or are not
too expensive to repair or relocate.
d. Quality Level ‘D’ is the most basic level of information for utility locations. It
comes solely from existing utility records or verbal recollections, both typically
unreliable sources. It may provide an overall ‘feel’ for the congestion of utilities, but
is often highly limited in terms of comprehensiveness and accuracy. Quality Level
‘D’ is useful primarily for project planning and route selection activities.
The following layer list is an example of commonly used layer names along with the Quality
Level designation when required. Modifications to or deviations from the layering standards
Title Block
SURV-BSHBD Title Block, Border, Text, Graphic Scale & Locus
SURV-LGND Legend
Survey Information
SURV-MNMT Monuments & Description Text (Plotting)
SURV-CTP Survey Control Points (STK, IP, SB)
SURV-TRV Traverse Lines
SURV-BMRK Bench Marks & Descriptions
SURV-BORG Borings & Test Pits
SURV-BORG-TEXT Borings & Test Pit Text
Survey Lines
SURV-PROP Property Lines
SURV-PRL-TEXT Property Line Text & Dims.
SURV-LOT-TEXT Lot Description & Text
SURV-ESL Easement Lines
SURV-EAS-TEXT Easement & Text Description
SURV-LIN City, Town, County, & State Lines
SURV-ABL Abutter Lines
SURV-ABU-TEXT Abutter Text (N/F)
SURV-NAM-TEXT Street, Stream, Lake Names
SURV-MSL Misc. Lines (Buffer, Setback, Zoning…)
SURV-MSL-TEXT Miscellaneous Line Text
SURV-FPL 100 Year Flood Plain Line
SURV-FPL-TEXT Flood Plain Text
Natural & Landscape
Features
SURV-LED Ledge & Rock Outcrop
SURV-PLANT-TREE Tree Line, Trees, Shrubs & Other Vegetation
SURV-TRE-TEXT Trees, Shrubs & Landscaping Text
SURV-WAT Edge of Stream, Lakes, Brooks, & Marsh
SURV-WAT-TEXT Stream, Lake, Brook Text
SURV-WTL Flagged Wetland Line
SURV-WTL-TEXT Wetland Flags & Text
SURV-MAR Marsh Symbol
Manmade Features
SURV-BLDG Buildings
SURV-BLD-TEXT Building Text
SURV-BLD-H Building Hatch
a. Allow users to isolate systems and drawing elements by controlling the visibility of
objects - improving system performance and eliminating visual clutter.
b. Expedite the import process and maintenance requirements for each set of drawings
upon import into the MIT Facilities Information Systems CAD system.
c. Facilitate the sharing of information between drawings and disciplines.
d. Allow users to control display and printing characteristics such as color, line type,
line weight, etc.
Upon completion of the survey project, the surveyor shall provide the following to MIT:
Printed Formats:
1. Two stamped and signed, original, hardcopy plans. The hardcopies must be submitted
bound and rolled, and must have the following information on the roll:
a. Name of Project.
b. MIT Project Number.
Digital Formats:
1. Two CD/DVDs containing all of the electronic files with all of the point information in
DWG format, and TIF or PDF format. Each CD/DVD must be clearly marked with the
following information:
1. Use only USNCS and MIT standard layer names – reference the layer names provided in
this document.
2. Use the minimum number of layers necessary to adequately separate entities in each
drawing. The number of layers contained in each drawing will vary depending on the
scope and complexity of the drawing, however drawings shall not contain extraneous,
redundant, or overly detailed layer names.
3. Purge each drawing of unused layers prior to submittal. The drawing file shall contain
only those layers necessary for displaying and plotting the information and drawing
entities contained in each drawing. To ensure that subsequent prints made from each
AutoCAD® drawing match the original, unused or unnecessary layers must be purged
from the drawing prior to delivery.
Control Recovery Data Sheets can be requested by emailing fis-request@mit.edu. Please fill out
all the information on this sheet when recovering control (see sample below).
Notes:
Control Tie Sketch Cards can be requested by emailing fis-request@mit.edu. Please fill out all the
information on this card and attach an image of the control tie (see sample below).
All electronic materials (CAD files, PDF files, TIF files, index table files, etc.) must be delivered
on a CD or DVD, formatted using Windows XP or higher. Indices for files must be submitted in
both paper format and electronically in Microsoft Excel 2003 or higher. Indices must follow a
format similar to the sample shown below. This template can be requested by emailing fis-
request@mit.edu.
May 2018
Table of Contents
5.! APPENDICES............................................................................................................ 6!
1. SPECIAL REQUIREMENTS
The Office of Campus Planning supports the MIT mission by serving as stewards of the evolving
physical campus and providing services that guide and inform campus strategy and
transformation. Through an inclusive and collaborative process, we pursue the continuing
creation of campus spaces that sustain and inspire the exceptional community at MIT.
The Office of Campus Planning collaborates with MIT Ground Services on site related
programming and design, OCP review is required at the concept, schematic design, and design
development stages of site projects of all scopes. OCP also supports some site projects through
Construction Documents and Construction Administration phases.
Special Resource Campus Landscapes: For any projects that include staging, construction, or
renovation in Special Resource Campus Landscapes, OCP must be consulted at the concept
phase. Areas include:
• Killian Court
• Kresge Lawn/Chapel Grove
• McDermott/Eastman Court
• North Court
• Campus open space on both sides of Massachusetts Ave. between Vassar Street and
Memorial Drive.
Please consult MIT Survey Standards. Requirements include documenting proposed and final
topography at six inch increments.
The Grand Junction Railroad has a right-of-way through the MIT campus and MIT has
agreements in place with Keolis Commuter Services and the Massachusetts Department of
Transportation. For a map of the right-of-way and construction requirements, coordinate with the
Office of Campus Planning.
Comply with American with Disabilities Act (ADA) and the requirements of the Massachusetts
Architectural Access Board (MAAB).
Slopes: Walkways as defined by Section 22.1 of 521 CMR shall be graded to a maximum of
4.5%. The cross-pitch (perpendicular to travel) for walkways and paths shall be constructed at
1.5%. The slopes of ramps and side slopes on handicap curb cuts as defined by Section 21.1 of
521 CMR shall be constructed at 7% maximum. Ramps as defined in Section 24.1 of 521 CMR
shall be constructed to a maximum slope of 7%.
Contractor shall assume that sidewalk grades will be verified and checked with a 2-foot long
electronic ‘smart level’.
A 5’-0” minimum level, 1.5% pitch, area shall be provided at entrances to buildings. Puddling or
ponding of water at the entrances will not be accepted.
The requirements specified hereinabove shall supersede the grades indicated on the Drawings. If
these requirements cannot be met with the grades indicated on the Drawings, the Architect or
Civil Engineer shall be notified immediately for direction.
• Accessible parking areas, including their adjacent access aisles, shall be level, with
surface slopes not exceeding 1.5% in all directions.
Contractor shall assume that parking area grades will be verified and checked with a 2-foot long
electronic ‘smart level’.
The requirements specified hereinabove shall supersede the grades indicated on the Drawings. If
these requirements cannot be met with the grades indicated on the Drawings, the Architect or
Civil Engineer shall be notified immediately for direction
Materials, products and procedures shall contribute to the Project’s sustainable design goals,
including those defined by SITES, Living Building Challenge Requirements, USGBC’s LEED
Green Building Design and Construction Reference Guide and Section 018113 - SUSTAINABLE
DESIGN REQUIREMENTS as applicable to the project. Confirm requirements with the MIT
Project Manager.
The Contractor shall ensure that the requirements related to the project’s sustainability design
goals are implemented to the fullest extent. Substitutions, or other changes to the work proposed
In general, requirements may include products manufactured from recycled content, and materials
or products that have been extracted, harvested, or recovered, as well as manufactured, within 500
miles of the project site.
Artwork and architectural landscape features shall be evaluated for the items below to ensure that
they do not present a hazard to public safety.
• Sharp edges, points, projections, or pinch-points with the potential to cut, puncture or cause
injury by impact to passing pedestrians or bicyclists.
• Overhead parts which may present a hazard to pedestrian traffic. Artwork architectural
features should follow minimum sign height requirements in areas where pedestrian traffic
is likely.
Work shall be performed by a Certified Arborist, selected by MIT and paid for by the Contractor
unless otherwise acceptable to the MIT Project Manager.
Specification Section 015640 – MIT Temporary Tree and Soil Protection will be provided by
MIT and shall be used for all applicable projects. The Section includes requirements for signage.
All protection measures shall remain in place throughout the construction period. Remove
protection devices only after written permission has been granted by the MIT Grounds
Supervisor. Signage shall be removed and returned to the MIT Grounds Supervisor.
Requirements apply to fill materials from off-site locations that are imported to complete the
work of the Project. This applies to all fills including, but not limited to, fill required to complete
surface treatments, landscaping, and child play areas.
Furnish materials from approved off-site sources as required, including performing testing and
providing data on the engineering properties and chemical characteristics representative of the
materials and soils proposed for use.
Specification Section 312322 – MIT Imported Fill Criteria and Management will be provided by
MIT and shall be used for all applicable projects. Materials not meeting these criteria are the
property of the Contractor and must be removed from the Project by the Contractor, at no cost to
the MIT and without any schedule impact to Project.
Scanning for pest burrows prior to earth disruption (by pest management vendor)
Reducing/controlling pest population using the most up to date green practice (pest euthanasia
using dry ice is kind to animals and would leave no chemical residues). Otherwise pests will seek
to relocate as the construction starts
Hollow spaces should be capped: Benches, tables, bollards, fencing, and bike racks can have
tubing, pipe, or other structural components that are hollow. These hollow elongated spaces can
become nesting spaces for insects. This is of particular concern for stinging insects. Hollow
tubing or pipe should be capped on both ends unless one of the ends is interred or comes to be
flush with the ground.
4.3 Planting
Shrubs and bushes should be kept trimmed at the base to prevent pest shelter and comfort. There
should be a 12 inch gap between ground surface and the base of the shrub.
Hosting a few bee sanctuaries aligns strongly with MIT’s Campaign for a Better World. If the
Institute would like to help support the New England bee population these bee sanctuaries should:
Placing a top lining of steel metal mesh, of 1/4 to 1/2 of an inch gauge, will prevent rats from
digging burrows in flower beds. Between 4-5 inches of soil can be place above the mesh. This
practice can become a challenge for planting, but flowers often can set roots through the mesh, or
holes can be cut in the mesh to make room for plants, yet discourage burrowing pests.
During winter months, particularly during harsh winters, tree and shrub bark can become a source
of food for burrowing pests. Lining the trunks of trees and shrubs with steel metal mesh in late
fall could help prevent severe injury or death to trees and shrubs.
Rats can eat through Tarmac and burrow underneath. Periodic waste management and grounds
cleanliness can control incentives to burrow in tarmac. Periodic inspection or at least awareness
by staff and community members that traffic on these pave spaces as well as reporting of holes or
cracks would help control or limit pest burrowing.
5. APPENDICES
Refer to the following documents, to be used in their entirety for applicable projects.
END OF DOCUMENT
May 2018
Table of Contents
MIT Design Standards | Mechanical and Electrical Rooms Thematic Folder Page 1 of 6
1. MECHANICAL AND ELECTRICAL ROOMS -
OVERVIEW
This MIT thematic folder is for all new construction and major renovation of mechanical and
electrical rooms spaces including, but not limited to, the following:
The requirements shall be incorporated into the design, planning and construction stages of all
projects by designers, architects, engineers, and contractors as applicable.
Comply with local, state, and federal codes including but not limited to the items listed following.
If the MIT standards are more stringent than code, follow the MIT standards.
1. Includes OSHA 1910 and 1926. Note that since MIT must comply with OSHA 1910, it
is important that those requirements be designed into the project. In our experience, this
has been lacking.
2.1 Clearances
Vertical Clearances:
1. Main mechanical and electrical rooms shall have clear ceiling heights of not less than 12
feet (3.6 m).
2. Catwalks shall be provided for equipment that cannot be maintained from floor levels.
3. Where maintenance requires lifting heavy parts of 100 pounds (45 kg) or more, provide
MIT Design Standards | Mechanical and Electrical Rooms Thematic Folder Page 2 of 6
hoists and hatchways.
Horizontal Clearances:
1. Mechanical and electrical rooms shall be configured with clear circulation aisles and
adequate access to equipment.
2. The arrangement shall consider future removal and replacement of equipment.
3. The mechanical and electrical rooms shall have adequate doorways, areaways, and
staging areas to permit replacement and removal of equipment without the need to
demolish walls or relocate other equipment.
4. Establish sufficient clearance areas, in accordance with the equipment manufacturer’s
recommendations, for maintenance and removal of coils, filters, motors, and similar
devices.
5. Required clearance shall be the length of the longest coil plus two feet (at location of
coil).
6. Required clearance at filters shall be the length required to replace the largest filter.
Equipment Access:
Mechanical and electrical room floors shall be uniformly sloped to drain with appropriate drains
in logical locations relative to equipment and piping.
1. Blow-offs and equipment drains shall be piped to a floor drain with pipes properly
supported and protected.
2. Tubing and hose are not considered permanent and should only be used for temporary
drains.
Equipment and housekeeping pads: 6 inch wider than equipment and at least 4 inches thick.
Wall and Floor Coatings: The wall coating color shall be MIT Off-White. The floor coating
color shall be MIT Grey and extend entirely across the floor and equipment platforms; apply
coating prior to installation of equipment. The safety marking color shall be MIT Safety Yellow
and extended at least 2 inches at curbs, corners, edges, and vertical legs. The safety striping color
MIT Design Standards | Mechanical and Electrical Rooms Thematic Folder Page 3 of 6
shall be MIT Safety Yellow and be located at equipment safety clearances. Refer to the MIT
Design Standards Division 09 - Finishes for paint materials and colors.
Mechanical and electrical rooms that may leak shall be waterproof including a minimum 4 inch
seamless upturn at walls and equipment pads.
Wastewater discharges may require special permitting or pre-treatment that should be reviewed
with EHS.
Mechanical and electrical room doors must have a label in accordance with OSHA requirements
and MIT standards. If more than one door is used, all doors shall be labeled. Labels are to be
fastened to the door or next to the door in accordance with MIT signage guidelines using
tamperproof screws. Double-sided tape is not acceptable for a permanent means of attachment.
Doors shall have appropriate warning signage where required by OSHA and in accordance with
MIT standards, which may include:
2.4 Doors
Mechanical and electrical room doors shall swing out of the room. Doors shall have crash bars,
closers with hold opens, and a stainless steel kick plate on the room side.
Doors leading into main mechanical and electrical rooms shall have at least one set of double
doors, preferably located near the elevator.
Card access shall be in accordance with Division 28 - Electronic Safety and Security.
Mechanical and electrical room doors must be locked from the exterior at all times. Doors shall
require key for entry, but shall not be lockable from inside the mechanical or electrical room.
MIT Design Standards | Mechanical and Electrical Rooms Thematic Folder Page 4 of 6
Exception: Doors opening directly onto roofs shall require key access from the inside of the
building and no key access or locking to egress from the roof.
For remodeling projects, floors, ceilings, and walls must be free of abandoned threaded rods,
strap hangers, conduit, clips and similar fasteners, supports or accessories that are no longer
required.
Abandoned equipment must be removed, including but not limited to, pipes, conduit, ductwork,
electrical feeds, and low voltage wires.
If chemicals are used in the space that are corrosive or present significant skin or eye contact or
absorption hazard, then eye wash and showers shall be provided as required in OSHA 1910.151.
Examples of use include but are not limited to chemicals to be used to treat water discharge, clean
equipment or HVAC components. Refer also to the EHS Thematic Folder.
3. ELECTRICAL
Disconnecting Means:
Provide Arc Flash warning labels and verified arc flash studies where required.
MI (mineral insulated) cables shall be clearly labeled in accordance with local electrical codes
and NEC, with label every 4 feet.
Low voltage wires shall be installed and protected from damage in accordance with the applicable
MIT Design Standards Thematic Folders and Technical Divisions.
Lighting levels must meet OSHA requirements or better for electrical spaces.
MIT Design Standards | Mechanical and Electrical Rooms Thematic Folder Page 5 of 6
3.2 Receptacles
All mechanical and electrical rooms must have Ground Fault Circuit Interrupter (GFCI) installed,
or receptacles are to be installed on the load side of a GFCI.
Each mechanical and electrical room wall shall have at least one outlet every 20 feet. If a wall is
less than 20 feet long, install one outlet per wall.
3.3 Wi-Fi
Comply with applicable NFPA, NEC and OSHA requirements and MIT standards. Provide
firesafing and firestopping at penetrations to meet local code requirements.
Fire Extinguishers:
1. Department of Facilities (DOF) rooms shall have fire extinguishers located inside the
room near the exit, or exits if multiple doors are used Comply with MIT policy on fire
extinguishers in Division 10 - Specialties.
END OF DOCUMENT
MIT Design Standards | Mechanical and Electrical Rooms Thematic Folder Page 6 of 6
!
!
!
!
MIT
Design Standards
!
!!
)
!
!
!"#$%&'(&)'*!%*!+&
%1! %'2#&3452%&') 6!
%%1! 7&!"#','5") 8!
!
,- ,*!.'/0)!,'*&
C.+!9T*!U:+U.,*!.V!9T-,!U+.<+=>W!9T*!9*+>!X6+.7*89!5:+/.;*+Y!+*V*+,!9.!9T*!9+=/,V*+!.V!+*,U./,-Z-[-9\!.V!=!
Z:-[]-/<^,!.U*+=9-./W!>=-/9*/=/8*W!9+.:Z[*,T..9-/<!=/]!+*U=-+!=89-;-9-*,!V+.>!9T*!U+.7*89!9*=>!9.!345^,!
AU*+=9-./,!<+.:U?!!J:+-/<!=!8./,9+:89-./!U+.7*89W!9T*!+*,U./,-Z-[-9\!.V!9T*,*!=89-;-9-*,!Z*[./<,!9.!9T*!
U+.7*89!9*=>!_T-8T!8./,-,9,!.V!9T*!I./,9+:89-./!3=/=<*+!`I3a!=/]!9T*!I=>U:,!I./,9+:89-./!`IIa!
]-;-,-./!.V!345?!!A/8*!=!U+.7*89!-,!8.>U[*9*W!9T*!+*,U./,-Z-[-9-*,!>:,9!Z*!9+=/,V*++*]!9.!345^,!AU*+=9-./,!
<+.:U!_T.!=89!=,!9T*!V=8-[-9\!._/*+,!=/]!.U*+=9.+,?!!5T-,!].8:>*/9!_-[[!*bU[=-/!9T*!U+.<+=>!V.+!9T*!
9+=/,V*+!.V!9T*,*!+*,U./,-Z-[-9-*,W!-/8[:]-/<!9T*!U[=//-/<!=/]!U+*U=+=9-./!=89-;-9-*,!+*c:-+*]!9.!->U+.;*!
9T*!+*,:[9,?!
5T*+*!=+*!=!/:>Z*+!.V!]-VV*+*/9!8./,9+:89-./!U+.7*89!9\U*,!:/]*+<./*!Z\!9T*!II!<+.:UW!,.!9T-,!U+.<+=>!
T=,!Z**/!Z+.d*/!-/9.!V.:+!,*89-./,!9T=9!8.;*+!*=8T!9\U*?!!5T.,*!U+.7*89!9\U*,!-/8[:]*0!
'? I=U-9=[!6+.7*89,!
&? I=U-9=[!1*/*_=[!6+.7*89,!
%? I.>>-99**!V.+!9T*!1*;-*_!.V!EU=8*!6[=//-/<!`I1E6a!6+.7*89,!
#? 3=7.+!1*U=-+!=/]!A;*+T=:[!6[:,!`31Aea!6+.7*89,!
5T-,!-/-9-=[!;*+,-./!.V!9T*!6+.7*89!5:+/.;*+!6+.<+=>!V.8:,*,!,.[*[\!./!9T*!=89-;-9-*,!+*c:-+*]!V.+!=!I=U-9=[!
6+.7*89?!!E:Z,*c:*/9!+*[*=,*,!.V!9T-,!].8:>*/9!_-[[!-/8[:]*!]*;*[.U>*/9,!-/!9T*!+*>=-/-/<!U+.7*89!9\U*!
,*89-./,!_-9T!-/U:9!V+.>!=]]-9-./=[!>*>Z*+,!9.!9T*!]*;*[.U>*/9!9*=>?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! %!
!
)
!
,,- 1'2%.*"*)%&
9LMNLOP)3QRQSMTPQUV)2QOPW)
J:*!9.!9T*!>:[9-U[*!U=+9-*,!-/;.[;*]!_-9T!9T*!9:+/.;*+!U+.8*,,W!-9!_=,!->U*+=9-;*!9T=9!9*=>,!Z*!
=,,*>Z[*]!9T=9!8./,-,9*]!.V!+*U+*,*/9=9-;*,!V+.>!*=8T?!!!K-9T!9T*!U+.<+=>!Z*-/<!Z+.d*/!-/9.!]-VV*+*/9!
U+.7*89!9\U*,W!9T*!9*=>,!_*+*!=[,.!Z:-[9!=+.:/]!9T*,*!U+.7*89!9\U*,!9.!=[[._!V.+!V.8:,!./!=+*=,!.V!
->U.+9=/8*!9.!*=8T?!!!5T:,W!9T*!]*;*[.U>*/9!.V!9T-,!].8:>*/9!T=,!-/;.[;*]!9T*!8.[[=Z.+=9-./!.V!9T+**!
,U*8-V-8!9*=>,!_T.!T=;*!U=+9-8-U=9*]!-/!9T*!8+*=9-./W!+*;-*_!=/]!=UU+.;=[!U+.8*,,?!
!
9XOWQ)%)Y)5OTZVOS)9LM[Q\V)5MSSO]MLOVZMU)2QOP)
C.+!9T*!V-+,9!UT=,*!.V!9T-,!].8:>*/9^,!]*;*[.U>*/9W!9T*!V.8:,!_=,!./!9T*!9:+/.;*+!.V!9T*!8=U-9=[!
U+.7*89,?!!5*=>!>*>Z*+,!_*+*!-/8[:]*]!V+.>!9T*!V.[[._-/<!<+.:U,0!
!
• I=>U:,!I./,9+:89-./!`IIa!
O 6+.7*89!3=/=<*>*/9!J-;-,-./!`63Ja!
O E\,9*>!6*+V.+>=/8*!f!5:+/.;*+!`E65a!
!
• AU*+=9-./,!
O C=8-[-9-*,!2/<-/**+-/<!`C2a!
O 1*U=-+!=/]!3=-/9*/=/8*!`1f3a!
!
• 4/V+=,9+:89:+*!g:,-/*,,!AU*+=9-./,!
O C=8-[-9\!4/V.+>=9-./!E*+;-8*,!`C4Ea!
!
• 2/;-+./>*/9=[!S*=[9T!=/]!E=V*9\!`2SEa!
!
• 4/V.+>=9-./!E*+;-8*,!=/]!5*8T/.[.<\!`4Ef5a!
!
9XOWQ)%%)Y)5OTZVOS)#QUQ^OS_)5#$9)B)+#&)9LM[Q\V)5MSSO]MLOVZMU)2QOP)
C.+!9T*!,*8./]!UT=,*!.V!8.[[=Z.+=9-./W!9T*!63F!9*=>,!V.+!I1E6W!I=U-9=[!1*/*_=[!f!31A!U+.7*89,!_-[[!Z*!
Z+.:<T9!-/!9.!.VV*+!9T*-+!:/-c:*!U*+,U*89-;*!./!9T*,*!U+.7*89!9\U*,!=/]!T._!9T*\!,**!=!,:88*,,V:[!
=UU[-8=9-./!.V!9T*!9:+/.;*+!U+.<+=>?!
!
9LMNLOP)4T`OVZUN)9SOU)
@,!9T*!/**],!V.+!U+.7*89!9:+/.;*+!8T=/<*!-/!9T*!V:9:+*W!9T-,!U+.<+=>!,T=[[!8./9-/:*!9.!Z*!+*;-*_*]!./!=!
+*<:[=+!Z=,-,!9.!=,,*,,!9T*!*VV*89-;*/*,,!.V!9T*!8:++*/9!U+.8*,,!=/]!=>*/]!=,!/**]*]!9.!=88.>>.]=9*!
9T.,*!8T=/<*,?!!@/\!*++.+,!.+!.>-,,-./,!V.:/]!,-/8*!9T*![=,9!:U]=9*!_-[[!=[,.!Z*!=88.:/9*]!V.+?!!5T-,!
+*;-*_!_-[[!Z*!8..+]-/=9*]!Z\!9T*!E65!F+.:U?!!@!/*_!;*+,-./!_-[[!Z*!8+*=9*]!=/]!]-,9+-Z:9*]W!-V!+*c:-+*]?!
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! #!
!
)
!
&
)"3,!"$&3.'4%)!+&
345!]*V-/*,!=!XI=U-9=[!6+.7*89Y!=,!=/\!/*_!Z:-[]-/<!8./,9+:89-./!U+.7*89!.+!Z:-[]-/<!+*/.;=9-./!U+.7*89!
9T=9!*b8**],!=!Z:]<*9!.V!hG!>-[[-./?!!5T-,!,*89-./!.V!9T*!U+.<+=>!_-[[!8.;*+!=89-;-9-*,W!]*[-;*+=Z[*,!=/]!
+*c:-+*>*/9,!9.!Z*!V.[[._*]!V.+!I=U-9=[!6+.7*89,!,U*8-V-8=[[\?!
56"!&,+&3.'4%)!&!0.*'2%.7&
5T*!9*+>!X6+.7*89!5:+/.;*+Y!+*V*+,!9.!9T*!9+=/,V*+!.V!+*,U./,-Z-[-9\!.V!=!Z:-[]-/<^,!.U*+=9-./W!
>=-/9*/=/8*W!9+.:Z[*,T..9-/<!=/]!+*U=-+!=89-;-9-*,!V+.>!9T*!U+.7*89!9*=>!9.!9T*!._/*+!.V!=!V=8-[-9\?!!
J:+-/<!=!8./,9+:89-./!U+.7*89W!9T*!+*,U./,-Z-[-9\!.V!9T*,*!=89-;-9-*,!Z*[./<,!9.!9T*!I./,9+:89-./!3=/=<*+!
=/]!-,!V=8-[-9=9*]!Z\!9T*!I=>U:,!I./,9+:89-./!]-;-,-./!.V!345?!!A/8*!=!U+.7*89!-,!8.>U[*9*W!9T*!
+*,U./,-Z-[-9-*,!>:,9!Z*!9+=/,V*++*]!9.!345^,!AU*+=9-./,!]-;-,-./?!!5T-,!U+.<+=>!_-[[!*bU[=-/!9T*!9+=/,V*+!
.V!9T*,*!+*,U./,-Z-[-9-*,W!=,!_*[[!=,!9T*!U[=//-/<!=/]!U+*U=+=9-./!=89-;-9-*,!+*c:-+*]!9.!->U+.;*!9T*!
*b*8:9-./?!
C+.>!9T*!U*+,U*89-;*!.V!9:+/.;*+W!9T*+*!=+*!V-;*!,9=<*,!-/!=/\!8./,9+:89-./!U+.7*890!
• 6[=//-/<$J*,-</!E9=<*!
• I./,9+:89-./!E9=<*!
• 5*,9-/<!f!)*+-V-8=9-./!E9=<*!
• 5:+/.;*+!E9=<*!
• K=++=/9\!E9=<*!
5T-,!].8:>*/9!_-[[!+*V*+!9.!=[[!UT=,*,!.V!=!U+.7*89W!Z:9!./[\!,U*=d!9.!9T*!=89-;-9-*,!=/]!+*c:-+*>*/9,!
=UU[-8=Z[*!9.!9T*!6+.7*89!5:+/.;*+!6+.<+=>?!
/"!%&'(&#%*%(,),"$&'))03"*)8&
5T*!J=9*!.V!g*/*V-8-=[!A88:U=/8\!`JgAa!-,!9T*!]=9*!,*9!Z\!9T*!8./,9+:89-./!9*=>!_T*/!9T*!Z:-[]-/<!
:,*+,!Z*<-/!9.!.88:U\!9T*!V=8-[-9\?!!5T-,!]=\!8.>>./[\!8.-/8-]*,!_-9T!9T*!I*+9-V-8=9*!.V!A88:U=/8\!]=9*W!
Z:9!>=\!/.9!8.-/8-]*!_-9T!9T*!E:Z,9=/9-=[!I.>U[*9-./!]=9*?!A/8*!=!U+.7*89!T=,!+*=8T*]!9T*!JgAW!9T*!
_=++=/9\!V.+!9T*!Z:-[]-/<!.VV-8-=[[\!Z*<-/,!=/]!=[[!,\,9*>,!Z*8.>*!9T*!.VV-8-=[!+*,U./,-Z-[-9\!.V!
AU*+=9-./,W!_-9T!9T*!*b8*U9-./!.V!,\,9*>,!9T=9!:/]*+<.!=!X6T=,*]!5:+/.;*+!6+.8*,,Y!`=,!]-,8:,,*]!-/!
E*89-./!'?L?&a!=,!=<+**]!:U./!Z\!63JW!E65W!C2!=/]!AU*+=9-./,?!!5T*!63J!,T=[[!U+.;-]*!9T*!JgA!9.!E65W!
C2W!AU*+=9-./,!=/]!I:,9.>*+!E*+;-8*!/.![=9*+!9T=/!R"!]=\,!-/!=];=/8*!.V!-9,!=++-;=[?!
3$"**,*1&9&/%+,1*&+!"1%&!0.*'2%.&")!,2,!,%+&
!"#"! $%&'(%()*+,-.+%-/0%,+1&%-2)(3&-
6+*U=+=9-./!V.+!9T*!9:+/.;*+!.V!=!V=8-[-9\!/**],!9.!Z*<-/!]:+-/<!9T*!U[=//-/<!=/]!]*,-</!,9=<*,!.V!=!
U+.7*89?!!5T-,!_-[[!=[[._!+*c:-+*>*/9,!9.!Z*!;*99*]!_-9T!=[[!-/;.[;*]!U=+9-*,!=/]!:/]*+,9..]!Z\!9T*!
U+.7*89!9*=>!<.-/<!V.+_=+]?!!5.!=88.>U[-,T!9T-,W!9T*+*!/**],!9.!Z*!8.[[=Z.+=9-./!=>./<!9T*!345!
V=8-[-9-*,!9*=>,!-/!,*99-/<!8[*=+[\!]*V-/*]!9:+/.;*+!<.=[,?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! G!
!
)
!
!
!
!
!"#"!"! $%&'()*+,(-.+/(0%(1(2*-*34(1+5$,/16+
5.!=88.>U[-,T!9T*!8.[[=Z.+=9-./!*VV.+9!.:9[-/*]!V.+!9T-,!U+.<+=>W!=/!*=+[\!]*,-</=9-./!.V!9*=>!>*>Z*+,!
-,!+*c:-+*]!V.+!8[*=+!:/]*+,9=/]-/<!.V!8.>>:/-8=9-./![-/*,?!5.!9T-,!*/]W!*=8T!<+.:U!9.!Z*!-/;.[;*]!_-9T!
=!U+.7*89!,T=[[!,*[*89!=!6+.7*89!5*=>!1*U+*,*/9=9-;*!]:+-/<!9T*!U[=//-/<!=/]!]*,-</!,9=<*!9T=9!,T=[[!Z*!
9T*!U.-/9!.V!8./9=89!V.+!;=+-.:,!=89-;-9-*,!+*V*+*/8*]!-/!9T-,!U+.<+=>?!!!5T*,*!651,!_-[[!8..+]-/=9*!=[[!
=89-;-9-*,W!=,!_*[[!=,!]-,,*>-/=9*!=[[!U+.7*89!-/V.+>=9-./!9.!9T*!>*>Z*+,!.V!9T*-+!+*,U*89-;*!9*=>!9T=9!
_-[[!U=+9-8-U=9*!-/!9T*!U+.7*89?!!651,!_-[[!Z*!,*[*89*]!V+.>!9T*!V.[[._-/<!<+.:U,!=9!=!>-/->:>0!
• 6+.7*89!3=/=<*>*/9!J-;-,-./!`63Ja!i!`4?*?!6+.7*89!3=/=<*+a!
• E\,9*>,!6*+V.+>=/8*!f!5:+/.;*+!`E65a!
• C=8-[-9-*,!2/<-/**+-/<!`C2a!
• AU*+=9-./,!
• 2/;-+./>*/9=[!S*=[9T!=/]!E=V*9\!`2SEa!
• 4/V.+>=9-./!E*+;-8*,!=/]!5*8T/.[.<\!`4Ef5a!
!"#"!"7 ,8%2&4(%+/(983%(.(2*1+
J:+-/<!9T-,!V-+,9!,9=<*!V.+!9T*!U+.7*89W!9T*!<:-]*[-/*,!V.+!=!U+.U*+!U+.7*89!9:+/.;*+!/**]!9.!Z*![=-]!.:9!
=/]!-/8[:]*]!-/!9T*!U+.7*89!8./9+=89!].8:>*/9,?!!5T*!II!9*=>!,T=[[!8..+]-/=9*!=!+*;-*_!.V!9T*!-9*>,!
[-,9*]!Z*[._!_-9T!9T*!651,!Z*V.+*!9T*\!=+*!V-/=[-j*]?!!5T-,!-/8[:]*,!9T*!V.[[._-/<0!
• 1*c:-+*>*/9,!V.+!9T*!4/9*+->!=/]!C-/=[!5:+/.;*+!6=8d=<*,!
• B**]!V.+!U+*O9+=-/-/<!Z:-[]-/<!9.:+,!
• 1*c:-+*>*/9,!V.+!A_/*+!5+=-/-/<!8.>U+-,-/<!.VW!Z:9!/.9![->-9*]!9.0!
o J-,8-U[-/*,!-/8[:]*]!
o 5.U-8,!9.!Z*!8.;*+*]!`,\,9*>![*;*[!=/]!*c:-U>*/9![*;*[a!
o J*[-;*+=Z[*,!
o J:+=9-./,!
o M.8=9-./!`8[=,,+..>!=/]$.+!V-*[]a!
o k:=[-V-8=9-./,!.V!9T*!9+=-/*+!
o J-<-9=[!+*8.+]-/<!U=+=>*9*+,!
• 6.,9O.88:U=/8\!U*+V.+>=/8*!;*+-V-8=9-./!U+.8*,,!`4?*?!'"!>./9T!_=++=/9\!;-,-9!;,?!U.,9O
.88:U=/8\!8.>>-,,-./-/<a!
• K=++=/9\!6+.8*]:+*,!
)'*+!.0)!,'*&+!"1%&!0.*'2%.&")!,2,!,%+&
!"4"! $%+5&6)-/&(7-8+607&,)()*+,-9&1*&:-
63J!,T=[[!-/8[:]*!9T*!;=+-.:,!<+.:U!>*>Z*+,!-/!9T*!]-,9+-Z:9-./!.V!8*+9=-/!8./,9+:89-./!].8:>*/9,!Z\!
,*/]-/<!9T*>!]-+*89[\!9.!9T*!651,!;-=!*>=-[W!=/!=88*,,-Z[*!345!/*9_.+d!]+-;*![.8=9-./!.+!9T+.:<T!=88*,,!
9.!=!U+.7*89!_*Z,-9*!_T*+*!9T*!].8:>*/9,!=+*!Z*-/<!d*U9?!!5T*,*!].8:>*/9,!-/8[:]*0!
• E:Z>-99=[!6=8d=<*,!
• I..+]-/=9-./!J+=_-/<,!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! L!
!
)
!
5T*!<+.:U!>*>Z*+,!_-[[!T=;*!=/!.UU.+9:/-9\!9.!8..+]-/=9*!8.>>*/9,!./!9T*,*!U=8d=<*,!_T-[*!:/]*+!
+*;-*_!Z\!9T*!U+.7*89!@+8T-9*89,!=/]!2/<-/**+,?!!@/\!8.>>*/9,!V+.>!9T*!;=+-.:,!<+.:U,!,T=[[!Z*!
8./,.[-]=9*]!Z\!9T*!651!=/]!U+.;-]*]!9.!9T*!63JW!_T.!9T*/!T=,!9T*!+*,U./,-Z-[-9\!.V!*[-8-9-/<!+*,U./,*,!
V+.>!9T*!]*,-</!9*=>?!5T*,*!+*,U./,*,!,T=[[!Z*!U+.;-]*]!-/!_+-9-/<!9.!9T*!651,?!
!"4"# ;+,<)%06)*+,-$%+3%&<<-=(>?@8+:,<-
J:+-/<!8./,9+:89-./W!9T*!C2!M*=]!,T=[[!,8T*]:[*!>./9T[\!Z:-[]-/<!_=[d,!9T=9!,T=[[!,9=+9!=9!=!9->*!=<+**]!
:U./!Z\!9T*!U+.7*89!9*=>?!!5T*,*!_=[dO]._/,!,T=[[!-/8[:]*!+*U+*,*/9=9-;*,!V+.>!=[[!<+.:U,!-/8[:]-/<!9T*!
8./9+=89.+,W!=,!=UU[-8=Z[*!V.+!9T*!U+.<+*,,!.V!8./,9+:89-./?!5T*!651,!,T=[[!]*,-</=9*!+*U+*,*/9=9-;*,!9.!
U=+9-8-U=9*!-/!9T*!8./,9+:89-./!U+.<+*,,!_=[dO]._/,?!!5T-,!_-[[!Z*!=/!.UU.+9:/-9\!V.+!<+.:U,!9.!9+=8d!9T*!
8./,9+:89-./!.V!9T*!Z:-[]-/<W!Z*99*+!:/]*+,9=/]!9T*!V=8-[-9\!=/]!-9,!,\,9*>,!=/]!9.!+=-,*!=/\!8./8*+/,!
=Z.:9!9T*!Z:-[]-/<!Z*V.+*!9T*!,\,9*>,!=+*!9+=/,V*++*]!9.!9T*-+!8./9+.[?!!0!
• 49!_-[[!Z*!9T*!C2!M*=]^,!+*,U./,-Z-[-9\!9.!].8:>*/9!=/]!]-,9+-Z:9*!c:*,9-./,!.+!8.>>*/9,!9T=9!
=+-,*!V+.>!9T*!_=[dO]._/,!9.!9T*!63J?!
• 49!_-[[!Z*!9T*!+*,U./,-Z-[-9\!.V!9T*!651,!9.!9=d*!9T*!-/V.+>=9-./!<[*=/*]!V+.>!9T*!_=[dO]._/,!
=/]!]-,,*>-/=9*!-9!=>./<,9!9T*!.9T*+!>*>Z*+,!.V!9T*-+!9*=>W!=,!_*[[!=,!Z+-/<!9.!9T*!=99*/9-./!
.V!9T*!II!9*=>W!c:*,9-./,!.+!8./8*+/,!V+.>!.9T*+!>*>Z*+,!.V!9T*-+!9*=>!+*[=9*]!9.!9T=9!
U=+9-8:[=+!U+.7*89?!
• !
!%+!,*1&9&2%.,(,)"!,'*&+!"1%&!0.*'2%.&")!,2,!,%+&
!"A"! ;+7'+,&,)-(,B-2C<)&7-/&<)*,3-
J:+-/<!9T*!5*,9-/<!f!)*+-V-8=9-./!E9=<*!.V!9T*!U+.7*89W!9T*!8./,9+:89-./!9*=>!_-[[!].!9T*!V.[[._-/<0!
• 5T*!@+8T-9*89:+=[$2/<-/**+-/<!9*=>!_-[[!=,,*,,!9T*!U+.7*89!=/]!8+*=9*!=!U:/8T![-,9!.V!-9*>,!9.!Z*!
+*,.[;*]!Z\!9T*!8./,9+:89-./!9*=>?!
• 5T*!I.>>-,,-./-/<!6+.;-]*+W!=[./<!_-9T!.9T*+!%+]!U=+9\!9*,9!=<*/8-*,W!_-[[!8T*8d!=/]!9*,9!9T*!
Z:-[]-/<!8.>U./*/9,!=/]!,\,9*>,!V.+!U+.U*+!-/,9=[[=9-./W!V:/89-./=[-9\!=/]!U*+V.+>=/8*?!!5T*,*!
8T*8d.:9,!=/]!9*,9,!_-[[!U+.]:8*!=![-,9!.V!]*V-8-*/8-*,!9.!Z*!8.++*89*]!Z\!9T*!8./,9+:89-./!9*=>?!
• 5T*!U+.7*89!9*=>!_-[[!9+=8d!=[=+>,!./!9T*!g:-[]-/<!@:9.>=9-./!E\,9*>!`g@Ea!=/]!T=;*!9T*>!
+*,.[;*]!Z\!9T*!=UU+.U+-=9*!8./9+=89.+?!
!
g\!9T*!JgAW!II!_-[[!>=d*!*;*+\!*VV.+9!9.!T=;*!=[[!.:9,9=/]-/<!U+.7*89!+*[=9*]!-,,:*,$!=[=+>,!+*,.[;*]!
Z*V.+*!,\,9*>,!=+*!9:+/*]!.;*+?!!5T-,!-/8[:]*,!=/\!.U*/!_.+d!9.!8.>U[*9*!-9*>,W!U:/8T![-,9!-9*>,W!1f3!
-/,U*89-./!-9*>,W!8.>>-,,-./-/<!=89-./![-,9!-9*>,!.+!=[=+>,!./!9T*!g@E?!
!
BA520!AU*/!-9*>,!./!=/\!<-;*/!,\,9*>!>=\!/.9!/*8*,,=+-[\!=VV*89!9T*!=Z-[-9\!9.!9:+/!.;*+!9T=9!,\,9*>?!!
2=8T!-,,:*$=[=+>!_-[[!Z*!=,,*,,*]!=,!9.!-9,!->U=89!./!9T*!9:+/.;*+!U+.8*,,?!!E**!E*89-./!'?G?&!V.+!U.,9O
9:+/.;*+!-,,:*$=[=+>!8[.,*.:9!U+.8*,,?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! P!
!
)
!
!0.*'2%.&+!"1%&")!,2,!,%+&
!"D"! /%(*,*,3-
B.![=9*+!9T=/!R"!]=\,!-/!=];=/8*!.V!9T*!JgAW!9T*!II!9*=>!_-[[!Z*<-/!9T*!8..+]-/=9-./!.V!9T*!9+=-/-/<!
U+.<+=>!V.+!AU*+=9-./,!U*+,.//*[!./!9T*!Z:-[]-/<!=/]!9T*!/*_[\!-/,9=[[*]!,\,9*>,?!!5T*!9+=-/-/<!
U+.<+=>!_-[[!-/8[:]*!9T*!V.[[._-/<!,9*U,0!
• E65W!63JW!C2!=/]!9T*!I3!_-[[!8+*=9*!=!U+*[->-/=+\!9+=-/-/<!U[=/!-/8[:]-/<!=!9+=-/-/<!,8.U*!Z=,*]!
./!U+.7*89!,U*8-V-8=9-./,!=/]!=!,8T*]:[*?!!"#$%&'()*#+,+,-(.&#,(/0*$(+1(%*02+3'3(+,(4%%',3+5(46!
• E65W!63J!=/]!C2!_-[[!T.[]!=!>**9-/<!_-9T!AU*+=9-./,!9.!+*;-*_!9T*!U+*[->-/=+\!9+=-/-/<!U[=/?!
5T-,!>**9-/<!_-[[!+*;-*_!,\,9*>,!9.!Z*!9+=-/*]!./W!9.U-8,!9.!Z*!8.;*+*]W!]:+=9-./!.V!,U*8-V-*]!
9+=-/-/<!U*+!,\,9*>!=/]!U+*[->-/=+\!,8T*]:[*!.V!9+=-/-/<!]=9*,?!!5T*!>**9-/<!_-[[!=[,.!*,9=Z[-,T!
=/!AU*+=9-./,!9+=-/-/<!8./9=89!V.+!8..+]-/=9-./!.V!9T*!9+=-/-/<!U+.<+=>W!-V!9T-,!U*+,./!-,!9.!Z*!
]-VV*+*/9!9T=/!9T*!U+.7*89!651?!!5T*+*!=+*!9_.!>=7.+!<.=[,!.V!9T-,!>**9-/<?!!C-+,9!-,!9.!.:9[-/*!9T*!
U+.<+=>!V.+!AU*+=9-./,!<-;-/<!9T*>!=];=/8*!/.9-8*!=,!9.!_T=9!_-[[!.88:+!]:+-/<!9T*!U+.<+=>?!!
5T*!,*8./]!-,!9.!=[[._!AU*+=9-./,!9T*!.UU.+9:/-9\!9.!U=+9-8-U=9*!-/!9T*!,9+:89:+*!.V!9T*!U+.<+=>!
=/]!U+.;-]*!;=[:=Z[*!-/V.+>=9-./!=Z.:9!_T*+*!9T*!9+=-/-/<!9->*!,T.:[]!Z*!V.8:,*]!9.!Z*,9!
Z*/*V-9!9T*-+!9*=>?!
• E65!,T=[[!8..+]-/=9*!,8T*]:[-/<!.V!9+=-/-/<!_-9T!AU*+=9-./,?!!@/\!,8T*]:[-/<!.+!,8T*]:[-/<!
8T=/<*,!,T=[[!Z*!]-,8:,,*]!_-9T!AU*+=9-./,!9.!*/,:+*!=;=-[=Z-[-9\!.V!U+.U*+!9*=>!>*>Z*+,?!!49!-,!
9T*!+*,U./,-Z-[-9\!.V!AU*+=9-./,!9+=-/-/<!8./9=89!9.!>=d*!,:+*!9T*!9+=-/**,!=99*/]!9T*!9+=-/-/<!
,*,,-./,!=/]!-9!-,!*bU*89*]!9T=9!9T*!9+=-/-/<!8./9=89!=/]$.+!]-,8-U[-/*!,:U*+;-,.+!Z*!U+*,*/9!=9!
9T*!Z*<-//-/<!.V!*=8T!,*,,-./!9.!=,,-,9!-/!8..+]-/=9-./!.V!9T*-+!9*=>?!!"#$%&'()*#+,+,-(7'80*3(
/0*$(+1(%*02+3'3(+,(4%%',3+5(96!
• 5T*!U+.7*89!,T=[[!Z*!=,,*,,*]!]:+-/<!]*,-</!-V!Z:-[]-/<!9.:+,!_-[[!Z*!+*c:-+*]!V.+!9T*!U+.7*89!=/]!
9T*!,U*8-V-8=9-./,!,T=[[!-/]-8=9*!9T*!+*c:-+*>*/9?!!4V!]**>*]!=UU+.U+-=9*!V.+!9T*!U+.7*89W!,9=+9-/<!
/.![=9*+!9T=/!%"!]=\,!-/!=];=/8*!.V!9T*!,8T*]:[*]!9+=-/-/<W!Z:-[]-/<!9.:+,!_-[[!Z*!<-;*/!V.+!*=8T!
1f3!]-,8-U[-/*!Z\!9T*!63JW!E65W!C2!=/]!U+.7*89!8./9+=89.+!+*U+*,*/9=9-;*,?!E->-[=+!9.!9T*!
9+=-/-/<!,*,,-./,W!-9!-,!9T*!+*,U./,-Z-[-9\!.V!AU*+=9-./,!9+=-/-/<!8./9=89!9.!>=d*!,:+*!9T*!9+=-/**,!
=99*/]!9T*!9.:+!=/]!-9!-,!*bU*89*]!9T=9!9T*!9+=-/-/<!8./9=89!=/]$.+!]-,8-U[-/*!,:U*+;-,.+!Z*!
U+*,*/9!=9!9T*!Z*<-//-/<!.V!*=8T!9.:+!9.!=,,-,9!-/!8..+]-/=9-./!.V!9T*-+!9*=>?!5.:+,!,T.:[]!Z*!
U+.;-]*]!V.+0!
o S)@I$3*8T=/-8=[!5*8T/-8-=/,!
o 2[*89+-8=[$C-+*!@[=+>!5*8T/-8-=/,!
o 6[:>Z-/<!5*8T/-8-=/,!$!6-U*!C-99*+,!!
o C-+*!6+.9*89-./!5*8T/-8-=/,!
o g:-[]-/<!I./9+.[!4/,9+:>*/9!5*8T/-8-=/,!
BA520!5T*!/:>Z*+!.V!9.:+,!+*c:-+*]!_-[[!]*U*/]!./!9T*!,-j*!=/]!8.>U[*b-9\!.V!9T*!U+.7*89?!!
C.+!*b=>U[*W![=+<*!V:[[!Z:-[]-/<!+*/.;=9-./,!>=\!+*c:-+*!:U!9.!#!9.:+,!9.!=88.>>.]=9*!=[[!
9T*!1f3!+*U+*,*/9=9-;*,!9T=9!/**]!9.!-/8[:]*]!=/]!9T*\!>=\!Z*!,8T*]:[*]!*=+[\!`4?*?!
P0%"@3a!-/!9T*!]=\!9.!=88.>>.]=9*!',9!,T-V9!U*+,.//*[!=/]$.+![=9*+!-/!9T*!]=\!]:+-/<!&/]!
,T-V9!`4?*?!%0%"63a?!!S._*;*+W!,>=[[!,-/<[*!,U=8*!U+.7*89,!>=\!/.9!+*c:-+*!=!,*U=+=9*!9.:+W!-V!
=<+**]!:U./!Z\!9T*!,9=d*T.[]*+,!9T=9!=!,\,9*>!.;*+;-*_!_=[d!]._/!-,!,:VV-8-*/9!V.+!9+=-/-/<?!
BA520!4V!9.:+,!=+*!->U[*>*/9*]W!%+]!,T-V9!U*+,.//*[!,T=[[!=99*/]!>.+/-/<!,*,,-./,W!=,!
=UU[-8=Z[*?!!5T*!AU*+=9-./,!651!_-[[!8..+]-/=9*!9T*-+!=;=-[=Z-[-9\?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! (!
!
)
!
• 4/!=]]-9-./!9.!9T*!9+=]-9-./=[!8.>U./*/9![*;*[!9+=-/-/<!.VV*+*]!Z\!9T*!8./9+=89.+,!=/]!;*/].+,W!
*=8T!,*,,-./!,T=[[!=[,.!-/8[:]*!=!X,\,9*>,Y!Z=,*]!9+=-/-/<!+*;-*_?!!5T*!]*,-</!*/<-/**+!=/]$.+!
8.>>-,,-./-/<!U+.;-]*+!,T=[[!U+.;-]*!9T-,!,\,9*>!Z=,*]!9+=-/-/<?!!@9!9T*!Z*<-//-/<!.V!*=8T!
]-,8-U[-/*!9+=-/-/<!,*,,-./W!9T*+*!_-[[!Z*!=!U+*,*/9=9-./!.V!9T*!.;*+=[[!,\,9*>!]*,-</!8./8*U9!=/]!
=!+*;-*_!.V!=UU[-8=Z[*!,\,9*>!:,-/<!,->U[-V-*]!,\,9*>!,8T*>=9-8,!`,-/<[*O[-/*!]+=_-/<,a!=/]!V[..+!
U[=/,?!
• @[9T.:<T!9+=-/-/<!+*c:-+*>*/9,!_-[[!Z*!]*9=-[*]!-/!9T*!U+.7*89!,U*8-V-8=9-./,W!>-/->:>!
*bU*89=9-./,!-/8[:]*0!
o I[=,,+..>!,*,,-./!_-9T!,\,9*>!.;*+;-*_!]-,8:,,-./,!<-;*/!Z\!9T*!*/<-/**+!.V!+*8.+]!.+!
8.>>-,,-./-/<!U+.;-]*+!*bU[=-/-/<!9T*!]*,-</!-/9*/9!=/]!.U*+=9-/<!8./8*U9,?!!4V!9T*!
U+.7*89!-,!-/8[:]*,!=!+*/.;=9-./W!]-,8:,,-./!_-[[!-/8[:]*!]*,8+-U9-./!.V!8T=/<*,!V+.>!
U+*;-.:,!8./V-<:+=9-./!=/]!.U*+=9-./?!
o C-*[]!,*,,-./!-/8[:]-/<!=!_=[dO]._/!.V!9T*!,\,9*>!9.!,T._![.8=9-./,!.V!*c:-U>*/9W!
8.>U./*/9,!=/]!]*;-8*,!+*[*;=/9!9.!9T*!,\,9*>W!=,!_*[[!=,!]*9=-[*]!*bU[=/=9-./,!.V!9T*!
*c:-U>*/9!=/]!U+.8*]:+*,!V.+!.U*+=9-/<W!=]7:,9-/<W!>=-/9=-/-/<W!9+.:Z[*,T..9-/<!=/]!
+*U=-+-/<!9T*!,\,9*>?!
o 5+=-/*+,!>:,9!Z*!_*[[!;*+,*]!-/!9T*!,\,9*>,!=/]!*c:-U>*/9!-/!_T-8T!9T*\!=+*!U+.;-]-/<!
9+=-/-/<W!=,!_*[[!=,!Z*!V=>-[-=+!_-9T!9T*!-/,9=[[=9-./!=/]!.U*+=9-./!.V!9T.,*!./!9T=9!
U=+9-8:[=+!U+.7*89?!!`4?*?!4V!V=89.+\!+*U+*,*/9=9-;*,!=+*!:,*]!V.+!*c:-U>*/9!9+=-/-/<W!Z:9!
9T*\!]-]!/.9!-/,9=[[!9T*!*c:-U>*/9W!9T*!,*,,-./!,T=[[!Z*!,:UU[*>*/9*]!Z\!=!
+*U+*,*/9=9-;*!.V!9T*!-/,9=[[-/<!8./9+=89.+?a!
o @9![*=,9!./*!,*,,-./!.V!*=8T!9+=-/-/<!8.:+,*!,T=[[!Z*!]-<-9=[[\!+*8.+]*]!V.+!A_/*+^,!:,*!
=V9*+!9T*!8.>U[*9-./!.V!9T*!9+=-/-/<!U+.<+=>?!!1*8.+]-/<!,T=[[!Z*!]./*!Z\!=!U+.V*,,-./=[!
;-]*.<+=UT*+W!T-+*]!Z\!9T*!I3?!!5T*,*!9+=-/-/<!;-]*.,!_-[[!Z*!9:+/*]!.;*+!_-9T!9T*!Af3!
].8:>*/9,!=/]!:U[.=]*]!./9.!9T*!3*+-]-=/!].8:>*/9!=+8T-;*?!
!"D"# $%+5&6)-9&>()&B-E<<0&FG>(%7-;>+<&+0)-
@,!U+*;-.:,[\!>*/9-./*]W!II!=,!_*[[!=,!9T*!.9T*+!>*>Z*+,!.V!9T*!6+.7*89!5*=>!`651,aW!_-[[!>=d*!*;*+\!
*VV.+9!9.!T=;*!=[[!.:9,9=/]-/<!U+.7*89!+*[=9*]!-,,:*,$!=[=+>,!+*,.[;*]!Z*V.+*!9T*!-/9*+->!9:+/*]!.;*+!9.!
9T*!AU*+=9-./,!9*=>?!!S._*;*+W!9T*+*!_-[[!Z*!,-9:=9-./,!_T*+*!-,,:*,!8=//.9!Z*!8.++*89*]!Z*V.+*!9T*!
JgA!=/]!9T*!U+.8*,,!Z*[._!]*,8+-Z*,!T._!9.!V=8-[-9=9*!9T*-+!+*,.[:9-./0!
• @/\!-,,:*,!9T=9!8=//.9!Z*!+*,.[;*]!Z*V.+*!9T*!JgA!_-[[!+*>=-/!9T*!+*,U./,-Z-[-9\!.V!9T*!
8./,9+:89-./!9*=>!_T*9T*+!9T*!,\,9*>!-9!U*+9=-/,!9.!-,!:/]*+<.-/<!=!UT=,*]!9:+/*]!.;*+!.+!/.9?!
• @!>=,9*+![-,9!.V!.U*/!-9*>,W!-/8[:]-/<!_.+d!9.!8.>U[*9*!-9*>,W!U:/8T![-,9!-9*>,W!1f3!-/,U*89-./!
-9*>,W!8.>>-,,-./-/<!=89-./![-,9!-9*>,!.+!=[=+>,!./!9T*!g@E!-,!8+*=9*]!9.!U+.;-]*!=!Z=,-,!.V!9T*!
+*,.[:9-./!U[=/?!
• 5T*!II!=/]!9T*!8./,9+:89-./!9*=>!_-[[!8./9-/:*!9.!_.+d!9.!+*,.[;*!9T*,*!.U*/!-9*>,!
• II!_-[[!8./]:89!+*<:[=+!>**9-/<,!_-9T!E65W!C2W!I3!=/]!AU*+=9-./,!9.!9+=8d!=/]!:U]=9*!=[[!./!9T*!
+*,.[:9-./!U+.<+*,,!
o AU*+=9-./,!,T.:[]!Z+-/<!.U*/!K.+d!A+]*+,!=/]!@[=+>,!9.!9T-,!>**9-/<!V.+!]-,8:,,-./?!
o AU*+=9-./,!,T.:[]!Z+-/<!=/\!-9*>,!.V!8./9+=89!_.+d!V.:/]!9.!9T-,!>**9-/<?!
• 5T-,!U+.8*,,!_-[[!8./9-/:*!:/9-[!=[[!-9*>,!=+*!8.++*89*]!.+!_T*/!=[[!U=+9-*,!=<+**!9T=9!-9!-,!/.!
[./<*+!Z*/*V-8-=[!9.!>**9?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! R!
!
)
!
!"D"4 2C<)&7-G<<&<<7&,)-
E65W!C2W!IIW!U+.7*89!]*,-</!9*=>!=/]!AU*+=9-./,!9*=>,!_-[[!8./]:89!=!,\,9*>!=,,*,,>*/9!./!=[[!/*_!
,\,9*>,!Z*V.+*!9:+/-/<!.;*+!9T*!+*,U./,-Z-[-9\!V.+!.U*+=9-./!=/]!>=-/9*/=/8*?!5T*!U:+U.,*!.V!9T-,!
=,,*,,>*/9!-,!9.!]*9*+>-/*!_T*9T*+!.+!/.9!9T*!,\,9*>!-,!8.>U[*9*!=/]!.U*+=9*,!U*+!9T*!U+.7*89^,!
]*,-</?!!I.>U[*9*!9+=/,V*+!.V!+*,U./,-Z-[-9\!]*U*/],!./!9T*!8./]-9-./!]*9*+>-/*]!V.+!*=8T!,\,9*>?!
6T=,-/<!=!,\,9*>,!9:+/.;*+!T*[U,!9.!+*]:8*!9T*!/:>Z*+!.V!8./,9+:89-./!.+!]*,-</!+*[=9*]!-,,:*,W!=,!_*[[!
=,!-/-9-=[!,*9!:U!=/]!U*+V.+>=/8*!=]7:,9>*/9,!9.!Z*!>=]*!Z\!AU*+=9-./,!9T=9!=+*!.V9*/!+*c:-+*]!_-9T!=!
/*_[\!-/,9=[[*]!,\,9*>?!
5T-,!=,,*,,>*/9!,T=[[!-/8[:]*!=!+*;-*_!.V!9T*!.:9,9=/]-/<!-9*>,!=VV*89-/<!.U*+=9-./W!=,!_*[[!=,!=/!
*;=[:=9-./!.V!9T*!V:/89-./=[!U*+V.+>=/8*!9*,9!+*,:[9,?!!6=+9-8:[=+!V.8:,!_-[[!Z*!./!,*c:*/8*,!.V!9T*!
9*,9-/<!9T=9!8.:[]!/.9!Z*!U*+V.+>*]!]:*!9.!,\,9*>!+*=]-/*,,!.+!,*=,./=[!8./,9+=-/9,?!
5T*+*V.+*W!=/\!,\,9*>!9T=9!-,!*-9T*+!]**>*]!,:Z,9=/9-=[[\!-/8.>U[*9*!.+!_T*+*!9T*+*!=+*!>=7.+!
c:*,9-./,!.+!8./8*+/,!+*<=+]-/<!9T*!.U*+=9-./!.V!9T=9!,\,9*>!_-[[!T=;*!-9,!9:+/.;*+!XUT=,*]Y?!!6T=,-/<!=!
,\,9*>^,!9:+/.;*+!-/;.[;*,!9+=/,V*++-/<!9T*!.U*+=9-/<!=/]!>=-/9*/=/8*!+*,U./,-Z-[-9-*,!V.+!9T=9!
U=+9-8:[=+!,\,9*>!9.!9T*!AU*+=9-./,!<+.:UW!Z:9!9T*!+*,U./,-Z-[-9\!V.+!9+.:Z[*,T..9-/<!=/]!+*U=-+!.V!9T=9!
,\,9*>!_-[[!+*>=-/!_-9T!9T*!II!9*=>!:/9-[!9T*!,\,9*>!-,!]**>*]!8.>U[*9*!=/]!.U*+=9-/<!U+.U*+[\!U*+!
]*,-</?!
49!,T.:[]!Z*!/.9*]!9T=9!=!,\,9*>!>=\!+*c:-+*!=/!=]]-9-./=[!=,,*,,>*/9!=V9*+!Z*-/<!9:+/*]!.;*+!9.!
AU*+=9-./,!-V!9T*!,\,9*>!*/8.:/9*+,!/:>*+.:,!.+![=+<*!.U*+=9-./=[!-,,:*,?!!5T*!=,,*,,>*/9!9*=>!_-[[!
+*8./;*/*!=/]!]*9*+>-/*!9T*!Z*,9!8.:+,*!.V!=89-./W!_T-8T!>=\!+*,:[9!-/!9T*!9+.:Z[*,T..9-/<!]:9-*,!
9+=/,V*++-/<!9.!9T*!II!9*=>!:/9-[!9T*!-,,:*,!=+*!+*,.[;*]?!
E**!9T*!E*89-./!'?L?&!X6T=,*]!E\,9*>!5:+/.;*+!6+.<+=>Y!Z*[._?!
!"D"A $%&@E,)&%*7-/0%,+1&%-H&&)*,3-
B.![=9*+!9T=/!'#!]=\,!-/!=];=/8*!.V!9T*!JgAW!E65!,T=[[!,8T*]:[*!=!>**9-/<!_-9T!9T*!651,!9.!]-,8:,,!9T*!
,9=9:,!.V!9T*!V=8-[-9\!=/]!T._!9T*!-/9*+->!9:+/.;*+$!UT=,*]!9:+/.;*+!U+.<+=>!_-[[!Z*!->U[*>*/9*]!V.+!
9T*!U+.7*89?!!5T*!651,!,T=[[!-/;-9*!=/\!=]]-9-./=[!+*U+*,*/9=9-;*,!V+.>!9T*-+!+*,U*89-;*!<+.:U,!9T*\!V**[!
=+*!/*8*,,=+\?!J:+-/<!9T-,!>**9-/<W!9T*!V.[[._-/<!9.U-8,!_-[[!Z*!]-,8:,,*]0!
• 1*;-*_!9T*!JgA!
• 1*;-*_!9T*!,\,9*>!=,,*,,>*/9!+*<=+]-/<!=88*U9*]!,\,9*>,!9T=9!+*c:-+*!=!UT=,*]!9:+/.;*+!
o 5T-,!-/8[:]*,!=!+*;-*_!.V!=/\!.U*/!.U*+=9-./=[!-,,:*,!V+.>!8./,9+:89-./!`U:/8T![-,9W!
8.>>-,,-./-/<W!*98?a!=/]!=/\!8:++*/9!=[=+>,!./!9T*!,\,9*>W!9.!Z*!8.++*89*]!Z\!9T*!
8./,9+:89-./!9*=>!
• II!_-[[!U+.;-]*!8./9+=89.+!8./9=89![-,9!V.+!AU*+=9-./,!=/]!I:,9.>*+!E*+;-8*!:,*!
• E9=9:,!.V!9T*!-/9*+->!9:+/.;*+!].8:>*/9=9-./!U=8d=<*!V.+!9T*!U+.7*89!
• K=++=/9-*,!=/]!U+.8*]:+*!V.+!_=++=/9\!-9*>!8.++*89-./!
• E9=9:,!.V!9T*!9+=-/-/<!U+.<+=>!
!"D"D E,)&%*7-/0%,+1&%-$(6?(3&-
A/!9T*!JgAW!E65!,T=[[!,:Z>-9!9T*!4/9*+->!5:+/.;*+!6=8d=<*!9.!AU*+=9-./,W!2SE!=/]!4Ef5!/.9-V\-/<!9T=9!
9T*!Z:-[]-/<!.U*+=9-./!=/]!>=-/9*/=/8*!+*,U./,-Z-[-9-*,!T=;*!Z**/!9+=/,V*++*]!9.!345?!
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! '"!
!
)
!
5T*!4/9*+->!5:+/.;*+!6=8d=<*!-,!]*,-</*]!9.!-/V.+>!9T*!<+.:U,!.V!345!+*,U./,-Z[*!V.+!.U*+=9-/<!9T*!
V=8-[-9\!=,!9.!9T*!8:++*/9!8./,9+:89-./!,9=9:,W!.U*/!-,,:*,!_-9T-/!9T*!V=8-[-9\!+*[=9*]!9.!9T*!U+.7*89!=/]!
=,,*>Z[*!9T*!>-/->:>!*,,*/9-=[!-/V.+>=9-./!+*c:-+*]!V.+!U+.U*+!V=8-[-9\!.U*+=9-./!=,!345!=_=-9,!9T*!
8.>U[*9-./!.V!=[[!_.+d!=/]!].8:>*/9,!*bU*89*]!U*+!9T*!8./9+=89!=,!U=+9!.V!9T*!V-/=[!Z:-[]-/<!9:+/.;*+?!!
5T*!U=8d=<*!-9,*[V!-,!=!,:>>=+\!.V!-/V.+>=9-./!_-9T!+*V*+*/8*,!9.!9T*![.8=9-./!.V!U*+9-/*/9!9:+/*]!.;*+!
].8:>*/9,?!!4/8[:]*]!-/!9T-,!U=8d=<*!_-[[!Z*0!
!
!
• @![*99*+!,9=9-/<!9T*!-/9*+->!9:+/.;*+!.V!9T*!,U=8*!=/]!,-</-V\-/<!9T*!9+=/,V*+!.V!.U*+=9-./=[!
+*,U./,-Z-[-9\!9.!345?!
• 6+*O-/9*+->!9:+/.;*+!>**9-/<!=<*/]=!=/]!,-</O-/!,T**9!
• @/!.:9[-/*!.V!=/\!,\,9*>,!9T=9!_-[[!:/]*+<.!=!UT=,*]!9:+/.;*+!U+.8*,,!`-V!+*c:-+*]a!
• M-,9-/<!.V!9T*!-/9*+->!9:+/.;*+!].8:>*/9,!=/]!9T*-+!,9=9:,!
• 5+=-/-/<!,8T*]:[*!=,!->U[*>*/9*]!
• M-,9-/<!.V!=/\!.:9,9=/]-/<!-,,:*,!.+!=[=+>,!9.!Z*!8.++*89*]!Z\!9T*!8./,9+:89-./!9*=>!
• @![-,9!.V!=[[!_=++=/9-*,!=,,.8-=9*]!_-9T!9T*!U+.7*89!-/8[:]-/<!*VV*89-;*!]=9*,!=/]!]:+=9-./!.V!
_=++=/9\!
• K=++=/9\!-9*>!8.++*89-./!U+.8*]:+*!
• I./9=89![-,9!V+.>!9T*!U+.7*89!V.+!_=++=/9\!+*U=-+!,*+;-8*?!
• !
!"D"I J*,(>-/0%,+1&%-$(6?(3&-
E65!,T=[[!,:Z>-9!=!C-/=[!5:+/.;*+!6=8d=<*!9.!AU*+=9-./,W!2SE!=/]!4Ef5!-/]-8=9-/<!9T=9!9T*!V-/=[!9:+/.;*+!
.V!9T*!V=8-[-9\!9.!345!T=,!Z**/!8.>U[*9*]?!
!
5T*!C-/=[!5:+/.;*+!6=8d=<*!-,!]*,-</*]!9.!:U]=9*!9T*!<+.:U,!.V!345!+*,U./,-Z[*!V.+!.U*+=9-/<!9T*!V=8-[-9\!
9T=9!=[[!U+.7*89!+*[=9*]!-,,:*,!T=;*!Z**/!+*,.[;*]!=/]!9T=9!=[[!-/V.+>=9-./!*bU*89*]!U*+!9T*!8./9+=89!=,!
U=+9!.V!9T*!V-/=[!Z:-[]-/<!9:+/.;*+!T=;*!Z**/!U+.;-]*]?!!5T*!U=8d=<*!-9,*[V!-,!=!,:>>=+\!.V!-/V.+>=9-./!
_-9T!+*V*+*/8*,!9.!9T*![.8=9-./!.V!U*+9-/*/9!9:+/*]!.;*+!].8:>*/9,?!!4/8[:]*]!-/!9T-,!U=8d=<*!_-[[!Z*0!
• @![*99*+!,9=9-/<!9T*!V-/=[!9:+/.;*+!.V!9T*!,U=8*W!,-</*]!Z\!9T*!-/V+=,9+:89:+*!]-+*89.+,!=/]!
J*U:9\!2b*8:9-;*!)-8*!6+*,-]*/9!
• M-,9-/<!.V!9T*!9:+/.;*+!].8:>*/9,!=/]!9T*-+!,9=9:,!
• 5+=-/-/<!,8T*]:[*!=,!->U[*>*/9*]!
• @![-,9!.V!=[[!_=++=/9-*,!=,,.8-=9*]!_-9T!9T*!U+.7*89!-/8[:]-/<!*VV*89-;*!]=9*,!=/]!]:+=9-./!.V!
_=++=/9\!
• K=++=/9\!-9*>!8.++*89-./!U+.8*]:+*!
• I./9=89![-,9!V+.>!9T*!U+.7*89!V.+!_=++=/9\!+*U=-+!,*+;-8*?!
!
!"D"K /0%,+1&%-8+607&,)()*+,-$(6?(3&<-
5T*!9:+/.;*+!].8:>*/9=9-./!U=8d=<*!-,!Z+.d*/!-/9.!9T+**!,*89-./,0!
• E:Z,9=/9-=[!I.>U[*9-./$A88:U=/8\$4/9*+->!6=8d=<*!i!5T-,!U=8d=<*!-,!+*c:-+*]!9.!Z*!8.>U[*9*]!
=9!9T*!4/9*+->!5:+/.;*+!,9=<*!.V!9T*!U+.7*89?!!@[[!].8:>*/9,![-,9*]!V.+!9T-,!U=8d=<*!T=;*!Z**/!
]**>*]!=,!9T*!/*8*,,=+\!>-/->:>!Z\!AU*+=9-./,!9.!+:/!9T*!V=8-[-9\?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! ''!
!
)
!
• 5:+/.;*+$@88*U9=/8*!6=8d=<*!i!5T-,!,*9!.V!].8:>*/9,!-,!+*c:-+*]!=9!9T*!C-/=[!5:+/.;*+!,9=<*!.V!
9T*!U+.7*89!=/]!345!T=,!=88*U9*]!9T*!,U=8*?!!49!-,!8.>U+-,*]!.V!9T*!.;*+=[[!U+.7*89!V-[*!,*9W!
-/8[:]-/<!,U*8-V-8!U*+9-/*/9!9*,9-/<!+*8.+],!=/]!;*+-V-8=9-./,!U:[[*]!.:9!V.+!*=,\!=88*,,?!
• C-/=/8-=[!I[.,*.:9!6=8d=<*!i!5T-,!U=8d=<*!-/8[:]*,!9T*!U+.7*89!V-/=/8-=[!8[.,*.:9!].8:>*/9,!/.9!
/*8*,,=+-[\!+*c:-+*]!V.+!9:+/.;*+W!Z:9!+=9T*+!V.+!345!9.!.VV-8-=[[\!8[.,*!.:9!=!U+.7*89?!!'&2"()2XZW)
TO\aONQ)ZW)UMV)ZU\Sb`Q`)ZU)VXQ)VbLUMRQL)TLM\QWW)OU`)ZW)PQUVZMUQ`)XQLQ)OW)ZUcMLPOVZMU)MUSd1!
5T*![-,9!-,!8.>U+*T*/,-;*!=/]!-/8[:]*,!-9*>,!9T=9!>=\!.+!>=\!/.9!Z*!=UU[-8=Z[*!9.!=!U=+9-8:[=+!U+.7*89?!!
5T*!63!-,!+*c:-+*]!9.!+*;-*_!9T*![-,9!_-9T!E65!9.!]*;*[.U!9T*!V-/=[!+*c:-+*>*/9,?!!E**!@UU*/]-b!J!V.+!9T*!
V:[[!].8:>*/9![-,9-/<?!
!":":"! ;&)8.(2*+;(1)%30*3&21+
E.>*!-9*>,!-]*/9-V-*]!-/!9T*!9:+/.;*+!].8:>*/9!U=8d=<*!=+*!8[*=+!=,!9.!_T=9!-,!9.!Z*!+*8*-;*]!`2?<?!
U*+>-9,W!9*,9!+*,:[9,W!8*+9-V-8=9*,W!*98?a?!!A9T*+,!>=\!+*c:-+*!V:+9T*+!]*V-/-9-./!=,!9.!_T=9!,T.:[]!Z*!
-/8[:]*]?!!g*[._!_*!8[=+-V\!=!/:>Z*+!.V!9T*!]*[-;*+=Z[*,0!
!":":"7 <(%*3=3)-*(+&=+>210()*3&2+5-11(.?@A+10-)(16+B+/(983%(C+=&%+>2*(%3.+,DE+
5gJ!
!":":"# F%)G3*()*+<&2*%-)*+;%-H32I1D+J0()3=3)-*3&21+5$;K+L+;MN6+B+/(983%(C+=&%+>2*(%3.+,DE+
I./9+=89!]+=_-/<,!=+*!U+*U=+*]!Z\!9T*!=+8T-9*89!]:+-/<!9T*!I./,9+:89-./!J.8:>*/9!`IJa!UT=,*!.V!
]*,-</?!!5T*\!=+*!9T*!]+=_-/<,!9T=9!V.+>!9T*!Z=,-,!.V!9T*!8./,9+:89-./?!5T*,*!]+=_-/<,!=+*!9.!Z*!
U+.;-]*]!]:+-/<!9T*!4/9*+->!5:+/.;*+!=,!=!,:UU[*>*/9!9.!9T*!]+=V9!=,OZ:-[9!,*9!=/]!U+.;-]*!=]]-9-./=[!
-/V.+>=9-./!9.!9T*!AU*+=9-./,!9*=>!_T-[*!9T*!V-/=[!=,OZ:-[9,!=/]!+*8.+]!]+=_-/<,!=+*!Z*-/<!8.>U[*9*]?!
!":":"O <-.?%3CI(+K3%(+;(0-%*.(2*+<@&1(&8*+P32C(%+B+/(983%(C+=&%+>2*(%3.+,DE+
5gJ!
+
!":":"Q F1RP83@*+5<&2=&%.(C6+;%-H32I1+B+/(983%(C+=&%+>2*(%3.+,DE+
!
5T*!=,OZ:-[9!`8./V.+>*]a!]+=_-/<,!=+*!U+*U=+*]!Z\!9T*!8./9+=89.+!,T._-/<!9\U-8=[[\!-/!+*]!-/dW!./O,-9*!
8T=/<*,!9.!9T*!.+-<-/=[!8./,9+:89-./!].8:>*/9,?!5T-,!,*9!.V!]+=_-/<,!]*U-89,!9T*!=89:=[!8./]-9-./,!.V!9T*!
8.>U[*9*]!8./,9+:89-./!X=,!-9!_=,!Z:-[9Y?!
J:*!9.!9T*!/=9:+*!.V!=,OZ:-[9!]+=_-/<,W!9T*\!8=//.9!Z*!8.>U[*9*]!=/]!9:+/*]!.;*+!Z\!9T*!JgA!.+!
4/9*+->!5:+/.;*+?!5T*+*V.+*W!9T*!U+.7*89!9*=>!-,!+*c:-+*]!9.!U+.;-]*!=/!-/9*+->!,*9!.V!]+=_-/<,!9T=9!
8./,-,9!.V!*-9T*+!=/!*[*89+./-8=[[\!,8=//*]!8.U\!.V!9T*!8./V.+>*]!]+=_-/<!,*9!.+!=!]+=V9!*[*89+./-8!8.U\!
V.+!:,*!Z\!AU*+=9-./,!:/9-[!9T*!+*8.+]!,*9!-,!8.>U[*9*?!!5T*,*!]+=_-/<,!=+*!9.!Z*!-/8[:]*]!_-9T!9T*!
-/9*+->!9:+/.;*+!].8:>*/9!U=8d=<*?!!C.+!V-/=[!9:+/.;*+W!9T*!8./9+=89.+,!=+*!+*c:-+*]!9.!U+.;-]*!=!
V-/=[-j*]!*[*89+./-8!8.U\!.V!9T*,*!]+=_-/<,?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! '&!
!
)
!
!":":": S9830.(2*+T31*+H3*G+$U+V8.?(%1+B+/(983%(C+=&%+>2*(%3.+,DE+
5T*!8./9+=89.+,!,T=[[!U+.;-]*!AU*+=9-./,!_-9T!=![-,9-/<!.V!=[[!+*>.;*]!*c:-U>*/9!=/]!/*_!*c:-U>*/9!
=]]*]!]:+-/<!9T*!U+.7*89?!!5T-,![-,9-/<!,T.:[]!-/8[:]*!=[[!>=-/9=-/*]!*c:-U>*/9!=,,.8-=9*]!_-9T!9T*!
U+.7*89?!!5T*![-,9!,T.:[]!-/8[:]*!U*+9-/*/9!]=9=!9T=9!_-[[!Z*!:,*]!9.!9+=8d!9T*!>=-/9*/=/8*!.V!*=8T!U-*8*!
.V!*c:-U>*/9!9T+.:<T.:9!-9,![-V*?!!E**!@UU*/]-b!2!V.+!=!,=>U[*!*c:-U>*/9![-,9?!
!":":"W M-%%-2*A+-2C+<&2*-)*+T31*+B+/(983%(C+=&%+>2*(%3.+,DE+
K=++=/9\!M-,90!5T*!_=++=/9\!-/V.+>=9-./!,T=[[!-/8[:]*!9T*!V.[[._-/<0!
• M-,9!.V!=[[!_=++=/9\!-9*>,!-/8[:]-/<!Af3!+*V*+*/8*,!V.+!U+.U*+!>=-/9*/=/8*!,.!=,!9.!>=-/9=-/!
9T*!;=[-]!_=++=/9-*,W!=,!_*[[!=,!:/=:9T.+-j*]!=89-./,!9T=9!>=\!-/;=[-]=9*!9T*!_=++=/9\?!
• K=++=/9\!,9=+9!]=9*,!=/]!]:+=9-./,!.V!Z.9T!9T*!Z:-[]-/<!_=++=/9\W!=,!_*[[!=,!-/]-;-]:=[!U-*8*,!.V!
*c:-U>*/9?!
• B=>*`,a!.V!,U*8-V-8!-/]-;-]:=[,!V+.>!9T*!I3!9.!=]>-/-,9*+!9T*!_=++=/9\!U*+-.]!
• @]>-/-,9+=9-;*!U+.8*,,!V.+!_=++=/9\!-9*>!8.++*89-./!-/8[:]-/<!-/,9+:89-./,!V.+!+*U.+9-/<!]*V*89,!
8.;*+*]!Z\!_=++=/9\!9.!9T*!I3!.+!.9T*+!=UU+.U+-=9*!8./9+=89.+!
I./9=89!M-,90!5T*!U:+U.,*!.V!9T*!8./9+=89.+!8./9=89![-,9!-,!9.!U+.;-]*!9T*!AU*+=9-./,!<+.:U!_-9T!=![-,9!.V!
U*.U[*!9.!8./9=89!-/!9T*!*;*/9!9T=9!9T*\!/**]!,:UU.+9!V+.>!9T*!-/,9=[[-/<!8./9+=89.+,!9.!=/,_*+!=!
c:*,9-./!.+!+*,.[;*!=!U+.Z[*>?!!5T*!8./9=89![-,9,!,T=[[!-/8[:]*!9T*!V.[[._-/<!-/V.+>=9-./!V.+!*=8T!8./9=89!
=9!=!>-/->:>0!
• B=>*!.V!I.>U=/\!
• B=>*!.V!I.>U=/\!1*U+*,*/9=9-;*!`,U*8-V-8!U*+,./a!
• J-+*89!6T./*!B:>Z*+!9.!1*U+*,*/9=9-;*!
• J-+*89!2>=-[!@]]+*,,!9.!1*U+*,*/9=9-;*!
• S.:+,!.V!g:,-/*,,!`4/8[:]*!=V9*+T.:+,$.VVOT.:+,!8./9=89!-/V.+>=9-./!-V!=UU[-8=Z[*a!
• E\,9*>,!=UU[-8=Z[*!9.!9T*!I.>U=/\!M-,9*]!
!":":"X F00%&4(C+,(1*32IY+FC'81*32I+-2C+P-@-2)32I+5,FP6+/(0&%*+B+/(983%(C+=&%+>2*(%3.+L+K32-@+,DE+
@9!=!>-/->:>W!=!]+=V9!5*,9-/<W!@]7:,9-/<!=/]!g=[=/8-/<!`5@ga!+*U.+9!-,!9.!Z*!-/8[:]*]!-/!9T*!-/9*+->!
9:+/.;*+!U=8d=<*?!5T-,!+*U.+9!,T=[[!Z*!U+.;-]*]!:/]*+!=!,*U=+=9*!8.;*+!V+.>!9T*!+*,9!.V!9T*!>*8T=/-8=[!
Af3!].8:>*/9=9-./?!
5T*!V-/=[!=UU+.;*]!5*,9-/<W!@]7:,9-/<!=/]!g=[=/8-/<!`5@ga!+*U.+9!-,!9.!Z*!-/8[:]*]!-/!9T*!V-/=[!9:+/.;*+!
U=8d=<*?!@<=-/W!9T-,!+*U.+9!,T=[[!Z*!U+.;-]*]!:/]*+!=!,*U=+=9*!8.;*+!V+.>!9T*!+*,9!.V!9T*!>*8T=/-8=[!
Af3!].8:>*/9=9-./?!!5T*!345!,T=[[!/.9!=88*U9!9T*!S)@I!,\,9*>,!_-9T.:9!=!8.>U[*9*]!5@g!+*U.+9!
=UU+.;*]!Z\!9T*!*/<-/**+!.V!+*8.+]?!
!":":"Z K32-@+<&..3113&232I+/(0&%*+B+/(983%(C+=&%+>2*(%3.+L+K32-@+,DE+
E**!345^,!I.>>-,,-./-/<!E9=/]=+]!V.+!=!]*V-/-9-./!.V!9T*!C-/=[!I.>>-,,-./-/<!1*U.+9?!
4/9*+->!`J+=V9a!I.>>-,,-./-/<!1*U.+9!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! '%!
!
)
!
@!]+=V9!V-/=[!8.>>-,,-./-/<!+*U.+9!,T=[[!Z*!,:Z>-99*]!9.!E65!V.+!9T*-+!+*;-*_?!!@/\!8.>>*/9,!./!9T*,*!
U=8d=<*,!_-[[!Z*!,*/9!Z=8d!9.!9T*!I.>>-,,-./-/<!6+.;-]*+W!9T+.:<T!9T*!E65W!V.+!8.++*89-./!=/]!
+*,:Z>-,,-./?!
C-/=[!I.>>-,,-./-/<!1*U.+9!
5T*!V-/=[!;*+,-./!.V!9T*!8.>>-,,-./-/<!+*U.+9!,T=[[!Z*!:U[.=]*]!-/9.!345^,!3*+-]-=/!].8:>*/9!=+8T-;*!
U+-.+!9.!9T*!V-/=[!9:+/.;*+!.V!9T*!,U=8*?!!5T-,!,T=[[!Z*!-/]-8=9*]!-/!9T*!C-/=[!5:+/.;*+!U=8d=<*?!
!":":"![ ELU1+B+/(983%(C+=&%+>2*(%3.+L+K32-@+,DE+
AU*+=9-./=[!=/]!3=-/9*/=/8*!3=/:=[,!-/8[:]*!*c:-U>*/9!,U*8-V-8=9-./,!=/]!,8T*]:[*,W!]+=_-/<,!=/]!
.;*+=[[!-/V.+>=9-./!/**]*]!9.!>=-/9=-/!-/,9=[[*]!*c:-U>*/9?!
4/9*+->!`J+=V9a!Af3!3=/:=[,!
@!]+=V9!,*9!.V!Af3!>=/:=[,!,T=[[!Z*!,:Z>-99*]!9.!9T*!C4E!]*U=+9>*/9!V.+!9T*-+!+*;-*_?!!`C.+!C4E!
+*c:-+*>*/9,!+*<=+]-/<!9T*,*!9:+/.;*+!U=8d=<*,W!,**!9T*!8:++*/9![=9*,9!+*;-,-./!.V!9T*!C4E!
XI@JfJ4F45@MlC4M2lFD4J2M4B2EY!=/]!X@1IS4)4BFlFD4J2M4B2EYa?!@/\!C4E!8.>>*/9,!./!9T*,*!
U=8d=<*,!_-[[!Z*!,*/9!Z=8d!9.!9T*!=:9T.+W!9T+.:<T!9T*!63JW!V.+!8.++*89-./!=/]!+*,:Z>-,,-./?!
C-/=[!Af3!3=/:=[,!
5T*!V-/=[!;*+,-./!.V!9T*!Af3!>=/:=[,!-,!]:*!Z*V.+*!9T*!V-+,9!]=\!.V!9+=-/-/<?!!5T*!Af3!>=/:=[,!,T=[[!Z*!
:U[.=]*]!-/9.!345^,!3*+-]-=/!].8:>*/9!=+8T-;*!V.+!AU*+=9-./,^!:,*!-/!.U*+=9-/<!9T*!Z:-[]-/<!./8*!9T*!
JgA!-,!+*=8T*]?!!@!8.U\!,T=[[!Z*!U+.;-]*]!9.!9T*!C4E!]*U=+9>*/9!V.+!+*8.+]!=/]!].8:>*/9!=+8T-;-/<!-/!
9T*!3*+-]-=/!].8:>*/9!=+8T-;*?!5T-,!,T=[[!Z*!-/]-8=9*]!-/!9T*!C-/=[!5:+/.;*+!U=8d=<*?!
!":":"!! ,%-3232I+;&)8.(2*-*3&2+$-)\-I(+B+/(983%(C+=&%+>2*(%3.+L+K32-@+,DE+
5T*!9+=-/-/<!].8:>*/9=9-./!,T=[[!Z*!9:+/*]!.;*+!=,!=!U=+9!.V!9T*!9:+/.;*+!U=8d=<*!=/]!,T=[[!-/8[:]*!9T*!
V.[[._-/<!<+.:U*]!=/]!V.+>=99*]!U*+!9T*!*b*8:9*]!9+=-/-/<!,*,,-./,0!
• 5T*!5+=-/-/<!6[=/!
• @[[!=UU+.;*]!9+=-/-/<!=<*/]=,!
• @[[!9+=-/-/<!T=/].:9!>=9*+-=[,!
• 5T*!5+=-/-/<!1*8.+]!].8:>*/9,!
• 5+=-/-/<!;-]*.,!!:,&;(*'<=+*'3(#>(?+,#&()@:6!
@!8.U\!.V!9T*!9+=-/-/<!>=9*+-=[!=/]!9+=-/-/<!;-]*.,!,T=[[!Z*!U+.;-]*]!9.!9T*!C4E!]*U=+9>*/9!V.+!+*8.+]!
=/]!].8:>*/9!=+8T-;-/<!-/!9T*!3*+-]-=/!].8:>*/9!=+8T-;*?!5T-,!,T=[[!Z*!-/]-8=9*]!-/!9T*!C-/=[!5:+/.;*+!
U=8d=<*?!
!":":"!7 $%&'()*+K3@(1+B+/(983%(C+=&%+K32-@+,DE+
6+.7*89!V-[*,!+*V*+,!9.!9T*!V.[]*+,!.V!V-[*,!8.[[*89*]!]:+-/<!9T*!U+.7*89!*b*8:9-./?!!5T*,*!V-[*,!=+*!9.!Z*!
=;=-[=Z[*!-/!9T*!*g:-[]*+!,\,9*>!V.+!V:9:+*!=88*,,!-V!+*c:-+*]?!
!":":"!# F%)G3*()*]1+/()&%C+;%-H32I1+-2C+J0()3=3)-*3&21+B+/(983%(C+=&%+K32-@+,DE+
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! '#!
!
)
!
1*8.+]!]+=_-/<,!=+*!U+*U=+*]!Z\!9T*!=+8T-9*89!=/]!+*V[*89!./O,-9*!8T=/<*,!9T*!8./9+=89.+!/.9*]!-/!9T*!
8./V.+>*]!,*9!.V!]+=_-/<,?!5T*\!=+*!.V9*/!8.>U-[*]!=,!=!,*9!.V!./O,-9*!8T=/<*,!>=]*!V.+!9T*!._/*+!U*+!
9T*!._/*+O=+8T-9*89!8./9+=89?!
J:*!9.!9T*!/=9:+*!.V!+*8.+]!]+=_-/<,W!9T*\!8=//.9!Z*!8.>U[*9*]!=/]!9:+/*]!.;*+!Z\!9T*!JgA!.+!4/9*+->!
5:+/.;*+?!5T*+*V.+*W!9T*!U+.7*89!9*=>!-,!+*c:-+*]!9.!U+.;-]*!=/!-/9*+->!,*9!.V!]+=_-/<,!9T=9!8./,-,9!.V!
=/!*[*89+./-8=[[\!,8=//*]!8.U\!.V!9T*!8./V.+>*]!]+=_-/<!,*9!V.+!:,*!Z\!AU*+=9-./,!:/9-[!9T*!+*8.+]!,*9!
-,!8.>U[*9*?!!5T*,*!]+=_-/<,!=+*!9.!Z*!-/8[:]*]!_-9T!9T*!-/9*+->!9:+/.;*+!].8:>*/9!U=8d=<*?!
J+=V9!1*8.+]!J+=_-/<!E*9!
@!]+=V9!,*9!.V!+*8.+]!]+=_-/<,!,T=[[!Z*!,:Z>-99*]!9.!9T*!C4E!]*U=+9>*/9!V.+!9T*-+!+*;-*_?!!5T*!U+.7*89!
,T=[[!,8T*]:[*!=[[!]+=_-/<!+*;-*_,!Z\!9T*!8./,9+:89-./!>=/=<*+W!8./,:[9=/9!*/<-/**+,!=/]!=+8T-9*89,!=,!
+*c:-+*]!;*+-V\-/<!=88:+=8\!=/]!8.>U[*9*/*,,!.V!]+=_-/<!-/V.+>=9-./W!U+-.+!9.!,:Z>-,,-./!9.!C4E?!!@/\!
C4E!8.>>*/9,!./!9T*,*!U=8d=<*,!_-[[!Z*!,*/9!Z=8d!9.!9T*!=:9T.+W!9T+.:<T!9T*!63JW!V.+!8.++*89-./!=/]!
+*,:Z>-,,-./?!`C.+!C4E!+*c:-+*>*/9,!+*<=+]-/<!9T*,*!9:+/.;*+!U=8d=<*,W!,**!9T*!8:++*/9![=9*,9!+*;-,-./!
.V!9T*!C4E!XI@JfJ4F45@MlC4M2lFD4J2M4B2EY!=/]!X@1IS4)4BFlFD4J2M4B2EYa?!
C-/=[!1*8.+]!J+=_-/<!E*9!
6+-.+!9.!C-/=[!5:+/.;*+W!9T*!V-/=[!+*8.+]!]+=_-/<!U=8d=<*!,T=[[!Z*!U+.;-]*]!9.!9T*!C4E!]*U=+9>*/9!V.+!
:U[.=]!-/9.!345^,!3*+-]-=/!].8:>*/9!=+8T-;*?!!5T-,!,T=[[!Z*!-/]-8=9*]!-/!9T*!C-/=[!5:+/.;*+!U=8d=<*?!
!":":"!O <&&%C32-*3&2+;%-H32I1+B+/(983%(C+=&%+K32-@+,DE+
5gJ!
!":":"!Q J8?.3**-@1+B+/(983%(C+=&%+K32-@+,DE+
6+.]:89!]=9=!,:Z>-99=[,W!,=>U[*,W!=/]!,T.U!]+=_-/<,!=+*!+*c:-+*]!U+->=+-[\!V.+!9T*!@+8T-9*89!=/]!
2/<-/**+!9.!;*+-V\!9T=9!9T*!8.++*89!U+.]:89,!_-[[!Z*!-/,9=[[*]!./!9T*!U+.7*89?!@!,T.U!]+=_-/<!-,!=!]+=_-/<!
.+!,*9!.V!]+=_-/<,!U+.]:8*]!Z\!9T*!8./9+=89.+W!,:UU[-*+W!>=/:V=89:+*+W!,:Z8./9+=89.+W!.+!V=Z+-8=9.+!
9\U-8=[[\!+*c:-+*]!V.+!U+*OV=Z+-8=9*]!8.>U./*/9,?!
5T*!9:+/.;*+!U=8d=<*!,T=[[!-/8[:]*!./[\!9T*!V-/=[!=UU+.;*]!,:Z>-99=[,!=/]!,T.U!]+=_-/<,?!!@/\!>=+d*]!
X@UU+.;*]!=,!B.9*]Y!>:,9!T=;*!9T*!=88.>U=/\-/<!/.9*,!V+.>!9T*!]*,-</*+!.V!+*8.+]?!
!":":"!: <(%*3=3)-*(+&=+E))80-2)A+P32C(%+B+/(983%(C+=&%+K32-@+,DE+
5gJ!
!":":"!W +
+
• +
• +
• +
• +
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! 'G!
!
)
!
!":":"!X JA1*(.1+U-28-@+
E**!345^,!I.>>-,,-./-/<!E9=/]=+]!V.+!=!]*V-/-9-./!.V!E\,9*>,!3=/:=[?!
J+=V9!E\,9*>,!3=/:=[!
B.![=9*+!9T=/!L"!]=\,!=V9*+!9T*!JgAW!=!]+=V9!,\,9*>,!>=/:=[!,T=[[!Z*!,:Z>-99*]!9.!II!V.+!9T*-+!+*;-*_?!!
@/\!8.>>*/9,!./!9T*,*!U=8d=<*,!_-[[!Z*!,*/9!Z=8d!9.!9T*!I.>>-,,-./-/<!6+.;-]*+W!9T+.:<T!9T*!E65W!V.+!
8.++*89-./!=/]!+*,:Z>-,,-./?!
C-/=[!E\,9*>,!3=/:=[!
B.![=9*+!9T=/!R"!]=\,!=V9*+!9T*!JgAW!9T*!V-/=[!;*+,-./!.V!9T*!,\,9*>,!>=/:=[!-,!]:*?!!5T*!,\,9*>,!>=/:=[!
,T=[[!Z*!:U[.=]*]!-/9.!345^,!3*+-]-=/!].8:>*/9!=+8T-;*!V.+!].8:>*/9!=+8T-;-/<!=/]!AU*+=9-./,!,T=[[!Z*!
/.9-V-*]!.V!-9,!:U[.=]!V.+!9T*-+!:,*?!
5".."*!8&+!"1%&")!,2,!,%+&
!"I"! L'&%()*+,-+.-=(%%(,)*&B-2C<)&7<-$+<)-E,)&%*7-/0%,-L1&%-
A/8*!=!,\,9*>!T=,!:/]*+<./*!-/9*+->!9:+/!.;*+!9.!AU*+=9-./,W!-9!-,!9T*-+!+*,U./,-Z-[-9\!9.!9+.:Z[*,T..9!
=/]!+*U=-+!=/\!/./O_=++=/9\!-,,:*,!=/]$.+!.;*+,**!9T*!+*U=-+!.V!=/\!_=++=/9\!-,,:*,!+*[=9*]!9.!9T=9!
,\,9*>?!
!"W"!"! >118(+/(1&@8*3&2+$%&)(11+=&%+JA1*(.1+^2C(%+M-%%-2*A+
5T*!U+.8*,,!V.+!8.>>:/-8=9-/<!=/]!8..+]-/=9-/<!9T*!8.++*89-./!.V!9T*,*!-,,:*,!]:+-/<!9T*!_=++=/9\!
U*+-.]!_-[[!Z*!=,!V.[[._,0!
'? AU*+=9-./,!_-[[!=,,*,,!_T*9T*+!9T*!-,,:*!-,!8./9+=89W!_=++=/9\!.+!/./O_=++=/9\!+*[=9*]!-9*>?!
• I./9+=89!K.+d!
- AU*+=9-./,!_-[[!8.>>:/-8=9*!9T*!-,,:*!9.!63J!_T.!_-[[!Z*!+*,U./,-Z[*!9.!8..+]-/=9*!
8./9+=89.+!8.++*89-./?!
• K=++=/9\!1*[=9*]!K.+d!
- AU*+=9-./,!_-[[!8./9=89!9T*!I3!=/]$.+!9T*!+*,U./,-Z[*!8./9+=89.+!]-+*89[\!9.!+*=89!=/]!
8.++*89!9T*!-,,:*?!!
- 4V!9T*!I3!-,!8./9=89*]W!9T*!I3!_-[[!V.[[._!:U!_-9T!9T*!=UU+.U+-=9*!8./9+=89.+!9.!+*;-*_!
9T*!-,,:*!=/]!,:UU.+9!9T*!+*,.[:9-./?!
- 5T*!I3$I./9+=89.+,!,T=[[!8.U\!9T*!AU*+=9-./,!`;-=!9T*!m./*!E:U*+;-,.+aW!63J!63W!C2!
M*=]!2/<-/**+!=/]!U+.7*89!V-[*!./!=[[!+*[*;=/9!8.++*,U./]*/8*?!
• B./OI./9+=89$B./OK=++=/9\!1*[=9*]!K.+d!
- AU*+=9-./,!-,!+*,U./,-Z[*!9.!+*=89!=/]!8.++*89!9T*!-,,:*?!
&TQLOVZMUWe5MUVLO\VMLW)FZc)WVZSS)MU)WZVQG!WXMbS`)UMV)`QSOd)VXQ)LQWTMUWQ)VM)OU)QPQLNQU\d)ML)\LZVZ\OS)
WZVbOVZMU1)),Ud)QPQLNQU\d)ML)\LZVZ\OS)WZVbOVZMU)\MLLQ\VZMUW)WXMbS`)]Q)ZPTSQPQUVQ`)F]Q)ZV)VQPTMLOLd)ML)
TQLPOUQUV)OW)UQ\QWWOLdG)OU`)]LMbNXV)VM)@"fW)OVVQUVZMU)OcVQL)VXQ)^MLa)ZW)\MPTSQVQ1)!4/!9T*!*;*/9!9T=9!
AU*+=9-./,!+*c:-+*,!*>*+<*/8\!,*+;-8*!V+.>!9T*!I3$8./9+=89.+,W!9T*\!,T=[[!V.[[._!9T*!U+.7*89!U+.9.8.[,!
:9-[-j-/<!9T*!I3^,!*>*+<*/8\!8./9=89![-,9?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! 'L!
!
)
!
!"I"# $M(<&B-2C<)&7-/0%,+1&%-$%+6&<<-
4V!=!,\,9*>!+*c:-+*,!=!UT=,*]!9:+/.;*+W!=,!]**>*]!/*8*,,=+\!V+.>!9T*!,\,9*>!=,,*,,>*/9!U+.8*,,W!9T*!
+*,U./,-Z-[-9\!V.+!.U*+=9-/<!=/]!>=-/9*/=/8*!V.+!9T=9!U=+9-8:[=+!,\,9*>!-,!9+=/,V*++*]!9.!9T*!AU*+=9-./,!
<+.:UW!Z:9!9T*!+*,U./,-Z-[-9\!V.+!9+.:Z[*,T..9-/<!=/]!+*U=-+!.V!9T=9!,\,9*>!_-[[!+*>=-/!_-9T!9T*!II!9*=>!
:/9-[!9T*!,\,9*>!-,!]**>*]!8.>U[*9*!=/]!.U*+=9-/<!U+.U*+[\!U*+!]*,-</?!5T-,!,*89-./!_-[[!*bU[=-/!9T*!
6T=,*]!5:+/.;*+!6+.8*,,?!
!"W"7"! >118(+/(1&@8*3&2+$%&)(11+=&%+$G-1(C+,8%2&4(%+JA1*(.1+^2C(%+M-%%-2*A+
5T*!U+.8*,,!V.+!8.>>:/-8=9-/<!=/]!8..+]-/=9-/<!9T*!8.++*89-./!.V!9T*,*!-9*>,!_-[[!Z*!=,!V.[[._,0!
'? C2!_-[[!=,,*,,!_T*9T*+!9T*!-,,:*!-,!=!8./9+=89W!_=++=/9\!.+!/./O_=++=/9\!+*[=9*]!-9*>?!
• I./9+=89!K.+d!
- C2!_-[[!8..+]-/=9*!_-9T!63J!_T.!_-[[!9T*/!Z*!+*,U./,-Z[*!9.!8..+]-/=9*!8./9+=89.+!
8.++*89-./?!
• K=++=/9\!1*[=9*]!K.+d!
- C2!_-[[!8..+]-/=9*!_-9T!63J!_T.!_-[[!9T*/!Z*!+*,U./,-Z[*!9.!8..+]-/=9*!_-9T!9T*!I3!.+!
+*,U./,-Z[*!8./9+=89.+!V.+!8.++*89-./?!AU*+=9-./,!m./*!E:U*+;-,.+!,T=[[!Z*!-/8[:]*]!-/!
9T*!8.++*,U./]*/8*?!
- 4V!9T*!I3!-,!8./9=89*]W!9T*!I3!_-[[!V.[[._!:U!_-9T!9T*!=UU+.U+-=9*!8./9+=89.+!9.!+*;-*_!
9T*!-,,:*!=/]!,:UU.+9!9T*!+*,.[:9-./?!
- 5T*!I3$I./9+=89.+,!,T=[[!8.U\!9T*!63J!63W!C2!M*=]!2/<-/**+W!AU*+=9-./,!`;-=!9T*!m./*!
E:U*+;-,.+a!=/]!U+.7*89!V-[*!./!=[[!+*[*;=/9!8.++*,U./]*/8*?!
• B./OI./9+=89$B./OK=++=/9\!1*[=9*]!K.+d!
- C2!_-[[!9+=/,V*+!_.+d!.+]*+!Z=8d!9.!AU*+=9-./,!_-9T!+*8.>>*/]*]!8.++*89-./!,9*U,?!
&TQLOVZMUWe5MUVLO\VMLW)FZc)WVZSS)MU)WZVQG!WXMbS`)UMV)`QSOd)VXQ)LQWTMUWQ)VM)OU)QPQLNQU\d)ML)\LZVZ\OS)
WZVbOVZMU1)),Ud)QPQLNQU\d)ML)\LZVZ\OS)WZVbOVZMU)\MLLQ\VZMUW)WXMbS`)]Q)ZPTSQPQUVQ`)F]Q)ZV)VQPTMLOLd)ML)
TQLPOUQUV)OW)UQ\QWWOLdG)OU`)]LMbNXV)VM)@"fW)OVVQUVZMU)OcVQL)VXQ)^MLa)ZW)\MPTSQVQ1)!4/!9T*!*;*/9!9T=9!
AU*+=9-./,!+*c:-+*,!*>*+<*/8\!,*+;-8*!V+.>!9T*!I3$8./9+=89.+,W!9T*\!,T=[[!V.[[._!9T*!U+.7*89!U+.9.8.[,!
:9-[-j-/<!9T*!I3^,!*>*+<*/8\!8./9=89![-,9?!
!"W"7"7 $G-132I+*G(+,8%2&4(%+
5T*!9+=/,V*+!.V!9+.:Z[*,T..9-/<!+*,U./,-Z-[-9-*,!.V!9T*!UT=,*]!,\,9*>,!9.!9T*!AU*+=9-./,!<+.:U!_-[[!.88:+!
=,!9T*!,\,9*>,!=+*!]**>*]!+*=]\?!!E65!_-[[!>=d*!*VV.+9,!9.!].!9T-,!-/!=,!V*_!UT=,*,!=,!U.,,-Z[*W!Z:9!9T*!
+*=]-/*,,!.V!9T*!,\,9*>,!_-[[!]-89=9*!9T*!Z+*=d.:9!=/]!9->*[-/*?!!@,!9T*!UT=,*]!,\,9*>,!=+*!8.>U[*9*]W!
E65!_-[[!8=[[!>**9-/<,!_-9T!63JW!C2W!AU*+=9-./,!=/]!I:,9.>*+!E*+;-8*W!=,!=UU[-8=Z[*W!9.!>=+d!9T*!
9:+/.;*+!.V!9T=9!,\,9*>?!!4/!9T*,*!>**9-/<,W!_*!_-[[!+*;-*_!9T*!UT=,*]!Z:-[]-/<!,\,9*>,!_-9T!=!V.8:,!./!
_T\!9T*!,\,9*>!_=,!UT=,*]W!-,,:*,!V.:/]!]:+-/<!9T*!UT=,*!U*+-.]!=/]!+*,.[:9-./,!9.!9T.,*!-,,:*,!9.!
=,,-,9!V:9:+*!9+.:Z[*,T..9-/<?!!5T-,!_-[[!=[,.!Z*!=/!.UU.+9:/-9\!V.+!AU*+=9-./,!9.!Z+-/<!:U!=/\!
.U*+=9-./=[!-,,:*,!9T*\!T=;*!*/8.:/9*+*]!_-9T!9T*!Z:-[]-/<!_T*+*!9T*!II!9*=>!>=\!=,,-,9!-/!+*,.[;-/<?!!
C.[[._-/<!9T*!9:+/.;*+!>**9-/<,W!E65!,T=[[!,:Z>-9!=]]-9-./=[!9:+/.;*+!/.9-V-8=9-./,!9.!AU*+=9-./,!
-/]-8=9-/<!9T=9!9T*!9+.:Z[*,T..9-/<!+*,U./,-Z-[-9-*,!T=;*!Z**/!9+=/,V*++*]!V.+!9T*,*!=]]-9-./=[!,\,9*>,?!
!"W"7"# JA1*(.+$%(4(2*-*34(+U-32*(2-2)(+
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! 'P!
!
)
!
@,!.V!9T*!JgAW!_-9T!9+=-/-/<!8.>U[*9*!=/]!9T*!-/9*+->!9:+/.;*+!].8:>*/9!U=8d=<*!U+.;-]*]!Z\!9T*!
8./9+=89.+,!`E**!E*89-./!'?G?P!V.+!].8:>*/9!+*c:-+*>*/9,aW!9T*!U+*;*/9=9-;*!>=-/9*/=/8*!
+*,U./,-Z-[-9-*,!Z*8.>*!345,?!!@[[!U+*;*/9=9-;*!>=-/9*/=/8*!.V!=/\!,\,9*>!-,!9T*!+*,U./,-Z-[-9\!.V!
AU*+=9-./,!+*<=+][*,,!.V!_T*9T*+!.+!/.9!9T*!,\,9*>!-,!:/]*+<.-/<!=!UT=,*]!9:+/*]!.;*+?!
!
!"I"4 $+<)@L660'(,6C-2C<)&7-G<<&<<7&,)<-
@V9*+!9T*!JgAW!9T*!U+.7*89!9*=>!T=,!9T*!.Z[-<=9-./!9.!*b*8:9*!,.>*!V.+>!.V!U.,9O.88:U=/8\!+*;-*_!./!
9T*!Z:-[]-/<!.U*+=9-./!=/]!U*+V.+>=/8*?!!J*U*/]-/<!./!9T*!,8.U*!.V!9T*!U+.7*89W!9T-,!_-[[!9=d*!./*!.V!
9_.!V.+>=9,?!
!"W"7"! P83@C32I+M-%%-2*A+/(43(H+
@UU+.b->=9*[\!'"!>./9T,!-/9.!9T*!_=++=/9\!U*+-.]W!9T*!U+.7*89!E65!_-[[!,8T*]:[*!=!Z:-[]-/<!+*;-*_!_-9T!
+*U+*,*/9=9-;*,!V+.>!9T*!63JW!C2W!AU*+=9-./,W!Z:-[]-/<!._/*+,$.88:U=/9,W!U+.7*89!*/<-/**+,W!I3!=/]!
8.>>-,,-./-/<!U+.;-]*+?!!5T-,!+*;-*_!_-[[!-/8[:]*!=!>**9-/<!=/]!=!Z:-[]-/<!_=[dO]._/!9.!=,,*,,!9T*!
V.[[._-/<!-9*>,0!
' @,,*,,>*/9!.V!9T*!8:++*/9!Z:-[]-/<!.U*+=9-./!`-/8[:]*,!+*;-*_!.V!Z:-[]-/<!_.+d!.+]*+,a!
& 1*,.[:9-./!U[=/,$,9=9:,!.V!=/\!.:9,9=/]-/<!-,,:*,!+*[=9-/<!9.!9T*!,*=,./=[!8.>>-,,-./-/<!
% @/!.UU.+9:/-9\!9.!-/9+.]:8*!/*_!_=++=/9\!+*[=9*]!-,,:*,!9T=9!T=;*!=+-,*/!,-/8*!.88:U=/8\!
J*V-8-*/8-*,!-]*/9-V-*]!9T+.:<T!9T-,!U+.8*,,!9T=9!=+*!]**>*]!9T*!+*,U./,-Z-[-9\!.V!9T*!U+.7*89W!_-[[!Z*!
8.++*89*]!Z\!9T*!U+.7*89!9*=>!=9!/.!=]]-9-./=[!*bU*/,*!9.!9T*!345?!
#"W"7"! $&1*RE))80-2)A+<&..3113&232I+
E9=+9-/<!V+.>!9T*!JgAW!9T*!I.>>-,,-./-/<!6+.;-]*+!,T=[[!.;*+,**!>./9T[\!>**9-/<,!_-9T!63JW!C2W!
AU*+=9-./,W!U+.7*89!*/<-/**+,!=/]!9T*!I3!_T*+*!9T*!V.[[._-/<!_-[[!Z*!+*;-*_*]0!
' 3./9T[\!+*U.+9,!.V!V-/]-/<,!V+.>!9+*/]!]=9=!;-=!9T*!Z:-[]-/<!=:9.>=9-./!=/]!345^,!V=:[9!
]*9*89-./!,\,9*>,!9.!]-,8:,,!-,,:*,!=/]!+*,.[:9-./,?!
& K.+d!.+]*+,!V+.>!9T*!AU*+=9-./,!9*=>!
J*V-8-*/8-*,!-]*/9-V-*]!9T+.:<T!9T-,!U+.8*,,!9T=9!=+*!]**>*]!9T*!+*,U./,-Z-[-9\!.V!9T*!U+.7*89W!_-[[!Z*!
8.++*89*]!Z\!9T*!U+.7*89!9*=>!=9!/.!=]]-9-./=[!*bU*/,*!9.!9T*!345?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! '(!
!
)
!
)"3,!"$&.%*%5"$&3.'4%)!+&
345!]*V-/*,!=!XI=U-9=[!1*/*_=[!6+.7*89Y!=,!=/\!Z:-[]-/<!+*/.;=9-./!8./,9+:89-./!U+.7*89!9T=9!X5.!g*!
J*V-/*]Y?!!5T-,!,*89-./!.V!9T*!U+.<+=>!_-[[!8.;*+!=89-;-9-*,W!]*[-;*+=Z[*,!=/]!+*c:-+*>*/9,!9.!Z*!V.[[._*]!
V.+!I=U-9=[!1*/*_=[!6+.7*89,!,U*8-V-8=[[\?!
!
E2I54AB!5A!g2!IDE5A34m2J!E434M@1!5A!5S2!E2I54AB!'0!I@645@M!61AH2I5E!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! 'R!
!
)
!
)'::,!!%%&('.&!6%&.%2,%5&'(&+3")%&3$"**,*1&;).+3<&
3.'4%)!+&
345!]*V-/*,!=!XI.>>-99**!9.!1*;-*_!EU=8*!6[=//-/<!`I1E6a!6+.7*89Y!=,!=/\!Z:-[]-/<!+*/.;=9-./!
8./,9+:89-./!U+.7*89!9T=9!X5.!g*!J*V-/*]Y?!!5T-,!,*89-./!.V!9T*!U+.<+=>!_-[[!8.;*+!=89-;-9-*,W!]*[-;*+=Z[*,!
=/]!+*c:-+*>*/9,!9.!Z*!V.[[._*]!V.+!I1E6!6+.7*89,!,U*8-V-8=[[\?!
!
E2I54AB!5A!g2!IDE5A34m2J!E434M@1!5A!5S2!E2I54AB!'0!I@645@M!61AH2I5E!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! &"!
!
)
!
:"4'.&.%3",.&'3%."!,'*+&3$0+&;:.'=<&3.'4%)!+&
345!]*V-/*,!=!X3=7.+!1*U=-+!AU*+=9-./,!`31Aa!6+.7*89Y!=,!=/\!Z:-[]-/<!+*/.;=9-./!8./,9+:89-./!U+.7*89!
9T=9!X5.!g*!J*V-/*]Y?!!5T-,!,*89-./!.V!9T*!U+.<+=>!_-[[!8.;*+!=89-;-9-*,W!]*[-;*+=Z[*,!=/]!+*c:-+*>*/9,!9.!
Z*!V.[[._*]!V.+!31A!6+.7*89,!,U*8-V-8=[[\?!
!
E2I54AB!5A!g2!IDE5A34m2J!E434M@1!5A!5S2!E2I54AB!'0!I@645@M!61AH2I5E!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! &'!
!
)
!
"33%*/,)%+&
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! &&!
!
)
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>!! &%!
!
)
!
"- !.",*,*1&3$"*&+":3$%&
5T-,!,T**9!-,!9.!Z*!V-[[*]!.:9!8.>U[*9*[\!Z\!9T*!8./9+=89.+,!=/]!+*;-*_*]!=/]!=UU+.;*]!Z\!9T*!63JW!C2!
=/]!AU*+=9-./,!U+-.+!9.!9T*!Z*<-//-/<!.V!9+=-/-/<?!!5T*!X345!5+=-/-/<!6[=/Y!V-[*!8=/!Z*!=88*,,*]!Z\!
8./9=89-/<!345^,!E\,9*>!6*+V.+>=/8*!=/]!5:+/.;*+!9*=>!=9!E65n>-9?*]:?!
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! @O'!
!
)
!
#- !.",*,*1&"1%*/"&+":3$%&
5T-,!,T**9!-,!9.!Z*!V-[[*]!.:9!8.>U[*9*[\!Z\!9T*!8./9+=89.+,!=/]!+*;-*_*]!=/]!=UU+.;*]!Z\!9T*!63JW!C2!
=/]!AU*+=9-./,!U+-.+!9.!9T*!Z*<-//-/<!.V!9+=-/-/<?!!5T*!X345!5+=-/-/<!@<*/]=Y!V-[*!8=/!Z*!=88*,,*]!Z\!
8./9=89-/<!345^,!E\,9*>!6*+V.+>=/8*!=/]!5:+/.;*+!9*=>!=9!E65n>-9?*]:?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! gO'!
!
)
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! gO&!
!
)
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! gO%!
!
)
!
)- !.",*,*1&.%)'./&+":3$%&
5T-,!8.;*+!,T**9!-,!9.!Z*!V-[[*]!.:9!8.>U[*9*[\!Z\!9T*!8./9+=89.+,!U+-.+!9.!9T*!9+=-/-/<!8.>>*/8-/<?!!5T*!
X345!5+=-/-/<!6[=/!1*8.+]Y!V-[*!8=/!Z*!=88*,,*]!Z\!8./9=89-/<!345^,!E\,9*>!6*+V.+>=/8*!=/]!5:+/.;*+!
9*=>!=9!E65n>-9?*]:?!
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! IO'!
!
)
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! IO&!
!
)
!
/- !0.*'2%.&/')0:%*!"!,'*&3")>"1%&
5T-,![-,9-/<!.V!+*c:-+*>*/9,!-,!9.!Z*!=,,*,,*]!./!=!U+.7*89!Z\!U+.7*89!Z=,-,!9.!]*9*+>-/*!_T-8T!-9*>,!=+*!
=UU[-8=Z[*?!!5T*![-,9!-,!9.!Z*!V-[[*]!.:9!8.>U[*9*[\!Z\!9T*!63J!=/]!E65!+*U+*,*/9=9-;*,!V+.>!9T*!U+.7*89!
=/]!-,!9:+/*]!.;*+!=,!U=+9!.V!9T*!4/9*+->!5:+/.;*+!6=8d=<*!=/]!9T*!C-/=[!5:+/.;*+!6=8d=<*?!!5T-,![-,9!V-[*!
8=/!Z*!=88*,,*]!Z\!8./9=89-/<!345^,!E\,9*>!6*+V.+>=/8*!=/]!5:+/.;*+!9*=>!=9!E65n>-9?*]:?!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! JO%!
!
)
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! JO#!
!
)
!
)*+,-./0!12)!'!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!345!6+.7*89!5:+/.;*+!6+.<+=>! JOG!
!
!
!
!" !#$%&'!()*+%,)*,-'&+!,*
/:#%#!#;4&<8#(3!=&%3&(6%!7$#!3'!>#!?#5#='<#?!>@!3:#!2'(3$723'$%!7(?!2'(37&(!3:#!$#8'5#?!7(?!(#A!#;4&<8#(3!7%%'2&73#?!A&3:!3:#!<$'1#23B!!/:#!
C#A!+;4&<8#(3!D&%3!&%!3'!>#!<$'5&?#?!7%!#7$=@!&(!3:#!<$'1#23!7%!<'%%&>=#!3'!7=='A!-./!3'!<$'5&?#!3:#!<$'1#23!3#78!A&3:!3:#!87&(3#(7(2#!376%!E'$!
&(%37==73&'(B!!/:#!*#8'5#?!+;4&<8#(3!D&%3!&%!3'!>#!34$(#?!'5#$!7%!<7$3!'E!3:#!.(3#$&8!/4$('5#$!072F76#B!!/:#%#!=&%3!E&=#%!27(!>#!722#%%#?!>@!
2'(3723&(6!-./G%!H@%3#8!0#$E'$87(2#!7(?!/4$('5#$!3#78!73!H0/I8&3B#?4B!
"#$!#%&'()#"*!+',*!,-)(+#!
!
! ! ! ! ! ! ! ! J'(3&(4#?!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9,!
!
!
!
"#$!#%&'()#"*!+',*!-+.,,/01!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9,!
!
!
!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9:!
!
!
!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9;!
!
!
!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9<!
!
!
!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9=!
!
!
!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9>!
!
!
!
0#).2#3!#%&'()#"*!+',*!,/)(+#!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9?!
!
!
!
"#$%&'()!*+"!,!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!-./!0$'1#23!/4$('5#$!0$'6$78! +9@!
!
MIT
Design Guidelines
Residences
Thematic Folder
May 2018
Table of Contents
1.1 Purpose
The MIT Design Standards describe specific planning and architectural requirements germane to
the design of new facilities and renovations to MIT's graduate and undergraduate residences.
They are general in their applicability and provide insight into MIT's residential life system.
These standards are not intended to take the place of a detailed architectural program for
comprehensive programmatic renewal or construction new residences.
In the undergraduate system, MIT (up to 2017) typically provides a double loaded corridor
design.
Massachusetts State standards for single bedrooms require a minimum of 80 square feet per
person and 60 square feet per person for each person in a shared bedroom to align with State
Sanitary Code.
The Massachusetts State requirements may not be an appropriate standard for evaluating MIT’s
housing capacities.
The MIT Housing space allocation (SQF) per person in singles doubles triples and quads will
exceed the MA Sanitary Code requirement of 60 square feet per person
MIT Housing Architectural Principals establish a minimum size for a single bedroom of 90 sf and
for a double bedroom of 180 sf. Below are area ranges to be used in establishing bedcount of
particular bedrooms. The ranges below are the minimum size for each room type:
In addition to the above area ranges, there are other, more subjective “Soft Factors” that exist
outside the scope of the preliminary bedroom space and fixture evaluation, which may further
limit the assignment capacity of each undergraduate residence. Examples of Soft Factors might
include:
2. Students per Head of House: Any student capacity above 375 requires the addition of a
Head of House apartment.
3. Students per Graduate Resident Tutor (GRT): This ratio should never exceed 35 students
per GRT with a comfortable range of 30-35 to ensure safe oversight of MIT students.
4. Dining Capacities: All residence halls should provide a dining hall.
In the graduate system, MIT typically provides apartment style design. Graduate apartments
include:
1. Efficiency Apartments:
4. Students per Head of House: Any student capacity above 375 requires an Associates
head of House apartment.
1. Music Practice.
2. Game Room.
3. Floor lounges.
4. Multiple meeting / study rooms.
5. Exercise Room.
6. Interior Bicycle Storage (capacity dictated by zoning ordinance).
7. Large Event Lounge.
1. Security check-in.
2. Package desk and supply storage room.
3. Rear of mailboxes are typically in this space.
Storage Rooms:
1. Furniture.
2. Cleaning supplies.
3. Note: Mechanical rooms may not be used for storage.
Refer to MIT Design Guidelines - Division 23 - Plumbing for plumbing fixture requirements.
Comply with MIT Systems Engineering Group design standards and Division 23 as required.
Thermostats:
1. Individual units.
2. Risers.
The Division of Student Life principles for network services in residential buildings include the
following:
1. Vision:
a. Network service is an essential residential utility (e.g. power, water, and heating)
that should be integrated into each building’s capital renewal plan.
b. The proportional costs incurred by IS&T to provide this utility and sustain
services as part of the overall campus network infrastructure shall be included in
each buildings capital renewal plan.
c. Due to evolving technology, this statement of principles will be reviewed
annually by a cross functioning team from IS&T, Residential Life comprised of
MIT Housing and the Office of Fraternities, Sororities, and Independent Living
Groups (FSILGs), and building resident representatives.
d. The review group, convened by IS&T, will also approve proposed changes to this
statement of principles.
a. Residents should be able to connect their personal devices to the MIT network,
including laptops, smart phones, and tablets to the extent these devices are
compatible with an enterprise class network.
b. Each residence building should have ubiquitous wireless coverage, both cellular
and Wi-Fi. Cellular coverage applies to campus buildings only.
c. Each resident should have at least 1 wired port per pillow in their residence.
Family housing units will have at least 2 wired ports per residence.
d. Network service will be provided subject to MIT’s campus network security
policies, with the expectation users will adhere to MITnet rules of use.
a. Telecom rooms will provide 24/7 cooling. UPS/Generator power and card
accessible doors with sufficient square footage for supporting networking needs
for equipment and cabling pathways. Refer to Division 27 for more information.
b. In the FSILGs, telecom rooms will adhere to the requirements of the FSILG
Network Maintenance Program of the MIT Association of Independent Living
Groups (AILG).
MIT Housing provides either a projector, screen and sound system, or monitor for television and
meeting functions in 1 or 2 meeting spaces in graduate and undergraduate residence halls.
Style and requirements are to be determined in collaboration between MIT Housing and MIT
Audio Visual.
Student Rooms:
Housing furnishes all non-family graduate housing and undergraduate bedrooms. Family
Housing apartments are typically unfurnished. Public event spaces are fully furnished in all
Housing buildings.
1. Bedrooms: Housing has standard furniture for use in all student rooms, comply with
MIT Housing standards.
2. Public and Event Spaces: Open for designer’s review or Housing standard on a project-
by-project basis.
3. Security Desks: See below.
4. Cabinets and Countertops: See below.
1. Vendor provides all laundry machines and folding tables. Internet jack is needed for each
machine.
2. Undergraduate and Non-Family Graduate Housing: Recommended ratio is 25 students
per washer / dryer pair.
3. Family Housing: Check with laundry vendor.
How a waste management system is established at the exterior of a residence, as well as within a
residence is an aspect of design that requires careful attention. Please consult with the pest
management vendor and MIT Recycling & Materials Management on setting up systems for
kitchen liquid/solid waste, composting, oil recycling, and general materials recycling.
Doorways grant access to people but also pests: the gap between a door and a door jamb should
be 1/4 of an inch or less.
Depending on the design of the cooling and heating system, these spaces can at times serve as
dark, quiet, and sheltered walkways for pests.
Prior to starting work in any residence a pest inspection of the space should be conducted, by the
pest management vendor and design team, to control or eliminate any pest and to seal any pest
access points in to the space.
After the work is concluded a follow up a pest inspection of the space should be conducted, by
the pest management vendor and design team to ensure all pest access points have been blocked
in a lasting way with suitable materials.
Focus for both inspections should be the perimeter of the room, kitchens, waste facilities
(internal, external, and the interface for both), closets, electrical systems, dropped ceilings, sewer
pipes and sewer systems, heating and cooling systems.
Purpose: To provide guidance on security system design standards for new construction.
1. Coordinate with Division 28 and the MIT IS&T Campus Safety and Security
Infrastructure Team for MIT Standard Models and Manufacturers.
2. Provide emergency power to maintain security in the event of a power outage, standby
power or emergency power as applicable.
1. Interior and exterior of all Resident Hall entry and exit doors, including roof doors, maker
spaces, security gates and roll-up doors.
2. Mechanical rooms and Tel/Data rooms.
Install card reader equipped doors in the following locations and where access control is required:
Verification card readers should be installed at security desks at a location that allows residents
with disabilities to be able to easily access card readers.
Install video door stations and video phones in the following locations:
1. Main and remote entry doors to allow for identification and approval of individuals
requesting access to Residence Halls.
2. Security gates and roll-up doors to facilitate deliveries.
3. Audio video master station at security desk.
Install panic buttons in the following locations: Please note all Panic Buttons must be approved
by MIT Campus Safety Working Group prior:
Refer to Division 28 - Electronic Safety and Security for MIT standard models and
manufacturers.
1. Security Desks: One door release button shall provide momentary unlock on the main
entry doors. A separate door release button shall provide momentary unlock on the main
entry doors and shall activate the automate door opener. [Remote entry doors equipped
with a video intercom door station shall already have on-board momentary release
buttons on the audio visual master station located at the security desk.].
2. Only install on doors with a Video Intercom door station.
1. Entry doors for one of each type of room in each Residency Hall (undergraduate singles,
doubles, triples, quad, and suites, and graduate apartments) to provide enhanced
accessibility to residence. All automatic door openers installed on doors that are also
equipped with access control shall be interfaced with the access control system to provide
the following functionality: The in-bound paddle shall be disabled when the door is in a
locked state. On valid admit where a card holder is flagged as ADA the access control
system shall automatically activate the automatic door opener. In all vestibules equipped
with access control an auto door openers having interior and exterior door sets, the
2. On Lobby entrances or locations with both interior and exterior doors, residents should be
allowed to enter through the exterior door using the handicap access button without
tapping a card, but must tap a VALID ID card to activate the card access sensor on
interior doors.
Key Control:
1. Key Type: Arrow restricted 3C keyway. 7 pin interchangeable core / key. Refer to
Appendix A: LOCKS for additional information.
2. Residences:
a. Housing uses their own key system in entry and student use spaces.
b. MIT Housing will provide cores for housing locks.
3. Dining:
Desk Design:
1. Desk heights shall allow for an unobstructed view of entry points, lobby areas, and
guests, even while sitting.
2. Design shall include lockable key storage drawers to facilitate lock-out key procedures.
3. Desk space shall allow for the installation of video monitors (see below), a desktop
computer or laptop with docking station, keyboard, mouse, analog or VOIP phones, and
the Audio Visual Intercom Master Station.
4. Space under the security desk can be used for installation of the desktop computer, and
proper ventilation and adequate leg room need to be incorporated into the design.
1. Allow for the installation of two 27 inch diagonal video monitors that cannot be viewed
by guests at the desk or personnel in the lobby area.
2. Monitor area should be easily viewed from sitting or standing position.
1. Three double port power outlets for 120W power connectivity of equipment and
computers.
2. Three Ethernet outlets for use of computer and VOIP phones.
3. One analog phone line for installation of security phone line.
Alarm System:
1. Ability to install panic button and remote door release buttons under the desktop.
2. Desk space for installation of Audio Visual Intercom Master Station.
Loading: Housing cabinets, countertops and related casework shall withstand the effects of the
following uniformly applied gravity loads and stresses without permanent deformation, excessive
deflection, or binding of drawers or doors:
Quality Standards: Interior architectural woodwork shall comply with Architectural Woodwork
Standards (AWS) by the Architectural Woodwork Institute (AWI), Architectural Woodwork
Manufacturers Association of Canada (AWMAC), and Woodwork Institute (WI). AWS
standards apply to project specifications, construction, finishing, installation, and as indicated.
1. Grade: As specified.
3.2 Construction
6. Semi-Exposed Surfaces:
Shop Finishing:
3.3 Products
Solid Surfacing:
1. Laminated Countertops and Wall Mounted Shelving: General Purpose, Grade HGS,
0.0482 inch nominal thickness.
2. Cabinets and Casework: Vertical Surface, Grade VGS, 0.0282 inch nominal thickness.
3. Melamine is not permitted for cabinet interiors, shelving, or other exposed or semi-
exposed surfaces.
Drawer Slides:
1. Typical: Accuride 3832EC, 100 pound rated, soft closing, full extension, bright
electroplate zinc finish.
2. Pullout Accessible Counters: Accuride 7434, 100 pound rated, 1.0 inch over travels,
bright electroplate zinc finish.
3. Trash Pullouts: Accuride 4034, 150 pound rated, 1.5 inch over travel, bright electroplate
zinc finish.
4. Adjustable Shelf Supports: Clear plastic support with steel pin, Richelieu #34004011 or
approved equal to meet loading requirements above.
Refer to http://www.lockingsystems.com/DownLoad%20PDFs/Arrow-Q-Series-Lever-Lock.pdf
Refer to https://www.bommer.com/ps/catalogs/BommerPSCatalog.pdf
MIT’s approach to learning is guided by the understanding that one learns best by
doing, and then by sharing what they learn with others.1 The residence halls are
anchored in this mission, and are places where peer-to-peer relations, student-faculty
engagement, and student-staff interaction have a profound effect on student
development.
"
!!"#$%$&$'()%*'+,-#.+/012'+0"+$3'+/&$&1'+04+5!,+6*&2-$%0"+71'8%9%"-1:+;'<01$#!&IJ#!
2KLLKMNOLIPPL!4QLPRPOPI!ST!0IMNQSUSVWX!+"!,SY#!+B"*#!HIZ#!/JJIQ[R\!8!ST!PNI!9RQKU!&IJS]PX!J#+*!
+
!=-$%0"-8+>$&*:+04+?%@%"A(?'-1"%"A+710A1-9##!&IJ#!,KPRSQKU!(MRIQMI!9SOQ[KPRSQX!/LLSMRKPRSQ!ST!
5SUUIVI!KQ[!%QRYI]LRPW!>SOLRQV!'TTRMI]L!4QPI]QKPRSQKUX!/5$/^!5SUUIVI!(PO[IQP!)[OMKPS]L!
4QPI]QKPRSQKUX!KQ[!,/($/^!(PO[IQP!/TTKR]L!/[_RQRLP]KPS]L!RQ!>RVNI]!)[OMKPRSQ!D,/($/FX!+BB?#!
HIZ#!NPPJ^``[]O_#URZ#O_[#I[O`NKQ[UI`"AB*`@*A+#!
A review of published student housing research, recent MIT student surveys and
housing and dining studies, and input from students, faculty, and staff across MIT have
informed these recommendations.3
I. STUDENT SPACES
The path each student takes from the entrance to his or her room is that student’s “critical
path.” How they travel through a building helps them interact with others and their
environment. Ideally each resident’s path would lead them past community-building
spaces and through hallways bustling with activity: students engaged in cooking, music
and dance rehearsals, projects under development, meetings, workouts, and games. The
spaces where such activities take place should be highly visible and easily accessible.
Ultimately, the critical path encourages peer-to-peer interaction.
Building Capacity
MIT has a goal of adding 700 new beds to the undergraduate housing system; however,
building one large residence hall for all 700 students is neither desirable nor in keeping
with the importance of fostering personal ties and building community.
*
!(SO]MIL!RQMUO[I!PNI!B0&#%"A+C-<-2%$:+;'@%')!D+B"8FX!5'$+D-1'30&#'+>23'9-$%2+E'#%A"!D+B"8FX!
5'$F+>$&*'"$+G*@%#01:+H10&<+;'<01$!D+B"8FX!E'<-1$9'"$+04+/-2%8%$%'#+5!,+;'#%*'"2'#+,3'9-$%2+
/08*'1!D+B";FX!(PO[IQP!>SOLRQV!/[YRLS]W!5SOQMRU!J]ILIQPKPRSQ!PS!PNI!-(:!7RLRPRQV!5S__RPPII!
D+B"8FX!(PO[IQP!>SOLRQV!/[YRLS]W!.]SOJ!TSMOL!LILLRSQL!D+B"8=";FX!KQ[!]IMIQP!LPO[IQP!LO]YIWL#!
Research suggested that double rooms off a corridor were an ideal housing design for
first-year student housing. This rooming type leads to increased contact among residents
and relationship building.5 Students advising on the MetX project suggested that MIT
should avoid triples as they “have a tendency to develop into a two versus one scenario.”
MIT’s newer residence halls were built with fewer singles. In Maseeh, which opened in
2011, 16% of the beds are singles, 64% are doubles, and 20% are triples and quads. In
Simmons, which opened in 2002, 45% of the beds are singles and 55% are doubles.6
Given the desire for a more efficient design, we recommend that new buildings have a
target ratio of approximately 30-40% singles and the balance as doubles, allowing most
(if not all) seniors to have a single and providing for accommodation needs. A mix of
doubles and singles housing approximately 30 residents (and a GRT apartment) would
form the residential cluster with approximately 10 single rooms and 10 double rooms per
cluster. Floors should be organized horizontally, and residents should have access to all
floors via stairways and ADA-compliant elevators.
6
!1UR_URQVX!.]IVS]W!(#!>$&*'"$+?'-1"%"A+%"+C088'A'+;'#%*'"2'+B-88#I+D3-$+D01.#J+D3-$+E0'#"K$J+
-"*+D3:#!"LP!I[#!(KQ!9]KQMRLMS^!aSLLIW=1KLLX!+B"8#!$]RQP#!J#!"@"!
8
!1UR_URQVX!.]IVS]W!(#!>$&*'"$+?'-1"%"A+%"+C088'A'+;'#%*'"2'+B-88#I+D3-$+D01.#J+D3-$+E0'#"K$J+
-"*+D3:#!"LP!I[#!(KQ!9]KQMRLMS^!aSLLIW=1KLLX!+B"8#!$]RQP#!!
;
!5'$F+>$&*'"$+G*@%#01:+H10&<+;'<01$#!5K_Z]R[VIX!2/^!2KLLKMNOLIPPL!4QLPRPOPI!ST!0IMNQSUSVW#!
%QJOZURLNI[#!J#!?!
Single 80-119 square feet 80-149 square feet 90 square feet (min.)
*Triples and quads are not a preferred rooming type; however, if the architecture
warrants a limited number of triples or quads, 90 square feet should be added per
occupant.
Furniture
Standard residence hall furniture should be used, including XL twin beds (with loftable
head- and footboards), wardrobes with drawers and a mirror, dressers incorporating three
or five drawers, and 4’ and 6’ bookshelves, all in oak finish. A couple of desk size
options should be made available to suit residents’ preferences. All desks should be in
oak finish, with multiple drawers, loft bookshelf, and drawer pedestal. The desk chair is a
Sauder upholstered armless chair.
Residents should have the flexibility to disassemble and reconfigure some of the standard
furniture. Also the building should have sufficient lockable storage space to hold unused
or unwanted furniture during the school year.
Specifications call for much of the furniture to be on casters. However student feedback
suggested that wheeled furniture may pose a hazard in certain circumstances, and wheel-
less furniture can be moved with only a little more difficulty. This matter bears additional
discussion as project development gets underway.
All bathrooms will be compliant with local, state, and federal guidelines on handicap and
gender accessibility. They will also be accessible directly by the hallways to allow for
ease in maintenance and cleaning. Ideally, each cluster will have three bathrooms to
allow for gendering based on the cluster’s preference. Standard fixtures consists of a
water closet (toilet), lavatories (sinks), and showers. Urinals are not to be used. The
student-to-toilet ratio should be 1:6 in new residence halls. This is the Massachusetts
code minimum for women, and better than the code minimum for men.
Bathrooms should allow for maximum privacy with lockable floor-to-ceiling doors on
toilets and showers that provide adequate privacy. There should be soap dispensers, hand
dryers, adequate shelving, and power outlets near sinks. In shower areas, hooks should be
installed to accommodate residents’ clothing and toiletries. If space is available, drying
areas with a bench might be considered to enhance convenience and privacy.
Food and eating are fundamental to building a positive residential experience and are
important to all students whether they live in dining dorms or cook-for-yourself
communities. Dining spaces create opportunities for socialization such as meeting a
professor over a meal, studying in a group while cooking, or hosting community
gatherings and events. MIT’s 2015 Enrolled Student Survey showed:
House Dining - There are five undergraduate residences with dining halls. These
facilities each incorporate a full kitchen and dedicated dining room. Some dining rooms
have removable furniture, which allows those spaces to be used in other community
building activities. All students who live in residences with dining halls are required to be
Cook-for-Yourself - As the name suggests, students who choose to cook for themselves
prepare their own meals in kitchens spread throughout residences without dining halls.
Kitchens help foster community, are used as social spaces, and promote healthy living
and self-reliance. In recent surveys, more than half of new students report they like to
cook often or sometimes, and nearly one third would like to learn how to cook.7
Deciding whether a new residence hall should have a dining hall or be a cook-for-
yourself community is outside the scope of this document. The design of spaces where
students eat should be considered and ultimately tailored to each community’s needs.
Dining Halls
A dining hall should incorporate a full commercial kitchen and seating for up to 75% of
the building’s total residential population, with additional space considerations for
students from cook-for-yourself communities who are on dining plans. The space should
be partitionable into smaller spaces suitable for 30-40 people, which could be used for
meals shared by affinity groups or student organizations. Furniture should not be fixed to
the floor, allowing students to reconfigure the space and enable social and academic
interactions. The furniture should be removable and stackable to allow the dining hall to
double as community-building space suitable for events.
Dining halls should have separate exterior entrances to simplify access for non-resident
and faculty diners, and for functions hosted by the community. Adequate gender-
inclusive restrooms should be located near the dining hall and accessible to all diners
without a card swipe.
Kitchens
The 2016 MetX Student Advisory Group noted that kitchens were an important part of the
residence hall living experience. All new residence halls—both dining and cook-for-
yourself—should have kitchens that incorporate a four-burner cooktop, oven, microwave,
large refrigerator with a sizeable freezer, and dishwasher. Each should have ample
counter space for ingredient preparation, and numerous cabinets for storing food, utensils,
?
!-RYRLRSQ!ST!(PO[IQP!:RTI#!C8-##+04+LMNO+/1'#39-"+B0&#%"A+>&1@':!KQ[!C8-##+04+LMLM+/1'#39'"+
B0&#%"A+>&1@':#!5K_Z]R[VIX!2/^!2KLLKMNOLIPPL!4QLPRPOPI!ST!0IMNQSUSVW#!%QJOZURLNI[#!
The ratio of kitchens to clusters should be different for dining dorms and cook-for-
yourself communities. For a dining dorm, there should be a minimum of one kitchen for
every 50 students; alternatively, three clusters could share an expanded kitchen with two
cooktops, ovens, and large refrigerators. This ratio is similar to current campus dining
dorms.
Additionally both dining and cook-for-yourself communities ideally would have “country
kitchens” that can be used as a teaching kitchen, and a place to cook with friends and to
share meals. These facilities would incorporate multiple full kitchens with the same
complement of appliances and as much preparation and storage space as cluster kitchens.
Adjacent to the kitchens would be seating for up to 50 people, which could be a multi-
purpose space. The furniture in this space would also be movable and stackable, to allow
the space to be used in other capacities.
All kitchens should be easy to clean, incorporate floor drains, and have durable
appliances that can stand up to frequent use.
In light of students’ desire to learn how to cook, where “country kitchens” are used in
both dining and cook-for-yourself communities for this purpose, local chefs could be
commissioned to teach a range of classes, from safe food-handling techniques, to basic
food preparation, to advanced cooking methods.
While security is a necessity for each residence hall, the security desk should not
dominate the entryway. Instead, the entryway should be both welcoming and
representative of the community’s culture.
A student worker desk separate from the security desk should be situated near the
entrance, adjacent to the mailboxes. Student workers should have ample space for storing
packages, small appliances (e.g., vacuum cleaners, sewing machines, irons), DVDs, video
games, and other amenities. They would also be responsible for distributing mail to
mailboxes.
An increasing number of students are athletes, artists, or musicians, with more than a
quarter of recent incoming undergraduate classes identifying as engaging in a range of
these activities. While it is recognized that some rooms should be “hard-coded” single-
function rooms (such as art studios, music rehearsal rooms, and gyms), the majority of
community-building spaces should be flexible enough to support a wide variety of
activities, from social gatherings to academic sessions—such as recitations, tutoring, and
mentoring sessions—to private meetings. Many of these spaces should be available by
reservation only, while some should be open to any residents for spontaneous use. It
should be noted that while flexibility is ideal, the ventilation, power, and AV
requirements for some of the aforementioned functions may not be interchangeable.
Additionally each cluster should have its own lounge for informal social gatherings and
Per the 2016 Met Warehouse Schematic Design Study, the average undergraduate housing
common space is 52 square feet. In keeping with the existing average, on a per-student
basis, community building space should account for approximately 45-50 square feet per
resident.
Project Spaces - The 2015 Final Report on the Institute-wide Taskforce on the Future of
MIT Education calls for a system of makerspaces that will help to hold “our educational
principles and values steady given an anchor in experiential learning and practical arts.”
The report notes, “Makerspaces are places for communities of people who have a passion
for making things, and who want to share that passion by making with others.”8
Given their community focus, makerspaces in residence halls could be ideal and should
be integrated into a building design, reinforcing the mens et manus ethos. That said,
makerspaces will add to the planning schedule and project costs given the need for space
and ventilation; hence, the design should be relatively simple. A makerspace in the
residence hall should have an appropriate scope that would not require dedicated on-site
personnel to oversee the safety and maintenance or to provide training. Consideration
should be given to security and access for residents and non-residents, and the types of
equipment in the space to ensure good air quality and overall student safety. For more
complex tools or for training, MIT’s Mobius App is available to help the students gain
access to other campus makerspaces. The new Victor and William Fung makerspace in
the Metropolitan Warehouse will be one of these options. Typical makerspace should be
large and well lit with high ceilings and appropriate ventilation. The spaces would
accommodate numerous workbenches, and lockable storage of various sizes for storing
hand tools, materials, and work in progress.
@
!!"#$%$&$'()%*'+,-#.+/012'+0"+$3'+/&$&1'+04+5!,+6*&2-$%0"+71'8%9%"-1:+;'<01$#!&IJ#!
2KLLKMNOLIPPL!4QLPRPOPI!ST!0IMNQSUSVWX!+"!,SY#!+B"*#!HIZ#!/JJIQ[R\!8!ST!PNI!9RQKU!&IJS]PX!J#*@!
!
Pathways and Corridors - The act of getting from one place to another in a residence
hall should be an educational experience for students, utilizing all aspects of the structure
and environment. The 2016 MetX Student Advisory Group noted, for example, that
location of the stairwells can “improve the flow of people through the building and help
to increase the usage of the central common areas and thus a larger sense of community
in the dormitory.” In this example, utilizing automatic fire doors would allow egress
stairwells to remain open and be more inviting. This would extend the stairs’ value
beyond simple utility and encourage socialization among floors. Even the corridors and
floors can offer work and hangout space given comfortable carpeting, furniture, and other
amenities.
One large, well-positioned exterior courtyard is preferred over multiple small, disjointed
areas. The courtyard should be closed to passersby, but with a gate that can be opened in
a way that allows the community to host outdoor events safely and securely.
Some landscaping and permanent fixtures (such as grills) should be incorporated, but
pushed to the margins of the space, leaving the majority open for flexible use. When
situating the courtyard in the context of the building itself, the designers should be
mindful of weather patterns (e.g., where does the sun rise and set), and the building’s
effect on wind in particular. Other communities’ exterior spaces are positioned in a way
that makes them very windy under certain conditions, which should be avoided.
Laundry - The 2016 MetX Student Advisory Group Report states, “Many of the
dormitory presidents that we spoke with told us that, at ratios of approximately 30
students per washer, the laundry systems present in residence halls now is inadequate for
the needs of students.” They recommend that the laundry facilities be in a convenient
location, but far enough away to minimize disturbing residents with noises and odors.
Laundry facilities should be well lit with an adequate number of machines, at a ratio of
The laundry rooms should incorporate floor drains, a slop sink, folding tables, and space
for ironing clothes. To prevent neglected loads of laundry from taking up washers or
dryers, laundry rooms should include cubby holes or baskets. Loads of laundry that have
been forgotten can be loaded into these storage areas, freeing up the machine for others to
use.
Flooring – Carpeting is suitable for corridors, common areas, and some community-
building spaces. The selected carpet should be durable, but soft enough for bare feet and
comfortable to sit on. Wall-to-wall carpeting should be avoided in residents’ rooms to
prevent against particulate contamination leading to allergic reactions.
Walls and Lighting – Walls in multi-use and academic areas should have whiteboards or
glass panels that allow users to write in marker during meetings.
The building design should incorporate large windows in key places to allow for copious
natural light to get deep into the building. All lightbulbs should be energy efficient and
easy to change. As much as possible, lights in student rooms, common spaces, and
community-building spaces should be locally controllable with dimmer switches to
permit flexible use. For the sake of sustainability, they may also be put on timers or
motion detectors but should not be controlled by remote or secured systems that require
disturbing house team members to use.
Other Utilities – Technology design should be included early in the building design
process to ensure the proper configuration of the network and power infrastructure
needed to support all specified, technology-enabled systems. Amenities such as flat panel
displays, AV systems in community-building space, online room reservation systems,
room signage displays, keyless locking systems, and perimeter security requirements
should be established up front to ensure proper design of physical requirements (e.g.,
wiring chaseways) and hardware requirements (e.g., network cabling, Wi-Fi
transmitters). Also any building systems that require network access (e.g., HVAC,
plumbing) should be incorporated in the technology design as early as possible.
At minimum the pillow-to-port ratio should be 1:1, but higher is better in the event that a
student’s Ethernet connection is malfunctioning. The WIFI signal should be strong and
even throughout the building. Additionally, care must be taken to ensure consistent and
strong cellular reception in the building to accommodate the multitude of mobile devices
In addition to these standards, each project team should evaluate and implement project
and site-specific sustainability strategies to address the following sustainable design
principles:
• Energy Efficiency
o Provide a project environmental impact statement that will include a
feasibility analysis of renewable energy potential for this project and an
assessment of this project’s anticipated greenhouse gas emissions impact.
o Evaluate passive and active design strategies to optimize energy
efficiency, including but not limited to design options for building
massing, building envelope systems, natural and mechanical ventilation
strategies, heating and cooling systems, daylighting, and lighting design.
o Coordinate the project’s measurement and verification strategy with
Campus Construction’s Systems Performance and Turnover Group, and
Systems Engineering Group.
• Water Use Reduction
o Exceed the LEED prerequisite baseline for interior water use
reduction (>20% reduction).
o Provide a feasibility study of innovative ways to reduce, track, manage,
and reuse water on site.
Each GRT apartment should be located in a student cluster, ensuring adequate oversight
and community-building among residents. Their apartments should have 300 - 450 square
feet minimum, one bedroom, one bathroom, living/dining room, and kitchen. It is
important to note that GRTs often have families with small children. They also frequently
cook and share meals with students in their cluster, so groups of up to 10 students should
fit comfortably in the GRT’s apartment.
The 2016 MIT Department of Facilities Design Standards note that facilities for support
staff should include the following:
2. Staff break rooms, which incorporate a microwave oven, room for a small
dining table and chairs, a bathroom and possibly a shower, and lockers for
storing personal belongings.
4. Storage space for MIT residence hall furniture and cleaning supplies.
Bicycle storage will comply with city ordinances, and be located
convenient to the building’s main entrance.
5. House manager’s office on the first floor, with space for meeting with
students and a glass window on the lobby to be visible by residents.
6. Area director’s office on the first floor, with space for meeting with
7. Flexible office space on the first floor for use primarily by Student Support
Services, mental health staff, or MIT Medical.
This group will consider ideal programming for new residence halls, including
sustainable design, room types and mix, capacity, dining spaces, affinity housing, house
team accommodations, social and academic spaces (such as art-making rooms, advising,
and mentoring spaces), and administrative space to support residence hall operations.
MIT has undertaken many studies in recent years to learn more about residence hall
design and usage. The group will consider these findings, consult with campus
stakeholders, and review student housing literature as a means of developing an
architectural principles document that will inform the future design of residence halls at
MIT.
Group Membership
• Suzy Nelson, Vice President and Dean for Student Life, Convener
• Matthew D. Bauer, Director of Communications and Special Assistant to the
Dean, DSL
• Lilly Chin ’17, East Campus (Proxy for Isaac B. Grosof)
• Dennis Collins, Director of Residential Life for Capital Renewal, Renovation, and
Construction, DSL
• Elizabeth Cox ’18, Baker House
• Peter Cummings, Executive Director for Administration, DSL
• Stephanie L. Eiler ’19, New House
END OF DOCUMENT
May 2018
Table of Contents
MIT Design Standards | Restrooms & Custodial Closets Thematic Folder Page 1 of 8
!
MIT Design Standards | Restrooms & Custodial Closets Thematic Folder Page 2 of 8
1. CONCEPT
The key to efficient restrooms that provide a positive experience for the user begins in the design
phase. The design team needs to focus on usage and volume as it relates to space allocation and
resources, particularly with regard to reducing wait time at peak usage. With high volume
restrooms, the supply and exhaust air should be designed to handle maximum occupancy / plus.
Restrooms must be durable and easy to clean. The trend in user behavior is a reluctance to touch
surfaces in a restroom. Due to this, we have moved towards providing battery-operated towel
dispensers and allowing for space at the restroom door for a free-standing waste receptacle.
Typical restrooms shall have a floor drain to handle overflow of water when there are plumbing
issues, and a hose bib to facilitate cleaning. Mop sinks must be located straight ahead from the
custodial closet door, not around a corner.
2. FINISHES
Flooring in restrooms should be a nonporous, hard surface, with as few grout lines or seams as is
practical for the type of flooring. In cleaning restroom floors, grout cleaning is always the most
difficult. From a safety and sustainability perspective, MIT does not use any type of caustic, acid
grout cleaners. Custodial Services has recommended that epoxy grout always be used in
restrooms on floors and walls, as it is not porous and can be cleaned more effectively. Grout
sealers are not needed for epoxy grout, and shall not be used.
Sealed / glazed ceramic or terrazzo tile for flooring is preferred. Light colors are strongly
preferred. Flooring that requires the application of floor finish is not acceptable. Vinyl or
linoleum are not acceptable. Slip resistance of floor tile shall meet or exceed ADA recommended
values.
Walls should follow the same guidelines as floors – light colors, non porous, as few seams and
grout lines as practical. Again, ceramic products are preferred and are serviceable.
Toilet partitions and urinal screens should be made of a material that can be effectively cleaned
with a minimum amount of labor. Phenolic type partitions meet the criteria of cost effective
cleaning. Stainless steel partitions are not acceptable, unless in an iconic architectural building
where stainless steel is a better fit for the architecture (i.e. Kresge Auditorium).
Countertops around sinks should also be made of material that can be cleaned cost-effectively.
The major issue with sinks / countertops is the splashing of water onto the countertops. The water
either stands idle or goes on the floor. This may be a design / installation issue. Sinks need to be
deep enough and faucets need to be designed to minimize splashing. The installer needs to make
MIT Design Standards | Restrooms & Custodial Closets Thematic Folder Page 3 of 8
sure the countertops are not installed with an angle toward the front of the countertop. MIT's
recommendation is to have a mock-up constructed and use the faucet / sink before purchase.
Floor-mounted overhead-braced solid HDPE with homogenous color throughout, 1 inch thick,
Class A fire rating and passing NFPA 286 (room corner test); The Mosaic Collection color range
by Scranton Products has been used frequently on campus. Wall brackets shall be continuous at
partitions, urinal screens and wraparound hinges. Visual gaps shall be eliminated to ensure
privacy.
Surface mounted paper towel dispensers are furnished by MIT for installation by the Contractor.
Currently MIT is using GP EnMotion paper towels. Surface mounting allows for easier
replacement of towels and replacement of a broken dispenser. In certain buildings there may be a
preference for recessed roll towel dispensers which is acceptable.
Electric hand dryers may be considered for replacing paper towels or as a supplement in addition
to paper towels, for those who do not want to use paper. For Custodial, the cleaning of hand
dryers is simple and not very time consuming. There are a number of models on the market that
control the issue water on the floor. Although water on the floor for hand dryers has never been a
major problem at MIT, there is a perception the water blown of someone’s hand could make the
floor slippery. Noise level for those outside the restrooms is a real concern as many hand dryers
produce sound levels of over 60dB.
Surface-mounted GOJO FMX-12 Foam Soap Dispenser, Dove Gray, are furnished by MIT for
installation by the Contractor. MIT is not in favor of countertop pump style soap dispensers. The
look is fine and they do save wall space, however changing soap cartridges under the counter can
be a safety issue for MIT staff. Many times the countertop is designed with a front panel that
needs to be removed, or MIT staff needs to lay on the floor to access the soap cartridge. Also
MIT Design Standards | Restrooms & Custodial Closets Thematic Folder Page 4 of 8
there are times when the countertop pumps are installed too close to the sink and the sink drain,
which leaves little room for the cartridge.
Surface mounted GP Compact Vertical Dispensers for toilet paper are furnished by MIT for
installation by the Contractor. Currently MIT is using GP coreless toilet paper. Dispensers come
in two and four roll types, which should be coordinated with building occupancy and use.
Custodial does not provide toilet seat covers. Some user groups purchase their own, and
Custodial installs. If seat covers are used, there must be space for the dispenser.
B-5806 Series by Bobrick, 1-1/4 inch diameter stainless steel grab bars with snap flange.
B-290 Series by Bobrick, glass mirror with stainless steel angle frame.
StepNpull.
B-204-3 by Bobrick, vinyl curtains with nickel-plated brass grommets every 6 inches.
B-295 by Bobrick, stainless steel shelf, above sinks and below mirrors.
B-6827 by Bobrick, surface-mounted hat and coat hook, satin-finish stainless steel.
MIT Design Standards | Restrooms & Custodial Closets Thematic Folder Page 5 of 8
3.13 Baby Changing Stations
Koala-Care, typically in handicap stalls, as applicable to anticipated building usage. Plastic units
shall be used. Stainless steel units are not acceptable.
Hose bibbs are required in each restroom, typically located under the sink counter, but easily
accessible.
4. TOILET FIXTURES
Refer to the Division 22 - Plumbing Specifications for the MIT Standard Specifications for toilet
fixtures including the following:
Sinks, toilets and seats, urinals, flush valves, mop sinks, mop bases and faucets.
Prefabricated showers, with grab bars and fold-up seat at accessible units.
For information, the following materials have been used on recent projects successfully. The use
of the particular items below is not mandatory.
Floor Tile: Unpolished 12x24 field tile, 6x12 cove base and trim including outcorners by
American Olean.
Wall Tile: Empire 7x21 porcelain stone by Crossville Inc., full-height. Include bullnosed tile and
not metal transition strips.
MIT Design Standards | Restrooms & Custodial Closets Thematic Folder Page 6 of 8
6. INTEGRATED PEST MANAGEMENT
Sewage is a common food source for roaches. Prior to starting work in any bathroom a pest
inspection of the space should be conducted by the pest management vendor, to control or
eliminate any pest and to seal any pest access points in to the space.
After the work is concluded a follow up a pest inspection of the space should be conducted, by
the pest management vendor to ensure all pest access points have been blocked in a lasting way
with suitable materials, and that any repairs to pipes have been carried out.
• Conditions of the pipes that support the bathroom (evaluate top and bottom for cracks)
• Floor drains
• Electrical systems
• Dropped ceilings
• Conditions of tiles and possible gaps between tiles and between tiles and wall mounted waste
bins
MIT Design Standards | Restrooms & Custodial Closets Thematic Folder Page 7 of 8
7. TYPICAL ELEVATIONS AND DETAILS
Refer to the attached elevations and details for the items listed above.
MIT Design Standards | Restrooms & Custodial Closets Thematic Folder Page 8 of 8
MIT
Design Standards
Signage v8.0
Thematic Folder
April 1, 2018
ϴ͘Ϭ ^ĂĨĞƚLJ^ŝŐŶƐ ϯϴ
ϴ͘ϭ ĂŶŐĞƌ,ŝŐŚsŽůƚĂŐĞ ϯϴ
ϴ͘Ϯ ĂŶŐĞƌŽŵďƵƐƟďůĞ&ƵĞů ϯϵ
ϴ͘ϯ ĂŶŐĞƌ&ĂůůWƌŽƚĞĐƟŽŶ ϰϬ
ϴ͘ϰ ĂŶŐĞƌŽŶĮŶĞĚ^ƉĂĐĞ ϰϭ
ϴ͘ϱ ĂƵƟŽŶ,ĞĂƌŝŶŐWƌŽƚĞĐƟŽŶ ϰϮ
ϴ͘ϲ tĂƌŶŝŶŐ>ŽǁKǀĞƌŚĞĂĚůĞĂƌĂŶĐĞ ϰϯ
ϴ͘ϳ EŽŶͲWŽƚĂďůĞtĂƚĞƌ ϰϰ
ϴ͘ϴ tĂƌŶŝŶŐƌĐ&ůĂƐŚΘ^ŚŽĐŬ,ĂnjĂƌĚ ϰϱ
ϴ͘ϵ tĂƌŶŝŶŐůĞĐƚƌŝĐĂůWĂŶĞůƌĞĂůĞĂƌĂŶĐĞ ϰϱ
ϵ͘Ϭ džƚĞƌŝŽƌ^ŝŐŶĂŐĞ ϰϲ
ϵ͘ϭ ƵŝůĚŝŶŐ/>ĞƩĞƌŝŶŐ ϰϲ
ϵ͘Ϯ &ŝƌĞĞƉĂƌƚŵĞŶƚŽŶŶĞĐƟŽŶ ϰϴ
ϵ͘ϯ EŽ^ŵŽŬŝŶŐ ϱϬ
&ĂĐŝůŝƟĞƐ/ŶĨŽƌŵĂƟŽŶ^LJƐƚĞŵƐ;&/^ͿŚĂƐƚŚĞƌĞƐƉŽŶƐŝďŝůŝƚLJĨŽƌŝŵƉůĞŵĞŶƟŶŐƉƌŽĐĞĚƵƌĞƐĂŶĚ
ƉŽůŝĐŝĞƐĐŽŶƚĂŝŶĞĚŝŶƚŚŝƐŵĂŶƵĂů͘ůůƌĞƋƵĞƐƚƐĨŽƌŶŽŶͲƐƚĂŶĚĂƌĚŽƌƐƉĞĐŝĂůƚLJƐŝŐŶƐĂƌĞƚŽďĞƐĞŶƚ
ƚŽ&/^ĨŽƌƌĞǀŝĞǁǁŝƚŚƚŚĞ^ŝŐŶĂŐĞŽŵŵŝƩĞĞ͘
ĂĐŚŽĨƚŚĞĨŽůůŽǁŝŶŐƐĞĐƟŽŶƐĐŽŶƚĂŝŶƐƚŚĞŵŽƐƚĞƐƐĞŶƟĂůĐƌŝƚĞƌŝĂĨŽƌƐŝŐŶĂŐĞƵƐĞŽŶƚŚĞD/d
Campus. WůĞĂƐĞƌĞĨĞƌƋƵĞƐƟŽŶƐƚŽƚŚĞWƌŽũĞĐƚDĂŶĂŐĞƌ͘
1.1 Purpose
dŽƐĞƚĂŶ/ŶƐƟƚƵƚĞͲǁŝĚĞƐƚĂŶĚĂƌĚĨŽƌďŽƚŚŝŶƚĞƌŝŽƌĂŶĚĞdžƚĞƌŝŽƌƐŝŐŶĂŐĞƚŽŐƵŝĚĞ͕ĚŝƌĞĐƚ͕
ŝŶĨŽƌŵ͕ŝĚĞŶƟĨLJĂŶĚƌĞŐƵůĂƚĞŵŽǀĞŵĞŶƚŽĨƉĞŽƉůĞĂŶĚǀĞŚŝĐůĞƐĂƚD/d͘
1.2 Policy
&/^ŚĂƐƚŚĞƌĞƐƉŽŶƐŝďŝůŝƚLJĨŽƌŝŵƉůĞŵĞŶƚĂƟŽŶ͕ĐŽŽƌĚŝŶĂƟŽŶ͕ĂŶĚŵŽŶŝƚŽƌŝŶŐŽĨƚŚĞ
ƐŝŐŶĂŐĞŐƵŝĚĞůŝŶĞƐǁŚŝĐŚĂƌĞƚŽďĞĞŵƉůŽLJĞĚĂƚD/dŽǁŶĞĚĂŶĚůĞĂƐĞĚĨĂĐŝůŝƟĞƐ͘
ϭ͘ϯ ^ŝŐŶĂŐĞŽŵŵŝƩĞĞ
KŶŽĐĐĂƐŝŽŶƐ͕ĚĞǀŝĂƟŽŶĨƌŽŵƚŚĞƐŝŐŶĂŐĞƐƚĂŶĚĂƌĚƐĂŶĚŐƵŝĚĞůŝŶĞƐŵĂLJďĞǁĂƌƌĂŶƚĞĚĚƵĞƚŽĂ
ŶƵŵďĞƌŽĨƌĞĂƐŽŶƐŽƌĐŝƌĐƵŵƐƚĂŶĐĞƐ͘,ŽǁĞǀĞƌ͕ďĞĐĂƵƐĞƚŚĞD/dĞƐŝŐŶ^ƚĂŶĚĂƌĚƐĨŽƌƐŝŐŶĂŐĞ
ǁĞƌĞĐƌĞĂƚĞĚƚŽďƌŝŶŐŚĂƌŵŽŶLJĂŶĚĐŽŶƐŝƐƚĞŶĐLJƚŽƚŚĞĐĂŵƉƵƐĂƐǁĞůůĂƐĨĂĐŝůŝƚĂƚĞƐŝŐŶĂŐĞ
ƌĞƉůŝĐĂƟŽŶ͕ĂĐŽŵŵŝƩĞĞǁĂƐĞƐƚĂďůŝƐŚĞĚƚŽƌĞǀŝĞǁĂŶLJƐŝŐŶƐƚŚĂƚĚĞǀŝĂƚĞĨƌŽŵƚŚĞƐĞƐƚĂŶĚĂƌĚƐ
and guidelines.
1.4 Procedure
͘ ůůƐŝŐŶƐůŽĐĂƚĞĚĂƚD/dĨĂĐŝůŝƟĞƐƐŚĂůůďĞĚĞƐŝŐŶĞĚĂŶĚŝŶƐƚĂůůĞĚŝŶĐŽŵƉůŝĂŶĐĞǁŝƚŚ
ƚŚĞƉŽůŝĐĞƐĂŶĚƐƉĞĐŝĮĐĂƟŽŶƐŽƵƚůŝŶĞĚŝŶƚŚĞD/d^ŝŐŶĂŐĞ^ƚĂŶĚĂƌĚƐ͘^ŝŐŶƐ
ŵƵƐƚĐŽŶĨŽƌŵƚŽƚŚĞůŽĐĂůŐŽǀĞƌŶŵĞŶƚnjŽŶŝŶŐůĂǁƐ͕ŽƌĚŝŶĂŶĐĞƐĂŶĚ
ƌĞŐƵůĂƟŽŶƐ͘
͘ &/^ǁŝůůĐŽŵƉĂƌĞĞĂĐŚŶĞǁƐŝŐŶƌĞƋƵĞƐƚǁŝƚŚƚŚĞĞƐƚĂďůŝƐŚĞĚƐƚĂŶĚĂƌĚƐĂŶĚŐƵŝĚĞůŝŶĞƐ
ƚŽĞŶƐƵƌĞĂŶ/ŶƐƟƚƵƚĞƐŝŐŶĂŐĞƐLJƐƚĞŵƚŚĂƚŝƐĐŽŶƐŝƐƚĞŶƚ͕ĂƩƌĂĐƟǀĞ͕ŝŶĨŽƌŵĂƟǀĞ͕ĂŶĚĐŽƐƚͲ
ĞīĞĐƟǀĞ͘
͘ ZĞƉůĂĐĞŵĞŶƚƐŝŐŶƐ;ŵŝƐƐŝŶŐŽƌĚĂŵĂŐĞĚͿƌĞůĂƚĞĚƚŽďƵŝůĚŝŶŐƌĞƋƵŝƌĞĚƐŝŐŶĂŐĞ
ƐŚŽƵůĚďĞƐƵďŵŝƩĞĚĂƐĂƌĞƉĂŝƌŶŽƟĮĐĂƟŽŶ͘
ϭ͘ &/^ǁŝůůƌĞǀŝĞǁƐŝŐŶĂŐĞƌĞƋƵĞƐƚƐ͘
Ϯ͘ /ĨŶĞĞĚĞĚ͕ĂƐŝƚĞǀŝƐŝƚǁŝůůďĞĐŽŶĚƵĐƚĞĚƚŽĞŶƐƵƌĞůŽĐĂƟŽŶ
ĂŶĚŵĞĂƐƵƌĞŵĞŶƚƐŽĨƌĞƋƵĞƐƚ͘/ĨŶĞĞĚĞĚ͕ƚŚĞĐƵƐƚŽŵĞƌǁŝůů
ďĞĐŽŶƚĂĐƚĞĚǁŝƚŚƋƵĞƐƟŽŶƐ͘
ϯ͘ >ĂLJŽƵƚǁŝůůďĞĐŽŵƉůĞƚĞĚĂŶĚĞŵĂŝůĞĚĨŽƌĂƉƉƌŽǀĂůĂůŽŶŐ
ǁŝƚŚƉƌŝĐĞƋƵŽƚĞŝĨƌĞƋƵĞƐƚĞĚ͘KŶĐĞĂƉƉƌŽǀĞĚ͕ƚŚĞŽƌĚĞƌ
ǁŝůůďĞƉůĂĐĞĚ͘
ϰ͘ KŶĐĞƚŚĞŽƌĚĞƌĂƌƌŝǀĞƐ͕ĂŶŝŶƐƚĂůůĂƟŽŶĚĂƚĞǁŝůůďĞƐĐŚĞĚƵůĞĚ͘
ϭ͘ /ĨƚĞŵƉŽƌĂƌLJĚĞƚŽƵƌƐŝŐŶƐĂƌĞŶĞĞĚĞĚĚƵĞƚŽĐŽŶƐƚƌƵĐƟŽŶ͕
ƌĞƋƵĞƐƚƐƐŚŽƵůĚďĞƐƵďŵŝƩĞĚŽŶĞǁĞĞŬƉƌŝŽƌƚŽĚĂƚĞ
needed.
Ϯ͘ ůĞĐƚƌŽŶŝĐŇŽŽƌƉůĂŶƐǁŝůůŶĞĞĚƚŽďĞƐƵďŵŝƩĞĚǁŝƚŚ&/^
approved room numbers for proper ADA signage and
ŵĞƌŐĞŶĐLJZŽƵƚĞŝĂŐƌĂŵƐ;Z͛ƐͿ͘
ϯ͘ ƵƐƚŽŵĞƌ/ŶĨŽƌŵĂƟŽŶŝƐƌĞƋƵŝƌĞĚŝĨŽĸĐĞůĞƩĞƌŝŶŐŝƐ
requested.
&͘ ,^ƐŚŽƵůĚďĞĐŽŶƚĂĐƚĞĚĨŽƌŝŶĨŽƌŵĂƟŽŶŽŶĂŶLJƐĂĨĞƚLJƌĞůĂƚĞĚƐŝŐŶĂŐĞŶŽƚ
ƐƉĞĐŝĮĞĚŝŶƚŚŝƐƐĞĐƟŽŶ͘dŚĞƐĞĂƌĞŵŽƐƚůLJƌĞůĂƚĞĚƚŽƚŚĞƐƉĞĐŝĮĐƌĞƐĞĂƌĐŚƚŚĂƚŵĂLJďĞ
ŽĐĐƵƌƌŝŶŐŝŶƚŚĞůĂďŝŶĐůƵĚŝŶŐƌĂĚŝĂƟŽŶ͕ďŝŽŚĂnjĂƌĚƐ͕ƵƐĞŽĨƌĞƐƉŝƌĂƚŽƌLJƉƌŽƚĞĐƟŽŶ͕
emergency response and other unique requirements. In some cases EHS provides the
ƐŝŐŶƐďƵƚƚŚĞŚŽůĚĞƌƐǁŝůůďĞƉƌŽǀŝĚĞĚďLJƚŚĞƉƌŽũĞĐƚ͘
G. Laboratory Signage
ZĞĨĞƌƚŽƚŚĞŶǀŝƌŽŶŵĞŶƚ͕,ĞĂůƚŚΘ^ĂĨĞƚLJdŚĞŵĂƟĐ&ŽůĚĞƌĨŽƌ,^ůĂďƐŝŐŶƐ͘&ƵƌƚŚĞƌ
ŝŶĨŽƌŵĂƟŽŶŶŽƚŝŶƚŚĞƐĞŐƵŝĚĞůŝŶĞƐ͕ƉůĞĂƐĞƌĞĨĞƌƚŽ͗ŚƩƉ͗ͬͬĞŚƐ͘ŵŝƚ͘ĞĚƵ
,͘ ZĞĨĞƌƚŽƚŚĞD/dĞƐŝŐŶ^ƚĂŶĚĂƌĚƐŝǀŝƐŝŽŶϮϱůĞĐƚƌŝĐĂůĨŽƌĐŽĚĞƌĞƋƵŝƌĞĚĞdžŝƚƐŝŐŶƐ͘
2.1 Typography
dŽŵĂŝŶƚĂŝŶĂĐŽŶƐŝƐƚĞŶƚŝŵĂŐĞ͕ĐŽŵƉůLJǁŝƚŚ'ƵŝĚĞůŝŶĞƐĂŶĚĨŽƌƌĞƋƵŝƌĞĚůĞŐŝďŝůŝƚLJ͕
ƚŚĞĨŽůůŽǁŝŶŐƚLJƉĞƐƚLJůĞƐŚĂǀĞďĞĞŶĐŚŽƐĞŶĨŽƌŝŶƚĞƌŝŽƌƐŝŐŶĂŐĞŽŶĐĂŵƉƵƐʹ,ĞůǀĞƟĐĂͬ
ƌŝĂůͬdŝŵĞƐEĞǁZŽŵĂŶͬZŽŵĂŶĂd
͘ ,ĞůǀĞƟĐĂEĞƵĞϱϱZŽŵĂŶ
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
1234567890.,/?&
͘ ,ĞůǀĞƟĐĂEĞƵĞϳϱŽůĚ
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
1234567890.,/?&
͘ ƌŝĂů;ZĞŐƵůĂƌͿ
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
1234567890.,/?&
͘ ƌŝĂů;ŽůĚͿ
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
1234567890.,/?&
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
1234567890.,/?&
'͘ ZŽŵĂŶĂd;ZĞŐƵůĂƌͿ
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
1234567890.,/?&
,͘ ZŽŵĂŶĂd;ŽůĚͿ
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
1234567890.,/?&
dŚĞĨŽůůŽǁŝŶŐƐLJŵďŽůƐĂŶĚŐƌĂƉŚŝĐƐƵƐĞĚŝŶƚŚŝƐƐŝŐŶĂŐĞŵĂŶƵĂůƐŚŽƵůĚĂƉƉĞĂƌƵŶŝĨŽƌŵůLJ
throughout the signage system.
MEN WOMEN
MIT Design Standards | Signage Guidelines 7
Page of 52
Ϯ͘ϯ sŝŶLJůŽŽƌ>ĞƩĞƌŝŶŐ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭͬ͟ϭЬ͟
DĂƚĞƌŝĂů͗ sŝŶLJů
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂͬƌŝĂůͬdŝŵĞƐZŽŵĂŶͬZŽŵĂŶĂ
DĞƐƐĂŐĞ͗ d
ŽůŽƌ͗ ůĂĐŬͬtŚŝƚĞͬ'ŽůĚͲsĂƌŝĞƐďLJĞƉĂƌƚŵĞŶƚ
͘ džĂŵƉůĞ
Ϯ͘ϰ ,ĂŶĚWĂŝŶƚĞĚŽŽƌ>ĞƩĞƌŝŶŐ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭͬ͟ϭЬ͟
DĂƚĞƌŝĂů͗ WĂŝŶƚ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĂŶĚ>ĞƩĞƌŝŶŐ&ŽŶƚ
DĞƐƐĂŐĞ͗ d
ŽůŽƌ͗ ůĂĐŬͬtŚŝƚĞͬ'ŽůĚ
͘ džĂŵƉůĞ
͘ ZƵůĞƐƚŽ&ŽůůŽǁ
ϭ͘ tŚĞŶƚŚĞƌĞŝƐĂĐĂƉŝƚĂůůĞƩĞƌ͕ŝŶƚŚĞďĞŐŝŶŶŝŶŐŽƌĞŶĚŽĨĂǁŽƌĚ͕
LJŽƵŵƵƐƚƵƐĞĂ͞ĐĂƉŝƚĂů͟ĚŽƚƚŽŝŶĚŝĐĂƚĞƚŚŝƐ͘
Ϯ͘ Examples:
/ĨƚŚĞƌĞĂƌĞŵŽƌĞƚŚĂŶŽŶĞĐĂƉŝƚĂůůĞƩĞƌƐ͕LJŽƵŵƵƐƚƵƐĞƚǁŽ
͞ĐĂƉŝƚĂů͟ĚŽƚƐ͘
ϯ͘ zŽƵƌŵƵƐƚƵƐĞƚŚĞ͞ŶƵŵďĞƌ͟ŝŶĚŝĐĂƚŽƌďĞĨŽƌĞǁƌŝƟŶŐĂŶƵŵďĞƌ͘
ϰ͘ /ĨƚŚĞƌĞŝƐĂůĞƩĞƌĂŌĞƌĂŶƵŵďĞƌ͕LJŽƵŵƵƐƚƵƐĞƚŚĞ͞ůĞƩĞƌ͟
ŝŶĚŝĐĂƚŽƌƚŽƐŚŽǁLJŽƵĂƌĞƐǁŝƚĐŚŝŶŐĨƌŽŵŶƵŵďĞƌƐƚŽůĞƩĞƌƐĂŐĂŝŶ͘
ϱ͘ NW22-‐410EA
zŽƵĚŽŶŽƚŶĞĞĚĂƐĞĐŽŶĚ͞ŶƵŵďĞƌ͟ŝŶĚŝĐĂƚŽƌĂŌĞƌĂĚĂƐŚ͘
͘ džĂŵƉůĞƐ
ϭ͘ tϭϲͲϭϬϯ
W16-‐103 5-‐407J
Ϯ͘ ϱͲϰϬϳ:
5-‐407J
Note: There is a 0 and a J in this room, which are the same symbol. If the
NW22-‐410EA
ϯ͘Ϯ ZŽŽŵEƵŵďĞƌ/ĚĞŶƟĮĐĂƟŽŶ^ŝŐŶƐ
/ŶƚĞƌŝŽƌƐŝŐŶƐĨŽƌŶĞǁďƵŝůĚŝŶŐƐ͕ĨƵůůLJƌĞŶŽǀĂƚĞĚďƵŝůĚŝŶŐƐ͕ŽƌĨƵůůLJƌĞŶŽǀĂƚĞĚŇŽŽƌŽĨĂ
ďƵŝůĚŝŶŐŵƵƐƚĐŽŵƉůLJǁŝƚŚĐĐĞƐƐŝďŝůŝƚLJ'ƵŝĚĞůŝŶĞƐĨŽƌƵŝůĚŝŶŐƐĂŶĚ&ĂĐŝůŝƟĞƐ
;'Ͳϰ͘ϯϬ^ŝŐŶĂŐĞͿ͘EŽƚĞ͗'ŵŽƵŶƟŶŐŚĞŝŐŚƚĂŶĚDŵŽƵŶƟŶŐŚĞŝŐŚƚƐĂƌĞ
ĚŝīĞƌĞŶƚ͘D/dĐŽŵƉůŝĞƐǁŝƚŚ'ŵŽƵŶƟŶŐŚĞŝŐŚƚǁŚŝĐŚŝƐϲϬ͟ĂďŽǀĞŇŽŽƌƚŽďŽƩŽŵŽĨ
braille.
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ Ϯ͟džϱ͟Θϱ͟džϱ͟
DĂƚĞƌŝĂů͗ /ŶũĞĐƚĞĚŵŽůĚĞĚΘůĞĂƌПШМ͟ĐƌLJůŝĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌƌĂŝƐĞĚПШЗЖ͟
DĞƐƐĂŐĞ͗ ƵŝůĚŝŶŐEƵŵďĞƌĂŶĚZŽŽŵEƵŵďĞƌ
ƌĂŝůůĞ͗ Ь͟'ƌĂĚĞϮƌĂŝƐĞĚПШЗЖ͟
ŽůŽƌ͗ ůĂĐŬʹtŚŝƚĞĐŽƉLJ
/ŶƐƚĂůů͗ ПШМ͟K^ƚĂŝŶůĞƐƐ^ƚĞĞů^ŶĂŬĞͲĞLJĞ&ĂƐƚĞŶĞƌƐ
'ůĂƐƐ/ŶƐƚĂůů͗ 'ůĂƐƐDŽƵŶƚĚƵŵŵLJƚŚĞƐĐƌĞǁƐŝŶƐŝŐŶ͕ǀŝŶLJůďĂĐŬĞƌ
DŽƵŶƟŶŐ,ĞŝŐŚƚ͗ ϱ͛ĨƌŽŵŇŽŽƌƚŽĐĞŶƚĞƌ
͘ džĂŵƉůĞƐ
ϭ͘ dŽƉWŽƌƟŽŶKŶůLJ
5"
1/16"
3/16" ϭͬϴΗƚŚŝĐŬŝŶũĞĐƚĞĚŵŽůĚĞĚ
ƐŝŐŶ
5/8"
2"
5/8" ŽƵŶƚĞƌƐƵŶŬŚŽůĞƐ
;ϭͬϴΗĚŝĂŵĞƚĞƌͿ
ϭͬϰΗ
3/16" 1/16” beveled edge
1/16"
'ƌĂĚĞϮƌĂŝůůĞ
;ƵŶĚĞƌηͿ
MIT Design Standards | Signage Guidelines 10
Page of 52
Ϯ͘ &Ƶůů^ŝŐŶǁŝƚŚ,ŽůĚĞƌ
5"
1/16"
3/16" ϭͬϴΗƚŚŝĐŬŝŶũĞĐƚĞĚŵŽůĚĞĚ
ƐŝŐŶ
5/8"
2"
5/8" ŽƵŶƚĞƌƐƵŶŬŚŽůĞƐ
;ϭͬϴΗĚŝĂŵĞƚĞƌͿ
ϭͬϰΗ
3/16" 1/16” beveled edge
1/16"
'ƌĂĚĞϮƌĂŝůůĞ
5" ;ƵŶĚĞƌηͿ
ůĞĂƌϭͬϴΗƚŚŝĐŬĂĐƌLJůŝĐ
2 7/8" ;ĞŶƚĂƐƐŚŽǁŶ
ŝŶƐŝĚĞWƌŽĮůĞͿ
Notes:
ZĂŝƐĞĚϱͬϴΗĐŽƉLJŚĞŝŐŚƚƌĂŝƐĞĚϭͬϯϮ͟Ͳ,ĞůǀĞƟĐĂZĞŐƵůĂƌΘ'ƌĂĚĞ//ƌĂŝůůĞϭͬϰ͟ĐŽƉLJŚĞŝŐŚƚƌĂŝƐĞĚϭͬϯϮ͟
WƌŽǀŝĚĞϳϬйĐŽŶƚƌĂƐƚďĞƚǁĞĞŶĮŶŝƐŚΘďĂĐŬŐƌŽƵŶĚĐŽůŽƌ͕ƌĞƋƵŝƌĞĚďLJ͕DĂƩĞ&ŝŶŝƐŚ
D/dƵƐĞƐĂĐƵƐƚŽŵĐŽůŽƌĐŚĂƌƚͲǀĞŶĚŽƌŵƵƐƚƉƌŽǀŝĚĞĂƐĂŵƉůĞŽĨĞĂĐŚĐŽůŽƌ
ϭͬϴΗK^ƚĂŝŶůĞƐƐƐƚĞĞůƐŶĂŬĞͲĞLJĞĨĂƐƚĞŶĞƌƐ͘
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϲ͟džϴ͟
DĂƚĞƌŝĂů͗ /ŶũĞĐƚĞĚŵŽůĚĞĚƉůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌƌĂŝƐĞĚПШЗЖ͟
DĞƐƐĂŐĞ͗ ƵŝůĚŝŶŐEƵŵďĞƌĂŶĚZŽŽŵEƵŵďĞƌǁŝƚŚWŝĐƚŽŐƌĂŵ;ƐͿ
ƌĂŝůůĞ͗ Ь͟'ƌĂĚĞϮƌĂŝƐĞĚПШЗЖ͟
ŽůŽƌ͗ ůĂĐŬďĂĐŬŐƌŽƵŶĚǁŝƚŚǁŚŝƚĞĐŽƉLJ
DŽƵŶƟŶŐ,ĞŝŐŚƚ͗ ϱ͛ĨƌŽŵŇŽŽƌƚŽĐĞŶƚĞƌ
1. MEN
6”
1/2”
5/8”
3/8”
1/4”
7/8”
8”
3”
7/8”
5/8”
3/8”
1/4”
3/16”
1/16”
6”
1/2”
5/8”
3/8”
1/4”
7/8”
8”
3”
7/8”
5/8”
3/8”
1/4”
3/16”
1/16”
6”
1/2”
5/8”
3/8”
1/4”
7/8”
8”
3”
7/8”
5/8”
3/8”
1/4”
3/16”
1/16”
6”
1/2”
5/8”
3/8”
1/4”
7/8”
8”
3”
7/8”
5/8”
3/8”
1/4”
3/16”
1/16”
6”
1/2”
5/8”
3/8”
1/4”
7/8”
8”
3”
7/8”
5/8”
3/8”
1/4”
3/16”
1/16”
6”
1/2”
5/8”
3/8”
1/4”
7/8”
8”
3”
7/8”
5/8”
3/8”
1/4”
3/16”
1/16”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭϭППШЕК͟džϴ͟
DĂƚĞƌŝĂů͗ ^ŝŶŐůĞͲWůLJDŽĚŝĮĞĚĐƌLJůŝĐĂŶĚůƵŵŝŶƵŵƌĂĐŬĞƚ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ
DĞƐƐĂŐĞ͗ ZŽŽŵEƵŵďĞƌ
ŽůŽƌ͗ ůĂĐŬďĂĐŬŐƌŽƵŶĚǁŝƚŚǁŚŝƚĞĐŽƉLJ
4.1 Engraved
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ sĂƌŝĞƐďLJĞƉĂƌƚŵĞŶƚϭ͟džϲͬ͟ϭЪ͟džϲͬ͟Ϯ͟džϴ͟
DĂƚĞƌŝĂů͗ WŚĞŶŽůŝĐŶŐƌĂǀŝŶŐ^ƚŽĐŬ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ sĂƌŝĞƐďLJĞƉĂƌƚŵĞŶƚ
DĞƐƐĂŐĞ͗ d
ŽůŽƌ͗ ůĂĐŬďĂĐŬŐƌŽƵŶĚǁŝƚŚǁŚŝƚĞƚĞdžƚ
,ŽůĚĞƌƐ͗ ŽůŽƌŽƉƟŽŶƐʹůĂĐŬͬ^ŝůǀĞƌͬ'ŽůĚ
DŽƵŶƚ͗ s,dĂƉĞͬsĞůĐƌŽͬ&ĂďƌŝĐWŝŶƐ
͘ džĂŵƉůĞ
1/16" two
ĐŽůŽƌƉůĂƐƟĐ
NAME HERE
beveled on
2" all four sides
ϭͬϮΗůĞƩĞƌ
height
Font:Gothic
1/8" 8"
Aluminum
2 1/16" Holder
Side View
MIT Design Standards | Signage Guidelines 21
Page of 52
4.2 Holder
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϮУШМ͟džϴСШМ͟ǁŝƚŚϮ͟džϴ͟ŝŶƐĞƌƚĂƌĞĂ;СШМ͟ŽƌĚĞƌͿ
DĂƚĞƌŝĂů͗ ПШЗЖ͟dŚŝĐŬ^ŝŶŐůĞͲWůLJDŽĚŝĮĞĚĐƌLJůŝĐͬEŽŶͲ'ůĂƌĞĐƌLJůŝĐͬ
ůĂĐŬĐƌLJůŝĐƩĂĐŚĞĚƚŽƚŽƉŽĨEŽŶͲ'ůĂƌĞWůĞdžŝСШМ͟ƚŚŝĐŬ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ Eͬ
DĞƐƐĂŐĞ͗ d
ŽůŽƌ͗ sĂƌŝĞƐďLJĞƉĂƌƚŵĞŶƚ
͘ džĂŵƉůĞ
8 3/8”
3/8”
2 5/8” 1 7/8”
3/8”
Open Window sign -‐ 2 5/8” x 8 3/8”
ϱ͘ϭ ,ĂůůǁĂLJ^ƚĂŝƌǁĞůů^ŝŐŶƐ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϳЬ͟džϭϭСШМ͟
DĂƚĞƌŝĂů͗ ^ŝŶŐůĞͲWůLJDŽĚŝĮĞĚĐƌLJůŝĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ
DŽƵŶƟŶŐ,ĞŝŐŚƚ͗ ϱ͛ĂďŽǀĞŇŽŽƌƐƵƌĨĂĐĞĂŶĚǀŝƐŝďůĞǁŚĞŶƐƚĂŝƌǁĂLJĚŽŽƌŝƐŽƉĞŶ
͘ džĂŵƉůĞ
7 1/4”
5/8”
1/2” ϭͬϭϲ͟DĂƩĞͬtŚŝƚĞDŝĐƌŽƐƵƌĨĂĐĞĚ/ŵƉĂĐƚ
ĐLJůŝĐƚǁŽůĂLJĞƌ
ϭͬϯϮ͟DĂƩĞůĂĐŬƐŝŶŐůĞƉůLJŵŽĚŝĮĞĚ
1” ĂĐƌLJůŝĐĂƩĂĐŚĞĚƚŽĨĂĐĞŽĨƐŝŐŶǁŝƚŚϯD
ŽƵďůĞͲ^ŝĚĞĚWŽůLJĞƐƚĞƌ&ŝůŵdĂƉĞ
3/8”
ϭͬϯϮ͟ůĞĂƌĂĐƌLJůŝĐĂƩĂĐŚĞĚƚŽĨĂĐĞŽĨƐŝŐŶ
1/4” ǁŝƚŚϯDŽƵďůĞͲ^ŝĚĞĚWŽůLJĞƐƚĞƌ&ŝůŵdĂƉĞ
'ƌĂĚĞ//ƌĂŝůůĞ
1/2”
5/8”
ϭͬϯϮ͟DĂƩĞůĂĐŬƐŝŶŐůĞƉůLJŵŽĚŝĮĞĚ
3/8” ĂĐƌLJůŝĐĂƩĂĐŚĞĚƚŽĨĂĐĞŽĨƐŝŐŶǁŝƚŚϯD
ŽƵďůĞͲ^ŝĚĞĚWŽůLJĞƐƚĞƌ&ŝůŵdĂƉĞ
3/4”
3/8”
11 3/8” ϭͬϯϮ͟ůĞĂƌĂĐƌLJůŝĐĂƩĂĐŚĞĚƚŽĨĂĐĞŽĨƐŝŐŶ
1/4” ǁŝƚŚϯDŽƵďůĞͲ^ŝĚĞĚWŽůLJĞƐƚĞƌ&ŝůŵdĂƉĞ
'ƌĂĚĞ//ƌĂŝůůĞ
5/8”
2 1/2”
ϭͬϯϮ͟DĂƩĞůĂĐŬƐŝŶŐůĞƉůLJŵŽĚŝĮĞĚ
ĂĐƌLJůŝĐĂƩĂĐŚĞĚƚŽĨĂĐĞŽĨƐŝŐŶǁŝƚŚϯD
ŽƵďůĞͲ^ŝĚĞĚWŽůLJĞƐƚĞƌ&ŝůŵdĂƉĞ
3/8”
ϭͬϯϮ͟ůĞĂƌĂĐƌLJůŝĐĂƩĂĐŚĞĚƚŽĨĂĐĞŽĨƐŝŐŶ
1/4” ǁŝƚŚϯDŽƵďůĞͲ^ŝĚĞĚWŽůLJĞƐƚĞƌ&ŝůŵdĂƉĞ
'ƌĂĚĞ//ƌĂŝůůĞ
5/8”
ϭͬϯϮ͟DĂƩĞůĂĐŬƐŝŶŐůĞƉůLJŵŽĚŝĮĞĚ
5/8” ĂĐƌLJůŝĐĂƩĂĐŚĞĚƚŽĨĂĐĞŽĨƐŝŐŶǁŝƚŚϯD
ŽƵďůĞͲ^ŝĚĞĚWŽůLJĞƐƚĞƌ&ŝůŵdĂƉĞ
3/8”
ϭͬϯϮ͟ůĞĂƌĂĐƌLJůŝĐĂƩĂĐŚĞĚƚŽĨĂĐĞŽĨƐŝŐŶ
1/4” ǁŝƚŚϯDŽƵďůĞͲ^ŝĚĞĚWŽůLJĞƐƚĞƌ&ŝůŵdĂƉĞ
'ƌĂĚĞ//ƌĂŝůůĞ
1/2”
DŽƵŶƚƚŽǁĂůůǁŝƚŚĨŽĂŵƚĂƉĞĂŶĚ
ĂĚŚĞƐŝǀĞĂƐƌĞƋƵŝƌĞĚ
MIT Design Standards | Signage Guidelines 23
Page of 52
ϱ͘Ϯ /ŶƐŝĚĞ^ƚĂŝƌǁĞůů^ŝŐŶƐǁŝƚŚƌĂŝůůĞ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϳПШИ͟džϱ͟
DĂƚĞƌŝĂů͗ ^ŝŶŐůĞͲWůLJDŽĚŝĮĞĚĐƌLJůŝĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ
DŽƵŶƟŶŐ,ĞŝŐŚƚ͗ ϱ͛ĂďŽǀĞŇŽŽƌƐƵƌĨĂĐĞĂŶĚǀŝƐŝďůĞǁŚĞŶƐƚĂŝƌǁĂLJĚŽŽƌŝƐŽƉĞŶ
͘ džĂŵƉůĞ
7 1/4”
3/4”
1/8'' Rowmark Bright white 3x1-204 plate
3/4”
1”
7/8”
STAIR 4 1/32'' Rowmark Matte Black 3x1-401 text attached to face of sign
with 3M Double-Sided Polyester File Tape
5”
LEVEL 1
1/32'' Rowmark Matte Black 3x1-401 text attached to face of sign
1” with 3M Double-Sided Polyester File Tape
3/8”
1/4” 1/32'' Clear acrylic Grade II Braillie
3/4”
EXIT
LEVEL 1
STAIR 4
11 1/4”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭϮ͟džϭϴУШМ͟;ϭϮ͟tdžϭϴ,ŵŝŶŝŵƵŵͿ
DĂƚĞƌŝĂů͗ ^ŝŶŐůĞͲWůLJDŽĚŝĮĞĚĐƌLJůŝĐͲŝŐŝƚĂůůLJWƌŝŶƚĞĚůĂĐŬdĞdžƚ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ;ŵŝŶŝŵƵŵůĞǀĞůŶƵŵďĞƌϱ͟ĂŶĚĐĞŶƚĞƌĞĚ͕
ŵŝŶŝŵƵŵƐƚĂŝƌŝĚĞŶƟĮĐĂƟŽŶϭПШЖ͕͟ĂůůŽƚŚĞƌĐŽƉLJϭ͟Ϳ
DŽƵŶƟŶŐ,ĞŝŐŚƚ͗ ϱ͛ĂďŽǀĞŇŽŽƌƐƵƌĨĂĐĞĂŶĚǀŝƐŝďůĞǁŚĞŶƐƚĂŝƌǁĂLJĚŽŽƌŝƐŽƉĞŶ
͘ džĂŵƉůĞ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
DĂƚĞƌŝĂů͗ ПШЕК͟EŽŶͲ'ůĂƌĞĐƌLJůŝĐďĂĐŬĞĚǁŝƚŚПШМ͟ůĂĐŬĐƌLJůŝĐǁŝƚŚŽŶĞ
side opened
ŽƌĚĞƌ͗ ПШЗЖdŚŝĐŬ^ŝŶŐůĞͲWůLJʹDŽĚŝĮĞĚĐƌLJůŝĐƩĂĐŚĞĚƚŽƚŽƉŽĨEŽŶͲ
'ůĂƌĞʹ^ƚĂŶĚĂƌĚ
ŽůŽƌƐ͗ ^ƚĂŶĚĂƌĚ'ƌĂƉŚŝƚĞ͕KƚŚĞƌĐŽůŽƌŽƉƟŽŶƐĂǀĂŝůĂďůĞ
DŽƵŶƚ͗ s,dĂƉĞͬ&ĂďƌŝĐWŝŶƐͬDĂŐŶĞƚƐ
͘ džĂŵƉůĞƐ
ϭ͘ ^ŝnjĞ͗ϰУШМ͟džϲПШМ͟ƚŽŚŽůĚĂϰПШИ͟džϱПШЖ͟ŝŶƐĞƌƚ
4 5/8”
3/8”
3/8" Graphite Border
3/8”
11 3/4”
3/8”
3/8”
ϭͬϭϲΗdŚŝĐŬEŽŶͲ'ůĂƌĞ
ĐƌLJůŝĐďĂĐŬĞĚǁŝƚŚϭͬϴΗ
dŚŝĐŬůĂĐŬĐƌLJůŝĐ
to hold 11" x 17"
ƉĂƉĞƌŝŶƐĞƌƚ
ϭͬϴΗdŚŝĐŬůĂĐŬĐƌLJůŝĐ
17 3/4”
3/8”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϲ͟džϴПШМ͟ƚŽŚŽůĚĂϲ͟džϴ͟ŝŶƐĞƌƚ
DĂƚĞƌŝĂů͗ &ŽƌŵĞĚĐůĞĂƌĂĐƌLJůŝĐ
ПШМ͟ƚŚŝĐŬĨŽƌŵĞĚĐůĞĂƌĂĐƌLJůŝĐƐŚĞĞƚ͕ƉŽůŝƐŚĂůůĞĚŐĞƐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ Eͬ
DĞƐƐĂŐĞ͗ d
ŽůŽƌ͗ ĂĐŬƐƉƌĂLJtŚŝƚĞ
/ŶƐƚĂůů͗ DŽƵŶƚĞĚƚŽǁĂůůǁŝƚŚĨŽĂŵƚĂƉĞĂŶĚƐŝůŝĐŽŶĞĂƐƌĞƋƵŝƌĞĚ
͘ džĂŵƉůĞ
6”
8 1/8”
ϳ͘ϭ ůĞĐƚƌŝĐĂůZŽŽŵEŽ^ƚŽƌĂŐĞůůŽǁĞĚ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϱ͟džϭϬ͟
DĂƚĞƌŝĂů͗ ПШЕК͟dǁŽWĂƌƚ^WůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ͕ϭ͟ĂŶĚПШЖ͟
͘ džĂŵƉůĞ
10”
3/4”
1”
1/2”
5”
1”
5/8”
1/2”
5/8”
ϳ͘Ϯ ŵĞƌŐĞŶĐLJůĞĐƚƌŝĐĂůZŽŽŵEŽ^ƚŽƌĂŐĞůůŽǁĞĚ
ϱ͟,yϭϬ͟tͲŽƉLJϭ͟ΘϭͬϮ͕͟,ĞůǀĞƟĐĂZĞŐƵůĂƌ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϱ͟džϭϰПШЖ͟
DĂƚĞƌŝĂů͗ ПШЕК͟dǁŽWĂƌƚ^WůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ͕ϭ͟ĂŶĚПШЖ͟
͘ džĂŵƉůĞ
14 1/2”
3/4”
1”
1/2”
5”
1”
5/8”
1/2”
5/8”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭϭ͟džϮϬ͟
DĂƚĞƌŝĂů͗ ПШЕК͟dǁŽWĂƌƚ^WůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ͕Ϯ͟ĂŶĚϭПШИ͟
͘ džĂŵƉůĞ
20”
3/4”
2”
3/4”
2”
11”
3/4”
2”
3/4”
1 1/4”
3/4”
MIT Design Standards | Signage Guidelines 31
Page of 52
ϳ͘ϰ ůĞǀĂƚŽƌDĂĐŚŝŶĞZŽŽŵEŽ^ƚŽƌĂŐĞůůŽǁĞĚ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϱ͟džϭϯ͟
DĂƚĞƌŝĂů͗ ПШЕК͟dǁŽWĂƌƚ^WůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ͕ϭ͟ĂŶĚСШИ͟
͘ džĂŵƉůĞ
13”
1/2”
1”
1/2”
5”
1”
3/4”
3/4”
1/2”
ϳ͘ϱ EŽ^ƚŽƌĂŐĞůůŽǁĞĚ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ Ϯ͟,ŝŐŚdžϭϯ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ПШЕК͟dǁŽWĂƌƚ^WůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ͕СШИ͟
͘ džĂŵƉůĞ
13”
5/8”
2” 3/4”
5/8”
2”x13” Arial Bold 3/4”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϯ͟,ŝŐŚdžϭϮ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ПШЕК͟dǁŽWĂƌƚ^WůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ͕ПШЖ͟
͘ džĂŵƉůĞ
12”
3/4”
1/2”
3”
1/2”
1/2”
3/4”
ϯΗŚŝŐŚdžϭϮǁŝĚĞĐŽƉLJϭͬϮ͕͟,ĞůǀĞƟĐĂZĞŐƵůĂƌ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϱ͟,ŝŐŚdžϭϲ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ПШЕК͟dǁŽWĂƌƚ^WůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ͕ϭПШИ͟
͘ džĂŵƉůĞ
16”
7/8”
1 1/4”
5” 3/4”
1 1/4”
7/8”
5” high x 16", 1 1/4” copy
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϱ͟,ŝŐŚdžϭϬПШЖ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ПШЕК͟dǁŽWĂƌƚ^WůĂƐƟĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌ͕СШИ͟
ŽƌĚĞƌ^ƚƌŝƉĞ͗ ПШЕК͕͟ŝŶƐĞƚПШИ͟
͘ džĂŵƉůĞ
10 1/2”
15/16”
3/4”
3/8”
5” 3/4”
1/2”
3/4”
15/16”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϲ͟džϭϬПШЖ͟
DĂƚĞƌŝĂů͗ ПШМdŚŝĐŬŶŽŶͲŐůĂƌĞĂĐƌLJůŝĐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌͬŽůĚ͕УШМ͟ĂŶĚϭСШМ͟
ŽƌĚĞƌ^ƚƌŝƉĞ͗ ПШМ͕͟ŝŶƐĞƚСШЕК͟
͘ džĂŵƉůĞ
10 1/2”
ϯͬϭϲ͟
ϭͬϴ͟
ϯͬϴ͟
ϱͬϴ͟
ϱͬϴ͟
ϭϯͬϴ͟
6”
ϱͬϴ͟
ϭϯͬϴ͟
ϯͬϴ͟
ϭͬϴ͟
ϯͬϭϲ͟
6”x 10 1/2” Engraved Sign
ZĞĚĂĐŬŐƌŽƵŶĚǁŝƚŚtŚŝƚĞ,ĞůǀĞƟĐĂZĞŐƵůĂƌΘŽůĚ͕ϱͬϴ͟Θϭϯͬϴ͞ĐŽƉLJĂŶĚϭͬϴ͟ďŽƌĚĞƌƐƚƌŝƉ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϱ͟džϱ͟
DĂƚĞƌŝĂů͗ СШЕК͟ĐůĞĂƌĂĐƌLJůŝĐǁŝƚŚƌĞǀĞƌƐĞƉƌŝŶƚĞĚďůĂĐŬƚĞdžƚ
ǁŚŝƚĞďĂĐŬŐƌŽƵŶĚ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐĞŶƚĞƌĞĚ͕СШМ͟
DĞƐƐĂŐĞ͗ d
͘ džĂŵƉůĞ
5”
1 3/16”
3/8”
1/4”
3/8”
5” 1/4”
3/8”
3/8”
5/8”
1 3/16”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭϭСШИt͟džϱ͟,;ϲ͟tdžϱ͟,ĂƐƐĞŵďůĞĚͿ
DĂƚĞƌŝĂů͗ ПШЗЖ͟WŽůLJƐƚƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂŽůĚ͕ПШЖ͟
DŽƵŶƟŶŐ,ĞŝŐŚƚ͗ ϳПШЖ͛ĂďŽǀĞŇŽŽƌǁŝƚŚϭ͛ĞdžĐĞƉƟŽŶĨŽƌĐůĞĂƌĂŶĐĞŽĨŽďƐƚƌƵĐƟŶŐ
emergency devices.
͘ džĂŵƉůĞ
ϴ͘ϭ ĂŶŐĞƌ,ŝŐŚsŽůƚĂŐĞ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϳ͟,ŝŐŚdžϭϬ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ŝŐŝƚĂůƉƌŝŶƚŽŶWŽůLJƐƚLJƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂůŽůĚ͕ϭ͟,ĞĂĚĞƌŽƉLJ͕ϭ͟ĂŶĚПШЖ͟KƚŚĞƌŽƉLJ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
10”
1/8” 1/8”
9 3/4”
1/8”
2”
1/8”
7”
4 5/8”
1/8”
7 1/4”
1/8” 2 3/8” 1/8” 1/8”
MIT Design Standards | Signage Guidelines 38
Page of 52
ϴ͘Ϯ ĂŶŐĞƌŽŵďƵƐƟďůĞ&ƵĞů
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϳ͟,ŝŐŚdžϭϬ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ŝŐŝƚĂůƉƌŝŶƚŽŶWŽůLJƐƚLJƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂůŽůĚ͕ϭ͟,ĞĂĚĞƌŽƉLJ͕СШИ͟ĂŶĚПШЖ͟KƚŚĞƌŽƉLJ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
10”
1/8” 1/8”
9 3/4”
1/8”
2”
1/8”
7”
4 5/8”
1/8”
7 1/4”
1/8” 2 3/8” 1/8” 1/8”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϳ͟,ŝŐŚdžϭϬ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ŝŐŝƚĂůƉƌŝŶƚŽŶWŽůLJƐƚLJƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂůŽůĚ͕ϭ͟,ĞĂĚĞƌŽƉLJ͕ХШМ͟KƚŚĞƌŽƉLJ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
10”
1/8” 1/8”
9 3/4”
1/8”
2”
1/8”
7”
4 5/8”
1/8”
7 1/4”
1/8” 2 3/8” 1/8” 1/8”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϳ͟,ŝŐŚdžϭϬ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ŝŐŝƚĂůƉƌŝŶƚŽŶWŽůLJƐƚLJƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂůŽůĚ͕ϭ͟,ĞĂĚĞƌŽƉLJ͕ХШМ͟ĂŶĚЧШЕК͟KƚŚĞƌŽƉLJ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
10”
1/8” 1/8”
9 3/4”
1/8”
2”
1/8”
7”
CONFINED
4 5/8”
SPACE
AUTHORIZED
PERSONNEL ONLY
1/8”
4 3/8” 5 1/4”
1/8” 1/8” 1/8”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϳ͟,ŝŐŚdžϭϬ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ŝŐŝƚĂůƉƌŝŶƚŽŶWŽůLJƐƚLJƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂůŽůĚ͕ϭ͟,ĞĂĚĞƌŽƉLJ͕УШМ͟KƚŚĞƌŽƉLJ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
10”
1/8” 1/8”
9 3/4”
1/8”
2”
1/8”
7”
4 5/8”
1/8”
4 3/8” 5 1/4”
1/8” 1/8” 1/8”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϳ͟,ŝŐŚdžϭϬ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ŝŐŝƚĂůƉƌŝŶƚŽŶWŽůLJƐƚLJƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂůŽůĚ͕ϭ͟,ĞĂĚĞƌŽƉLJ͕СШИ͟KƚŚĞƌŽƉLJ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
10”
1/8” 1/8”
9 3/4”
1/8”
2”
1/8”
7”
4 5/8”
4 3/8” 5 1/4”
1/8” 1/8” 1/8”
^ŝnjĞ͗ ϱ͟,ŝŐŚdžϳ͟tŝĚĞ
DĂƚĞƌŝĂů͗ sŝŶLJůWƌŝŶƚ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂůŽůĚ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
7”
1/2”
5/16”
1/2”
3/4”
1/4”
5”
3/4”
1/2”
3/8”
3/16”
3/8”
1/2”
Notes:
Yellow Background with Black and Red Copy
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϯ͟,ŝŐŚdžϰ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ŝŐŝƚĂůƉƌŝŶƚŽŶWŽůLJƐƚLJƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂůŽůĚ͕ПШЖ͟,ĞĂĚĞƌŽƉLJ͕ПШИ͟KƚŚĞƌŽƉLJ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
4”
3”
ARC FLASH & SHOCK HAZARD
Appropriate personal protection
equipment required
ϴ͘ϵ tĂƌŶŝŶŐůĞĐƚƌŝĐĂůWĂŶĞůƌĞĂůĞĂƌĂŶĐĞ^ƟĐŬĞƌ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϯ͟,ŝŐŚdžϰ͟tŝĚĞ
DĂƚĞƌŝĂů͗ ŝŐŝƚĂůƉƌŝŶƚŽŶWŽůLJƐƚLJƌĞŶĞ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂŽůĚ͕ПШЖ͟,ĞĂĚĞƌŽƉLJ͕ПШИ͟KƚŚĞƌŽƉLJ
DĞƐƐĂŐĞ͗ ^ĞĞƌĂǁŝŶŐ
͘ džĂŵƉůĞ
4”
WARNING
3”
AREA IN FRONT OF THIS
ELECTRICAL
PANEL MUST BE
KEPT CLEAR FOR 36 INCHES
OSHA-NEC REGULATIONS
ϵ͘ϭ ƵŝůĚŝŶŐ/>ĞƩĞƌŝŶŐ
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϯ͟DŝŶŝŵƵŵŶƵŵďĞƌǁŝƚŚĂĚĚƌĞƐƐ
DĂƚĞƌŝĂů͗ sŝŶLJůŽƌWĂŝŶƚĞĚ>ĞƩĞƌŝŶŐ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌͬŽůĚ
DĞƐƐĂŐĞ͗ d
͘ džĂŵƉůĞƐ
ϭ͘ ϯ>ŝŶĞdžĂŵƉůĞ
Ϯϯͬϰ͟
ϯϭͬϴ͟
ϳϭͬϮ͟
ϭϭͬϰ͟
ϯϭͬϴ͟
Ϯϭͬϴ͟
ϯϭͬϴ͟
EƵŵďĞƌͲ,ĞůǀĞƟĐĂŽůĚϳϭͬϮͬ͟ĚĚƌĞƐƐͲ,ĞůǀĞƟĐĂŽůĚϯϭͬϴͬ͟ƵŝůĚŝŶŐͲ,ĞůǀĞƟĐĂZĞŐƵůĂƌϯϭͬϴ͟
7 1/2”
1 1/2”
3”
1 1/4”
3”
1 1/2”
2 1/2”
1 1/4”
2 1/2”
EƵŵďĞƌͲ,ĞůǀĞƟĐĂŽůĚϳϭͬϮͬ͟ĚĚƌĞƐƐͲ,ĞůǀĞƟĐĂŽůĚϯͬ͟
ƵŝůĚŝŶŐͲ,ĞůǀĞƟĐĂZĞŐƵůĂƌϮϭͬϮͬ͞<ƌĞƐŐĞͲ,ĞůǀĞƟĐĂZĞŐƵůĂƌϮϭͬϮ͟
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭϰ͟džϭϴ͟
DĂƚĞƌŝĂů͗ ͘ϬϴϬtŚŝƚĞůƵŵŝŶƵŵ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂZĞŐƵůĂƌͬŽůĚ
͘ džĂŵƉůĞƐ
ϭ͘ ^ƚĂŶĚĂƌĚKŶĞ>ŝŶĞ,ĞĂĚĞƌ
18”
1/2”
2 1/2” 1 1/2”
1 3/8”
3”
8”
14” 3/4”
3”
7/8”
1 3/8”
3 1/2”
3/8”
3/4”
1/2”
1/2”
1 1/2”
3 1/2”
3/8”
3/4”
1 1/4”
3”
8”
15” 3/4”
3”
7/8”
1 3/8”
3 1/2”
3/8”
3/4”
1/2”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭϮ͟džϭϴ͟
DĂƚĞƌŝĂů͗ ͘ϬϴϬtŚŝƚĞůƵŵŝŶƵŵ
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ,ĞůǀĞƟĐĂŽůĚ
͘ džĂŵƉůĞƐ
ϭ͘ EŽ^ŵŽŬŝŶŐtŝƚŚŝŶϮϱĨĞĞƚŽĨƵŝůĚŝŶŐ
12”
1 1/2”
1/2”
1 3/4”
3/4”
1 3/4”
3/4”
18”
5”
3/4”
1 1/4”
3/4”
1 1/4”
1/2”
3/8”
1 1/2” 3/4”
3/8”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϭϮ͟džϳПШЖ͟
DĂƚĞƌŝĂů͗ sŝŶLJůĞĐĂů
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂů͕ϭПШИ͟DĂŝŶŽƉLJ͕СШИ͟KƚŚĞƌŽƉLJ
͘ džĂŵƉůĞ
12”
3/8”
1 1/4”
1 1/2”
7 1/2” 3/4”
3/8”
3/4”
3/8”
3/4”
1 3/8”
͘ ^ƉĞĐŝĮĐĂƟŽŶƐ
^ŝnjĞ͗ ϴ͟džϱ͟
DĂƚĞƌŝĂů͗ sŝŶLJůĞĐĂů
dLJƉĞ^ƚLJůĞͬ&ŽŶƚ͗ ƌŝĂů͕ХШМ͟DĂŝŶŽƉLJ͕СШМ͟KƚŚĞƌŽƉLJ
͘ džĂŵƉůĞ
8”
1/4”
7/8”
1 1/2”
5”
3/8”
1/4”
3/8”
3/8”
1 3/8”
MIT
Design Standards
Space Accounting
Thematic Folder
! !
May 2018
!
!
!
!
!
!
"#$%&!'(!)'*"&*"+!
!"! !#$%&'()$!&#* +!
,"! -%&).'(%./* 0!
,",! %.1(./$!#2*#.3*4(!5'!#2*#(64.%/* 0!
,"7! %.1(./$!#2*%&&6*#(64.%/* 0!
,"8! /-9).*9))&(#$!#2* :!
"#$#"! %&'(')*+'%)! ,!
"#$#-! ./.+01*+'2!*34'+!5'2&6! ,!
"#$#$! *4!7%2!*34'+! ,!
7"! 4(!5'!#2*!#;.#$&%<* =!
7",! 4(!5'!#2*$<-./* =!
7"7! 4(!5'!#2*#(64.%/* =!
-#-#"! 83'94')(!:&0;'<0.! =!
-#-#-! 83'94')(!.3;;'<0.! ">!
-#-#$! 2%3)+')(!83'94')(.! ">!
7"8! 2%&//*9%.9*4%.9>'&3#* ,,!
-#$#"! *&0*!40;')'+'%).! ""!
+"! %.B.%.#)./* ,!
,- ,*".'/0)",'*!
!
+?@!4@ABCDE@FD!GH!;BIJKJDJ@LM!;BIJKJDJ@L!'FHGCEBDJGF!.NLD@EL!OCGPA!JL!1'+QL!GHHJIJBK!LGPCI@!HGC!RPJKSJFOM!
RPJKSJFO!IGEAGF@FDLM!BFS!CGGE!FPER@CL#!!+?@!OCGPA!BKLG!EBFBO@L!D?@!BIBS@EJI!AGCDHGKJG!LABI@!
JFT@FDGCJ@L#!+?@L@!JFT@FDGCJ@L!BC@!U@AD!IPCC@FD!TJB!LABI@!BPSJDJFO#!
!
!"#$%#&'()&*+,-./#+&V!
1'+!?BL!DWG!RPJKSJFO!AGCDHGKJGLM!D?@!'FT@LDE@FD!:GCDHGKJG!BFS!D?@!*IBS@EJI!:GCDHGKJG#!+?@!'FT@LDE@FD!
:GCDHGKJG!IGFLJLDL!GH!RPJKSJFOL!D?BD!1'+!K@BL@L!DG!GPDLJS@!PL@CL!HGC!JFIGE@!GC!HPDPC@!IGFT@CLJGF#!+?@L@!
RPJKSJFOL!BC@!FGD!IPCC@FDKN!JFIKPS@S!JF!D?@!.ABI@!*IIGPFDJFO!JFT@FDGCJ@L#!
!
!"#$%#&'(012345(
1'+!IPCC@FDKN!PL@L!D?C@@!RPJKSJFO!DNA@L!5BIBS@EJIM!C@LJS@FDJBKM!L@CTJI@6M!?GW@T@CM!4CBA@C!IGFLDJDPD@S!B!
HGPCD?!DNA@!RBL@S!GF!?JLDGCJIBK!SBDB#!!+?@!4CBA@C!HBIJKJDJ@L!GIIPAJ@S!RN!D?@!2?BCK@L!.DBCU!4CBA@C!
9BRGCBDGCN!5AC@TJGPLKN!UFGWF!BL!D?@!'FLDCPE@FDBDJGF!9BRGCBDGCN6!W@C@!SJT@LD@S!HCGE!1'+!GF!XPKN!"M!
"=Y$#!
!
!"#$%#&'(6"-73,45(
ZJD?JF!D?@!1BJF!(CGPAM!RPJKSJFOL!DG!D?@!W@LD!GH!D?@!(C@BD!4GE@!BC@!FPER@C@S!WJD?!GSS!FPER@CL!BFS!
RPJKSJFOL!DG!D?@!0BLD!GH!D?@!(C@BD!4GE@!BC@!FPER@C@S!WJD?!@T@F!FPER@CL!5D?@!@[I@ADJGF!DG!D?JL!LI?@E@!
JL!RPJKSJFO!\]6#!+?JL!AKBF!WBL!BHH@ID@S!JF!"="]!WJD?!IGEAK@DJGF!GH!D?@!HJCLD!1'+!RPJKSJFOL!GF!D?@!
2BERCJSO@!LJD@!BD!D?@!DJE@!GH!D?@!'FLDJDPD@^L!EGT@!HCGE!JDL!GCJOJFBK!8GLDGF!KGIBDJGF#!!!
!
8,+44(9,3.(!,3.:%+;&5(
'F!D?@!"=Y>QLM!D?@!;@S@CBK!2GFLDCPIDJGF!2GPFIJK!APRKJL?@S!GHHJIJBK!S@HJFJDJGFL!BFS!LDBFSBCSL!HGC!
E@BLPCJFO!BFS!IGEAJKJFO!SBDB!GF!RPJKSJFOL!JF!D?@V!
!
• ;@S@CBK!2GFLDCPIDJGF!2GPFIJK!+@I?FJIBK!&@AGCD!)G#!\>!5:PRKJIBDJGF!"-$\6!
• 2KBLLJHJIBDJGF!GH!8PJKSJFO!*C@BL!
• )BDJGFBK!*IBS@EN!GH!.IJ@FI@L!
• 8PJKSJFO!&@L@BCI?!*STJLGCN!8GBCS!
!
+?@L@!W@C@!LPAAK@E@FD@S!RN!B!?J@CBCI?N!GH!EGC@!S@DBJK@S!IKBLLJHJIBDJGFL!GH!RPJKSJFO!LABI@!BFS!D?@JC!
S@HJFJDJGFL!APRKJL?@S!JF!D?@!;BIJKJDJ@L!'FT@FDGCN!BFS!2KBLLJHJIBDJGF!1BFPBKM!"=]$M!3.470ZM!%HHJI@!GH!
0SPIBDJGF#!!+?JL!SGIPE@FD!WBL!D?@F!PASBD@S!BFS!C@APRKJL?@S!BL!D?@!:GLDL@IGFSBCN!0SPIBDJGF!;BIJKJDJ@L!
'FT@FDGCN!BFS!2KBLLJHJIBDJGF!1BFPBKM!&@TJL@S!BFS!&@ACJFD@S!*ACJK!"==_!BFS!EGC@!C@I@FDKNM!3.4%0M!
)BDJGFBK!2@FD@C!HGC!0SPIBDJGF!.DBDJLDJIL#!'FD@FS@S!HGC!PL@!RN!H@S@CBK!BO@FIJ@LM!D?@L@!S@HJFJDJGFL!?BT@!
R@@F!WJS@KN!BSGAD@S!RN!IGKK@O@L!BFS!PFJT@CLJDJ@L!GT@C!EBFN!N@BCLM!JFIKPSJFO!1'+#!!2PCC@FDKNM!1'+!
C@H@C@FI@L!D?@!->>Y!@SJDJGF!GH!D?@!:GLDL@IGFSBCN!0SPIBDJGF!;BIJKJDJ@L!'FT@FDGCN!BFS!2KBLLJHJIBDJGF!
1BFPBK#!
!
1.')&/0.&+!
2-2 .&30&+",*4!*&5!$0,%/,*4!*06$&.+!
!
"# +?@!:CG`@ID!1BFBO@C!WJKK!IGFDBID!D?@!;'.!OCGPA!BD!HJLaC@bP@LDcEJD#@SP!DG!C@bP@LD!B!F@W!
RPJKSJFO!FPER@C!SPCJFO!D?@!@BCKN!S@LJOF!LDBO@L#!!+?@!ACG`@ID!EBFBO@C!WJKK!ACGTJS@L!D?@!HGKKGWJFO!
JFHGCEBDJGF!DG!;'.V!
• ;GGDACJFD!5SCBWJFO!GC!LU@DI?!L?GWJFO!B!LA@IJHJI!RPJKSJFO!GPDKJF@M!SJLDJFOPJL?BRK@!HCGE!
F@JO?RGCJFO!GC!IGFF@ID@S!LDCPIDPC@L6!
• 8PJKSJFO!)BE@!5LDC@@D!BSSC@LL!JH!B!SGFGC!FBE@!JL!FGD!BTBJKBRK@6!
• .DC@@D!*SSC@LL!
• 0=""!*SSC@LL!5JH!SJHH@C@FD!HCGE!D?@!LDC@@D!BSSC@LL6!
• 8PJKSJFO!3L@!5*IBS@EJIM!&@LJS@FDJBKM!.@CTJI@6!
• :@CI@FDBO@!GH!8PJKSJFO!%IIPAJ@S!RN!1'+!5A@C!ACG`@ID!C@bPJC@E@FD6!
• :GD@FDJBK!%IIPANJFO!4@ABCDE@FD!
• 2GFLDCPIDJGF!LDBCD!SBD@!
• 0LDJEBD@S!IGEAK@DJGF!SBD@!5LPRLDBFDJBK!IGEAK@DJGFdGIIPABFIN6!
• 8PJKSJFO!%WF@CL?JA!5%WF@S!RN!1'+!d!9@BL@S6!
-# +?@!;'.!OCGPA!WJKK!BLLJOF!B!RPJKSJFO!FPER@C!JF!\a]!RPLJF@LL!SBNL#!.@@!(CJS!JF!*AA@FSJ[!*#!
!
2-7 .&30&+",*4!.''6!*06$&.+!!
!
+G!JFLPC@!ACGA@C!JFD@OCJDN!WJD?!D?@!TBCJGPL!1'+!BSEJFJLDCBDJT@!LNLD@ELM!BS?@C@FI@!DG!BFS!EBJFD@FBFI@!
GH!D?@!1'+!CGGE!FPER@CJFO!LDBFSBCS!@FLPC@L!D?BD!BLLJOF@S!LABI@!JS@FDJHJ@CL!BKWBNL!C@EBJF!PFJbP@#!
!
"# Z?@F!CGGE!KBNGPDL!BC@!@LDBRKJL?@SM!L@FS!AKBFL!BFS!D?@!CGGE!FPER@C!C@bP@LD!DG!HJLa
C@bP@LDcEJD#@SP#!&@bPJC@S!JFHGCEBDJGF!JFIKPS@LV!
• 1'+!:CG`@ID!)PER@C
• 1'+!:CG`@ID!1BFBO@C5L6
• 8PJKSJFO!)PER@C
• ;KGGC
• &GGE!)PER@CL!5@[JLDJFO6
• %COBFJeBDJGF!d!4@ABCDE@FD
• 0LDJEBD@S!.DBCD!4BD@
• 0LDJEBD@S!2GEAK@DJGF!4BD@
• 0K@IDCGFJI!HKGGC!AKBF!5*PDG2*4#SWO!AC@H@CC@S6!L?GWJFO!CGGE!PL@!KBR@KL!
-# +?@!;'.!OCGPA!WJKK!BLLJOF!GHHJIJBK!CGGE!FPER@CL!BFS!WJKK!C@DPCF!B!EBCU@S!PA!IGAN!GH!D?@!AKBF!
WJD?JF!\!f!]!5DNAJIBK!C@FGTBDJGF6!@LDJEBD@S!RPLJF@LL!SBNL!GC!]a">!5IBAJDBK!ACG`@IDL6!RPLJF@LL!SBNL#!
'H!BFN!HPCD?@C!I?BFO@L!5J@#!BCI?JD@IDPCBK!C@IGFHJOPCBDJGFLM!CGGE!PLBO@LM!GC!GCOBFJeBDJGFBK!
I?BFO@L6!GIIPC!SPCJFO!S@LJOF!GC!IGFLDCPIDJGFM!D?@!;'.!OCGPA!EPLD!R@!IGFDBID@S!BL!LGGF!BL!
AGLLJRK@!HGC!C@TJL@S!CGGE!FPER@CL#!
2-8 +1#)&!#))'0*",*4!
!
.ABI@!*IIGPFDJFO!BD!1'+!@[JLDL!DG!SGIPE@FD!BFS!EBJFDBJF!D?@!BIIPCBIN!GH!D?@!HGKKGWJFO!@K@E@FDL!BL!
C@KBD@S!DG!1'+!LABI@V!
!
• 1'+!&GGE!)PER@CL!
• &GGE!3LBO@!
• *CI?JD@IDPCBK!2GFHJOPCBDJGF!
• %COBFJeBDJGFBK!*LLJOFE@FD!
!
.bPBC@!HGGDBO@!IBKIPKBDJGFL!BC@!S@CJT@S!HCGE!D?@!BCI?JD@IDPCBK!IGFHJOPCBDJGF!GH!LABI@L!5WBKKLM!ABCDJDJGFLM!
GA@FJFOLM!@DI#6!BFS!BS?@C@!DG!D?@!OPJS@KJF@L!@LDBRKJL?@S!JF!D?@!3#!.#!4@ABCDE@FD!GH!0SPIBDJGF^L!
g:GLDL@IGFSBCN!0SPIBDJGF!;BIJKJDJ@L!'FT@FDGCN!BFS!2KBLLJHJIBDJGF!1BFPBKg!5;'216#!
!
+?@!HGPCD?!SBDB!@K@E@FDM!GCOBFJeBDJGFBK!BLLJOFE@FDM!JL!S@D@CEJF@S!RN!D?@!2GEEJDD@@!HGC!&@TJ@W!GH!
.ABI@!:KBFFJFO!52&.:!2GEEJDD@@6!BFS!IGEEPFJIBD@S!DG!;'.#!
!
!"#"! $%&'&()*&+(,
!
.ABI@!BIIGPFDJFO!BPSJDJFO!GCJOJFBD@L!HCGE!EPKDJAK@!BC@BLV!
!
• 2BAJDBK!2GFLDCPIDJGF!:CG`@IDL!
• 2GFLDCPIDJGF!&@FGTBDJGF!:CG`@IDL!
• .@KH!.@CTJI@!*PSJDJFO!&@bP@LDL!
• +?@!2GEEJDD@@!HGC!&@TJ@W!GH!.ABI@!:KBFFJFOd:CGTGLD!%HHJI@!
!
0T@CN!DWG!N@BCL!D?JL!JFIKPS@L!D?@!'2&M!GC!'FSJC@ID!2GLD!&@IGT@CNM!BPSJD#!
!
!"#"- ./0*12)*&3,456&*,789:;,
!
+?JL!BPSJD!JL!IGEAK@D@S!RN!KGGUJFO!JFDG!@BI?!BFS!@T@CN!CGGEh!RPJKSJFO!RN!RPJKSJFOM!HKGGC!RN!HKGGCM!CGGE!RN!
CGGE#!;GC!EBFN!N@BCL!D?@!LDBFSBCS!?BL!R@@F!DG!SG!D?JL!BFFPBKKNM!IGT@CJFO!D?@!JFSJC@IDaIGLDaC@IGT@CBRK@!
RPJKSJFOL!GF@!N@BC!BFS!D?@!FGFaC@IGT@CBRK@!RPJKSJFOL!D?@!HGKKGWJFO!N@BC#!+?JL!DWGaN@BC!INIK@!JL!
ACGEAD@S!RN!D?@!C@bPJC@E@FD!JF!8PC@BP!GH!D?@!8PSO@D!2JCIPKBC!*a-"!D?BD!RPJKSJFO!LABI@!JFT@FDGCJ@L!
PAGF!W?JI?!H@S@CBK!JFSJC@ID!IGLD!C@IGT@CN!JL!RBL@S!R@!PASBD@S!BFFPBKKN#!!
!"#"# 46,<+3,456&*,
!
+?JL!BPSJD!JL!IGEAK@D@S!RN!KGGUJFO!JFDG!@BI?!CGGE!D?BD!?BL!PFS@COGF@!B!LABI@!I?BFO@M!W?JI?!IBF!CBFO@!
HCGE!B!LJFOK@!LABI@!DG!BF!@FDJC@!RPJKSJFO#!+?@!IPCC@FD!LDBFSBCS!JL!DG!IGT@C!LABI@!I?BFO@L!BL!LGGF!BL!
AGLLJRK@M!HGKKGWJFO!D?@JC!IGEAK@DJGFM!GF!B!IGFDJFPGPL!EGFD?aDGaEGFD?!RBLJL#!+?@!DJE@KJF@LL!GH!D?JL!INIK@!
BSSC@LL@L!D?@!SBJKN!BFS!@[A@SJ@FD!F@@SL!GH!D?@!1'+!IGEEPFJDNM!W?JI?!R@F@HJDL!HCGE!IPCC@FD!BFS!
BIIPCBD@!SBDB!EBS@!BTBJKBRK@!JF!RGD?!D?@!SBDBRBL@!BFS!D?@!HKGGCAKBFL#*
$0,%/,*4!,*9&*"'.:!
!
+?@!*IBS@EJI!:GCDHGKJG!IGFLJLDL!GH!RPJKSJFOL!PL@S!SBNaDGaSBN!HGC!BIBS@EJIM!C@LJS@FDJBK!GC!L@CTJI@!
BIDJTJDJ@L#!!1GLD!GH!D?@L@!RPJKSJFOL!BC@!GWF@S!RN!1'+M!?GW@T@C!LGE@!BC@!K@BL@S!GC!ABCDJBKKN!K@BL@S!RN!
GPDLJS@!GWF@CL#!!+?@!.ABI@!*IIGPFDJFO!JFT@FDGCJ@L!JFIKPS@!HIJK!D?@!RPJKSJFOL!JF!D?@!*IBS@EJI!:GCDHGKJGM!
D?@C@HGC@!D?@L@!BC@!D?@!GFKN!RPJKSJFOL!IGPFD@S!BFS!BLLJOF@S!DNA@LM!FPER@CL!BFS!GCOBFJeBDJGFL#!
!
7-2 $0,%/,*4!":1&+!
!
8PJKSJFOL!JF!D?@!*IBS@EJI!:GCDHGKJG!BC@!IBD@OGCJe@S!JFDG!GF@!GH!D?@!HGKKGWJFO!D?C@@!DNA@L!RBL@S!GF!D?@!
AC@SGEJFBFD!BIDJTJDN!WJD?JF!D?@EV!
!
• *IBS@EJI!f!JFIKPS@L!D@BI?JFO!BFS!C@L@BCI?!HBIJKJDJ@L!
• &@LJS@FDJBK!f!JFIKPS@L!LDPS@FD!?GPLJFO!BFS!D?@!:C@LJS@FDQL!?GPL@!
• .@CTJI@!f!JFIKPS@L!BSEJFJLDCBDJT@M!BD?K@DJIM!KJRCBCNM!E@SJIBKM!C@KJOJGPLM!LDPS@FD!I@FD@CM!BPSJDGCJPEM!
PDJKJDNdE@I?BFJIBKM!LDGCBO@!BFS!ABCUJFO!OBCBO@!HBIJKJDJ@L!
!
7-7 $0,%/,*4!*06$&.+!
!
1'+!GHHJIJBK!RPJKSJFO!FPER@CL!BC@!BLLJOF@S!DG!BKK!RPJKSJFOL!JF!D?@!*IBS@EJI!:GCDHGKJG!JFIKPSJFO!RPJKSJFOL!
K@BL@S!RN!1'+!HCGE!FGFa1'+!GWF@CL#!'F!D?JL!KBDD@C!IBL@!D?@!1'+!FPER@CL!BC@!PL@S!GFKN!JFD@CFBKKN!BFS!BC@!
BLLJOF@S!HGC!IGFLJLD@FIN!BFS!@BL@!GH!C@H@C@FI@!JF!BSEJFJLDCBDJT@!EBDD@CL#!!
!
+?@!RGPFSBCJ@L!GH!D?@L@!BS`BI@FD!0BLDM!Z@LDM!)GCD?!BFS!GD?@C!L@IDGCL!W@C@!SCBHD@S!JF!B!AKBF!AC@ABC@S!
RN!4GFBKS!Z?JLDGF!51'+!2KBLL!GH!"=$-6#!+?@!RGPFSBCJ@L!GH!L@IDGCL!PL@S!HGC!FPE@CJIBK!BLLJOFE@FDL!GH!
">^LM!->^LM!@DI@D@CB!WJD?JF!@BI?!GH!D?@L@!L@IDGCL!W@C@!JFIKPS@S!JF!D?@!Z?JLDGF!AKBF!5@#O#!0">!DG!0"=6#!!
!
-"-"! =5&>6&(',?%1@&A10,
!
8PJKSJFOL!BC@!OCGPA@S!JFDG!D?@!HGKKGWJFO!@JO?D!O@GOCBA?JIBK!BC@BL!JF!C@KBDJGF!DG!D?@!1BJF!(CGPA!BFS!BC@!
BLLJOF@S!FPER@CL!RBL@S!GF!D?@L@!KGIBDJGFLV!
!
• 1BJF!(CGPA!f!D?@L@!RPJKSJFOL!BC@!BLLJOF@S!FPER@CL!WJD?GPD!BF!BKA?BR@DJIBK!AC@HJ[!5@#O#!"!GC!Y,6!
• )!f!D?JL!BKA?BR@DJI!AC@HJ[!JL!PL@S!HGC!RPJKSJFOL!D?BD!LJD!FGCD?!GH!D?@!1BJF!(CGPA!5@#O#!)_6!
• )0!f!D?JL!BKA?BR@DJI!AC@HJ[!JL!PL@S!HGC!RPJKSJFOL!D?BD!LJD!FGCD?@BLD!GH!D?@!1BJF!(CGPA!
• )Z!f!D?JL!BKA?BR@DJI!AC@HJ[!JL!PL@S!HGC!RPJKSJFOL!D?BD!LJD!FGCD?W@LD!GH!D?@!1BJF!(CGPA!
• 0!f!D?JL!BKA?BR@DJI!AC@HJ[!JL!PL@S!HGC!RPJKSJFOL!D?BD!LJD!@BLD!GH!D?@!1BJF!(CGPA!
• 00!f!D?JL!BKA?BR@DJI!AC@HJ[!JL!PL@S!HGC!RPJKSJFOL!D?BD!LJD!HBCD?@C!@BLD!GH!D?@!1BJF!(CGPA!
• Z!f!D?JL!BKA?BR@DJI!AC@HJ[!JL!PL@S!HGC!RPJKSJFOL!D?BD!LJD!W@LD!GH!D?@!1BJF!(CGPA!
• ZZ!f!D?JL!BKA?BR@DJI!AC@HJ[!JL!PL@S!HGC!RPJKSJFOL!D?BD!LJD!HBCD?@C!W@LD!GH!D?@!1BJF!(CGPA!
• %2!f!D?JL!BKA?BR@DJI!AC@HJ[!JL!PL@S!HGC!RPJKSJFOL!D?BD!LJD!R@NGFS!D?@!CBFO@!GH!D?@!2BERCJSO@!
2BEAPL!
-"-"- =5&>6&(',.5@@&A10,
!
*!GF@!K@DD@C!LPHHJ[!JL!PL@S!JF!D?@!HGKKGWJFO!IJCIPELDBFI@LV!
!
• Z?@F!D?@C@!JL!B!LPAAK@E@FDBCN!GC!BP[JKJBCN!A?NLJIBK!LDBDPL!BFS!HPFIDJGFBK!CGK@!GH!B!RPJKSJFO!
@JD?@C!BS`GJFJFO!GC!BS`BI@FD!DG!B!F@BCRN!ACJFIJAK@!LDCPIDPC@!DG!W?JI?!D?@C@!JL!BF!BLLJOF@S!FPER@C!
5@#O#!Z\]!BFS!Z\]*6#!
• Z?@F!D?@C@!JL!B!IGEAGF@FD!GH!B!KBCO@C!LDCPIDPC@!WJD?!BF!@bPBK!HPFIDJGFBK!CGK@!DG!BKK!D?@!GD?@C!
IGEAGF@FDL#!!'F!D?JL!IBL@!D?@C@!EBN!R@!FG!BC@B!BLLJOF@S!WJD?GPD!B!LPHHJ[!5@#O#!8BD@L!%2"=*!
D?CGPO?!%2"=i6#!
!
-"-"# 9+5(*&(',=5&>6&('0,
!
+?@!LABI@!BIIGPFDJFO!JFT@FDGCJ@L!IGPFD!1'+!RPJKSJFOL!JF!D?@!EBFF@C!S@LICJR@S!R@KGWV!
!
• &@LJS@FDJBK!RPJKSJFOL!WJD?!EPKDJAK@!IGEAGF@FDL!BFS!EPKDJAK@!K@DD@C!LPHHJ[@L!BC@!IGPFD@S!BL!GF@!
RPJKSJFO!5@#O#!RPJKSJFO!ZY"6#!
!
• 0[I@ADJGFV!Z,\!JL!IGPFD@S!BL!GF@!RPJKSJFO!W?JK@!Z,\*a8a2M!Z,\4a0M!Z,\;a(!BFS!Z,\7aXaj!BC@!
IGPFD@S!BL!HGPC!RPJKSJFOL#!
!
!
!
!
!
• )GFaC@LJS@FDJBK!RPJKSJFOL!BFS!D?@JC!BP[JKJBCJ@L!GC!IGEAGF@FDL!BC@!IGPFD@S!JFSJTJSPBKKN!5@#O#!Y!
BFS!Y8!BC@!IGPFD@S!BL!DWG!5-6!RPJKSJFOL6#!
!
!
!
!
o 0[I@ADJGFV!"_!BFS!"_)a.a0aZ!BC@!IGPFD@S!BL!GF@!RPJKSJFO#!
!
!
!
!
7-8 4.'++!#.&#!$.&#;/'5*!
-"#"! 4%1),B1@&(&*&+(0,
!
+?@!PFJD!GH!E@BLPC@!HGC!BKK!RPJKSJFO!BC@B!E@BLPC@E@FDL!BFS!C@IGCS@S!SBDB!JF!D?@!.ABI@!*IIGPFDJFO!
JFT@FDGCJ@L!JL!LMNOPQ*RQQS!5LH6#!!!
!
1'+!?BL!BSGAD@S!D?@!S@HJFJDJGFL!BFS!LDBFSBCSL!HGC!E@BLPCJFO!BFS!IGEAJKJFO!SBDB!GF!RPJKSJFOL!HCGE!D?@!
:GLDL@IGFSBCN!0SPIBDJGF!;BIJKJDJ@L!'FT@FDGCN!BFS!2KBLLJHJIBDJGF!1BFPBKM!C@TJL@S!BFS!C@ACJFD@S!*ACJK!
"==_M!3.4%0M!)BDJGFBK!2@FD@C!HGC!0SPIBDJGF!.DBDJLDJIL!5BKLG!D?@!->>Y!@SJDJGF6#!!+?@!HGKKGWJFO!JL!B!KJLD!GH!
S@HJFJDJGFL!BFS!IKBLLJHJIBDJGFLV!!
!
"#$%%!&#'(!k!.DCPIDPCBK!*C@B!l!)@D!3LBRK@!*C@B!
!
<3*#&#/#+&5!!+?@!LPE!GH!BKK!BC@BL!GF!BKK!HKGGCL!GH!B!RPJKSJFO!JFIKPS@S!WJD?JF!D?@!GPDLJS@!HBI@L!GH!JDL!@[D@CJGC!
WBKKLM!JFIKPSJFO!BKK!T@CDJIBK!A@F@DCBDJGF!BC@BLM!HGC!IJCIPKBDJGF!BFS!L?BHD!BC@BL!D?BD!IGFF@ID!GF@!HKGGC!DG!
BFGD?@C#!
!
!
)*#+,*+#(-!&#'(!.!8,+44(9,3.(=(63/(>4.7$3(9,3.(
!
<3*#&#/#+&5!!+?@!LPE!GH!BKK!BC@BL!GF!BKK!HKGGCL!GH!B!RPJKSJFO!D?BD!IBFFGD!R@!GIIPAJ@S!GC!APD!DG!PL@!R@IBPL@!
GH!LDCPIDPCBK!RPJKSJFO#!!5'#0#!:CJFIJABKKN!D?@!LPE!GH!BKK!ICGLLaL@IDJGFBK!BC@BL!GH!@[D@CJGC!WBKKL!BFS!JFD@CJGC!
ABCDJDJGFL#6!
!
!
/$01(%%230(4-'!&#'(!k!.PE!GH!D?@!*C@BL!4@LJOFBD@S!BL!D?@!$!FGFaBLLJOFBRK@!GH!D?@!"$!EB`GC!LABI@!PL@!
IBD@OGCJ@L!
!
<3*#&#/#+&5!!+?@!LPE!GH!BKK!BC@BL!GF!BKK!HKGGCL!GH!B!RPJKSJFO!FGD!BTBJKBRK@!HGC!BLLJOFE@FD!DG!BF!GIIPABFD!GC!
HGC!LA@IJHJI!PL@M!RPD!F@I@LLBCN!HGC!D?@!O@F@CBK!GA@CBDJGF!GH!B!RPJKSJFO#!
!
?.@+,(>434(A&+&B.44#'&.7$3C5!
• 8PJKSJFO!.@CTJI@!*C@B!5IPLDGSJBK!LPAAKJ@LM!`BFJDGCJBK!LJFU!CGGELM!`BFJDGCJBK!IKGL@DLM!BFS!APRKJI!C@LD!CGGEL6!
• 2JCIPKBDJGF!*C@B!
• 1@I?BFJIBK!*C@B!
!
!
<3*#&#/#+&5!+?@!LPE!GH!BKK!BC@BL!GF!BKK!HKGGCL!GH!B!RPJKSJFO!PL@S!HGC#!
!
!
/'*!&%%230(4-'!&#'(!k!.PE!GH!*C@BL!4@LJOFBD@S!RN!">!GH!D?@!"$!BLLJOFBRK@!EB`GC!LABI@!PL@!IBD@OGCJ@L!
!
<3*#&#/#+&5!!+?@!LPE!GH!BKK!BC@BL!GF!BKK!HKGGCL!GH!B!RPJKSJFO!BLLJOF@S!DGM!GC!BTBJKBRK@!HGC!BLLJOFE@FD!DG!BF!
GIIPABFD!GC!LA@IJHJI!PL@#(
?.@+,(D2.E3(>43(F./3'+,#345(
!
• 2KBLLCGGEL!
• 9BRGCBDGCJ@L!
• %HHJI@L!
• .DPSN!
• .A@IJBK!3L@!
• (@F@CBK!3L@!
• .PAAGCD!
• 7@BKD?!2BC@!
• &@LJS@FDJBK!
• 3FIKBLLJHJ@S!
!
!
/'*!5%(4-'!&#'(!k!*LLJOFBRK@!*C@B!l!)GFaBLLJOFBRK@!*C@B!
!
<3*#&#/#+&5!!+?@!LPE!GH!BKK!BC@BL!GF!BKK!HKGGCL!GH!B!RPJKSJFO!@JD?@C!BLLJOF@S!DG!GC!BTBJKBRK@!HGC!BLLJOFE@FD!
DG!BF!GIIPABFD!GC!LA@IJHJI!PL@!GC!F@I@LLBCN!HGC!D?@!O@F@CBK!GA@CBDJGF!GH!B!RPJKSJFO#!5'#0#!'FIKPS@S!WJD?JF!
D?@!JFLJS@!HBI@L!GH!JDL!WBKKL!BFS!ABCDJDJGFL#6!
.''6!,*9&*"'.:!#*/!*06$&.+!
!
&GGE!FPER@CL!HGKKGW!B!LA@IJHJIM!IGFLJLD@FD!HGCEBD!D?BD!JL!JFDPJDJT@!BFS!IGFT@NL!E@BFJFOHPK!JFHGCEBDJGF!
DG!D?@!RPJKSJFO!PL@CL#!+?@!HPKK!FPER@C!JL!IGEACJL@S!GH!D?C@@!L@OE@FDLM!D?@!GHHJIJBK!RPJKSJFO!FPER@CM!D?@!
HKGGC!FPER@C!BFS!D?@!BLLJOF@S!CGGE!FPER@C#!!
0[BEAK@V!
!
4NTJUTIV*#NWXQP BJHHP* %HHW*#NWXQP
! #NWXQP
3 0F . G 7 F: /
!
8-2 4&*&.#%!.0%&+!
!
• (CGPFS!HKGGC!CGGE!FPER@CL!R@OJF!F@BC!D?@!ACJFIJABK!AGJFD!GH!BII@LL!DG!D?@!RPJKSJFO!BFS!JFIC@BL@!
BWBN!HCGE!D?BD!AGJFD#!
• *KK!PAA@C!BFS!KGW@C!HKGGC!CGGE!FPER@CL!BAACG[JEBD@KN!IGCC@LAGFS!DG!D?@!CGGE!FPER@CL!GF!D?@!
OCGPFS!HKGGC#!
• .PRaRBL@E@FDL!WGPKS!?BT@!B!HKGGC!FPER@C!GH!n>>QM!D?@C@HGC@!B!IGEAK@D@!CGGE!FPER@C!JF!D?@!
LPRaRBL@E@FD!EJO?D!KGGU!KJU@!)0_=a>>"]#!
• 8BL@E@FDL!?BT@!B!HKGGC!FPER@C!GH!>!BKKGWJFO!D?@!(CGPFS!HKGGC!DG!?BT@!B!HKGGC!FPER@C!GH!"M!D?@!
.@IGFS!HKGGC!DG!?BT@!B!HKGGC!FPER@C!GH!-!BFS!LG!GF#!!
• &GGE!FPER@CL!BC@!AKBI@S!PLJFO!D?@!nAGLD!GHHJI@!LNLD@EQ!LG!D?BD!BKK!@T@F!FPER@CL!BC@!GF!GF@!
LJS@M!W?JK@!GSS!FPER@CL!BC@!GF!D?@!GAAGLJD@!LJS@#!
• (BAL!BC@!GHD@F!JFDCGSPI@S!DG!BKKGW!HGC!BSSJDJGFBK!FPER@CL!DG!R@!JFL@CD@S!JF!D?@!@T@FD!GH!B!HPDPC@!
C@FGTBDJGF#!
• +?@!I@FD@CKJF@QL!GH!D?@!RPJKSJFOQL!LDCPIDPCBK!OCJS!JL!PL@S!BL!B!HGCEBD!HGC!IGFLDCPIDJFO!B!RBLJI!
BCCBFO@E@FD!GH!FPER@CLM!W?JI?!JL!PL@S!BL!B!OPJS@!GF!BKK!HKGGCL#!ZJD?JF!@BI?!I@KKM!D?@!CGGE!
FPER@C!5GH!D?@!AGLLJRJKJDJ@L!BLLJOF@S!DG!B!I@KK6!JL!S@D@CEJF@S!RN!D?@!SGGC!KGIBDJGF!JF!D?@!I@KK#!+?@!
FPER@C!GH!I@KKL!SJTJS@S!RN!">>!JL!D?@!EB[JEPE!FPER@C!D?BD!IBF!R@!BLLJOF@S!A@C!HKGGC!JF!D?@!
1'+!CGGE!FPER@CJFO!LNLD@E#!+?JL!LNLD@E!JL!PL@S!DG!@LDBRKJL?!BFS!EBJFDBJF!B!IGFLJLD@FD!
FPER@CJFO!LI?@E@!HGC!D?@!KJH@!GH!D?@!RPJKSJFO#!
• &GGEL!C@BI?@S!TJB!D?@!EBJF!IGCCJSGC!BC@!BLLJOF@S!FPER@CL!RBL@S!GF!D?@!OCJS#!
• &GGEL!C@BI?@S!TJB!GD?@C!CGGEL!BC@!C@IGOFJe@S!PLJFO!D?@!nLPJD@!LNLD@EQ#!!8@OJFFJFO!WJD?!D?@!HJCLD!
CGGE!DG!D?@!K@HD!GH!D?@!ACJEBCN!BII@LL!AGJFDM!K@DD@CL!5R@OJFFJFO!WJD?!*M!LUJAAJFO!0M!'M!XM!1"M!%M!BFS!
+6!BC@!BLLJOF@S!JF!B!IKGIUWJL@!SJC@IDJGF#!!
• &GGEL!GC!LABI@L!WJD?JF!CGGEL!D?BD!BKC@BSN!IBCCN!B!LPHHJ[!WGPKS!?BT@!D?@!HJCLD!K@DD@C!HGKKGW@S!RN!
BFGD?@C!K@DD@C!5R@OJFFJFO!WJD?!*M!LUJAAJFO!0M!'M!XM!1M!%M!BFS!+6!
• %IIBLJGFBKKN!D?JL!LI?@E@!JL!C@IPCLJT@!DG!D?@!@[D@FD!GH!DWG!BAA@FS@S!K@DD@CL#!
• .A@IJBK!CGGE!LPHHJ[@L!BC@!PL@S!HGC!APRKJI!IJCIPKBDJGFM!RPJKSJFO!L@CTJI@M!E@I?BFJIBK!BC@BLM!BFS!
E@eeBFJF@L#!!+?@!DBRK@!R@KGW!L?GWL!D?@L@!LPHHJ[@L!WJD?!@[BEAK@LV!
!
9PQO* $KYQ* /NRRTZ* .ZOWYJQ*
8PJKSJFO!.@CTJI@! XBFJDGCJBK!*C@BL! X! "-$X!
2JCIPKBDJGF! 8CJSO@d+PFF@K! 2*M!28M!22M!@DI#! ">>2*M!">>28!
! 2GCCJSGC! 2*M!28M!22M!@DI#! ">>2*M!->>2*!
! 0K@TBDGC! 0"M!0-M!0$M!@DI#! ">>0"M!">>0-!
! 9GRRN! 9*M!98M!92M!@DI#! ">>9*M!">>98!
! .DBJCWBN! .*M!.8M!.2M!@DI#! ">>.*M!">>.8!
1@I?BFJIBK! .?BHD!5*II@LLJRK@6! o! "-$o!
! 0K@IDCJIBK!2KGL@D! 0! "-$0!
! +@K@2GEE!2KGL@D! +! "-$+!
1@eeBFJF@! *KK!&GGE!+NA@L! 1! "-$1!
!
p!)GFaBII@LLJRK@!L?BHDL!BC@!FGD!BLLJOF@S!B!CGGE!FPER@C#!
p!*KK!LABI@L!WJD?!B!I@JKJFO!?@JO?D!GH!K@LL!D?BF!$Qa>q!BC@!FGD!BLLJOF@S!B!CGGE!FPER@C#!
p!%A@F!BJC!LABI@L!D?BD!BC@!IGT@C@S!RN!D?@!CGGH!GH!B!RPJKSJFO!C@I@JT@!B!FPER@C!5PLPBKKN!9!
GC!.6#!
p!9BFSJFO!SGIUL!WJD?!CGGHL!BC@!OJT@F!B!FPER@C!HCGE!D?@!OCJS!LNLD@E#!
!
4@TJBDJGFL!HCGE!D?@!LDBFSBCS!GHD@F!GIIPC!R@IBPL@!GH!A?NLJIBK!BFS!?JLDGCJIBK!IJCIPELDBFI@L!@FIGPFD@C@S!
JF!ABCDJIPKBC!RPJKSJFOL#!
!
8-7 '.4#*,<#",'*+!#++,4*&/!+1#)&!#"!6,"!
!
+?@!2&.:!2GEEJDD@@!BLLJOFL!LABI@!DG!D?@!HGKKGWJFO!GCOBFJeBDJGFLV!
!
• *IBS@EJI!4@ABCDE@FDL!BFS!4JTJLJGFL!
• 'FS@A@FS@FD!C@L@BCI?!2@FD@CL!BFS!9BRGCBDGCJ@L!
• *SEJFJLDCBDJT@!%HHJI@L!
• :C@LJS@FD^L!BFS!:CGTGLD^L!%HHJI@LM!4@BFL^!%HHJI@LM!rJI@!:C@LJS@FDL^!%HHJI@LM!BFS!D?@!%HHJI@L!GH!D?@!
2?BJCEBF!BFS!GH!D?@!.@IC@DBCN!GH!D?@!2GCAGCBDJGF!
!
!
!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
"
!3FK@LL!JD!JL!B!E@eeBFJF@!K@T@K!
8-8 "=&!('0.!.&30,.&/!/#"#!&%&6&*"+!
!
+?@!HGKKGWJFO!HGPC!SBDB!@K@E@FDL!BC@!C@bPJC@S!HGC!@BI?!CGGE!C@IGCS@S!JF!D?@!.ABI@!*IIGPFDJFO!
JFT@FDGCN!SBDBRBL@V!
!
• 1'+!CGGE!FPER@C!
• &GGE!PL@!
• %COBFJeBDJGFBK!BLLJOFE@FD!
• *C@B!GH!D?@!CGGE!JF!LbPBC@!H@@D!
!
+?@!DWG!C@AC@L@FDBDJGFL!GH!D?@!HGPC!C@bPJC@S!SBDB!@K@E@FDL!BC@!BL!HGKKGWLV!
!
• ;KGGCAKBFL!5OCBA?JI6!
• 4BDBRBL@!5DBRPKBC6!
!
8-> '"=&.!/#"#!&%&6&*"+!
!
+?@!.ABI@!*IIGPFDJFO!?GE@ABO@M!?DDALVddHKGGCAKBFL#EJD#@SPdM!?BL!KJFUL!DG!8PJKSJFO!BFS!4@ABCDE@FD!
&GGE!9JLDL!BFS!DG!4@ABCDE@FDBK!.A@IJBK!'FD@C@LD!&@AGCDL#!'F!BSSJDJGF!DG!D?@!HGPC!C@bPJC@S!SBDB!@K@E@FDLM!
D?@L@!C@AGCDL!SJLAKBN!BFGD?@C!SBDB!@K@E@FDM!BLLGIJBD@S!WJD?!@BI?!CGGEM!IBKK@S!D?@!gOCGPAg!HJ@KS#!!4BDB!
SJLAKBN@S!JF!D?JL!HJ@KS!?BL!R@@F!ACGTJS@S!GC!C@bP@LD@S!RN!D?@!S@ABCDE@FDL!DG!W?JI?!D?@!CGGEL!BC@!
BLLJOF@S#!!
!
1GC@GT@CM!GD?@C!SBDB!@K@E@FDL!BC@!PL@S!HGC!LA@IJBK!APCAGL@L!W?JI?!EBN!GHD@F!R@!C@HK@ID@S!JF!
4@ABCDE@FDBK!.A@IJBK!'FD@C@LD!&@AGCDL#!!
.''6!0+&!/&(,*,",'*+!
DG>HFI5!!+?@!HGKKGWJFO!S@HJFJDJGFL!BC@!RBL@S!PAGF!D?GL@!APRKJL?@S!JF!D?@!->>Y!@SJDJGF!GH!D?@!3#!.#!
4@ABCDE@FD!GH!0SPIBDJGF^L!g:GLDL@IGFSBCN!0SPIBDJGF!;BIJKJDJ@L!'FT@FDGCN!BFS!2KBLLJHJIBDJGF!1BFPBKg!
5;'216#!!+?@N!?BT@!R@@F!BSBAD@S!BFS!BSS@S!DGM!DG!BKJOF!WJD?!1'+QL!HBIJKJDN!LABI@!EBFBO@E@FD!ACBIDJI@L!
BFS!AGKJIJ@L#!+?@N!LPAAGCD!D?@!ACGI@LL!GH!JFSJC@ID!IGLD!C@IGT@CN!BL!W@KK!BL!O@F@CBK!BSEJFJLDCBDJGF!BFS!
ACGTJLJGF!GH!IGEEPFJDN!JFHGCEBDJGF#!
!
Major Use Techspace Abbrev.
Classrooms CLASSRMS
Laboratories LABS
Offices OFFICES
Study STUDY
Special Use SPECIAL
General Use GENERAL
Support SUPPORT
Healthcare HEALTH
Residential RESIDENT
Unclassified UNCLASS
Building Service BLDG SRV
Circulatory CIRCULAT
Mechanical MECHANIC
!
1GC@!S@DBJK@S!JFHGCEBDJGF!GF!D?JL!LPR`@ID!IBF!R@!HGPFS!BD!?DDALVddHKGGCAKBFL#EJD#@SPd!PFS@C!
g0<:9%&*+'%).gV!&GGE!3L@!4@HJFJDJGFL#!!
>-2 6#?'.!.''6!0+&@!)%#++.''6+!
+?JL!IBD@OGCN!BOOC@OBD@L!IKBLLCGGE!HBIJKJDJ@L!BL!BF!JFLDJDPDJGFaWJS@!C@LGPCI@M!@T@F!D?GPO?!D?@L@!BC@BL!
EBN!HBKK!PFS@C!SJHH@C@FD!K@T@KL!GH!GCOBFJeBDJGFBK!IGFDCGK#!+?@!D@CE!sIKBLLCGGEq!JFIKPS@L!FGD!GFKN!O@F@CBK!
APCAGL@!IKBLLCGGELM!RPD!BKLG!K@IDPC@!?BKKLM!C@IJDBDJGF!CGGELM!L@EJFBC!CGGELM!BFS!GD?@C!LABI@L!PL@S!
ACJEBCJKN!HGC!LI?@SPK@S!FGFaKBRGCBDGCN!JFLDCPIDJGF#!
!
67878!9-(%%#$$:!
JGH?900I<5!529*..&%%1!d!29*..!d!296!
<3*#&#/#+&V!!*!CGGE!PL@S!HGC!LI?@SPK@S!JFLDCPIDJGF!BFS!FGD!DJ@S!DG!B!LA@IJHJI!LPR`@ID!GC!SJLIJAKJF@!RN!@bPJAE@FD!JF!
D?@!CGGE!GC!RN!D?@!IGFHJOPCBDJGF!GH!D?@!CGGE#!
<34E,#2/#+&V!!+?@L@!CGGEL!EBN!R@!IBKK@S!O@F@CBK!APCAGL@!IKBLLCGGEL!GC!L@EJFBC!CGGEL#!!+?@N!EBN!R@!@bPJAA@S!
WJD?!DBRK@D!BCEI?BJCL!GC!WJD?!DBRK@L!BFS!I?BJCL#!!+?@N!EBN!IGFDBJF!EPKDJE@SJB!GC!D@K@IGEEPFJIBDJGFL!
@bPJAE@FD#!!*!IKBLLCGGE!EBN!R@!HPCFJL?@S!WJD?!LA@IJBK!@bPJAE@FD!BAACGACJBD@!DG!B!LA@IJHJI!BC@B!GH!LDPSNM!JH!D?JL!
@bPJAE@FD!SG@L!FGD!C@FS@C!D?@!CGGE!PFLPJDBRK@!HGC!PL@!RN!IKBLL@L!JF!GD?@C!BC@BL!GH!LDPSN#!
!
!
6787;!9-(%%#$$:!)'#<2,'!
JGH?900I<5(AFK9DDHGG?(DLF(M(FK9(DL(M(FDC!
<3*#&#/#+&V!!*!CGGE!D?BD!SJC@IDKN!L@CT@L!GF@!GC!EGC@!IKBLLCGGEL!GC!K@IDPC@!?BKKL!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!
JF!D?GL@!CGGEL#!
<34E,#2/#+&V!!'FIKPS@L!ACG`@IDJGF!CGGELM!D@K@IGEEPFJIBDJGFL!IGFDCGK!RGGD?LM!AC@ABCBDJGF!CGGELM!IGBD!CGGELM!
IKGL@DLM!LDGCBO@!CGGELM!LDGIU!CGGELM!@bPJAE@FD!JLLP@!CGGEL!BFS!LJEJKBC!HBIJKJDJ@LM!JH!D?@N!L@CT@!IKBLLCGGEL!GC!
K@IDPC@!?BKKL#!
(
!
6787=!>',*+#'!?(--!
JGH?900I<5!5902+3&0!7*99!d!902+!7!d!976!
<3*#&#/#+&5(((+NAJIBKKN!B!KBCO@!CGGE!PL@S!DG!S@KJT@C!K@IDPC@L!BL!LI?@SPK@S!JFLDCPIDJGF!DG!B!KBCO@!FPER@C!GH!
LDPS@FDL!D?BD!SG@L!FGD!C@bPJC@!LA@IJBK!APCAGL@!@bPJAE@FD#!
<34E,#2/#+&5(((*!K@IDPC@!?BKK!EBN!R@!@bPJAA@S!WJD?!DBRK@DaBCE!I?BJCLM!GHD@F!HJ[@S!DG!B!LD@AA@S!HKGGC#!!'D!EBN!R@!
HPCFJL?@S!WJD?!LA@IJBK!@bPJAE@FD!BAACGACJBD@!DG!B!LA@IJHJI!BC@B!GH!LDPSNM!JH!@bPJAE@FD!SG@L!FGD!C@FS@C!D?@!
CGGE!PFLPJDBRK@!HGC!PL@!RN!IKBLL@L!JF!GD?@C!BC@BL!GH!LDPSN#!
!
!
>-7 6#?'.!.''6!0+&@!%#$'.#"'.,&+!
*!KBRGCBDGCN!JL!B!HBIJKJDN!I?BCBID@CJe@S!RN!LA@IJBK!APCAGL@!@bPJAE@FD!GC!B!LA@IJHJI!LABI@!IGFHJOPCBDJGF!
D?BD!KJEJDL!JFLDCPIDJGFBK!GC!C@L@BCI?!BIDJTJDJ@L!DG!B!ABCDJIPKBC!SJLIJAKJF@!GC!B!IKGL@KN!C@KBD@S!OCGPA!GH!
SJLIJAKJF@L#!
+?@L@!BIDJTJDJ@L!EBN!R@!JFSJTJSPBK!GC!OCGPA!JF!FBDPC@M!WJD?!GC!WJD?GPD!LPA@CTJLJGF#!9BRGCBDGCJ@L!EBN!R@!
HGPFS!JF!BKK!HJ@KSL!GH!LDPSN!JFIKPSJFO!K@DD@CLM!?PEBFJDJ@LM!FBDPCBK!LIJ@FI@LM!LGIJBK!LIJ@FI@LM!TGIBDJGFBK!BFS!
D@I?FJIBK!SJLIJAKJF@LM!@DI#!
+?@!FBDPC@!GH!KBRGCBDGCN!@[A@CJ@FI@L!?BL!I?BFO@S!JF!EBFN!SJLIJAKJF@L!WJD?!D?@!JFDCGSPIDJGF!GH!IGEAPD@C!
LJEPKBDJGF!JF!IGERJFBDJGF!WJD?M!GC!BL!C@AKBI@E@FD!GHM!D?@!GKS!sW@D!KBRq!@[A@CJ@FI@!JF!RGD?!FBDPCBK!BFS!
LGIJBK!LIJ@FI@L#!2PCCJIPKBC!JFD@FD!L?GPKS!R@!IGFLJS@C@S!BL!W@KK!BL!D?@!A?NLJIBK!LDCPIDPC@!GH!D?@!LABI@#!
!
67;78!&02:(-!@'%'(#,A!>(4$#(*$#B!
JGH?900I<5!5*)'1*9!&.27!9*8!d!*)!9*8!d!*)6!
<3*#&#/#+&5((*!CGGE!PL@S!HGC!KBRGCBDGCN!BAAKJIBDJGFL!BFS!C@L@BCI?!JFTGKTJFO!D?@!PL@!GH!BFJEBKL!BFS!C@bPJCJFO!
LA@IJBK!APCAGL@!@bPJAE@FD!HGC!LDBHH!BFSdGC!LDPS@FD!@[A@CJE@FDBDJGF!GC!GRL@CTBDJGF#!
<34E,#2/#+&5('FIKPS@L!BFJEBK!CGGELh!IBO@!CGGELh!LDBKKLh!WBCSLh!BFS!ACGI@SPC@M!GA@CBDJFOM!C@IGT@CNM!JLGKBDJGFM!
bPBCBFDJF@M!BFS!LJEJKBC!LABI@L!HGC!JFLDCPIDJGF!BFS!C@L@BCI?#!
!
!
67;7;!&02:(-!)'#<2,'!
JGH?900I<5!5*)'1*9!.0&r'20!d!*)!.r!d!*.6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!GF@!GC!EGC@!BFJEBK!C@L@BCI?!KBRGCBDGCJ@L!BL!BF!@[D@FLJGF!GH!D?@!
BIDJTJDJ@L!JF!D?GL@!CGGEL#!
<34E,#2/#+&5(('FIKPS@L!H@@S!LDGCBO@!CGGELM!H@@S!EJ[JFO!CGGELM!IBO@!WBL?JFO!CGGELM!IBO@!LDGCBO@!CGGELM!IBLDJFO!
CGGELM!JFLDCPE@FD!CGGELM!BFS!JFD@CFBK!5FGFAPRKJI6!IJCIPKBDJGF!LABI@#!
!
!
67;7=!C(#D!@$$:!
JGH?900I<5!54*&j!&%%1!d!4j!&1!d!4j6!
<3*#&#/#+&5((*!CGGE!ACJEBCJKN!PL@S!HGC!D?@!ACGI@LLJFO!BFS!S@T@KGAE@FD!GH!A?GDGOCBA?JI!HJKEM!HGC!C@L@BCI?!GC!
D@BI?JFO!APCAGL@L#!!'FIKPS@S!BC@!KJO?D!KGIU!T@LDJRPK@L!D?BD!DNAJIBKKN!BC@!BF!JFD@OCBK!ABCD!GH!B!SBCU!CGGE#!
MIT Design Standards | Space Accounting Thematic Folder ! !Page 18 of 32
!
!
!
!
67;76!C#(E*203!@$$:!
JGH?900I<5!54&*;+')(!&%%1!d!4&*;+!d!4&6!
<3*#&#/#+&5((*!CGGE!ACJEBCJKN!PL@S!HGC!BIDJTJDJ@L!D?BD!C@bPJC@!D?@!PL@!GH!SCBHDJFO!@bPJAE@FD#!
!
!
67;7F!G0%*#+,*2$0!)A$H!I$#!9-(%%!>(4$#(*$#B!J!KG9LM!
JGH?900I<5!5').+&32+'%)!.7%:!d!').+&2!d!'.6!
<3*#&#/#+&5((*!CGGE!PL@S!ACJEBCJKN!RN!C@OPKBCKN!LI?@SPK@S!IKBLL@L!D?BD!C@bPJC@!LA@IJBK!APCAGL@!@bPJAE@FD!LPI?!BL!
AGW@C!DGGKL!BFS!?BFS!DGGKLM!BFS!D?@!KJU@M!HGC!LDPS@FD!ABCDJIJABDJGFM!@[A@CJE@FDBDJGFM!GRL@CTBDJGFM!GC!ACBIDJI@!JF!
B!HJ@KS!GH!LDPSN#!!*F!'FLDCPIDJGF!.?GA!JL!S@LJOF@S!HGC!BFSdGC!HPCFJL?@S!WJD?!@bPJAE@FD!DG!L@CT@!D?@!F@@SL!GH!B!
ABCDJIPKBC!SJLIJAKJF@!HGC!OCGPA!JFLDCPIDJGF!JF!C@OPKBCKN!LI?@SPK@S!IKBLL@L#!!+?@!S@LJOF!GH!BFSdGC!@bPJAE@FD!JF!
LPI?!B!CGGE!FGCEBKKN!KJEJDL!GC!AC@IKPS@L!JDL!PL@!HGC!GD?@C!SJLIJAKJF@L#!
!
!
67;7N!G0%*#+:'0*!@$$:!
JGH?900I<5!5').+&310)+!&%%1!d!').+&3!d!'&6!
<3*#&#/#+&5((*!CGGE!IGFDBJFJFO!LA@IJBKJe@S!E@BLPCJFO!JFLDCPE@FDL!BFS!ACJEBCJKN!S@TGD@S!DG!D?@JC!PL@M!SJC@IDKN!
L@CTJFO!GF@!GC!EGC@!KBRGCBDGCJ@LM!BL!BF!@[D@FLJGF!GH!D?@!@[A@CJE@FDBK!BIDJTJDJ@L!JF!D?GL@!CGGEL#!
(
67;7O!>(4$#(*$#B!)'#<2,'!
JGH?900I<5!59*8%&*+%&/!.r2!d!9*8!.r!d!9r6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!GF@!GC!EGC@!C@L@BCI?!GC!D@BI?JFO!KBRGCBDGCJ@L!BL!BF!@[D@FLJGF!GH!D?@!
BIDJTJDJ@L!JF!D?GL@!CGGEL#(
<34E,#2/#+&5(('FIKPS@L!ACG`@IDJGF!CGGELM!D@K@IGEEPFJIBDJGFL!IGFDCGK!RGGD?LM!AC@ABCBDJGF!CGGELM!IGBD!CGGELM!
IKGL@DLM!LDGCBO@!CGGELM!LDGIU!CGGELM!@bPJAE@FD!JLLP@!CGGELM!D@EAGCBCN!?BeBCSGPL!EBD@CJBKL!LDGCBO@M!IGKS!
CGGELM!BFS!LJEJKBC!HBIJKJDJ@LM!JH!D?@N!L@CT@!C@L@BCI?!GC!D@BI?JFO!KBRGCBDGCJ@L#(
!
!
67;7P!>(4$#(*$#B!)+HH$#*!)A$H!
JGH?900I<5!59*8!.3::%&+!.7%:!d!9*8!.:!d!9.6!
<3*#&#/#+&5((*!L?GA!WJD?!EBI?JF@!DGGKL!GC!GD?@C!DGGKL!HGC!IPDDJFOM!HGCEJFOM!HBRCJIBDJFO!GC!BLL@ERKJFO!@bPJAE@FD!
ACJEBCJKN!JF!LPAAGCD!GH!C@L@BCI?!KBRGCBDGCJ@L#!+NAJIBKKNM!LA@IJBK!KBR!HJ[DPC@LM!AJAJFOM!OKBLLWBC@M!@K@IDCJIBK!GC!
@K@IDCGFJI!@bPJAE@FD!BC@!ACGSPI@S!GC!C@ABJC@S!JF!LPAAGCD!GH!D?@!C@L@BCI?!HPFIDJGF#!
!
!
67;7Q!L+%2,!R#(,*2,'!@$$:!
JGH?900I<5!513.'2!:&*2+'20!d!13!:&*!d!136!
<3*#&#/#+&5((*!CGGE!PL@S!ACJEBCJKN!HGC!JFSJTJSPBK!LDPS@FD!@[A@CJE@FDBDJGFM!GRL@CTBDJGF!GC!ACBIDJI@!JF!D?@!HJ@KS!GH!
EPLJI#!!.DBDJGFL!EBN!R@!OCGPA@S!GC!JFSJTJSPBKJe@S#!
!
!
67;78S!@'%'(#,A!>(4$#(*$#B!
JGH?900I<5!5&0.0*&27!9*8!d!&.!9*8!d!&96!
<3*#&#/#+&5((*!CGGE!PL@S!ACJEBCJKN!HGC!KBRGCBDGCN!@[A@CJE@FDBDJGFM!C@L@BCI?!GC!DCBJFJFO!JF!C@L@BCI?!E@D?GSLM!GC!
ACGH@LLJGFBK!C@L@BCI?!BFS!GRL@CTBDJGFM!GC!LDCPIDPC@S!IC@BDJT@!BIDJTJDN!WJD?JF!B!LA@IJHJI!ACGOCBE#(
<34E,#2/#+&5(((+?@!BIDJTJDJ@L!JF!D?@L@!CGGEL!BC@!O@F@CBKKN!IGFHJF@S!DG!HBIPKDNM!C@L@BCI?!BLLGIJBD@L!BFS!OCBSPBD@!
LDPS@FDL!BFS!BC@!BAAKJIBRK@!DG!BFN!BIBS@EJI!SJLIJAKJF@#!!*IDJTJDJ@L!EBN!JFIKPS@!@[A@CJE@FDBDJGFM!BAAKJIBDJGFM!
GRL@CTBDJGFM!IGEAGLJDJGFM!GC!C@L@BCI?!DCBJFJFO!JF!B!LDCPIDPC@S!@FTJCGFE@FD!SJC@ID@S!RN!GF@!GC!EGC@!HBIPKDN!GC!
ACJFIJABK!JFT@LDJOBDGC5L6#!!+?@L@!BIDJTJDJ@L!SG!FGD!JFIKPS@!ACBIDJI@!GC!JFS@A@FS@FD!LDPSN!ACG`@IDL!BFS!BIDJTJDJ@L!
W?JI?M!BKD?GPO?!S@KJT@CJFO!gF@W!UFGWK@SO@g!DG!B!LDPS@FDM!BC@!FGD!JFD@FS@S!HGC!B!RCGBS@C!BIBS@EJI!5GC!
LAGFLGCJFO6!IGEEPFJDN!5@#O#M!B!AC@L@FDBDJGF!GC!APRKJIBDJGF6#!!+?JL!IBD@OGCN!JFIKPS@L!KBRL!D?BD!BC@!PL@S!HGC!
@[A@CJE@FDLM!D@LDJFO!GC!gSCN!CPFLg!JF!LPAAGCD!GH!JFLDCPIDJGFBKM!C@L@BCI?!GC!APRKJI!L@CTJI@!BIDJTJDJ@L#(
!
!
67;788!@'%'(#,A!>(4$#(*$#B!TEE2,'!
JGH?900I<5!5&.27!9*8a%;;'20!d!&0.!9%!d!&%6!
<3*#&#/#+&5((*!C@L@BCI?!KBRGCBDGCN!D?BD!JFIKPS@L!B!WCJDJFO!LPCHBI@M!LPI?!BL!B!S@LU!GC!DBRK@M!PAGF!W?JI?!D?@!
C@L@BCI?@C!EBN!C@IGCS!KBRGCBDGCN!GRL@CTBDJGFL!BFS!D?@!KJU@#!
(
(
67;78;!)A$H!)'#<2,'!
JGH?900I<5!5.7%:!.0&r'20!d!.7:!.r!d!.r6!
<3*#&#/#+&5((*!LABI@!D?BD!SJC@IDKN!L@CT@L!GF@!GC!EGC@!KBRGCBDGCN!LPAAGCD!L?GAL!GC!JFLDCPIDJGF!L?GAL!BL!BF!
@[D@FLJGF!GH!D?@!BIDJTJDJ@L!JF!D?GL@!CGGEL#(
<34E,#2/#+&5(('FIKPS@L!LDGIU!CGGEL!HGC!@bPJAE@FDM!DGGKLM!LPAAKJ@L!BFS!EBD@CJBKL!PL@S!JF!L?GAL#(
!
!
67;78=!)*+U2$!
JGH?900I<5!5.+34'%!d!.+34'%!d!.46!
<3*#&#/#+&5((*!CGGE!PL@S!ACJEBCJKN!RN!JFHGCEBKKN!GC!JCC@OPKBCKN!LI?@SPK@S!IKBLL@L!D?BD!C@bPJC@!LA@IJBK!APCAGL@!
@bPJAE@FD!HGC!LDPS@FD!ABCDJIJABDJGFM!@[A@CJE@FDBDJGFM!GRL@CTBDJGFM!GC!ACBIDJI@!JFTGKTJFO!S@LJOFM!EGS@K!RPJKSJFO!
GC!GD?@C!LPI?!BIDJTJDN!C@KBDJFO!DG!BCI?JD@IDPC@!GC!D?@!BCDL#!
(
(
67;786!V'(,A203!>(4$#(*$#B!
JGH?900I<5!5+0*27')(!9*8!d!+2!9*8!d!+96!
<3*#&#/#+&5((*!CGGE!PL@S!ACJEBCJKN!HGC!HGCEBKKN!GC!C@OPKBCKN!LI?@SPK@S!IKBLL@L!D?BD!C@bPJC@!LA@IJBK!APCAGL@!
@bPJAE@FD!GC!B!LA@IJHJI!CGGE!IGFHJOPCBDJGF!HGC!LDPS@FD!ABCDJIJABDJGFM!@[A@CJE@FDBDJGFM!GRL@CTBDJGFM!GC!ACBIDJI@!
JF!BF!BIBS@EJI!SJLIJAKJF@#(
<34E,#2/#+&5((*!D@BI?JFO!KBRGCBDGCN!JL!S@LJOF@S!HGC!GC!HPCFJL?@S!WJD?!@bPJAE@FD!DG!L@CT@!D?@!F@@SL!GH!B!
ABCDJIPKBC!SJLIJAKJF@!HGC!OCGPA!JFLDCPIDJGF!JF!HGCEBKKN!GC!C@OPKBCKN!LI?@SPK@S!IKBLL@L#!!+?JL!LA@IJBK!@bPJAE@FD!
FGCEBKKN!KJEJDL!GC!AC@IKPS@L!D?@!CGGE^L!PL@!RN!GD?@C!SJLIJAKJF@L#(
(
!
>-8 6#?'.!.''6!0+&@!'((,)&+!
%HHJI@!HBIJKJDJ@L!BC@!JFSJTJSPBKM!EPKDJA@CLGFM!GC!WGCULDBDJGF!LABI@L!LA@IJHJIBKKN!BLLJOF@S!DG!BIBS@EJIM!
BSEJFJLDCBDJT@M!BFS!L@CTJI@!HPFIDJGFL!GH!D?@!JFLDJDPD@#!
!
67=78!9$0E'#'0,'!@$$:!
JGH?900I<5!52%);0&0)20!&%%1!d!2%);!d!2)6!
<3*#&#/#+&5((*!CGGE!L@CTJFO!BF!GHHJI@!IGEAK@[!BFS!PL@S!ACJEBCJKN!HGC!LDBHH!E@@DJFOL!BFS!S@ABCDE@FDBK!BIDJTJDJ@L#(
<34E,#2/#+&5(((%HD@F!PL@S!RN!B!LA@IJHJI!GCOBFJeBDJGFBK!PFJD!GC!GHHJI@!BC@BM!B!IGFH@C@FI@!CGGE!JL!SJLDJFOPJL?@S!HCGE!
HBIJKJDJ@L!LPI?!BL!L@EJFBC!CGGELM!K@IDPC@!CGGELM!BFS!IKBLLCGGEL!R@IBPL@!JD!JL!PL@S!ACJEBCJKN!HGC!BIDJTJDJ@L!GD?@C!
D?BF!LI?@SPK@S!IKBLL@L#!!*!IGFH@C@FI@!CGGE!JL!JFD@FS@S!ACJEBCJKN!HGC!HGCEBK!OBD?@CJFOL!W?@C@BL!B!KGPFO@!JL!
JFD@FS@S!HGC!C@KB[BDJGF!BFS!IBLPBK!JFD@CBIDJGF#(
(
(
67=7;!TEE2,'!
JGH?900I<5!5%;;'20!d!%;;!d!%;6!
<3*#&#/#+&5((*!CGGE!PL@S!RN!GF@!GC!EGC@!A@CLGFL!WGCUJFO!ACJFIJABKKN!BD!S@LULM!DBRK@L!GC!WGCULDBDJGFL#(
<34E,#2/#+&5((('FIKPS@L!HBIPKDNM!BSEJFJLDCBDJT@M!IK@CJIBKM!OCBSPBD@!LDPS@FDM!D@BI?JFO!BLLJLDBFD!BFS!GD?@C!LDPS@FD!
GHHJI@L!W?JI?!EBN!IGFDBJF!BFN!GH!B!TBCJ@DN!GH!DNAJIBK!GHHJI@!HPCFJL?JFOL!GC!@bPJAE@FD#(
(
(
67=7=!TEE2,'!)'#<2,'!
JGH?900I<5!5%;;'20!.0&r'20!d!%;;!.r!d!%.6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!BF!GHHJI@!GC!OCGPA!GH!GHHJI@L!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!JF!D?GL@!
CGGEL#(
<34E,#2/#+&5(('FIKPS@L!HJK@!CGGELM!RC@BU!CGGELM!UJDI?@F@DD@L!L@CTJFO!GHHJI@!BC@BLM!IGAN!BFS!;*<!CGGELM!IKGL@DLM!
C@IGCSL!CGGELM!GHHJI@!LPAAKN!CGGELM!HJCLD!BJS!CGGEL!L@CTJFO!GHHJI@!BC@BL!BFS!LDPS@FD!IGPFL@KJFO!CGGEL#(
(
(
67=76!R#2<(*'!92#,+-(*2$0!
JGH?900I<5!5:r+!2'&239*+'%)!d!:!2'&2!d!:26!
<3*#&#/#+&5(((:BLLBO@WBN!GC!BJLK@!LABI@!PL@S!HGC!JFD@CFBK!BII@LL!DG!B!LPJD@!GH!CGGEL!GC!LPRaSJTJLJGFL!GH!LABI@#!!'D!JL!
S@ABCDE@FDBKKN!IGFDCGKK@S!BFS!GFKN!JFSJC@IDKN!BII@LLJRK@!DG!D?@!APRKJI#(
(
(
67=7F!R#2<(*'!>(<(*$#B!
JGH?900I<5!5:r+!9*r*+%&/!d!:!9*r!d!:96!
<3*#&#/#+&5(((*!KBTBDGCN!HBIJKJDN!D?BD!JL!KJEJD@S!DG!PL@!RN!D?@!GIIPABFDL!GH!D?@!JEE@SJBD@KN!BS`BI@FD!BLLJOFBRK@!
BC@B#!!+?@L@!CGGEL!BC@!DNAJIBKKN!FGD!KGIBD@S!GF!APRKJI!IGCCJSGCL!FGC!F@@S!D?@N!R@!SJHH@C@FDJBD@S!R@DW@@F!EBK@!
GC!H@EBK@!KBTBDGCJ@L#(
(
(
67=7N!)',#'*(#BW@','H*2$0!@$$:!
JGH?900I<5!5.02/d&020:+'%)!d!.02/d&!d!.06!
<3*#&#/#+&5((*!CGGE!PL@S!RN!L@IC@DBCJBK!A@CLGFF@K!BFSdGC!HGC!C@I@ADJGF!GH!TJLJDGCL!DG!GIIPABFDL!GH!BS`BI@FD!
GHHJI@L#(
(
(
67=7O!X(+-*!
JGH?900I<5!5r*39+!d!r*39+!d!r*6!
<3*#&#/#+&5((*!LA@IJBKKN!IGFLDCPID@S!CGGE!HGC!D?@!LBH@aU@@AJFO!GH!TBKPBRK@L#(
!
!
>-> 6#?'.!.''6!0+&@!+"0/:!
.DPSN!LABI@!JL!IKBLLJHJ@S!JFDG!HJT@!IBD@OGCJ@LV!LDPSN!CGGEM!LDBIUM!GA@FaLDBIU!LDPSN!CGGEM!ACGI@LLJFO!
CGGEM!BFS!LDPSN!L@CTJI@#!%HHJI@L!PL@S!HGC!KJRCBCN!BIDJTJDJ@L!BC@!IGS@S!BL!GHHJI@!HBIJKJDJ@L#!*!LDPSN!LABI@!
EBN!IGFDBJF!@bPJAE@FD!GC!EBD@CJBKL!D?BD!BJS!D?@!LDPSN!GC!K@BCFJFO!ACGI@LL!5@#O#M!IGEAPD@CLM!EPKDJE@SJB!
IBCC@KLM!24!BFS!4r4!AKBN@CLM!DNA@WCJD@CLM!C@IGCSL!BFS!DBA@L6!BFS!D?BD!SG!FGD!C@LDCJID!D?@!LABI@!DG!B!
ABCDJIPKBC!BIBS@EJI!SJLIJAKJF@!GC!SJLIJAKJF@!OCGPA#!Z?@C@BL!B!.DPSN!&GGE!EBN!BAA@BC!JF!BKEGLD!BFN!DNA@!
GH!RPJKSJFO!GF!IBEAPL!5@#O#M!BIBS@EJIM!C@LJS@FDJBKM!LDPS@FD!L@CTJI@6M!.DBIULM!%A@Fa.DBIU!.DPSN!&GGELM!
BFS!:CGI@LLJFO!&GGEL!BC@!DNAJIBKKN!KGIBD@S!JF!I@FDCBKM!RCBFI?M!BFS!S@ABCDE@FDBK!KJRCBCJ@L#!'S@FDJHJIBDJGF!
GH!KJRCBCN!LABI@!L?GPKS!R@!EBS@!D?CGPO?!D?@!PL@!GH!HPFIDJGFBK!IBD@OGCJ@LM!BFS!S@ABCDE@FDBK!LABI@!
D?CGPO?!D?@!IGERJF@S!PL@!GH!BIBS@EJI!SJLIJAKJF@!BFS!HPFIDJGFBK!IBD@OGCJ@L#!
!
67678!>24#(#B!R#$,'%%203!@$$:!
JGH?900I<5!59'8&*&/!:&%20..!d!9'8!:&!d!9:6!
<3*#&#/#+&5((*!CGGE!GC!BC@B!S@TGD@S!DG!ACGI@LL@L!BFS!GA@CBDJGFL!JF!LPAAGCD!GH!KJRCBCN!HPFIDJGFL#(
<34E,#2/#+&5((*!ACGI@LLJFO!CGGE!JL!JFD@FS@S!HGC!LA@IJHJI!KJRCBCN!GA@CBDJGFL!W?JI?!LPAAGCD!D?@!GT@CBKK!KJRCBCN!
EJLLJGF#!!'FIKPS@S!BC@!IBCSM!EJICGHJI?@M!BFS!GFaKJF@!IBDBKGO!BC@BLh!C@H@C@FI@!S@LU!BFS!IJCIPKBDJGF!S@LU!BC@BLh!
RGGURJFSJFO!CGGELh!GFaKJF@!L@BCI?!CGGELh!EPKDJE@SJB!EBD@CJBKL!ACGI@LLJFO!BC@BLh!JFD@CKJRCBCN!KGBF!ACGI@LLJFO!
BC@BLh!BFS!GD?@C!BC@BL!WJD?!B!LA@IJHJI!ACGI@LL!GC!GA@CBDJGF!JF!LPAAGCD!GH!KJRCBCN!HPFIDJGFL#(
(
(
6767;!)*(,DW)*+UB!@$$:!
JGH?900I<5!5.+*2jd.+34/!d!.+j.+4!d!.&6!
<3*#&#/#+&5((*!IGERJFBDJGF!C@BSJFO!GC!LDPSN!CGGE!BFS!LDBIUM!O@F@CBKKN!WJD?GPD!A?NLJIBK!RGPFSBCJ@L!R@DW@@F!D?@!
LDBIU!BFS!LDPSN!BC@BL#(
<34E,#2/#+&5((.@BDJFO!BC@BL!JFIKPS@!D?GL@!DNA@L!GH!LDBDJGF!BFS!L@BDJFO!BCCBFO@E@FDL!S@LICJR@S!PFS@C!.DPSN!
&GGE#!!+?@!LDBIU!BC@BL!GH!D?@L@!CGGEL!EBN!JFIKPS@!IGKK@IDJGFL!GH!@SPIBDJGFBK!EBD@CJBK!JF!BFN!HGCE!GH!E@SJB#(
(
(
6767=!)*+UB!@$$:!
JGH?900I<5!5.+34/!&%%1!d!.+34/!d!./6!
<3*#&#/#+&5((*!CGGE!GC!BC@B!PL@S!RN!JFSJTJSPBKL!DG!LDPSN!BD!D?@JC!IGFT@FJ@FI@M!W?JI?!JL!FGD!C@LDCJID@S!DG!B!
ABCDJIPKBC!LPR`@ID!GC!SJLIJAKJF@!RN!IGFDBJF@S!@bPJAE@FD#(
<34E,#2/#+&5(('FIKPS@L!LDPSN!CGGEL!KGIBD@S!JF!KJRCBCJ@LM!C@LJS@FDJBK!HBIJKJDJ@LM!BIBS@EJI!GC!LDPS@FD!L@CTJI@!
HBIJKJDJ@LM!LDPSN!IBCC@K!BFS!RGGD?!BC@BLM!BFS!LJEJKBC!CGGEL!W?JI?!BC@!JFD@FS@S!HGC!O@F@CBK!LDPSN!
APCAGL@L#!.DPSN!LDBDJGFL!EBN!R@!OCGPA@SM!GC!JFSJTJSPBKJe@SM!BL!JF!B!IBCC@K#!.DPSN!LDBDJGFL!EBN!JFIKPS@!
EJICGIGEAPD@CLM!DNA@WCJD@CLM!IGEAPD@C!D@CEJFBKLM!EJICGHJKE!C@BS@CLM!GC!GD?@C!EPKDJE@SJB!
@bPJAE@FD#!.DPSN!CGGEL!BC@!ACJEBCJKN!PL@S!RN!LDPS@FDL!GC!LDBHH!HGC!K@BCFJFO!BD!D?@JC!IGFT@FJ@FI@M!
BKD?GPO?!BII@LL!EBN!R@!C@LDCJID@S!RN!B!IGFDCGKKJFO!PFJD!5@#O#M!S@ABCDE@FDBK!LDPSN!CGGE6#!'FIKPS@L!
EPLJI!KJLD@FJFO!CGGEL#,+*#$-(,3.%3,4N(+,(+/O3,(-"$/#-3%#.(3P"#2-3&/Q((D/"%1(,++-4(.,3(2,#-.,#$1("43%(71(
4/"%3&/4(+,(4/.**(*+,($3.,&#&'(./(/O3#,(E+&R3&E3N(.$/O+"'O(.EE344(-.1(73(,34/,#E/3%(71(.(E+&/,+$$#&'("&#/(A3Q'QN(
%32.,/-3&/.$(4/"%1(,++-CQ(()&E$"%34(-"4#E($#4/3&#&'(,++-4Q(
!
!
>-A 6#?'.!.''6!0+&@!+1&),#%!0+&!
+?JL!IBD@OGCN!JFIKPS@L!L@T@CBK!LABI@!PL@!IBD@OGCJ@L!D?BD!BC@!LPHHJIJ@FDKN!LA@IJBKJe@S!JF!D?@JC!ACJEBCN!
BIDJTJDN!GC!HPFIDJGF!DG!E@CJD!B!PFJbP@!LABI@!IGS@#!*KD?GPO?!EBFN!GH!D?@L@!LA@IJBK!PL@!HBIJKJDJ@L!ACGTJS@!
L@CTJI@!DG!GD?@C!BC@BLM!D?@JC!LA@IJBK!PL@!GC!IGFHJOPCBDJGF!SJIDBD@L!D?BD!D?@L@!BC@BL!FGD!R@!IGS@S!BL!
L@CTJI@!LABI@L#!
!
67F78!&02:(-!Y+(#*'#%!
JGH?900I<5!5*)'1*9!i3*&+0&.!d!*)!i+&!d!*i6!
<3*#&#/#+&5((*!CGGE!D?BD!?GPL@L!KBRGCBDGCN!BFJEBKL!PL@S!HGC!C@L@BCI?!GC!JFLDCPIDJGFBK!APCAGL@L#(
<34E,#2/#+&5(('FIKPS@L!BFJEBK!CGGELM!IBO@!CGGELM!LDBKKLM!WBCSL!BFS!LJEJKBC!CGGEL!JF!W?JI?!BFJEBKL!BC@!
EBJFDBJF@S!HGC!JFLDCPIDJGF!BFS!C@L@BCI?#(
(
(
67F7;!&*A-'*2,!K(,2-2*B!
JGH?900I<5!5*+790+'2!;*2'9!d!*+790+!d!*+6!
<3*#&#/#+&5((*!CGGE!GC!BC@B!PL@S!RN!LDPS@FDLM!LDBHH!GC!D?@!APRKJI!HGC!BD?K@DJI!GC!A?NLJIBK!@SPIBDJGF!BIDJTJDJ@L#(
<34E,#2/#+&5((('FIKPS@L!ONEFBLJPELM!RBLU@DRBKK!IGPCDLM!?BFSRBKK!IGPCDLM!LbPBL?!IGPCDLM!WC@LDKJFO!CGGELM!W@JO?D!
GC!@[@CIJL@!CGGELM!CBIbP@DRBKK!IGPCDLM!JFSGGC!LWJEEJFO!AGGKLM!JFSGGC!JI@!CJFULM!JFSGGC!DCBIULM!BFS!HJ@KS!?GPL@L#(
(
(
67F7=!&*A-'*2,!>$,D'#!@$$:!
JGH?900I<5!5*+7!9%2j0&!&%%1!d!*+7!9j!d!*96!
<3*#&#/#+&5((*!KGIU@C!CGGE!D?BD!SJC@IDKN!L@CT@L!BF!BD?K@DJI!GC!A?NLJIBK!@SPIBDJGF!HBIJKJDN!BL!BF!@[D@FLJGF!GH!D?@!
BIDJTJDJ@L!JF!D?BD!HBIJKJDN#(
(
(
67F76!&*A-'*2,!)'#<2,'!
JGH?900I<5!5*+790+'2!.0&r'20!d!*+7!.r!d!*r6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!BF!BD?K@DJI!GC!A?NLJIBK!@SPIBDJGF!HBIJKJDN!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!
JF!D?BD!HBIJKJDN#(
<34E,#2/#+&5(('FIKPS@L!FGFaGHHJI@!IGBI?@L^!CGGELM!DJIU@D!RGGD?LM!BFS!CGGEL!HGC!SC@LLJFOM!@bPJAE@FDM!LPAAKNM!
LDGCBO@M!HJCLDaBJSM!LUBD@aL?BCA@FJFOM!DGW@KLM!@DI#(
(
(
67F7F!&*A-'*2,!)A$Z'#!@$$:!
JGH?900I<5!5*+7!.7%Z0&!&%%1!d!*+7!.7!d!*Z6!
<3*#&#/#+&5((*!L?GW@C!CGGE!D?BD!SJC@IDKN!L@CTJI@L!BF!BD?K@DJI!GC!A?NLJIBK!@SPIBDJGF!HBIJKJDN!BL!BF!@[D@FLJGF!GH!D?@!
BIDJTJDJ@L!JF!D?BD!HBIJKJDN#(
(
(
67F7N!L'U2(!R#$U+,*2$0!
JGH?900I<5!5104'*!:&%432+'%)!d!104'*:!d!146!
<3*#&#/#+&5((*!CGGE!PL@S!HGC!D?@!ACGSPIDJGF!GC!SJLDCJRPDJGF!GH!EPKDJE@SJB!EBD@CJBKL!GC!LJOFBKL#(
<34E,#2/#+&5((('FIKPS@L!CGGEL!O@F@CBKKN!IBKK@S!+r!LDPSJGLM!CBSJG!LDPSJGLM!LGPFS!LDPSJGLM!A?GDG!LDPSJGLM!TJS@G!GC!
BPSJG!IBLL@DD@!BFS!LGHDWBC@!ACGSPIDJGF!GC!SJLDCJRPDJGF!CGGELM!BFS!E@SJB!I@FD@CL#!!+?@L@!CGGEL!?BT@!B!IK@BCKN!
S@HJF@S!ACGSPIDJGF!GC!SJLDCJRPDJGF!HPFIDJGF!D?BD!L@CT@L!B!RCGBS@C!BC@B!5@#O#M!S@ABCDE@FDM!@FDJC@!IBEAPL6!D?BF!
WGPKS!B!DNAJIBK!L@CTJI@!CGGE#(
(
(
67F7O!L'U2(!)'#<2,'!
JGH?900I<5!5104'*!.0&r'20!d!104'*.!d!1.6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!B!E@SJB!ACGSPIDJGF!GC!SJLDCJRPDJGF!CGGE!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!
JF!D?BD!HBIJKJDN#(
<34E,#2/#+&5((+?@!ACJEBCN!ICJD@CJGF!?@C@!JL!D?BD!D?@!CGGE!L?GPKS!L@CT@!B!E@SJB!ACGSPIDJGF!GC!SJLDCJRPDJGF!CGGE!
BFS!FGD!BFGD?@C!ACJEBCN!BIDJTJDN!CGGE#!!0[BEAK@L!JFIKPS@!HJKEM!DBA@M!GC!IBLL@DD@!KJRCBCJ@L!GC!LDGCBO@!BC@BLh!
E@SJB!@bPJAE@FD!LDGCBO@!CGGELh!C@IGCSJFO!CGGELh!@FOJF@@CJFO!EBJFD@FBFI@!CGGELh!SBCUCGGELh!AC@ABCBDJGF!
CGGELh!LDPSJG!IGFDCGK!RGGD?Lh!BFS!GD?@C!LPAAGCD!BC@BL!D?BD!LA@IJHJIBKKN!L@CT@!B!E@SJB!ACGSPIDJGF!GC!SJLDCJRPDJGF!
CGGE#(
!
>-B 6#?'.!.''6!0+&@!4&*&.#%!0+&!
(@F@CBK!PL@!HBIJKJDJ@L!BC@!I?BCBID@CJe@S!RN!B!RCGBS@C!BTBJKBRJKJDN!DG!HBIPKDNM!LDPS@FDLM!LDBHHM!GC!D?@!APRKJI!
D?BF!BC@!.A@IJBK!3L@!;BIJKJDJ@LM!W?JI?!BC@!DNAJIBKKN!KJEJD@S!DG!B!LEBKK!OCGPA!GC!LA@IJBK!AGAPKBDJGF#!(@F@CBK!
PL@!HBIJKJDJ@L!IGEACJL@!B!IBEAPL!O@F@CBK!L@CTJI@!GC!HPFIDJGFBK!LPAAGCD!LNLD@E!5@#O#M!BLL@ERKNM!@[?JRJDJGFM!
SJFJFOM!C@KB[BDJGFM!E@CI?BFSJLJFOM!C@IC@BDJGFM!O@F@CBK!E@@DJFOLM!BFS!SBN!IBC@6!HGC!D?@!JFLDJDPDJGFBK!BFS!
ABCDJIJABFD!IGEEPFJDN!AGAPKBDJGFL#!
!
67N78!9$(*!@$$:!
JGH?900I<5!52%*+!&%%1!d!2%*+!d!2+6!
<3*#&#/#+&5((*!IGBD!CGGE!D?BD!SJC@IDKN!L@CT@L!BF!BLL@ERKN!HBIJKJDN#(
(
(
67N7;!C(B!9(#'!
JGH?900I<5!54*/!2*&0!d!4*/!2&!d!426!
<3*#&#/#+&5((*!CGGE!PL@S!DG!ACGTJS@!SBN!GC!FJO?DM!I?JKS!GC!@KS@CKN!BSPKD!IBC@!BL!B!FGFE@SJIBK!L@CTJI@!DG!E@ER@CL!
GH!D?@!JFLDJDPDJGFBK!IGEEPFJDN#(
<34E,#2/#+&5(('FIKPS@L!BKK!ACJEBCN!BIDJTJDN!CGGEL!D?BD!ACGTJS@!GT@CLJO?DM!LPA@CTJLJGFM!S@T@KGAE@FDBK!DCBJFJFO!BFS!
O@F@CBK!A@CLGFBK!IBC@!HGC!BLLJOF@S!I?JKSC@F!GC!BSPKDL!5@#O#M!AKBN!BC@BLM!FGFaLDBHH!@BDJFO!BC@BLM!I?JKS!DCBJFJFO!
CGGELM!BFS!I?JKS!C@LD!CGGEL6#!!+?JL!DNA@!GH!HBIJKJDN!L@CT@L!BL!B!I@FDCBK!L@CTJI@!I@FD@C!HGC!HBIPKDNM!LDBHHM!BFS!
LDPS@FDLM!WJD?!E@ER@CL!GH!D?@!IGEEPFJDN!R@JFO!L@CT@S!BL!F@@S@S#!!+?JL!JL!FGD!B!E@SJIBK!IBC@!HBIJKJDN!5J#@#M!
E@SJIBK!BDD@FDJGF!JL!LDCJIDKN!KJEJD@S!DG!EBJFDBJFJFO!AC@LICJR@S!E@SJIBDJGF!LI?@SPK@L!BFS!ACGTJSJFO!HJCLD!BJS6#(
(
(
67N7=!C(B!9(#'!)'#<2,'!
JGH?900I<5!54*/!2*&0!.r!d!42!.r2!d!4.6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!B!ACJEBCN!BIDJTJDN!CGGE!JF!B!SBN!IBC@!HBIJKJDN!BL!BF!@[D@FLJGF!GH!D?@!
BIDJTJDJ@L!JF!D?BD!CGGE#(
<34E,#2/#+&5('FIKPS@L!LDGCBO@!CGGELM!IKGL@DLM!UJDI?@FLM!ABFDCJ@LM!ACJTBD@!GC!LDBHHaGFKN!C@LD!CGGELM!LDBHH!@BDJFO!BFS!
RC@BU!BC@BLM!BFS!GD?@C!DNAJIBK!L@CTJI@!CGGEL!D?BD!LPAAGCD!B!ACJEBCN!BIDJTJDN!BC@B#!!(
(
(
67N76![\A242*2$0!K(,2-2*B!
JGH?900I<5!50<7'8'+'%)!;*2'9!d!0<7'8!d!0<6!
<3*#&#/#+&5((*!CGGE!GC!BC@B!PL@S!HGC!@[?JRJDJGF!GH!EBD@CJBKLM!WGCUL!GH!BCDM!BCDJHBIDLM!@DI#M!BFS!JFD@FS@S!HGC!O@F@CBK!
PL@!RN!HBIPKDNM!LDPS@FDLM!LDBHHM!BFS!D?@!APRKJI#(
<34E,#2/#+&5((('FIKPS@L!RGD?!S@ABCDE@FDBK!BFS!JFLDJDPDJGFaWJS@!EPL@PELM!OBKK@CJ@L!BFS!LJEJKBC!@[?JRJDJGF!BC@BL!
W?JI?!BC@!PL@S!DG!SJLAKBN!EBD@CJBKL!BFS!JD@EL!HGC!TJ@WJFO!RN!RGD?!D?@!JFLDJDPDJGFBK!AGAPKBDJGF!BFS!D?@!APRKJI#(
(
(
67N7F![\A242*2$0!)'#<2,'!
JGH?900I<5!50<7'8'+'%)!.r2!d!0<7!.r!d!0.6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!BF!@[?JRJDJGF!HBIJKJDN!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!JF!D?BD!HBIJKJDN#(
<34E,#2/#+&5(('FIKPS@L!LDGCBO@!CGGELM!AC@ABCBDJGF!BC@BLM!ACG`@IDJGF!CGGELM!IGFDCGK!CGGELM!@DI@D@CBM!JH!D?@N!L@CT@!
@[?JRJDJGF!HBIJKJDJ@L#(
(
(
67N7N!K$$U!K(,2-2*B!
JGH?900I<5!5;%%4!;*2'9'+/!d!;%%4!d!;46!
<3*#&#/#+&5((*!CGGE!ACJEBCJKN!PL@S!HGC!@BDJFO#(
<34E,#2/#+&5(('FIKPS@L!SJFJFO!?BKKLM!IBH@D@CJBLM!LFBIU!RBCLM!C@LDBPCBFDL!BFS!LJEJKBC!@BDJFO!BC@BLM!JFIKPSJFO!D?GL@!JF!
C@LJS@FI@!?BKKLM!HBIPKDN!IKPRLM!BFS!@KL@W?@C@#!!+?JL!IBD@OGCN!JFIKPS@L!HBIJKJDJ@L!GA@F!DG!LDPS@FDLM!HBIPKDNM!LDBHHM!GC!
D?@!APRKJI!BD!KBCO@#!!'DL!ACJEBCN!SJLDJFIDJGF!JL!?BTJFO!LGE@!HGCE!GH!BIIGEEGSBDJGF!5L@BDJFOM!IGPFD@CLM!DBRK@L6!HGC!
@BDJFO!GC!SCJFUJFO#!!.JDaSGWF!KPFI?!CGGEL!BFS!T@FSJFO!BC@BL!WJD?!LPI?!BIIGEEGSBDJGF!BC@!JFIKPS@S#!!ZBKUa
BWBN!T@FSJFO!BC@BL!BC@!IGFLJS@C@S!E@CI?BFSJLJFO!HBIJKJDJ@L#(
(
(
67N7O!K$$U!K(,2-2*B!)'#<2,'!
JGH?900I<5!5;%%4!;*2'9!.r2!d!;%%4.r!d!;.6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!B!HGGS!HBIJKJDN!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!JF!D?BD!HBIJKJDN#(
<34E,#2/#+&5(('FIKPS@L!UJDI?@FL!BFS!GD?@C!AC@ABCBDJGF!BC@BLM!IGKS!LDGCBO@!BFS!HC@@e@C!C@HCJO@CBDJGF!CGGELM!
SJL?WBL?JFO!CGGELM!HGGS!L@CTJFO!BC@BLM!IK@BFJFO!BC@BL!BFS!T@FSJFO!BC@BL!SJC@IDKN!L@CTJFO!HGGS!HBIJKJDJ@L!GC!
BS`BI@FD!DG!@BDJFO!BC@BL#(
(
(
67N7P!>(+0U#B!K(,2-2*B!
JGH?900I<5!59*3)4&/!;*2'9!d!9*3)!d!9)6!
<3*#&#/#+&5((*!CGGE!ACJEBCJKN!PL@S!HGC!SGJFO!KBPFSCN#(
(
(
67N7Q!>$+03'!
JGH?900I<5!59%3)(0!d!9%3)(0!d!9(6!
<3*#&#/#+&5((*!CGGE!PL@S!HGC!C@LD!BFS!C@KB[BDJGF!BFS!JFHGCEBK!LGIJBKJeJFOM!GHD@F!FGD!C@LDCJID@S!DG!B!LA@IJHJI!OCGPA!
GH!A@GAK@M!PFJD!GC!BC@B#(
<34E,#2/#+&5((*!KGPFO@!HBIJKJDN!JL!DNAJIBKKN!@bPJAA@S!WJD?!PA?GKLD@C@S!HPCFJDPC@M!SCBA@CJ@LM!GC!IBCA@DJFOM!BFS!EBN!
JFIKPS@!T@FSJFO!EBI?JF@L!JH!D?@!ACJEBCN!PL@!GH!D?@!CGGE!JL!FGD!HGC!@BDJFO#(
(
(
67N78S!L'#,A(0U2%203!K(,2-2*B!
JGH?900I<5!510&27*)4!;*2'9!d!10&27!d!106!
<3*#&#/#+&5((*!CGGE!PL@S!DG!L@KK!ACGSPIDL!GC!L@CTJI@L#(
<34E,#2/#+&5(('FIKPS@L!ACGSPID!BFS!L@CTJI@!LBK@L!BC@BL!LPI?!BL!RGGULDGC@LM!LDPS@FD!LPAAKN!LDGC@LM!RBCR@C!GC!
R@BPDN!L?GALM!AGLD!GHHJI@LM!IBEAPL!HGGS!LDGC@LM!WBKUaBWBN!T@FSJFO!EBI?JF@!CGGELM!BFS!I@FDCBK!DJIU@D!GPDK@DL!
L@CTJIJFO!EPKDJAK@!HBIJKJDJ@L!GH!BIDJTJDJ@L#(
(
(
67N788!L'#,A(0U2%203!)'#<2,'!
JGH?900I<5!510&27*)4!.r2!d!10&!.r!d!1r6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!B!E@CI?BFSJLJFO!HBIJKJDN!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!JF!D?BD!HBIJKJDN#(
<34E,#2/#+&5('FIKPS@L!LDGCBO@!CGGEL!BFS!IKGL@DLM!LGCDJFO!CGGELM!ACJTBD@!C@LD!CGGELM!BFS!GD?@C!LPAAGCD!CGGEL!JH!
D?@N!SJC@IDKN!L@CT@!B!1@CI?BFSJLJFO!HBIJKJDN#(
(
(
67N78;!L+-*21R+#H$%'!@$$:!
JGH?900I<5!5139+'a:3&:%.0!&1!d!139+'!d!1:6!
<3*#&#/#+&5!!*!CGGE!PL@S!HGC!EPKDJAK@!UJFSL!GH!FGFaIKBLL!E@@DJFOL!GC!BIDJTJDJ@L#(
(
(
67N78=!/$01&*A-'*2,!>$,D'#!@$$:!
JGH?900I<5!5)%)a*+7!9%2j&!&1!d!)a*!9j!d!)96!
<3*#&#/#+&5((*!CGGE!PL@S!HGC!I?BFOJFO!IKGD?@L!BFSdGC!LDGCJFO!A@CLGFBK!EBD@CJBKLM!FGD!C@KBD@S!DG!BD?K@DJI!BIDJTJDN#(
(
(
67N786!@',#'(*2$0!K(,2-2*B!
JGH?900I<5!5&02&0*+'%)!;*2'9!d!&02&0*!d!&;6!
<3*#&#/#+&5!!*!CGGE!PL@S!RN!LDPS@FDLM!LDBHH!GC!D?@!APRKJI!HGC!C@IC@BDJGFBK!APCAGL@L#!
<34E,#2/#+&5!!!'FIKPS@L!@[@CIJL@!BFS!O@F@CBK!HJDF@LL!CGGELM!RJKKJBCSL!CGGELM!OBE@!BFS!BCIBS@!CGGELM!RGWKJFO!
BKK@NLM!DBRK@!D@FFJL!CGGELM!SBFI@!GC!RBKKCGGELM!I?@LL!CGGELM!IBCS!AKBNJFO!CGGELM!?GRRN!CGGELM!+r!CGGELM!
C@BSJFO!5FGFaLDPSN6!CGGELM!BFS!EPLJI!KJLD@FJFO!CGGEL!D?BD!BC@!PL@S!HGC!C@IC@BDJGF!BFS!BEPL@E@FD!!BFS!FGD!HGC!
JFLDCPIDJGFBK!APCAGL@L#!!&@IC@BDJGF!CGGEL!BFS!BC@BL!BC@!PL@S!HGC!C@KB[BDJGFM!BEPL@E@FDaDNA@!BIDJTJDJ@LM!
W?@C@BL!*D?K@DJI!GC!:?NLJIBK!0SPIBDJGF!HBIJKJDJ@L!BC@BL!DNAJIBKKN!PL@S!HGC!D?@!EGC@!TJOGCGPL!APCLPJDL!WJD?JF!
A?NLJIBK!@SPIBDJGFM!JFD@CIGKK@OJBD@!BD?K@DJILM!BFS!JFDCBEPCBK!ACGOCBEL#!
!
!
>-C 6#?'.!.''6!0+&@!+011'."!
.PAAGCD!HBIJKJDJ@LM!W?JI?!ACGTJS@!I@FDCBKJe@S!LABI@!HGC!TBCJGPL!BP[JKJBCN!LPAAGCD!LNLD@EL!BFS!L@CTJI@L!GH!B!
IBEAPLM!?@KA!U@@A!BKK!JFLDJDPDJGFBK!ACGOCBEL!BFS!BIDJTJDJ@L!GA@CBDJGFBK#!Z?JK@!FGD!BL!SJC@IDKN!BII@LLJRK@!
DG!JFLDJDPDJGFBK!BFS!IGEEPFJDN!E@ER@CL!BL!(@F@CBK!3L@!;BIJKJDJ@L!52GS@!Y>>!L@CJ@L6M!D?@L@!BC@BL!ACGTJS@!
B!IGFDJFPGPLM!JFSJC@ID!LPAAGCD!LNLD@E!DG!HBIPKDNM!LDBHHM!LDPS@FDLM!BFS!D?@!APRKJI#!.PAAGCD!HBIJKJDJ@L!BC@!
I@FDCBKJe@S!JF!D?BD!D?@N!DNAJIBKKN!L@CT@!BF!BC@B!CBFOJFO!HCGE!BF!@FDJC@!RPJKSJFO!GC!GCOBFJeBDJGFBK!PFJD!DG!
D?@!@FDJC@!IBEAPL#!
!
67O78!9$:H+*'#!K(,2-2*B!
JGH?900I<5!52%1:3+0&!;*2'9!d!21:3+&!d!2;6!
<3*#&#/#+&5((*!CGGE!PL@S!AC@SGEJFBFDKN!BL!B!IGEAPD@CaRBL@S!JFHGCEBDJGF!ACGI@LLJFO!GC!D@K@IGEEPFJIBDJGFL!
CGGE#(
(
(
67O7;!9$:H+*'#!)'#<2,'!
JGH?900I<5!52%1:3+0&!.0&r'20!d!21:!.r!d!2r6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!B!IGEAPD@C!HBIJKJDN!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!JF!D?BD!HBIJKJDN#(
<34E,#2/#+&5(('FIKPS@L!GHHaKJF@!ACJFD@C!CGGELM!LDGCBO@!CGGELM!BFIJKKBCN!@bPJAE@FD!CGGEL!D?BD!LPAAGCD!F@DWGCU!
GA@CBDJGFL!BFS!D?@!KJU@#(
(
(
67O7=!L(2-!@$$:!
JGH?900I<5!51*'9!&1!d!1*'9!d!1&6!
<3*#&#/#+&5((*!CGGE!GC!BC@B!D?BD!JL!PL@S!HGC!D?@!ACGI@LLJFO!BFS!SJLDCJRPDJGF!GH!EBJK#(
<34E,#2/#+&5(('FIKPS@S!JF!D?JL!IBD@OGCN!BC@!CGGEL!W?JI?!HPFIDJGF!BL!D?@!IGKK@IDJGF!AGJFD!HGC!GPDOGJFO!EBJKM!D?@!
S@KJT@CN!AGJFD!HGC!JFIGEJFO!EBJKM!D?@!ACGI@LLJFO!GH!EBJKM!BFS!D?@!SJLDCJRPDJGF!GH!EBJK#(
(
(
67O76!L(20*'0(0,'!)A$H!
JGH?900I<5!51*')+0)*)20!.7%:!d!1!.7%:!d!1*6!
<3*#&#/#+&5((*!CGGE!PL@S!HGC!D?@!EBFPHBIDPC@M!C@ABJCM!GC!EBJFD@FBFI@!GH!ACGSPIDL!GC!@bPJAE@FD#(
<34E,#2/#+&5(('FIKPS@L!IBCA@FD@CM!AKPERJFOM!7r*2M!@K@IDCJIBK!BFS!ABJFDJFO!L?GALM!BFS!LJEJKBC!A?NLJIBK!AKBFD!
EBJFD@FBFI@!HBIJKJDJ@L#(
(
(
67O7F!R#20*WC+H-2,(*'!)A$H!
JGH?900I<5!5:&')+d43:!.7%:!d!:&d43:!d!:46!
<3*#&#/#+&5((*!CGGE!PL@S!HGC!D?@!ACJFDJFO!GC!SPAKJIBDJFO!GH!WCJDD@F!EBD@CJBKLM!D?BD!O@F@CBKKN!L@CT@L!D?@!JFLDJDPDJGF!
BD!KBCO@#(
(
(
67O7N!@','2<203!@$$:!
JGH?900I<5!5&020'r')(!&%%1!d!&2r(!d!&r6!
<3*#&#/#+&5((*!CGGE!PDJKJe@S!HGC!D?@!C@I@JTJFO!BFSdGC!L?JAAJFO!GH!EBD@CJBKL!BFS!OGGSL#(
(
(
67O7O!)*$#(3'!K(,2-2*B!
JGH?900I<5!5.+%&*(0!;*2'9'+/!d!.+%&!d!.+6!
<3*#&#/#+&5((*!CGGE!PL@S!DG!LDGC@!@bPJAE@FD!GC!EBD@CJBKL!?BTJFO!I?BCBID@CJLDJIL!GH!KGFO!D@CE!LDGCBO@M!KGW!
DPCFGT@CM!JFHC@bP@FD!BII@LL!GC!SJLDBFD!KGIBDJGF#(
<34E,#2/#+&5((+?@!EB`GCJDN!GH!CGGEL!PL@S!HGC!LDGCBO@!SJC@IDKN!LPAAGCD!LGE@!ACJEBCN!CGGE!PL@!BFS!BC@!KBR@KK@S!
WJD?!D?@!WGCS!gL@CTJI@gM!@#O#!g%HHJI@!.@CTJI@gM!g2KBLLCGGE!.@CTJI@gM!@DI#!!+?@L@!BC@!I?BCBID@CJe@S!RN!L?GCD!D@CEM!
?JO?!DPCFGT@CM!HC@bP@FD!BII@LL!BFS!ACG[JEJDN!DG!D?@!ACJEBCN!PL@!CGGEL#!!'F!IGFDCBLDM!D?@!LDGCBO@!HBIJKJDN!
S@LICJR@S!?@C@!EBN!R@!TJ@W@S!BL!WBC@?GPL@M!LPCAKPL!LDGCBO@M!I@FDCBK!LPAAKN!GC!JFBIDJT@!LDGCBO@!LABI@#(
(
(
67O7P!X'A2,-'!)*$#(3'!
JGH?900I<5!5r07'290!.+%&*(0!d!r07!.+!d!r.6!
<3*#&#/#+&5((*!CGGE!GC!LDCPIDPC@!D?BD!JL!PL@S!DG!?GPL@!GC!LDGC@!T@?JIK@L#(
<34E,#2/#+&5((+?@!S@HJFJDJGF!GH!gT@?JIK@g!JL!RCGBSKN!JFD@CAC@D@S!?@C@!DG!JFIKPS@!HGCUKJHDLM!EGTJFO!@bPJAE@FDM!BFS!
GD?@C!DCBFLAGCD!S@TJI@L!GC!@bPJAE@FD!BL!W@KK!BL!BPDGEGRJK@L!BFS!DCPIUL#!*KLG!JFIKPS@S!JL!D?@!IGT@C@S!IJCIPKBDJGF!
BC@B!C@bPJC@S!HGC!D?@!nT@?JIK@LQ!DG!@FD@CM!EBF@PT@C!W?JK@!WJD?JFM!BFS!@[JD!D?@!ABCUJFO!LDCPIDPC@L#!!+?JL!IBD@OGCN!
SG@L!FGD!JFIKPS@!PFCGGH@S!LPCHBI@!ABCUJFO!KGDL#(
!
!
!
>-D 6#?'.!.''6!0+&@!=&#%"=!)#.&!!
+?JL!L@CJ@L!ACGTJS@L!LABI@!PL@!IKBLLJHJIBDJGFL!HGC!ABDJ@FD!IBC@!BC@BL!D?BD!BC@!KGIBD@S!JF!L@ABCBD@KN!GCOBFJe@S!BFS!
RPSO@D@S!?@BKD?!IBC@!HBIJKJDJ@LV!LDPS@FD!JFHJCEBCJ@L!BFS!I@FD@CLM!D@BI?JFO!?GLAJDBKLM!LDBFSaBKGF@!IKJFJIL!CPF!RN!D?@L@!
?GLAJDBKLM!BFS!T@D@CJFBCN!BFS!E@SJIBK!LI?GGKL#!.ABI@!IGS@L!BFS!S@HJFJDJGFL!BAAKN!DG!RGD?!?PEBF!BFS!BFJEBK!?@BKD?!
IBC@!BC@BLh!@[IKPS@S!BC@!IKJFJI!HBIJKJDJ@L!KGIBD@S!GPDLJS@!GH!L@ABCBD@KN!GCOBFJe@S!BFS!RPSO@D@S!?@BKD?!IBC@!HBIJKJDJ@L#!
*KD?GPO?!D?@!IGS@L!JF!D?JL!L@CJ@L!BC@!IGFHJF@S!DG!D?@!L@DDJFOL!KJLD@SM!D?@L@!HBIJKJDJ@L!EBN!BKLG!?GPL@!BC@BL!D?BD!BC@!
IKBLLJHJ@S!PLJFO!BAAKJIBRK@!IGS@L!HCGE!GD?@C!IKBLLJHJIBDJGF!L@CJ@L!5@#O#M!IKBLLCGGEM!KBRGCBDGCNM!GHHJI@M!LA@IJBK!PL@M!
O@F@CBK!PL@M!LPAAGCDJFO!HBIJKJDJ@LM!@DI#6#!
!
67P78!C2(30$%*2,!)'#<2,'!>(4$#(*$#B!
JGH?900I<5!54'*()%.!.r2!9*8!d!4.!9*8!d!496!
<3*#&#/#+&5(((*!KBRGCBDGCN!D?BD!ACGTJS@L!SJBOFGLDJI!LPAAGCD!L@CTJI@L!DG!BF!@FDJC@!?@BKD?!IBC@!HBIJKJDN#(
(
(
67P7;!R(*2'0*!](*A#$$:!
JGH?900I<5!5:*+'0)+!8*+7&%%1!d!:8*+7!d!8*6!
<3*#&#/#+&5((*!CGGE!IGFDBJFJFO!ABDJ@FD!RBD?!BFS!DGJK@D!HBIJKJDJ@L#(
<34E,#2/#+&5(('FIKPS@S!JF!D?JL!IBD@OGCN!BC@!DGJK@D!BFS!RBD?!HBIJKJDJ@L!BS`GJFJFO!GC!JF!IGF`PFIDJGF!WJD?!ABDJ@FD!
R@SCGGEL#(
(
(
67P7=!R(*2'0*!]'U#$$:!
JGH?900I<5!5:*+'0)+!804&%%1!d!:804&!d!806!
<3*#&#/#+&5((*!CGGE!@bPJAA@S!WJD?!B!R@S!BFS!PL@S!HGC!ABDJ@FD!IBC@#(
<34E,#2/#+&5(('FIKPS@L!O@F@CBK!FPCLJFO!IBC@M!@E@CO@FIN!R@S!IBC@!PFJDL!BFS!C@L@BCI?!GRL@CTBDJGF!PFJDL#!!
2GFF@ID@S!IKGD?@L!IKGL@DL!EBN!R@!BOOC@OBD@S!WJD?!D?@!:BDJ@FD!8@SCGGE!LABI@#(
(
(
67P76!?'(-*A!9(#'!)'#<2,'!
JGH?900I<5!570*9+7!2*&0!.r2!d!72!.r!d!7.6!
<3*#&#/#+&5((*!CGGE!D?BD!SJC@IDKN!L@CT@L!GF@!GC!EGC@!?@BKD?!IBC@!CGGEL!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!JF!D?GL@!
CGGEL#(
<34E,#2/#+&5(('FIKPS@L!CGGEL!PL@S!HGC!LPAAKJ@LM!?GPL@U@@AJFOM!KJF@F!LDGCBO@!BFS!?BFSKJFOM!LEBKK!BFD@CGGELM!
A?BCEBIN!LPAAKN!BFS!LDGCBO@!CGGELM!SJLA@FLBCN!BC@BLM!?@BKD?!IBC@!C@KBD@S!UJDI?@F!BFS!@BDJFO!BC@BLM!ABDJ@FD!
I?BFOJFOdSC@LLJFO!CGGEL#(
(
(
67P7F!/+#%'!)*(*2$0!
JGH?900I<5!5)3&.0!.+*+'%)!d!)3&.0!d!).6!
<3*#&#/#+&5((*!CGGE!GC!BC@B!PL@S!RN!FPCL@L!GC!GD?@C!ABDJ@FD!IBC@!LDBHH!W?G!BC@!LPA@CTJLJFO!GC!BSEJFJLD@CJFO!
?@BKD?!IBC@!L@CTJI@L#(
<34E,#2/#+&5((+?JL!JL!D?@!ACJEBCN!WGCULDBDJGF!BC@B!PL@S!RN!FPCL@L!BFS!GD?@C!ABDJ@FD!IBC@!LDBHH!BFS!JFIKPS@L!WBCS!
C@I@ADJGF!BFS!BSEJLLJGFL!S@LUL!BFS!C@IGCSL!GC!I?BCDJFO!WGCU!BC@BL#(
(
(
67P7N!R+4-2,!^(2*203!
JGH?900I<5!5:389'2!Z*'+')(!d!:!Z*'+!d!:Z6!
<3*#&#/#+&5((*!CGGE!PL@S!RN!D?@!APRKJI!DG!BWBJD!BSEJLLJGFM!DC@BDE@FD!GC!JFHGCEBDJGF!WJD?JF!B!?@BKD?!IBC@!HBIJKJDN#(
<34E,#2/#+&5(('FIKPS@S!BC@!KGRRN!BC@BL!D?BD!BC@!LA@IJHJIBKKN!IGFHJOPC@S!BFS!HPCFJL?@S!HGC!APRKJI!WBJDJFOh!A?NLJIBK!
RGPFSBCJ@L!L?GPKS!R@!BLLJOF@SM!BL!F@@S@SM!DG!S@HJF@!FGFaBLLJOFBRK@!BC@BL!GH!@FDCBFI@!KGRRJ@L!W?JI?!LJEAKN!
L@CT@!B!IJCIPKBDJGF!HPFIDJGF#!!*KLG!JFIKPS@L!ABDJ@FD!WBJDJFO!CGGELM!C@I@ADJGF!BFS!TJLJDJFO!BC@BLM!TJ@WJFO!CGGEL!
BFS!WBCS!SBN!CGGEL#(
(
(
67P7O!)+#3'#B!
JGH?900I<5!5.3&(0&/!d!.3&(!d!.(6!
<3*#&#/#+&5!!*!CGGE!PL@S!HGC!LPCO@CN#(
<34E,#2/#+&5!!+?@L@!CGGEL!BC@!DNAJIBKKN!@bPJAA@S!WJD?!GA@CBDJFO!CGGE!DBRK@LM!LD@CJK@!KJO?DLM!BF@LD?@LJB!EBI?JF@L!
BFS!TBCJGPL!DNA@L!GH!EGFJDGCJFO!@bPJAE@FD#(
(
(
67P7P!V#'(*:'0*W[\(:20(*2$0!@$$:!
JGH?900I<5!5+&0*+1)+d0<*1!&1!d!+&+d<1!d!+<6!
<34E,#2/#+&5!!*!CGGE!PL@S!HGC!SJBOFGLDJI!@[BEJFBDJGF!BFSdGC!D?@CBA@PDJI!DC@BDE@FD#(
<34E,#2/#+&5!!'FIKPS@S!BC@!CGGEL!PL@S!HGC!CBSJGKGONM!BFS!BKK!GD?@C!HGCEL!GH!JEBOJFOM!LBEAKJFOM!D@LDJFO!BFS!
@[BEJFJFO!BFS!DC@BDJFO!JFIKPSJFO!S@FDBK!@[BEJFBDJGF!BFS!DC@BDE@FD#!*KLG!JFIKPS@L!IGERJF@S!SGIDGC^L!GHHJI@!BFS!
DC@BDE@FDd@[BEJFBDJGF!CGGEL#(
!
!
>-E 6#?'.!.''6!0+&@!.&+,/&*",#%!
&@LJS@FDJBK!HBIJKJDJ@L!JFIKPS@!?GPLJFO!HGC!LDPS@FDLM!HBIPKDNM!LDBHHM!BFS!TJLJDGCL!DG!D?@!JFLDJDPDJGF#!7GD@K!GC!
EGD@K!BFS!GD?@C!OP@LD!HBIJKJDJ@L!BC@!JFIKPS@S!JF!D?JL!L@CJ@L!JH!D?@N!BC@!GWF@S!GC!IGFDCGKK@S!RN!D?@!
JFLDJDPDJGF!BFS!PL@S!HGC!APCAGL@L!BLLGIJBD@S!WJD?!S@HJF@S!JFLDJDPDJGFBK!EJLLJGFL!5J#@#M!@[IKPSJFO!
IGEE@CIJBK!JFT@LDE@FD6#!)GD!BKK!LABI@!JF!C@LJS@FDJBK!HBIJKJDJ@L!JL!IGS@S!PLJFO!D?@!&@LJS@FDJBK!1B`GC!&GGE!
3L@#!2GFT@FDJGFBK!ACJEBCN!BIDJTJDN!BFS!L@CTJI@!IGS@LM!BL!WJD?!KJRCBCJ@LM!BAAKN!DG!LA@IJHJI!BC@BL#!'FIKPS@S!
BC@!%HHJI@LM!9GPFO@LM!.DPSN!&GGELM!SJFJFO!BC@BLM!&@IC@BDJGF!CGGELM!BFS!D?@JC!IGCC@LAGFSJFO!L@CTJI@!
IGS@L#!.@CTJI@!CGGEL!D?BD!DNAJIBKKN!BAA@BC!JF!C@LJS@FDJBK!HBIJKJDJ@L!BC@!LA@IJHJ@S!JF!D?@!.K@@Ad.DPSN!.@CTJI@!
GC!*ABCDE@FD!.@CTJI@!S@LICJADJGFL#!
!
67Q78!&H(#*:'0*!
JGH?900I<5!5*:*&+10)+!d!*:+1)+!d!*:6!
<3*#&#/#+&5!!*!IGEAK@D@!KJTJFO!PFJD!WJD?!ACJTBD@!IGGUJFO!HBIJKJDJ@L!D?BD!JL!FGD!B!L@ABCBD@!LDCPIDPC@#(
(
(
67Q7;!&H(#*:'0*!)'#<2,'!
JGH?900I<5!5*:*&+10)+!.r2!d!*:+.r2!d!*16!
<3*#&#/#+&5!!*F!BFIJKKBCN!CGGE!W?JI?!SJC@IDKN!L@CT@L!D?@!GIIPABFDL!GH!BF!BABCDE@FD!GC!BABCDE@FDL!BL!BF!
@[D@FLJGF!GH!D?@!BIDJTJDJ@L!JF!D?GL@!HBIJKJDJ@L#(
(
(
67Q7=!"+'%*!@$$:!
JGH?900I<5!5(30.+!&%%1!d!(30.+!d!(&6!
<3*#&#/#+&5!!8@SCGGEL!BFS!BLLGIJBD@S!CGGEL!JF!B!HBIJKJDN!PL@S!HGC!GT@CFJO?D!OP@LDL#(
(
(
67Q76!?$+%':(%*'#!&H(#*:'0*!
JGH?900I<5!57%3.01*.+0&!*:+!d!7!1.+&!d!716!
<3*#&#/#+&5!!!*F!BABCDE@FD!JF!B!LDPS@FD!SGCEJDGCN!GC!BABCDE@FD!RPJKSJFOM!C@L@CT@S!HGC!GC!GIIPAJ@S!RN!B!C@LJS@FD!
?GPL@EBLD@C#(
(
(
67Q7F!>2<203!Y+(#*'#%!
JGH?900I<5!59'r')(!i3*&+0&.!d!9'r')(!d!9i6!
<3*#&#/#+&5!!!&GGEL!D?BD!BC@!ABCD!GH!BF!BABCDE@FD!LPJD@!RPD!BC@!FGD!R@SCGGEL#!!'FIKPS@S!BC@!UJDI?@FM!KJTJFO!CGGEM!
@DI@D@CB!W?@F!GF!B!L@ABCBD@!HKGGC!HCGE!CGGEL!IKBLLJHJ@S!BL!GF@M!DWGM!@DI#!R@SCGGE!BABCDE@FD#(
(
(
67Q7N!)-''HW)*+UB!Z2*A!V$2-'*!$#!](*A!
JGH?900I<5!5.900:d.+4!Zd8*+7!d!.9:8+7!d!.86!
<3*#&#/#+&5!!*!C@LJS@FDJBK!CGGE!HGC!GF@!GC!EGC@!JFSJTJSPBKL!DNAJIBKKN!HPCFJL?@S!WJD?!R@S5L6M!WBCSCGR@5L6M!IKGL@D5L6M!
BFS!I?BJC5L6M!WJD?!BF!JFD@CFBKKN!IGFF@ID@S!RBD?!GC!DGJK@D#(
(<34E,#2/#+&5!!'FIKPS@L!LJFOK@!GC!EPKDJAK@!LK@@AdLDPSN!CGGEL#!!*!LK@@AdLDPSN!HBIJKJDN!EBN!R@!B!CGGE!HGC!IGERJF@S!
LK@@AdLDPSNM!B!CGGE!@[IKPLJT@KN!HGC!LK@@AJFOM!GC!B!CGGE!HGC!KJTJFO!BFS!LDPSNM!BFS!JFIKPS@L!IGFF@ID@S!IKGL@DL#(
(
(
67Q7Q!V'##(,'!
JGH?900I<5!5+0&&*20!d!+0&&!d!+06!
<3*#&#/#+&5!!*!IGT@C@S!BC@B!@[D@CFBK!DG!D?@!@[D@CJGC!KJF@!GH!D?@!RPJKSJFO!GC!RPJKSJFOL!DG!W?JI?!JD!JL!BLLGIJBD@SM!WJD?!
GC!WJD?GPD!BFN!LJOFJHJIBFD!WBKK!LDCPIDPC@!LPCCGPFSJFO!JDM!D?BD!JL!PL@S!BL!BF!@[D@FLJGF!GH!D?@!BIDJTJDJ@L!GH!D?@!
RPJKSJFO!BC@BL!HCGE!W?JI?!D?@!+@CCBI@!JL!BII@LL@SM!@JD?@C!SJC@IDKN!GC!JFSJC@IDKN#(
!
!
>-2F 6#?'.!.''6!0+&@!0*)%#++,(,&/!
3FIKBLLJHJ@S!HBIJKJDJ@L!JFIKPS@!D?GL@!BLLJOFBRK@!BC@BL!D?BD!BC@!JFBIDJT@!GC!PFBLLJOF@Sh!JF!D?@!ACGI@LL!GH!
R@JFO!BKD@C@SM!C@FGTBD@SM!GC!IGFT@CD@Sh!GC!JF!BF!PFHJFJL?@S!LDBD@#!
!
678S78!&-*'#(*2$0W9$0<'#%2$0!
JGH?900I<5!5*9+0&d2%)r0&.'%)!d!*9+0&!d!*26!
<3*#&#/#+&5!!&GGEL!D@EAGCBCJKN!GPD!GH!PL@!R@IBPL@!D?@N!BC@!R@JFO!BKD@C@SM!C@EGS@K@SM!GC!C@?BRJKJDBD@S!BD!D?@!
DJE@!GH!D?@!JFT@FDGCN#(
!
!
>-22 6#?'.!.''6!0+&@!$0,%/,*4!+&.9,)&!#.&#!
)GFBLLJOFBRK@!LABI@L!PL@S!DG!LPAAGCD!B!RPJKSJFOQL!IK@BFJFO!BFS!APRKJI!?NOJ@F@!HPFIDJGFL#!
!
678878!K':(-'!>(<(*$#B!
JGH?900I<5!5;01*90!9*r*+%&/!d!;!9*r!d!;96!
<3*#&#/#+&5!!*!APRKJI!KBTBDGCN!HGC!H@EBK@L#(
(
(
67887;!_(02*$#2(-!9-$%'*!
JGH?900I<5!5X*)'+%&!29%.0+!d!X*)!29!d!X26!
<3*#&#/#+&5!!*!LABI@!PL@S!HGC!D?@!IBC@!BFS!EBJFD@FBFI@!GH!D?@!RPJKSJFO!@#O#M!`BFJDGCL^!IKGL@DL#(
(
(
67887=!_(02*$#2(-!>$,D'#!@$$:!
JGH?900I<5!5X*)'+%&!9%2j0&!d!X*)!9j!d!X96!
<3*#&#/#+&5!!*!LABI@!W?@C@!D?@!IPLDGSJBK!LDBHH!IBF!I?BFO@!JFDG!D?@JC!WGCU!IKGD?@L#(
(
(
678876!_(02*$#2(-!)*$#(3'!
JGH?900I<5!5X*)'+%&!.+%&*(0!d!X*)!.+!d!X.6!
<3*#&#/#+&5!!*!CGGE!PL@S!DG!LDGC@!IPLDGSJBK!EBD@CJBKL#(
(
(
!67887F!L(-'!>(<(*$#B(
JGH?900I<5!51*90!9*r*+%&/!d!1!9*r!d!196!
<3*#&#/#+&5!!*!APRKJI!KBTBDGCN!HGC!EBK@L#(
(
(
67887N!R+4-2,!>(<(*$#B!
JGH?900I<5!5:389'2!9*r*+%&/!d!:8!9*r!d!:86!
<3*#&#/#+&5!!*!PFJL@[!APRKJI!KBTBDGCN#(
(
(
67887O!V$2-'*!$#!](*A!
JGH?900I<5!5+%'90+!%&!8*+7!d!8*+7!d!+86!
<3*#&#/#+&5!!*!DGJK@D!GC!RBD?CGGE!JFD@FS@S!GFKN!HGC!D?@!GIIPABFDL!GH!B!C@LJS@FDJBK!HBIJKJDN!CBD?@C!D?BF!HGC!D?@!
APRKJI#(
!
>-27 6#?'.!.''6!0+&@!),.)0%#",'*!#.&#!
)GFBLLJOFBRK@!LABI@L!C@bPJC@S!HGC!A?NLJIBK!BII@LL!DG!HKGGCL!GC!LPRSJTJLJGFL!GH!LABI@!WJD?JF!D?@!RPJKSJFOM!
W?@D?@C!SJC@IDKN!RGPFS@S!RN!ABCDJDJGFL!GC!FGD#!
!
678;78!]#2U3'WV+00'-!
JGH?900I<5!58&'4(0d+3))09!d!8&d+3)!d!8+6!
<3*#&#/#+&5!!*!RCJSO@!GC!DPFF@K!IGFF@IDJFO!DWG!LABI@L!GC!RPJKSJFOL#(
(
(
678;7;!9$##2U$#!
JGH?900I<5!52%&&'4%&!d!2%&&!d!2&6!
<3*#&#/#+&5!!2GEEGF!APRKJI!ABLLBO@WBN!GC!BJLK@L#(
(
(
678;7=![-'<(*$#!
JGH?900I<5!5090r*+%&!d!090r!d!096!
<3*#&#/#+&5!!.ABI@!PDJKJe@S!HGC!@K@TBDGC!IBRL!BFS!D?@JC!LPCCGPFSJFO!L?BHD!LABI@#(
!
!
!
!
!
>-28 6#?'.!.''6!0+&@!6&)=#*,)#%!#.&#!
)GFBLLJOFBRK@!LABI@L!GH!B!RPJKSJFO!S@LJOF@S!DG!?GPL@!E@I?BFJIBK!@bPJAE@FD!BFS!PDJKJDN!L@CTJI@LM!BFS!
L?BHD!BC@BL#!
!
678=78![-',*#2,(-WV'-',$::+02,(*2$0%!9-$%'*!
JGH?900I<5!50902d+09!29%.0+!d!09d+09!d!0+6!
<3*#&#/#+&5!!*!CGGE!IGFDBJFJFO!RGD?!@K@IDCJIBK!BFS!D@K@IGEEPFJIBDJGFL!@bPJAE@FD!L@CTJIJFO!B!RPJKSJFO#(
(
(
678=7;![-',*#2,(-!9-$%'*!
JGH?900I<5!50902+&'2!29%.0+!d!0902!d!026!
<3*#&#/#+&5!!*!CGGE!IGFDBJFJFO!@K@IDCJIBK!@bPJAE@FD!L@CTJIJFO!D?@!RPJKSJFO!BFS!@[IKPSJFO!D@K@IGEEPFJIBDJGFL!
<3*#&#/#+&5!!*!CGGE!IGFDBJFJFO!@K@IDCJIBK!@bPJAE@FD!L@CTJIJFO!D?@!RPJKSJFO!BFS!@[IKPSJFO!D@K@IGEEPFJIBDJGFL!
@bPJAE@FD#(
(
(
678=7=!)A(E*!)H(,'!
JGH?900I<5!5.7*;+!.:*20!d!.7*;+!d!..6!
<3*#&#/#+&5!!*!T@CDJIBK!ABLLBO@!@FIKGL@S!RN!WBKKL#(
(
(
678=76!V'-',$::+02,(*2$0%!9-$%'*!
JGH?900I<5!5+0902%1!29%.0+!d!+090!d!+26!
<3*#&#/#+&5!!*!CGGE!IGFDBJFJFO!D@K@IGEEPFJIBDJGFL!@bPJAE@FD!L@CTJIJFO!D?@!RPJKSJFO!BFS!@[IKPSJFO!@K@IDCJIBK!
@bPJAE@FD#(
(
(
678=7F!5*2-2*BWL',A(02,(-!@$$:!
JGH?900I<5!53+'9'+/d1027!&1!d!3d1!d!316!
<3*#&#/#+&5!!*!CGGE!?GPLJFO!E@I?BFJIBK!BFS!PDJKJDN!@bPJAE@FD!F@@S@S!HGC!?@BDJFO!GC!KJO?DJFO!B!RPJKSJFO#
! (
!
!
!
#11&*/,)&+!
!
!
!
#- )#610+!$0,%/,*4!4.,/!
!
!
.&(&.&*)&+!
2NCGLM!j#!9#!5->>Y6#!S+4/43E+&%.,1(I%"E./#+&(J.E#$#/#34()&R3&/+,1(.&%(F$.44#*#E./#+&(?.&".$(AJ)F?C5(TUUV(
I%#/#+&Q!ZBL?JFODGFV!)BDJGFBK!2@FD@C!HGC!0SPIBDJGF!.DBDJLDJIL#!
!
MIT Design Standards | BIM and CAD Drawing Standards Thematic Folder !Page 33 of 33
MIT
Design Standards
Sustainability
Thematic Folder
May 2018
Table of Contents
End!
MIT is committed to the stewardship of natural systems and the holistic integration of sustainable
design in its built environment. The Institute supports the development of high performance
projects that include metrics for greenhouse gas emissions, analyzing life cycle costs, minimizing
resource consumption and emphasizing human well-being and ecological health. It supports
planning and design of campus buildings and sites that measure and promote ecosystem services
such as carbon sequestration, protection of air and water quality, and mitigation of heat island
effect. In addition, MIT’s Plan for Action on Climate Change, released on October 21, 2015, sets
forth various Institute-wide goals, including a greenhouse gas reduction goal of 32% below 2014
levels by 2030, inclusive of growth.
The MIT Sustainability Design Standards establish practices that are to be integrated in all
projects. These standards clarify the sustainability scope for consultants to be integrated in their
proposals for each phase of the project. Planning level phase requirements are addressed
separately and will help establish initial goals for projects to ensure that MIT can meet its
sustainability goals.
MIT will engage sustainability, energy and LEED consultants (referred to in this document as
MIT SC) directly and separately from the design team as part of a project. The design team will
actively engage with the MIT SC. Additional information, such as detailed deliverables and
project specific requirements, will be outlined in the Request for Proposals for a project. Finally,
the standards outlined below are in addition to Commonwealth of Massachusetts and City of
Cambridge requirements, such as the Stretch Energy Code, low-emitting materials and
construction waste management.
Assume one interactive design charrette prior to commencing design. The purpose of the
charrette is to identify solutions to meet sustainability goals. Areas of focus include site, energy,
water, indoor environmental quality, human health and materials. The charrette should include
representatives from all impacted parties. Representatives will be proposed by the project
sustainability POC and could include:
a. Architect.
b. Landscape Architect.
c. Mechanical, Electrical, and Plumbing (MEP) Engineers.
d. Energy Consultant.
e. Lighting Designer.
f. Cost Consultant.
g. Other relevant consultants.
a. Construction Manager.
b. General Contractor.
c. Relevant subcontractors/suppliers.
The MIT SC will provide “simple box” energy models to study design alternatives identified in
an integrated design charrette and explore relationships between options and integrative system
performance. The CT will provide required building data for the energy model as applicable.
Incorporate sensitivity analysis. Integrate resilience scenarios based on Cambridge Climate
Vulnerability Assessment and MIT-specific Climate Vulnerability Assessment.
The MIT SC will lead the development of an initial life cycle cost analysis of options with
significant budget impacts. MIT will provide a Life Cycle Cost Calculator for use with projects.
Use cost bundling strategies to ensure adequate evaluation of integrative options.
The MIT SC will participate in the development of the Owners Project Requirements (OPR) for
commissioning. Refer to Division 01 Section “019113 - General Commissioning Requirements”
for specifications.
2.5 Documentation
The MIT SC will submit an initial sustainability narrative. Sustainability narratives include
analysis performed by the consultant team to identify holistic design strategies to meet
sustainability goals to reduce energy use and conserve water, enhance human health, support
ecosystem services provided by water, soil, and vegetation systems, and address climate change
projections. Categories will include as applicable:
1. Passive and active design strategies, including lighting, daylighting and shading,
siting and orientation, natural and mechanical ventilation and heating, cooling and
envelope systems.
2. Site strategies, including landscape and stormwater strategies and urban forestry
management and their associated environmental and human health impacts.
3. Control strategies and renewable energy potential.
4. Active spaces and healthy spaces.
5. Acoustic, air quality and thermal comfort.
6. Building material choice impacts.
7. Integrated water reduction strategies.
8. Climate resilience scenarios based on projected changing climate projections from
the Cambridge Vulnerability Assessment.
9. Life cycle cost analysis.
10. GHG calculations.
11. Energy model documentation.
Assume a minimum of two interactive design charrettes during schematic design. Charrettes
should include representatives from all impacted parties. See Par. 2.1 for potential participants.
The MIT SC will provide energy model studies to test different options to meet project
sustainability goals.
The MIT SC will provide updated LCCA of major options including energy, water, and
stormwater, as required. Integrate LCCA in Value Engineering (VE) process. Changes in the
project design due to Value Engineering should be approved by the entire team.
The CT will develop a Measurement and Verification Plan in accordance with LEED guidelines
and Eversource requirements with consideration for the following:
1. Building level metering for all major energy and water streams, including electricity,
natural gas, chilled water, steam, hot water, domestic water and irrigation.
2. Submeter by end use all systems that consume more than 10% of building energy.
3. Submeter significant uses such as large kitchens, data centers, labs, innovative
technology strategies, or as directed by MIT.
4. Identify additional requirements and monitoring goals for operational management,
programmatic needs, and user engagements.
5. Integrate metering strategies with building fault detection systems.
The MEP Engineer on the CT will develop a Basis of Design (BOD) for commissioning in
accordance with the OPR. Refer to Division 01 Section “019113 - General Commissioning
Requirements” for specifications.
3.6 Documentation
The MIT SC will develop parametric studies of specific areas of study as required for project and
provide the following:
The MIT SC will provide updated LCCA if required. Integrate LCCA in Value Engineering (VE)
process. Changes in the project design due to Value Engineering need to be approved by the
entire team.
4.6 Documentation
The MIT SC will provide energy model updates for LEED, code compliance, and Eversource
Utility Report at 50% and 100% Construction Documents.
The MIT SC will provide updated LCCA as required and for Value Engineering alternatives.
Changes in the project design due to Value Engineering shall be approved by the entire team.
Changes in the Measurement and Verification Plan due to Value Engineering shall be approved
by the entire team.
5.6 Documentation
The MIT SC will provide energy modeling documents including the following:
The CM and the CT will support commissioning activities. Refer to Division 01 Section “019113
- General Commissioning Requirements” for specifications.
MIT requires LEED NC v.4 Gold Certification for all new construction and major renovation
projects including the following credits, categories, and options:
Water metering
The MIT project team and the consultant team shall determine which components indicated
below are required based on the scale and scope of the project prior to commencement of the
project. For partial renovations and limited scope projects that have greenhouse gas (GHG)
emissions or have impacts on multiple systems, a charrette is recommended and sustainability
goals and requirements for energy calculations /modeling and LCCA should be determined.
If required, hold one interactive design charrette at project kick-off. Additional charrettes may be
required depending on the scale and scope of the project. The charrette should include
representatives from all impacted parties. Representatives will be proposed by the project
sustainability POC and could include:
a. Architect.
b. Landscape Architect.
c. Mechanical, Electrical, and Plumbing (MEP) Engineers.
d. Energy Consultant.
e. Lighting Designer.
f. Cost Consultant.
g. Other relevant consultants.
a. Construction Manager.
b. General Contractor.
c. Relevant subcontractors/suppliers.
If required, the MIT SC and CT will test different design options to meet project sustainability
goals. If energy modeling is required, see energy modeling requirements for more information. If
energy modeling is not required, MIT will provide GHG calculator for use with projects.
The MIT SC will provide LCCA of design options for energy, water, stormwater systems with
budget, greenhouse gas (GHG) emissions, maintenance and operations impacts if required. If
possible, cost-bundling strategies will be used to ensure adequate evaluation of integrative
options. MIT will provide tools for calculations for use with projects.
The CT will develop a Measurement and Verification Plan with consideration for the following:
1. Building level metering for all major energy and water streams, including electricity,
natural gas, chilled water, steam, hot water, domestic water and irrigation
2. Submeter by end use all system that consume more than 10% of building energy.
3. Submeter significant uses such as large kitchens, data centers, labs, innovative
technology strategies, or as directed by MIT.
4. Identify additional requirements and monitoring goals for operational management,
programmatic needs, and user engagements.
5. Integrate metering strategies with building fault detection systems.
8.7 Documentation
The MIT SC will submit an initial sustainability narrative. Sustainability narratives include
analyses to identify holistic design strategies to meet sustainability goals to reduce energy use and
conserve water , enhance human health, support ecosystem services provided by water, soil, and
vegetation systems, and address climate change projections. The analysis will include one or
more of the categories noted below based on project scope:
1. Passive and active design strategies, including lighting, daylighting and shading, siting
and orientation, natural and mechanical ventilation and heating, cooling and envelope
systems.
2. Site strategies, including landscape and stormwater strategies and urban forestry
management and their associated environmental and human health impacts.
3. Active spaces and healthy spaces.
4. Acoustic, air quality and thermal comfort.
5. Building material choice impacts.
6. Integrated water reduction strategies.
7. Life cycle cost analysis.
8. Energy model documentation.
9. GHG calculations.
If included in the project scope, the MIT SC will provide updated GHG calculations or energy
model results for LEED, code compliance, and utility report.
The CT will integrate LCCA in the Value Engineering process. Changes in the project design
due to Value Engineering shall be approved by the entire team.
If energy modeling or GHG calculations are required, the MIT SC will submit documentation
including:
The CM and the CT will support commissioning activities. Refer to Division 01 Section “019113
- General Commissioning Requirements” for specifications.
LEED V4 CI certification is preferred but not required. Meet the following credits, if within the
project scope:
Water metering
Materials and Resources Building Product Disclosure and Option 1, Explore Option 2
Optimization - EPD's
Building Product Disclosure and Explore Option 1 and explore
Optimization - Sourcing of Raw Option 2
Materials
Building Product Disclosure and Option 1, Explore Option 2
Optimization - Material Ingredients
Construction and Demolition Waste 90%
Management
As the MIT campus undergoes a major renewal for the next 50-100 years and beyond, we grapple
with new and emerging data about climate risks that are projected to be more extreme and more
frequent than conditions our campus experienced during its first century. Designing resiliency for
a campus and its associated buildings means analyzing and understanding the specific hazards
that a property may be exposed to within the particular region it is located in and determining
strategies to adapt to those risks. Identified MIT campus risks include chronic heat stress, inland
flooding from precipitation, rising sea levels and storm surges and extended power outages.
Resilience will play a major role in the design even when discounting hazard events. For
example, cumulative “normal” weather events will have deleterious effects on the function of the
building and those effects must be minimized. Water management (both bulk and vapor) along
with UV damage and thermal cycling effects will be addressed to lessen their on-going
cumulative damaging effects. The design of the building (configuration, materials, methods) must
respond to the identified existing hazards to the degree to which they exist and on a scale of
greatest to least to risk.
In addition to preparing the campus for climate change risks, responding to tragic emergencies
and disasters has potential safety, social, and reputational impacts. Through the MIT Police
department, the Office of Emergency Management & Business Continuity, and other internal and
external campus partners, MIT strives to maintain and improve its disaster resiliency through
preparedness, mitigation, response, and recovery efforts, keeping life safety, incident
stabilization, and protection of property and the environment as its top priorities.
Goals:
1. Design new buildings to incorporate flexible and adaptable design strategies that will provide
a basic level of resilience and ability to respond to and recover from a variety of climate and
man-made risks and disasters.
2. Emphasize and incorporate preparedness and mitigation measures into the project in order to
address and mitigate the effects of emergencies prior to their occurrence.
Projects will develop an emergency plan based on the following criteria in order of priorities:
• Enable life-safety of the occupants
• Prevent catastrophic failure
• Prevent major damage
• Prevent minor damage
• Ensure continued occupancy immediately following certain hazard events as defined by MIT
• Critical equipment to be located above the 26-ft flood level (Cambridge Datum).
• Elevators to have pit flood sensors and auto return to the lowest floor above the design-flood-
elevation.
• Emergency backup power to be provided for all critical building functions at a minimum.
• Specific areas that to remain operational are:
o Lighting
o Plumbing systems
o Hot water pumps
o Others to be determined at a project by project level
• Durable, moisture-resistant interior and exterior building materials to be included in the
specifications, with special consideration for materials on the lower levels of the building that
can dry out without requiring replacement
• Sustainable stormwater management and landscape-based strategies to provide additional
capacity to mitigate flooding potential and address urban head island effect
• Other considerations to be considered during design:
o PV battery storage with a software platform to manage energy use and provide
emergency backup power will be vetted during Design Development.
o Redundancy in critical building systems, to provide basic utilities and services to
occupants during an emergency.
o Emergency sheltering strategies
o Security features to protect occupants from violent intruders, such as secure-in-place
strategies, intrusion detection systems, closed circuit television camera system,
communication systems, etc.
o Strategies to reduce indoor flooding, such as sump pumps, internal drainage systems, etc.
o Ground level adaptive strategies to mitigate flood impacts such as raising the ground
floor level, flood walls, etc.
END OF DOCUMENT
SITES Performance Standards for MIT Projects will help ensure that individual projects support the
larger campus sustainability goals identified by the Sustainable Stormwater and Landscape Ecology
Plan (currently under development). The key goals established by the Plan are intended to address the
following campus and regional issues:
The SITES Performance Standards for MIT Projects build on several credits established under the
American Society of
ǯȋǯȌ SITES v2 Rating System in the Water, Soil +
Vegetation, and Human Health + Well-‐Being categories. The SITES credit rating system supplements
the USGBC LEED® Rating System credit rating system, which is heavily weighted on the building
sustainability performance and not site and campus issues, which are currently reviewed as part of most
design projects on campus.
Consistent with the Sustainable Stormwater and Landscape Ecology Plan, the selected SITES credits
were identified as having relevance for addressing campus-‐wide resiliency, stormwater, and landscape
ecology priorities. The selected SITES credits were further adapted to suit the urban campus.
Expanding on the SITES criteria of Dz
ǯ
r
ǡ
ǡdzǡ
site runoff
through Dz-‐bendzto stormwater management that provide other benefits such as
resiliency, habitat creation, urban heat island mitigation, and potable water conservation.
The recommended Performance Standards shall be reviewed and considered by individual projects on
ǯ
as part of the planning and design process, as directed by MIT. Priority credits have been
identified with the priority icon .
2
4
MANAGE PRECIPITATION ON SITE
REFERENCE SITES V2 CREDITS: WATER P3.1, WATER C3.3
Intent
Maintain site water balance, protect water quality, and reduce negative impacts to aquatic ecosystems,
channel morphology, and dry weather base flow by replicating natural hydrologic conditions and
providing retention and treatment for precipitation on site.
Project Performance
Credit 3.3: Manage precipitation beyond baseline by retaining or treating the precipitation volume
from the 90th percentile precipitation event through on-‐site infiltration, evapotranspiration, and reuse.
Any precipitation volume for the 90th percentile storm event that is not retained through on-‐site
infiltration, evapotranspiration, and reuse (due to site constraints) shall be treated for total suspended
solids (TSS), phosphorus, and bacteria through landscape-‐based treatment systems. Perform load-‐
based water quality calculations to confirm 80% TSS removal and 65% phosphorus removal.
Clarifications
The calculated 90th percentile precipitation event as defined by the US EPA in the Technical Guidance
on Implementing the Stormwater Runoff Requirements for Federal Projects under Section 438 of the
Energy Independence and Security Act is approximately 1.2-‐inches. The calculated 95th percentile
͙Ǥ͞dzǤ
These strategies to retain and treat the 90th percentile storm event (1.2 inches) slightly exceeds the City
of Cambridge requirement to provide TSS and phosphorus removal for the 1-‐inch storm. The City also
requires peak runoff rate mitigation so that the proposed 25-‐year storm peak rate is consistent with the
existing 2-‐year peak rate. The strategies used to meet Credit 3.3 will contribute to meeting the peak
rate reduction requirement, however additional detention strategies and calculations may be required
to confirm
ǯ.
Strategies and Toolkit
ǯ includes several strategies for managing stormwater in a manner that is
integrated with the landscape, including:
x Green Roofs
x Porous Pavement
x Bioretention Practices
x Infiltration Practices
x Filtration Practices
x Rainwater Harvesting
6
REDUCE OUTDOOR WATER USE
REFERENCE SITES V2 CREDITS: WATER P3.2, WATER C3.4
Intent
Conserve water resources and minimize energy use by encouraging water conservation strategies that
limit the use of potable water, natural surface water, and groundwater withdrawals for landscape
irrigation and other outdoor use.
Project Performance
Prerequisite: Reduce the use of potable water, natural surface water, and groundwater withdrawals for
landscape irrigation (beyond plant establishment) by reducing water usage by at least 50 percent from
the baseline case as required in SITES v2 Prerequisite 3.2 (Reduce water use for landscape irrigation)
Option 1.
Credit: Reduce the use of potable water, natural surface water, and groundwater withdrawals for
landscape irrigation by aligning with SITES v2 Credit 3.4 (Reduce outdoor water use) Option 1 by
reducing water use by at least 75 percent from a baseline case.
Clarifications
Projects should align with this credit by using conservation and reuse strategies to reduce the use of
potable water for landscape irrigation in alignment with the Prerequisite and Option 1.
Note, Water P3.2 is more stringent than the LEEDv4 Prerequisite for outdoor water use (option 2)
͛͘
ǯ
month.
Note, Water C3.4 is more stringent than the LEEDv4 Credit for outdoor water use reduction (Option 2),
͘͝
ǯ
month.
In the case where created water features are proposed on a given project, Water C3.4 guidance under
Options 1, 2, and/or 3 should be considered.
7
Strategies and Toolkit
8
DESIGN MULTI-‐BENEFIT
STORMWATER FEATURES
REFERENCE SITES V2 WATER C3.5
Intent
Provide a connection to the local climate and hydrology by integrating aesthetically pleasing
stormwater features that are visually and physically accessible and manage on-‐site stormwater.
Project Performance
Align with SITES v2 Credit 3.5 (Design functional stormwater features as amenities) by ensuring site
precipitation is treated as an amenity in the way itǯs received, conveyed, and managed (Option 1).
Clarifications
For the purposes of this credit, projects should use landscape-‐based, multi-‐benefit stormwater
strategies wherever space allows, as well as collecting and repurposing stormwater
Green Roofs
9
USE APPROPRIATE PLANTS
REFERENCE SITES V2 SOIL VEG P4.3
Intent
Improve landscape performance and reduce resource use by installing only plants that are appropriate
for site conditions, climate, and design intent.
Project Performance
Minimum Requirement: Select plants species that are suitable for site conditions, climate, and design
intent as required by SITES v2 Prerequisite 4.3 (Use appropriate plants) by using only appropriate plant
species that are suitable for the site conditions, climate, and design intent for both native and non-‐
native plants. Use plants that are nursery-‐grown or salvaged for reuse from on or off site. All nursery-‐
grown plants must use standards set by the ANSI Z60.1-‐2004 American Standard for Nursery Stock.
Clarifications
ǯ
ǡlant selections must be species that have proven to be resilient and
tolerant of urban planting conditions including criteria such as reduced planting soil volumes, pollution,
paved rooting zones, root structure, reduced watering, heat reflectance from pavements and buildings,
temperature extremes, wind, and pollution. (DzdzǡǤȌ
While use of urban-‐tolerant native plants is encouraged, plant selection should also consider native
ǡ
ǯ
Ǥ
those that were not originally part of the natural ecosystem but have evolved to a point where the
physical conditions such as soil, climate, and water needs are conducive for healthy growth.
https://www.forestadaptation.org/ne-‐species
Dz
dzǡ
ǡ
published by the MA Executive Office of Energy and Environmental Affairs.(Dzand
dzǡǤȌ
Plants that are susceptible to being infected by known invasive alien species of pests should not be
planted. Refer tDz
dz. Infected plants should be
10
evaluated by a certified arborist for treatment and, if untreatable, should be removed. (Dz
dzǡǤȌ
Plants infected by the diseases should be evaluated by a certified arborist for their potential to spread
to other trees. Evaluate infected trees for efficacy of treatment and determine if trees should be
removed. (DzdzǡǤȌ
Soil volumes are critical for long-‐term health and resiliency for urban trees due to the prevalence of
Ǥ
ȋDzdzǡȌ
require that roots occupy soil below pavement.
Structural Soil, or another proven material or system, proven to maximize soil volume for trees in
pavement.
Resilient Urban Plants: MIT to develop urban plant palette acceptable for their campus.
https://forestadaptation.org/framework-‐components/forest-‐adaptation-‐resources and
https://species.itreetools.org/selector/
Plant Soil Volumes: Calculate soil volumes based on anticipated mature caliper size. For trees:
http://www.greenblue.com/na/resources/soil-‐calculator/
11
CONSERVE HEALTHY SOILS AND
APPROPRIATE VEGETATION
REFERENCE SITES V2 SOIL + VEG C4.4
Intent
Protect existing ecosystem services and landscape performance and protect soil heath by limiting the
disturbance of existing appropriate plants and healthy soils.
Support healthy plants, biological communities, and water storage and infiltration by planning for soil
restoration in the design stage and limiting soil disturbance during construction.
Alignment with Campus Goals
Project Performance
Align with SITES v2 Credit 4.4 (Conserve healthy soils and appropriate vegetation) (Option 1) by
conserving existing healthy soils and plants that are appropriate for site conditions, climate, and design
intent in Vegetation and Soil Protection Zones (VSPZs). This will be different for every MIT site and
should be determined on a case-‐by-‐case basis taking into consideration plant health, soil condition,
amendment program, constructability, and construction sequencing. The primary aims are to prevent
damage to soil structure that can result in the inability to amend and re-‐use soil resources and to
eliminate construction practices that threatens tree health.
Clarifications
Disregard the percentage requirements for vegetated soil protection zones (VSPZ). ǡǯ
Specification Section 015640 DzTemporary Tree and
dz
VSPZs.
12
elsewhere on campus. When soil must be removed ǯcampus, all jobs must contact MIT
Environment, Health & Safety for disposal protocol.
The preliminary soil management plan (SMP) should also identify special status trees and other plants
and specifically identify these zones as part of the VSPZ. Emphasis for soil management should be
placed on preserving and creating contiguous soil zones for plant roots, regardless of final surface
condition. For plants in impervious surfaces, extend root zones below pavement by using sand-‐based
structural soil, or another proven material or system that is beneficial for urban tree growth. Consider
the viability of using and connecting to root zones on adjacent sites to improve the overall campus
connectivity for plant roots. To the extent possible, use permeable pavements over root zones to allow
great water infiltration and air exchange.
Trees adjacent to a development site, including street trees, could also be impacted by construction
activity. During the analysis phase, examine site context and identify trees at risk. Recommend extent
of tree protection.
Protection of trees should be aligned with BMP for urban trees, see Strategies and Toolkit, below:
Strategies and Toolkit
ǣǯ
͙͘͘͜͝͞ǡ
dz
https://www.nycgovparks.org/pagefiles/84/standard-‐tree-‐protection-‐notes-‐for-‐permits-‐and-‐plan-‐
review-‐spring-‐2015.pdf
13
CONSERVE SPECIAL STATUS
VEGETATION
REFERENCE SITES V2 SOIL + VEG C4.5
Intent
Protect existing ecosystem services by identifying and conserving all vegetation on site designated as
special status.
Project Performance
Align with SITES v2 Credit 4.5 (Conserve Special Status Vegetation) by protecting special status
vegetation such as heritage or legacy trees, specimen trees, rare and endangered species, rare
vegetation in a unique habitat, and unusual genetic variants of a particular species.
Clarifications
For MIT, the following areas have Special Status Vegetation and require a protection plant and soil
protection plan (VSPZ, reference Project Performance Standard section entitled Dz
Soils and Appropriate Vegetationdz):
Chapel Grove.
Walker Memorial / Hayden Memorial Allee Honey Locusts and mixed planting.
14
Dzdzǯdz͚͙͘͟Inventorydzhall be evaluated for retention.
https://mit.treekeepersoftware.com/.
Regardless of their physical condition, special status shall not be given to plants that are listed on the
Dz
dzǡ
ǡ
Energy and Environmental Affairs: http://www.mass.gov/eea/agencies/agr/farm-‐
products/plants/massachusetts-‐prohibited-‐plant-‐list.html
15
MINIMIZE EFFECTS ON MICROCLIMATE
REFERENCE SITES V2 SOIL + VEG C4.9, SOIL + VEG C4.10
Intent
Minimize effects on microclimate and human and wildlife habitat by using vegetation in strategic
locations to reduce energy consumption and heat island effects.
Project Performance
Align with SITES v2 Credit 4.9 (Reduce urban heat island effects) by using existing plant material and
installing plants that provide shade over paving areas. Use formula provided by SITES to measure
reduction of urban heat island effect for site paving and structures or alternative approach using solar
reflectance index (SRI) and solar reflectance (SR) as provided by SITES.
Align with SITES v2 Credit 4.10 -‐ Study the options for vegetation: reduce energy use, provide shade,
provide windbreak.
Clarifications
Note Credit 4.9 is the same as the LEED v 4 Credit for Heat Island Reduction. The LEED credit also
allows for an optional compliance path to provide covered parking.
Note, although LEED suggests that landscape can be used as a strategy to reduce building energy use,
SITES v.2 Credit 4.10 establishes criteria for using landscape to reduce energy use.
16
PROVIDE OPTIMUM SITE
ACCESSIBILITY, SAFETY, AND
WAYFINDING
REFERENCE SITES V2 HHWB C6.2
Intent
Project Performance
Align with SITES v2 C6.2 (Provide optimum site accessibility, safety, and wayfinding) by providing site
access and usability, improving safety, and creating an environment that makes it easy and intuitive for
users to orient themselves and navigate from place to place.
Clarifications
Wherever possible, design the accessible route so that it is also the main route to the building for
everyone. This can be done by using pavement slopes equal to 5% or less (NOTE: using a maximum
4.5% slope is recommended to allow for construction tolerances. Review MIT Site Standards
Dz
dzsection 1.3 ADA and MAAB Compliance for MIT recommended
slopes.)
17
SUPPORT HUMAN WELL-‐BEING
REFERENCE SITES V2 HHWB C6.4, HHWB C6.5, HHWB C6.6
Intent
Improve human health and well-‐being by providing visual and physical connections to restorative
outdoor spaces, encourage outdoor physical activity and support people gathering, eating, working and
playing together.
Project Performance
Align with SITES v2 C6.4 (Support mental restoration) by providing accessible, quiet outdoor spaces
that include seating for five percent of total site users, visual and physical access to vegetation,
elements that reduce noise and mitigate negative distractions, and elements that address microclimate
and other site-‐specific conditions (e.g. sun, shade, wind). For sites with regularly occupied buildings,
provide unobstructed views of vegetation, from 50 percent of common spaces (e.g., office spaces,
classrooms, waiting rooms, living areas, dining rooms).
Align with SITES v2 C6.5 (Support physical activity) by developing and implementing a functional plan
that encourages outdoor physical activity, provide services to support site users during physical activity,
and considers outdoor physical activity features.
Align with SITES v2 C6.6 (Support social connection) by providing outdoor spaces to encourage social
connections that include seating for a minimum of 10 percent of the total site users that accommodate
a variety of group sizes and is appropriate to the site; elements that address microclimate and other
site-‐specific conditions (e.g. sun, shade, wind); and amenities, services, or activity spaces (e.g. games,
wireless access, food concessions, picnic or dining areas, outdoor auditoriums, ǯ, ǯ
markets)
Clarifications
For Credit C6.5 (Support physical activity), disregard the requirement to provide at least two of the
following five outdoor physical activity features. The number of outdoor physical activities does not
need to be quantified unless required by MIT planning/facilities staff.
18
Work with MIT Planning to determine the best and highest use of outdoor spaces for each development
area.
ǯ
activities and social spaces, relative to what would be appropriate and desirable on the proposed
development site.
Human well-‐being: Restorative Benefits of Nature: Toward an Integrated Framework, by Stephen
Kaplan http://www.wienerzeitung.at/_em_daten/_wzo/2015/08/07/150807_1710_kaplan_s._19951.pdf
19
!
!
MIT
Design Standards
Campus Safety and Security Services
Thematic Folder
May 2018
!
!
1.0! MIT IS&T Overview & Goals """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" #!
2.0 ! MIT IS&T Campus Safety and Security Services """""""""""""""""""""""""""""""""""""""""""""""""""""" #!
3.0 ! MIT IS&T Campus Safety and Security Governance """""""""""""""""""""""""""""""""""""""""""""""" #!
4.0! Vendor Requirements""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" $!
5.0 ! Definitions, Terminologies, and Sub Components """""""""""""""""""""""""""""""""""""""""""""""""""""" $!
6.0! Access Control Points """"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" %!
7.0! MIT Telecommunication Room Requirements """""""""""""""""""""""""""""""""""""""""""""""""""""""""" &!
8.0! Building Roof Tops Doors and Hatches"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" '!
9.0! Monitor Points (MPT) """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" (!
10.0! Access Control Panels (ACP)"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" (!
11.0! Device Cabling """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" )*!
12.0! Elevator Access Control"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" ))!
13.0! Magnetic Hold Open Devices"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" ))!
14.0! Electric Locking Door Hardware """"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" )+!
15.0! Key Management Solution"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" )+!
16.0! Intrusion Alarm Zones and Intrusion Alarm Panels """""""""""""""""""""""""""""""""""""""""""""""" )+!
17.0! Emergency Phones"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" ),!
18.0! Life Safety Panic Alarm"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" )%!
19.0! Intercom Systems and Devices"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" )%!
20.0! Exterior Video Surveillance"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" )%!
21.0! Interior Video Surveillance""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" )&!
22.0 Specialty Cameras """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" )&!
APPENDIX A: Physical Security Services Requiring Approval Prior to Installation""""""" )(!
APPENDIX B: Door Typicals """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" +*!
APPENDIX C: Access Control Panel (ACP) Enclosure Typical (ISTAR)""""""""""""""""""""""""" #+!
APPENDIX D: Access Control Panel (ACP) Enclosure Typical – Mercury""""""""""""""""""""""" ##!
APPENDIX E: CSSI Definitions of Terms as They Relate to Electric Locking Hardware #%!
APPENDIX F: Electric Lock Type Options""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" #(!
APPENDIX G: Standard Security System Products """"""""""""""""""""""""""""""""""""""""""""""""""""""""" $*!
APPENDIX H: Software House iSTAR Ultra SE controller """"""""""""""""""""""""""""""""""""""""""""" $+!
APPENDIX I: Programming Ccure 800 and Ccure 9000 Naming Schema """"""""""""""""""""""" $%!
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 2 of 150
APPENDIX J: Roof Top Doors and Hatches """"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" $&!
APPENDIX K: Key and Asset Management Solutions""""""""""""""""""""""""""""""""""""""""""""""""""""""" $(!
APPENDIX L: Emergency Phone Stanchions """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" %*!
APPENDIX M: Emergency Stanchions """""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""" '%!
APPENDIX N: Camera Equipment"""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""""")*+!
APPENDIX O: Camera Viewing Minimum System Requirements"""""""""""""""""""""""""""""""""")$*!
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 3 of 150
1.0 MIT IS&T Overview & Goals
Information Systems and Technology (IS&T) is MIT's central IT organization, tasked with supporting MIT's core mis-
sion: "...to advance knowledge and educate students in science, technology, and other areas of scholarship that will best
serve the nation and the world in the 21st century."
Video Surveillance
Access Control
Intrusion Alarm
Audio/Visual Intercoms
Emergency Phones
!!
The MIT Campus Safety Working Group (CSWR) governs the installation of all physical security devices installed
throughout campus which requires connection and/or response from MIT Police. The below services require approval
from the CSWR team prior to installation. Submission of request for approval should be submitted by the requester of
this service. Please see the IS&T contact person for details on how to submit a request for installation of these services.
Please see appendix A for list of physical services requiring approval prior to installation.
RELATED DOCUMENTS
DIV. 26
DIV. 27, 3.1 – BDF Room and Location Physical Requirements
DIV. 27, 4.1 – IDF Room and Location Physical Requirements
DIV. 27, 5.2 – Communication Cable System Conduit
DIV. 27, 5.3 – Conduit Installation Guidelines
DIV. 27, 5.4 – Communication Cable System Pull Boxes
DIV. 27, 5.5 – Horizontal Cable Support Hardware (Non-Continuous)
DIV. 27, 3.1 – BDF Room and Location Physical Requirements
DIV. 27, 4.1 – IDF Room and Location Physical Requirements
DIV. 27, 5.2 – Communication Cable System Conduit
DIV. 27, 5.1 – Communication Cable Trays
DIV. 27, 5.3 – Conduit Installation Guidelines
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 4 of 150
DIV. 27, 5.4 – Communication Cable System Pull Boxes
DIV. 27, 5.5 – Horizontal Cable Support Hardware (Non-Continuous)
Vendor requirements: Vendor must be authorized and certified in the systems devices, and components, all makes and
manufacturer that is contained in the project scope.
!
As Built drawings: As Built drawings must be provided to the IS&T Project Manager or Project lead
electronically both in AutoCAD and PDF prior to closing a project"
There are a number of names and acronyms used to describe the components of the MIT security environment. Abbre-
viations and assumed sub components throughout this document and related standards include:
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 5 of 150
! PDL-IN: Inbound Paddle
! PDL-OUT: Outbound Paddle
Requirements:
Card Reader/Access Control Points (CR) are doors equipped with card readers (RDR), electric locking hardware
(LCK), door contacts (DC), and request to exit devices (RTE) unless the request for exit device is embedded in
the LCK. They may also include a local sounder (S). They may need to be interfaced with an Auto Door
Opener (ADO) device or Magnetic Door Hold Open device (DHO). Door functions such as fail safe/fail secure,
interface with ADO, delayed egress, and positive latch for smoke compartmentalization determine electric lock-
ing hardware choices (See appendix F for list), and need to be considered during the design phase of a project.
All devices associated with a CR shall be “home run” to their hosting Access Control Panel (ACP). There shall
be no remote Reader Module (RM) boards or remote Input/Output (I/O) boards unless specifically called for in
project specifications or directed by MIT CSSI.
1. Access Control Point Cabling: The Contractor shall provide the following:
a. Cable Bundles: A standard cable bundle for an Access Control Point is one 18/2, one 22/6
shielded, and one 22/12 conductors (all plenum rated).
b. Horizontal or Vertical Penetrations out of the TR: Refer to TR section of this document for re-
quirements.
a. Horizontal Cable Runs: In each corridor, where possible, provide and install D-rings or similar
hardware attached to the side of Tel/Data cable trays. Where no cable tray is available and the
cable bundle cannot be run “soft”, provide and install in conduit.
b. Pathways: To be provided by the Electrical contractor. Pathway should be a shared pathway,
calculated based on needs and growth. To work in accordance with Division 27. Please work
with MIT IS&T for design.
c. Extra Cable Lengths: Extra cable length and unused conductors shall be labeled on both ends
and stored at each Access Control Point in junction box for future use and at each ACP in 6 by
6-inch cable trough for future use.
2. Access Control Point Devices: The Security Contractor shall provide the following:
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 6 of 150
a. Electric locking Hardware (electrified strikes, mortise sets, crash bars).- Provided and Installed
by others. Refer to Appendix F for the list of MITs approved Electronic lock devices and ap-
propriate electric locking hardware decisions
ii. All RDR shall be programmed by CSSI to accept the MIT proximity card access security proto-
cols prior to reader installation. The Security Contractor shall work with CSSI personnel to
perform this pre-installation programming on all Card Readers.
iii. Each RDR shall be mounted on the wall or in a single gang box with pipe to cable junction box
at appropriate ADA height and distance from the door.
v. Physical cable labeling is required using a labeler is according to MIT CSSI standards.
vi. Security Contractors shall comply with MIT CSSI naming schemes, and provide final connec-
tions, configuration, and testing of various Access Control and Security Devices in accordance
with CSSI. – Please see Appendix I for naming schemes.
• MIT IS&T’s telecom rooms (TRs) require the installation of mortice style electronic locking mecha-
nisms via an electrified transfer hinge (with integrated REX), multiclass & Bluetooth built-in card read-
ers, and recessed door contacts. EOL resistors installed at field end of REX and DSM. Below are the
specifics for input supervision standards.
• Each TR door cabled back to an access control enclosure located in the buildings MDF/BDF using spe-
cially chosen composite cabling.
• See Appendix D (Cabling Requirement) for MIT IS&T Mercury cabling requirements
• Cabling pathways in accordance with Div. 27
• MIT IS&T will provide network connections (including patch cables) capable of routing to the access
control servers.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 7 of 150
• MIT IS&T will configure the dipswitches, username/password, and network address of the network
managed hardware. Access control system configuration and programming is the responsibility of MIT
IS&T with the expectation of a full system signoff upon job completion.
• To facilitate systems pre-programming, the integrator will provide one-line diagrams/risers electronically
before commencing any work. This will allow for a smooth transition into systems testing. Provided the
floorplan door number in conjunction with which input/output/reader slot index (Panel ID # - Slot In-
dex). For example, W79-375T-REX-1<--->MR52-2-INPUT2. Door contacts connect to first input pair
allotted per door, door monitor (DSM) followed by request to exit (REX.) Each ACP board’s first four
inputs allotted for doors, inputs 5-8 are spare or allotted for AED or panic button inputs.
• A representative of MIT IS&T Campus Safety and Security Infrastructure (CSSI) group will conduct
systems testing upon completion. All installed hardware shall be functional and conform to manufac-
turer’s installation guidelines. The integrator will be present during the systems testing, assuring func-
tionality and quality of work.
MIT’s rooftop egress access doors and hatches will be equipped with access control technology to provide card access
(doors) and monitoring points (for hatches). Doors will be outfitted with mortice style electronic locking modules (with
integrated REX) via an electrified transfer hinge, card readers, local low voltage sounders, and recessed or surface-mount
door contacts. (EOL resistors installed at field end of REX, DSM specified has resistors built-in.) Exterior camera will
be installed to view the door(s) and will be monitored by MIT Police. If an exterior camera cannot be installed, consult
with MIT Campus Safety and Infrastructure team for location for interior camera. See Appendix J for door hardware list
and requirements along with input supervision standards. See Appendix O for Camera and Mounting Requirements
Genetec Synergis Cloud Link (SCL) controller and separate enclosure will also be required per MIT building (enabling
the host-server connection: See Appendix J for Genetec Synergis Cloud Link & Enclosure Specifics). SCLs are POE
devices, the POE network connection to be provided by others. Exact location shall be coordinated with MIT Network
Infrastructure team. Mounting of SCLs will be the responsibility of the access control integrator (ACI).
Each of the rooftop doors/hatches cable back to an access control panel (ACP) in a location to be coordinated through
MIT Network Infrastructure team (see Appendix J access control panel hardware list for specifics). The ACI will be ex-
pected to hang/mount each of the ACPs. Final location of ACP to be coordinated by IS&T Network Infrastructure’s pro-
ject manager. 120v A/C ACP power and pathway will be provided by others.
Doorways leading to rooftop open-air space will be (a-typically) piped accessible from the unsecure side (See Appendix
J ‘door typical’ drawings). This will alleviate roofing membrane penetration issues and exposure to the elements. Fit-
tings and box covers of ACI pathways for mortice, door contact and REX installed on the unsecure side require tamper-
proof hardware.
Roof hatches require the ACI install surface mounted door contact and local low voltage sounder (see Appendix J for
sounder hardware requirements). Surface contact installation should be mounted in a fashion that does not pose an ob-
struction for personnel climbing out of the hatch, nor should it impede the mechanical operation of the hatch/hinge.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 8 of 150
MIT IS&T will provide network connections for ACPs and SCLs (including patch cables) capable of routing to the ac-
cess control servers.
MIT IS&T will configure the dipswitches, username/password, and network address of the EP1502 & MR52’s. Power
supply management interface will be configured by MIT IS&T. Access control system configuration and programming
is the responsibility of MIT IS&T with the expectation of a full system signoff upon completion.
To facilitate system pre-programming, the integrator will provide one-line diagrams and/or panel schedules electronically
before commencing any work. This will allow for a smooth transition into systems testing. The list of provided
doors/hatches defined by which input/output/reader slot index (Panel ID # - Slot Index). For example, W79-375T-REX-
1<--->MR52-2-INPUT2. Door contacts connect to first input pair allotted per door, door monitor (DSM) followed by
request to exit (REX.) Each board’s first four inputs allotted for doors, inputs 5-8 and outputs 3 &4 are intended for
monitoring points (hatches).
A representative of MIT IS&T Campus Safety and Security Infrastructure (CSSI) group will conduct systems testing
upon completion. All installed hardware shall be functional and conform to manufacturer’s installation guidelines. After
conducting field testing, CSSI may have a list of input troubles, or general functionality issues which will be reported as
a punch list.
The ‘Door Typical’ drawings included are meant to be a reference for block/concrete hall scenarios. Any space where
hollow-wall chases can be provided, should be.
Wherever possible recessed door contacts and electrified hinges should be used. In restrictive spaces or impenetrable
medium; surface-mount contacts and door cords can be used with approval from CSSI. See Appendix J for approved
door hardware list specific for rooftop doorways and hatches.
Requirements:
• MIT standard is to run the same cable bundle to a MPT door that would otherwise be used for an Ac-
cess Control Point (CR) door (the extra cable conductors already in place at the door to add a card
reader and electric lock in the future if MIT decides)
• Needs to “home run” back to the hosting Access Control Panel (ACP).
All card reader equipped doors shall be hosted on an Access Control Panel (ACP). Design/infrastructure for Access
Control Panel shall be consulted with IS&T CSSI prior. See appendix C and appendix D for details on the 2 ACP
options.
ACP’s are installed in Telecommunication Rooms (TR’s) on a wall taking up a space 4 feet wide from floor to ceil-
ing. Height of panel shall be 8 feet at top of the panel maximum.
TR’s are required to be outfitted with a separate 4” sleeve out, up, and down as necessary to accommodate security
device wiring.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 9 of 150
a. Minimum ACP components:
• Input/output boards and power supplies as necessary to supply inputs and outputs for
alarmed points not associated with a Card Reader Access Control Point.
• Non-card reader Monitor Point doors and redundant intrusion Alarm Zone inputs from
Alarm Panels or additional input boards.
• Alarm sounders that may require outputs from additional output boards.
• No ACP inputs or outputs shall be utilized for any purpose other than access control as
specified so inputs and outputs associated with Card Reader installations remain available
for future expansion of the Access Control System.
• Troughs, approximately 6 by 6 inch, to store unused, labeled cable for future use above or
below the Access Panel Enclosure.
• Accessories inside each enclosure to accept network drops provided by others.
• Provisioned for Fail Safe or Fail Secure doors.
o Security Contractors shall work with CSSI to establish secure network communications to MIT’s
Security servers inside MITs BMS Network.
o Connection to the building’s emergency power supply (20-amp dedicated circuit/110 volt termi-
nated at each ACP location) with a duplex outlet located inside each ACP enclosure provided by
others.
o Connection to the building’s automatic fire detection system via a module located directly above
each ACP enclosure provided by others. The Security Contractor (SC) shall connect the elec-
tronic lock power supply to the automatic fire detection system module and shall ensure that all
the fail-safe and fail-secure doors operate properly in a fire emergency with an active signal from
the automatic fire detection system.
o We need a dry contact that opens upon general activation of the FA system and remains open
until the FA panel is fully reset, not just silenced. No lock power is routed through this relay,
only coil power for our isolation relay, which is 24 VDC at less than .25 amp.
o Working with MIT and other Contractors to ensure the Security System interfaces properly with
other various building systems (including Elevator Access Control, Automatic Fire Detection
System and Automatic Door Openers as necessary) to provide the necessary functionality.
o Final device connections and configuration and setup and testing of key supervision and tamper
alarm events to be monitored by MIT personnel as appropriate.
Requirements:
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 10 of 150
Standards for Device Cabling – All cabling out to field devices to support an Access Control Point (RDR) or a
Monitor Point (MPT) can make use of all low voltage pathways. Please consult with IS&T for the appropriate
cable fill ratios for all applicable pathways.
Call Button Access Control – With Call Button Elevator Access Control, a card reader is mounted outside of the elevator
cab next to the elevator call button. In this application, the security system interrupts the function of the elevator call
button when the elevator is in controlled access. A passenger presents a card and if authorized for use, the security sys-
tem closes a normally open relay allowing the call button to function. In this application, the entire function falls under
the security contractor’s scope of work.
In-Cab Floor Control – With In-Cab Elevator Access Control, the card reader is mounted inside the elevator cab itself
next to the floor buttons. The card reader is connected to conductors in the elevator’s travelling cable (six plenum-
shielded conductors are required). The elevator controller is interfaced with the security system. When a floor button is
in controlled access, it does not function. If a passenger presents a card to the in-cab card reader, the security system
communicates to the elevator controller which floors (if any) the passenger is authorized to use. Those previously con-
trolled floor buttons then become functional or uncontrolled. As soon as the authorized passenger selects a floor button,
all of the previously controlled buttons become controlled again (referred to as “closing the access window” and required
for all floor controls in elevator). The elevator controller shall communicate to the security system which floor button
the passenger chose so MIT can retain an access record of where that passenger went.
• Whenever in-cab floor control is called for in an elevator as part of a project, all floors (except the fire-
man’s floor or egress floor) shall be equipped for floor control even if the initial intent of the project is
for only some floors to be controlled.
• Integration of the security system and the elevator controller(s) falls on both the security contractor and
the elevator contractor. Both contractors need to include systems integration as part of their project
scopes including the technician time necessary for both contractors to work together to interface the sys-
tems.
• The integration of the security system and elevator controller shall be contained in an enclosure mounted
outside of the elevator control room (so the security system portion of the interface can be serviced and
maintained without requiring access to the elevator machine room).
• The integration of the security system and elevator controllers shall be “fail safe” meaning that if the in-
terface fails for any reason, the default state of the elevator floors shall be free access or uncontrolled ac-
cess.
Magnetic Hold Open Devices – Magnetic Hold Open Devices are devices used to keep corridor doors or other doors held
open for long periods of time.
These devices are usually used on smoke compartmentalization doors that need to close on an active fire event. As such,
they are hosted on and powered from the building’s automated fire detection system and are part of the fire system pro-
ject scope.
Whenever these devices are used on a door(s) that also includes Access Control (and/or whenever it is MIT’s desire is to
close these doors on a regularly occurring schedule), the Security System shall be used to control the schedule of activa-
tion for these devices (because there is much more flexibility of schedule control in the Security System).
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 11 of 150
Where this is called for, the Security System shall interrupt the power to the Magnetic Hold Open Device using a nor-
mally open relay. When the relay is closed, the Magnet Hold Open Devices are allowed to be energized thus holding the
door open. When the relay is open, the Magnet Hold Open Devices are de-energized causing the door to close.
The security system does not host these devices. The security system merely provides a normal schedule for the energiz-
ing/de-energizing of these devices. The master control of these devices shall always be the building’s automated fire
detection system (so that even if the security system relay is closed, the fire system can de-energize these devices when
there is an active fire event).
Requirements:
Refer to Appendix G for Standard Security System Products in addition to preferred products listed below.
1. All electric locking hardware in use at the Institute shall conform to the requirements of Massachusetts
State Building Code.
2. All electric locking hardware in use at the Institute shall be Fail-Secure unless prescribed to be Fail-Safe by
building code or as directed by MIT’s CSSI to be setup as Provisional Unlock.
3. MIT CSSI does not approve the use of electro-magnetic door locking hardware (“Mag-Locks).
All Key and Asset Management Solutions shall be interfaced with MIT Security System for the automated import of card
credential data.
An Intrusion Alarm Zone is a physical area (room, suite, floor, etc.) or a set of physical assets (computers, displays, art
work, etc.) that is secured with a series of door contacts, motion sensors, alarm sounders, and other alarm devices such as
asset contacts and is armed/disarmed with an arm/disarm keypad and card reader.
All Intrusion Alarm Zones shall have at least one arm/disarm LCD Keypad with a Card Reader mounted on center below
it. The Card Reader shall be hosted on an ACP and shall be interfaced with the Intrusion Alarm Panel to provide
arm/disarm functionality.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 12 of 150
All Intrusion Alarm Panels and associated components shall be located inside the Access Control Panel (ACP) enclosure
located inside a Telecommunications Room (TR).
Each ACP enclosure that houses an Intrusion Alarm Panel shall have an arm/disarm LCD Keypad mounted on the out-
side of the panel enclosure to be used for servicing/maintaining the Intrusion Alarm Panel.
o Security Contractors shall work with CSSI to establish secure network communications to MIT’s
Security servers inside MITs BMS Network with a quad network connection (3 network ports
and 1 analog port where available) located inside each ACP enclosure provided by others. These
panels are in the TR rooms, please refer to division 27 for details.
o Connection to the building’s optional standby power supply where available (20-amp dedicated
circuit/110 volt terminated at each ACP location) with a duplex outlet located inside each ACP
enclosure provided by others.
o Pathways and Cable from Intrusion Alarm Zones to Intrusion Alarm Panels located in TR’s pro-
vided and installed by others.
o Working with MIT and other Contractors to ensure the Intrusion Alarm Panel and Intrusion
Alarm Zones interface with the building’s Access Control System for arming/disarming all In-
trusion Alarm Zones.
o Final device connections and configuration and setup and testing of key supervision and tamper
alarm events to be monitored by MIT personnel as appropriate.
Emergency Phones, enclosures, and accessories installed on campus function to dial MIT police department’s dispatch
center in case of an emergency. Emergency Phone enclosures will also be equipped with a public address option for is-
suing emergency information or notifications. The manufacturer of the core equipment is Code Blue Corporation. There
are two variants, Wall-mount and Stanchion style deployments. For outdoor Emergency Phones, use Stanchion vs Wall
unless otherwise specified. All Emergency Phones must be integrated with a Camera and each camera should have vis-
ual sighting of the next camera. See Appendix N for MIT Camera Specifications.
Security cameras associated with emergency phone installations will be furnished by MIT’s IS&T CSSI team though the
hardware and installation cost will be carried by the project. Stanchion style will include both a front-facing camera and
overhead pan-tilt-zoom camera, wall-mounted include a front-facing camera. See Appendix L and N for details.
Emergency power and data cabling pathway considerations and specifications in accordance with DIV. 26 & 27 apply
when planning to provision emergency phones. Pathways approved by MIT IS&T Infrastructure representative. The
120 VAC dedicated electrical circuit on standby power where available.
All technical programming, network addressing and configuration will be the responsibility of MIT IS&T.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 13 of 150
Contact Dig Safe prior to any work.
HARDWARE
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 14 of 150
• Voltage: 120 VAC
• Power Option: Line Power
• Communication Option: Line Communications
• Lighting: LED Beacon Strobe
• Public Address System
Emergency Phone: Wall-mounted; Front-Facing Camera
Within a CB2e enclosure, a front-facing camera is both furnished and installed by MIT IS&T, while the cost for the
hardware is funded by the project. Configuration and programming of camera will be the responsibility of MIT IS&T.
EXECUTION
Manufacture guidelines and installation procedures are to be followed. In the event of missing hardware or system com-
ponents contact the vendor to have the missing parts provided. Provided tamper-proof external hardware should not be
substituted otherwise. !,-!./0120!314.!-2254!0.!62!7-!082!6342!.9!082!403-:87.-"
Conduit pathways for power and data are to be separate and in accordance with state code and MIT DIV 26 & 27. The
pathway will pass through the pedestal’s foundation to feed the stanchion in the cleanest manner. Decisions on conduit
and cabling pathway will be facilitated with help of MIT IS&T Network Infrastructure Engineers.
Each enclosure receives an optional standby power where available. All data cabling used in the stanchion is required to
be uplinked from a network connection that is powered by a battery back-up system.
Six activated BMS Network connections are required for each Stanchion deployment. All six connections should appear
sequentially on the BMS patch panel and be labeled A six-port RJ45 wall plate on a single gang surface-mount box
should be affixed inside the stanchion behind the upper removable plate (where the front facing camera lives). Offset the
box to the side to make room for future expansion and to not interfere with the front facing camera. An adequate service
loop should be provided from conduit stub to box, no longer 15’, and neatly coiled within the stanchion. Cat6A network
patch cables should be used from the jack to each camera and VOIP phone with an adequate length for serviceability.
See Appendix L for cabling pathway for the PTZ camera.
While standing, unless actively working on system components, the stanchion should remain bagged off until IS&T has
fully commissioned the phone and peripherals. Enshrouding the phone clearly to indicate that the call station is ‘not in
use’.
Conduit pathways for power and data are to be separate and in accordance with state code and MIT DIV 26 & 27. Deci-
sions on conduit and cabling pathway will be facilitated with help of MIT IS&T Network Infrastructure Engineers.
Each enclosure receives an optional standby where available. All data cabling used in the enclosure is required to be
uplinked from a network connection that is powered by a battery back-up system.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 15 of 150
Four activated BMS Network connections are required for each deployment. An RJ45 wall plate on a single gang sur-
face-mount box can be free-moving (not-mounted) in the bottom trough of the enclosure. An adequate service loop
should be provided from conduit stub to box, no longer 7’, and neatly coiled within the enclosure. Cat6A network patch
cables should be used from the jack to VOIP phone with an adequate length for serviceability.
After mounting the enclosure, unless actively working on system components, the housing should remain bagged off un-
til IS&T has fully commissioned the phone and peripherals. Enshrouding the phone clearly to indicate that the call sta-
tion is ‘not in use’.
Requirement:
These devices come in 2 types. See Appendix D for hardware details
A single BMS network connection will both connect and power (POE) the master controller enclosure (see APENDIX-
A: Master Controller for hardware specifics). ACP & master controller to be located in the BDF/MDF of the building it
supports.
Cabling to meet the part number specified for AED/Panic buttons in ‘Cabling Requirements’ in Appendix D (Cabling
Requirements). Cabling to comply with Division 27 standards. EOL resistors will be added within the button’s shell to
prevent tampering. See below for resistance value specifics. Panic button contact closures will be monitored on inputs
5-8 of each ACP board (leaving inputs 1-4 for doors).
A. Cameras installed in exterior locations, or interior locations that may require a stricter environmental re-
quirement (such as garages) – should be an exterior type camera. See Appendix N – Section 1 for environ-
mental specifications.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 16 of 150
B. Exterior cameras have several mounting options – wall mount, pole mount, ceiling mount, and roof mount.
C. See Appendix N – Section 1 for exterior type camera models, mounts, and associated peripherals.
D. See Appendix N – Section 1 for installation instructions of exterior type cameras and peripherals.
A. Cameras installed in an interior location, should be an interior type camera. Interior locations that may re-
quire a stricter environmental requirement (such as garages) – should be an exterior type camera. See Appendix
N – Section 1 for environmental specifications
B. Interior cameras have a couple mounting options – surface mount and recessed ceiling mount.
C. See Appendix N – Section 2 for interior camera models, mounts, and associated peripherals.
D. See Appendix N – Section 2 for installation instructions of interior type cameras and peripherals.
A. Campus emergency phones utilize a specialty camera, referenced as a ‘front facing camera’.
B. See Appendix N – Section 3 for camera model, mounts, and associated peripherals.
A. Wiring
B. CAT6 termination at the device shall be to a RJ-45 Male Plug. No splices, taps, or extensions
PTZ termination shall be Axis Communications, P/N 39680, IP66 rated connector only.
B. Installation
A. Final camera locations shall be walked with MIT IS&T Infrastructure Representative to determine exact
camera placement locations.
B. Minimum elevation for wall mount cameras shall be 96 inches, not to exceed 144 inches. Elevations
should be the same throughout the entirety of the project. Exceptions to be approved by MIT IS&T In-
frastructure Representative in writing.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 17 of 150
C. If POE exceeding the output of IEEE 802.3af is required, an appropriate POE midspan shall be installed
in MDF or IDF
C. Monitoring Stations
A. If required, end user monitoring stations to monitor cameras shall be furnished by the MIT Customer.
C. Support for the computer system is the responsibility of end user; IS&T recommends purchasing a IS&T
Hardware and Software Deployment team provisioned computer system that meets minimum system re-
quirements.
D. Any Monitoring Station request must be approved by Campus Safety Working group.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 18 of 150
APPENDIX A: Physical Security Services Requiring Approval Prior to Installation
• Emergency Phones
• Panic/Duress Button
• Intrusion Alarms
• Cameras
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 19 of 150
APPENDIX B: Door Typicals
Drawing 500.1
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 20 of 150
Drawing 500.2
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 21 of 150
Drawing 500.3
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 22 of 150
Drawing 500.4
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 23 of 150
Drawing 500.5
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 24 of 150
Drawing 500.6
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 25 of 150
Drawing 500.7
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 26 of 150
Drawing 500.8
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 27 of 150
Drawing 500.9
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 28 of 150
Drawing 500.10
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 29 of 150
Drawing 500.11
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 30 of 150
Drawing 500.12
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 31 of 150
Drawing 500.13
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 32 of 150
Drawing 500.14
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 33 of 150
Drawing 500.15
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 34 of 150
Drawing 500.16
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 35 of 150
Drawing 500.17
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 36 of 150
Drawing 500.18
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 37 of 150
Drawing 500.19
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 38 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 39 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 40 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 41 of 150
APPENDIX C: Access Control Panel (ACP) Enclosure Typical (ISTAR)
• Access Control Panels, components, and devices shall be wall mounted (no rack mounted).
• Each ACP shall be fully built out to host up to 16 card readers hosted on Access Control Modules (ACM).
• Access Control Modules (ACM) and all requisite power supply and relays with the capacity to host up to 16 card
readers on each ACP regardless of the final project capacity use on each panel.
• Each ACP and all of its systems components shall be housed in a single enclosure.
• Power supply unit for each ACP shall be an iSCAN FlexPower LifeSafety Power supply.
• Power supply unit for each ACP shall be installed directly below the panel enclosure.
• Fire Alarm Module (provided and installed by others) shall be located directly above the ACP.
• Connection to the building’s emergency power supply (provided and installed by others) shall be located inside
• Connection to the building’s communication network (provided and installed by others) shall be located inside
APPENDIX C - continued
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 42 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 43 of 150
APPENDIX D: Access Control Panel (ACP) Enclosure Typical – Mercury
A dual BMS Network drop and A/C power will need to be furnished to the ACP enclosure, ACP to be located in the
BDF/MDF of the building it supports.
Cabling Requirements
:@PA5.O!23M6>5/15=.! Q3.K=>! H@>1!7="! 7=13M!
Door Hardware
J@>KL@>3!23M6>5/15=.! GNO! H@>1!7="! 7=13M!
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 44 of 150
,::244!+.-0<.1!O2352<4! ;V>! c(%#@#ZE)@,%LR! 7+F,GG!GE!OBL%!^311!G=70:8!O2352<!
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 45 of 150
APPENDIX E: CSSI Definitions of Terms as They Relate to Electric Locking Hardware
Free Egress – The ability to exit at will. Free Egress can never been impeded but it can be delayed (see Delayed Egress
below). The only exception where Free Egress can be impeded is in a secured Elevator Lobby (see Elevator Lobby be-
low)
Delayed Egress – A delay between the attempt to exit and the ability to exit. In door hardware systems, it is accom-
plished by the triggering of a switch within a component of the door hardware during the course of an exit attempt. The
switch starts an irrevocable 15 second timing sequence leading to the unlocking of the door in the direction of egress.
There can be only one Delayed Egress electric lock on the path of egress.
Lock Function – A term used to describe a selection from the classification system for the functional characteristics of
locks. Four functions are commonly used with electrically controlled access systems:
• Passage Function – Free egress and ingress. No locking controls are present from either side. Commonly used
with electromagnetic locks to provide necessary latching for fire-labeled doors.
• Classroom Function – Free egress. Exterior lever can be locked or unlocked using a key, resulting in a me-
chanical function change from passage to storeroom. Used, but not recommended for electric locking systems as
it introduces the human error of forgetting to relock the door.
• Storeroom Function – Free egress. Non-functioning exterior lever. Key retracts latch for entry. Available as an
electrically controllable lock in both fail-secure and fail-safe. Application or removal of electric current tempo-
rarily changes function to passage.
• Asylum Function, aka Institutional Function – Locked from both sides. Key required to retract latch from ei-
ther side. Cannot be left unlocked from either side. Available as an electrically controllable lock in both fail-
secure and fail-safe. Application or removal of electric current temporarily changes function to passage.
• Switch Bar, aka Active Dummy with Switch – A panic style bar with no latching mechanism that is designed
to switch a low voltage electrical current. Some are UL Listed for the purpose of directly breaking power to an
electromagnetic lock.
Fail-Safe – A term used to describe an electric lock that has a mechanical state of being unlocked and requires power to
lock it. Allows Free Ingress when unpowered.
Fail-Secure – A term used to describe an electric lock that has a mechanical state of being locked and requires power to
unlock it. Prevents Free Ingress when unpowered.
“Provisional Unlock” – A term used at MIT to describe an electric lock that has a mechanical state of being locked
(Fail-Secure) which is powered during an active fire systems event thereby allowing Free Ingress during a fire emer-
gency. Typically used on main entrances to the MIT building and electrically locked Fail-Secure doors on the path the
emergency responders would use to reach the Fire Command Center in the building. Allows Free Ingress on active Fire
Systems emergency but prevents Free Ingress on building loss of power.
• All electric locking hardware in use at the Institute shall conform to the requirements of Massachusetts State
Building Code.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 46 of 150
• All electric locking hardware in use at the Institute shall be Fail-Secure unless prescribed to be Fail-Safe by
building code or as directed by MIT’s Campus Safety & Security Infrastructure Team (CSSI) to be setup as Pro-
visional Unlock.
Locking vs Latching – “A door can be latched, but not locked; locked, but not latched or locked and latched”
• Positive Latching A type of latching where the latch will not disengage the strike unless another mechanical
event occurs, such as pushing on a panic bar or turning a lever or knob.
• Latch, (n.) aka latch bolt. The beveled, spring loaded component of a door hardware device that projects into or
behind an obstruction (called a strike) to prevent the door from opening. Ex.: The lock has a latch.
• Latch, (v.) The action of the beveled, spring loaded device component as it drops into or behind the hole or ob-
struction. Ex.: Did the door latch?
• Latched, (v.) A condition where the beveled, spring loaded device component has projected into or behind the
hole or obstruction Ex.: Is the door latched?
• Latching, (n.) The capability of the beveled, spring loaded device component Ex.: Make sure that the locks are
latching properly.
• Lock, (n.) A device used to prevent passage through a door by restricting its movement from a closed position.
Ex.: Take the lock out of the box and install it.
• Lock, (v.) The action of using a device to prevent passage through a door by restricting its movement from a
closed position Ex.: Will you lock the door?
• Locked, (v.) A condition where the device has restricted the movement of the door from a closed position Ex.:
The door is locked.
• A Fail-Secure, Storeroom Function, Mortise Lock is a free egress door lock with a small solenoid inside that will
change the function of the lock to passage when power is applied. It is also known as electrically unlocked.
Latching is maintained and the lock is available as a fire-listed device.
• A Fail-Safe, Storeroom Function, Electric Mortise Lock is a free egress door lock with a small solenoid inside
that will change the function of the lock to passage when power is removed. It is also known as electrically
locked. Latching is maintained and the lock is available as a fire-listed device, making it an ideal choice for
high-rise stair towers.
Electric Strike (Only where Auto Door Opener devices are planned for use)
• A Fail-Secure Electric Strike is a replacement for the flat strike plate used with cylindrical locks, mortise locks
and mortise panic bars, or the surface mounted obstruction used to engage a rim panic bar latch. Locks used
with electric strikes typically have their own method of mechanical release, either by turning a lever or pushing
on a panic bar, making the door free-egress. These are the preferred strikes for security and can be fire-listed.
• A Fail-Safe Electric Strike is a replacement for the flat strike plate used with cylindrical locks, mortise locks, and
mortise panic bars, or the surface mounted obstruction used to engage a rim panic bar latch. Removing power
causes the fail-safe electric strike to fail in a released position. It can also control locks reversed to protect an of-
fice suite located off of an elevator lobby. Typically, these electric strikes are wired to release on alarm from the
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 47 of 150
fire system. The drawback to their use is that they cannot be fire listed as their release would prevent positive
latching.
Panic Bars
• Electric latch retraction (or release) panic bars always allow free egress and allow ingress by electrically retract-
ing or releasing the latch. They are available as fire-exit hardware.
• Electric Trim, Fail-Secure, for Panic Bars controls ingress, only, and can be fire-listed. Free egress is provided
by the panic bar and is not impeded by the electric trim. Door will remain locked from the outside when power is
removed.
• Electric Trim, Fail-Safe, for Panic Bars controls ingress, only, and can be fire-listed. Free egress is provided by
the panic bar and is not impeded by the electric trim. Door will unlock from the outside when power is removed.
This device is perfect for high-rise stair tower doors (IBC 403.5.3).
Electromagnetic Lock (Not Allowed for Use on Campus except where CSSI Permits)
• An Electromagnetic Lock is a surface mounted lock with no moving parts. It is always fail-safe and has no inter-
locking mechanisms. It cannot bind or lock when power is removed. It requires additional devices to release it
by removing power to it. Additional devices include panic bars with switches, non-latching bars with switches,
and button/timer/motion detector combinations, depending on the code used, the year, and local supplements.
• A Shear Style Lock is a specially engineered, low power electromagnetic lock mounted with the shear line hori-
zontally positioned. Both the lock face and the armature have mechanical interferences that cause them to inter-
lock when powered. Some models can bind if released using bars with switches.
Secured Elevator Lobby – Free Egress can be impeded in the case of a Secured Elevator Lobby as allowed in Massa-
chusetts State Building Code as long as there is only one electrically locked door on the path of egress, the electric lock-
ing hardware is Fail-Safe, the electric locking hardware is connected to the building’s automated Fire System so that it
loses power on active fire event, and there is an automatic ring-down phone in the elevator lobby that directly connects to
security personnel monitored 24/7 with signage thereof as prescribed by building code.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 48 of 150
APPENDIX F: Electric Lock Type Options
Classroom Function
Storeroom Function
Positive Latch
Key Override
Fail Secure
Fail Safe
(Smoke)
Electric Lock Type Options Notes
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 49 of 150
APPENDIX G: Standard Security System Products
Access Control Electric Locks Make Model Notes
Electric Mortise Lock w/Integrated REX Switch Schlage L9092 RX Switch Preferred Electric Mortise Lock w/Built-in REX Device
Electric Mortise (does both EU & EL) Schlage L9092 Electric Mortise Lock w/o REX (Requires REX Motion S
Electric Strike Von Duprin 6111 US32D 24VDC FS/FSE Preferred Surface Mounted Electric Strike
Electric Strike Von Duprin 6210 US32D 24VDC FS/FSE Preferred Electric Strike (fits an ANSI cutout)
Electric Strike Von Duprin 6211 US32D 24VDC FS/FSE Preferred Electric Strike (fits an ANSI cutout)
Electric Strike Von Duprin 6215 US32D 24VDC FS/FSE Preferred Electric Strike for Solid Wood Frame
Electric Strike Von Duprin 6223 US32D 24VDC FS/FSE Preferred Electric Strike for Double Wood Door
Electric Strike Von Duprin 6300 US32D 12/24VDC FS/FSE Preferred Electric Strike Surface Mounted
Electric Strike Adams Rite 7100-510-628-00 Electric Strike for Storefront (not preferred)
Electric Strike Adams Rite 7140-510-313-00 Electric Strike for Storefront (not preferred)
Electric Strike HES 9400-12/24D-613 Electric Strike for Certain Surface Mount (not preferred)
Electric Strike HES 9600 12/24V-630 Electric Strike for Certain Surface Mount (not preferred)
Electric Strike HES 4500 12/24V-630 Electric Strike for Certain Circumstances (not preferred)
Electric Strike Surface Mounted Folger Adams 310-4-1 F24D630 Electric Header Strike (preferred for all-glass doors)
Electric Latch Retraction Crashbar (can be rim or vertical) Von Duprin QEL 9927 Whatever Model with "Q" at beginning (like "QEL")
Power Supply w/battery back up Von Duprin PS914-2RS-BB (replaces 873-2) Necessary When Too Many QEL's on Panel (more than t
QEL+ Conversion Kit Von Duprin QEL+ Conversion Kit Converts Existing Crashbar to Electric
Electric Mortise Crashbar Von Duprin E7500 US32D 24VDC FS Preferred Mortise Crashbar
Electric Trim for Crashbar Von Duprin E996L-M US32D 24VDC 06 LHR Preferred Fail Safe to Match Up w/Mech Crashbar
Delayed Egress Crashbar Von Duprin Chex-It Used for Alarmed Only Delayed Egress Doors
Delayed Egress Crashbar w/Mortise Von Duprin Chex-It w/Mortise Used for Alarmed Only Delayed Egress Doors
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 50 of 150
Appendix G - continued
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 51 of 150
APPENDIX H: Software House iSTAR Ultra SE controller
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 52 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 53 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 54 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 55 of 150
!
!
!
o !"#$%&'()*"'%#&+)(,%-(#"./&#"(%(0"#-(1#&"2(3")*#&4$+#(2+55+6&'7(#++,('/,1"#(89:;<;<;==>?(@'$"#&+#A(3"<
'+$")($B"(&''"#(3++#(+2(0")$&1/5"C!
• ,+B4k!lJ/7157-AmNli1..<!>247A-307.-mNl@VZ!O..]!#."m!lO292<2-:2!#."!6B"#"(,/5$&45"(4%'"5)(5&0"(&'($B"()%,"(
#++,(m!W2"A"!b*N*N*(*ZN7GZ,O!*!_!b*N*N*(*ZN7GZ,O!(!
• >..<!@.-70.<4k!,??2-5!nN>G@a!0.!082!5..<!-3]2!W2"A"!b*N*N*%%FJN>G@Y!
• O2Q/240!0.!EM70k!,??2-5!nNOZEa!0.!082!5..<!-3]2!W2"A"!b*N*N*%%FJNOZEY!
• @.-70.<!B.7-04k!,??2-5!nN@BZa!0.!082!5..<!-3]2!W2"A"!b*N*N*%%FJN@BZY!
• EX2-04j!,??2-5!nNEoZa!EM:1/57-A!;$Hi$!5293/10!EX2-04!W2"A"!b*N*N*%%FJ!G./-52<NEoZY!
• ,+B!EX2-04!WZ3]?2<_!J3002<D_!,+!i371Yk!B<2?2-5!n,+B!n!0.!082!EX2-04!:<23025!.-!7-?/0!3:07X307.-!W2"A"!,+B!b*N*N
*(*ZN7GZ,O!*!Z3]?2<NEoZY!
• J7>!>2X7:2!V-?/0!WJ7N>7<2:07.-31!G2<731!V-?/0Yk!,??2-5!nNJ7>a!W2"A"!*N(N(**!O23<!@.07.-NJ7>Y!
• >G+!B3-21!EX2-0!W9<.]!J7>!VBZYk!B<2?2-5!n>G+B!a!W2"A"!>G+B!*N(N(%I!B.=2<!i371NEoZY!
• >G+!,13<]!EX2-0!9.<!@.-70.<H@.07.-!W9<.]!J7>!VBZYk!B<2?2-5!n>G+!a!W2"A"!n>G+!*N(N(**!>..<NEoZa!.<!n>G+!*N(N
(**!@.07.-NEoZaY!
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 56 of 150
APPENDIX J: Roof Top Doors and Hatches
Electric Mortise Lock w/Integrated Schlage L9092 RX Switch REX switch installed and tested w/ EOL Supervision (See Supervision
REX Switch Standards Section)
4.5"x4.5" 8 wire hinge Stanley CECB179-58 Special consideration for existing hardware
3/4" SPST DSM-Door Switch GRI 190-12WG-BL W/2- Snugly fitted, and sealed in place. Installed and tested. EOL resistors
Monitor Black with EOL Built-in 1k are molded into contact.
Rare Earth Magnet GE 1840-N Placed and permanently installed with adhesive. Used for steel doors
with hollow opening where magnet would be. (or Equivalent)
SPST Biased Surface Mount Con- GRI 4400AB W/2-1k Used if flush/recessed contact not allowed. Installed and tested. EOL
tact with Built-in EOL (Not Pre- resistors Build-in.
ferred)
Access Control Card Readers: With HID FP3231A+/10022 26 Bit Wiegand-1L
single gang cover
Access Control Card Reader: Mul- HID FP3511A+/10022 26 Bit Wiegand-1L
lion Style Mullion style permitted for use in tight spaces
Mini Horn Sounder Gentex GN-9041277 Mounted to 4” square device ring at junction box provided by others,
see line item below for plate to provide
4” Square Box Single Gang Device RACO 768 Or equivalent single gang device ring. Provided to mount sounder
Cover
Cabling Description Vendor Part No. Notes
Plenum Access Control Composite Windy City Wire, Inc. 4461050 Provided by others. Used for Door Access Control
Cable (Purple)
Plenum 22-6 (Purple) Windy City Wire, Inc. 444391-50 Provided by others. Used for Hatch Monitoring Point
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 57 of 150
!
!
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 58 of 150
APPENDIX K: Key and Asset Management Solutions!
)2D!3-5!,4420!@3-3A2]2-0!G.1/07.-4!
!
,11!)2D!3-5!,4420!@3-3A2]2-0!G.1/07.-4!48311!62!Z<3S3!)2D!+367-204!W@NG2<724_!GNG2<724_!.<!FNG2<724Y!.<!212:N
0<.-7:!1.:S2<4!WF3?0.?!F.:S2<4_!Z36120!F.:S2<4_!F3<A2!i.<]30!F.:S2<4_!@.5/13<!F.:S2<4_!.<!Z2]?.<3<D!G0.<3A2!
F.:S2<4Y"!
!
,11!)2D!3-5!,4420!@3-3A2]2-0!G.1/07.-4!48311!62!7-02<93:25!=708!+N+TOE!c%%%!9.<!082!3/0.]3025!7]?.<0!.9!:3<5!
:<252-0731!5303"!
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 59 of 150
APPENDIX L: Emergency Phone Stanchions
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 60 of 150
CB 1-e CB 1-s
CB 1 Series with Public Address
CB 1-w with Solar/GSM/Wireless
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 61 of 150
Installation, Configuration, Operation & Troubleshooting
Administrator Guide
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 62 of 150
CB 1 Series
WARNING Administrator Guide
ONLY QUALIFIED PERSONNEL SHOULD INSTALL THESE UNITS. THE INSTALLATION SHOULD
CONFORM TO ALL LOCAL CODES. IN SOME COUNTRIES, A CERTIFIED ELECTRI- CIAN MAY BE
REQUIRED.
NOTICE TO USERS
Copyright © Code Blue Corporation. All rights reserved. This guide or software described herein, in whole or part, shall
not be reproduced, translated or reduced to any machine-readable form without prior written approval from Code Blue
Corporation.
CODE BLUE CORPORATION PROVIDES NO WARRANTY WITH REGARD TO THIS GUIDE, THE
SOFTWARE OR OTHER INFORMATION CONTAINED HEREIN AND HEREBY EXPRESSLY DIS- CLAIMS
ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICU- LAR PURPOSE
WITH REGARD TO THIS GUIDE, THE SOFTWARE OR SUCH OTHER INFORMA- TION. IN NO EVENT
SHALL CODE BLUE CORPORATION BE LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, OR SPECIAL
DAMAGES, WHETHER BASED ON TORT, CONTRACT, OR OTHERWISE, ARISING OUT OF OR IN
CONNECTIONS WITH THIS GUIDE, THE SOFTWARE OR OTHER INFORMATION CONTAINED HEREIN OR
THE USE THEREOF.
Code Blue Corporation reserves the right to make any modifications to this guide or the information contained herein at
any time without notice. The software described herein may also be governed by the terms of a separate user license
agreement.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 63 of 157
CB 1 Series
Getting Started Administrator Guide
1.1.A.1.1.1.1.1 Basic Install Instructions
1. EIA/TIA, ANSI, CSA and BICSI cabling or similar standards shall be adhered to for proper operation of Code
Blue communication devices connected to copper or fiber infrastructures. Communications cable and electrical
cable in the same conduit is not an acceptable install- lation and shall not be supported. Analog phones require a
minimum of 23mA for proper operation (26-29mA recommended).
2. Each analog speakerphone requires its own phone line or PBX extension. Multiple units shall not be sup-
ported.
3. Speakerphones require programming before operation. Consult the User Guide or Admin- istrator Guide en-
closed with the unit or visit www.codeblue.com > Support > Downloads to read or download manuals.
4. If you are installing IP speakerphones, please read the appropriate manuals and consult with your Network
Administrator.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 64 of 157
CB 1 Series
1 Dome Top Assembly (Solar not Included)
Administrator Guide
1 WindAssist™ (Solar Option Only)
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 65 of 157
CB 1 Series
Administrator Guide
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 66 of 157
Power Requirements
(The following power requirements include the 9 Series and also ALL OTHER Code Blue units.)
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 67 of 157
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 68 of 157
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 69 of 157
CB 1-s with Dual Faceplates High Voltage Exploded View
13
10
11
12
13
15
14
DISCLAIMER: Product design and component use subject to change without notice. Product shown reasonably represents current of-
fering and is intended to assist in component identification. Reference the model and serial number from the unit ID tag and contact
manufacturer to confirm replacement part version and availability.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 71 of 157
CB 1-e and CB 1-s Installation Instructions
2.1 Screw one set of nuts and washers onto the anchor bolts – After the foundation has set, screw one set of nuts
followed by one set of washers onto the anchor bolts. Set the nuts so the lowest washer is about 2! inches above
the concrete and at an even height. To accomplish this, use a small level and check from front to back, side to
side and diagonally. These nuts are NOT adjustable after the unit is in place. The bottom edge of the Code Blue
unit will be
!-inch above the concrete when installed.
IMPORTANT: The leveling of the bottom nuts is crucial to the leveling of the unit. A small error
in the adjustment of these will be magnified after installation.
IMPORTANT: A !-inch minimum air gap is required between the foundation and the unit. Moisture prob-
lems may result if this condition is not complied with.
2.2 Set the Code Blue unit on the anchor bolts – Align the phone plate in the desired direction and lift the Code
Blue unit over the anchor bolts. The unit may be lifted using the bracket on the inside of the unit. Note that the
unit weighs approximately 330 pounds. Use appropriate lifting materials and methods to avoid possible injury
and/or damage.
2.3 Secure the Code Blue unit – Access the mounting studs through the door on the side of the unit. Place the sec-
ond washer, then nut and tighten the mounting nuts onto the anchor bolts. This may be more convenient if a long
socket, extension and universal joint is used to tighten the hardware.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 72 of 157
4.1 Remove the clear Lexan dome from the black metal casting. The casting complete with strobe should be brought
to the top of the unit (pedestal) where the wiring will be connected (match black and red wire connectors; match
yellow to yellow connectors). After the wiring is complete, set the white disc on top of the lens located inside the
unit (CB 1-s only). Set the casting on top of the pedestal and fasten the casting to the bollard by reaching through
the openings and tightening the three 10-24 X 1-inch stainless steel thumbscrews against the inner wall. Finally,
reattach the clear Lexan dome to the black metal casting with the security screws provided.
NOTE: Take care not to overdrive the security screws against the Lexan as fracturing may occur.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 73 of 157
5.2 24V AC supply – Bring the power connection into the unit and using the proper crimping tool, attach the incom-
ing power wires to the appropriate black and red manifold wires or 24V fuse block.
5.3 120V AC supply – Bring the incoming power into the junction box. Using the proper crimping tool, attach and
fasten each of the incoming power wires to the power brick’s white/yellow and black/brown wires.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 74 of 157
(CB 1-s as shown)
1.1.A.2 FIGURE 2
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 75 of 157
All wiring must be installed and connected by experienced and certified personnel to meet
local and national electrical codes, and will include a service disconnect.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 76 of 157
16 CB 1 Series Tower Base Gasket Installation Instructions
1.1.A.2.1.1.1.1 1.0 FOUNDATION (see anchor bolt installation instructions)
2.1 Screw one set of nuts and washers onto the anchor bolts. After the foundation has set, screw one set
of nuts, followed by one set of washers, onto the anchor bolts. Set the nuts so the lowest washer is
about 2! inches above the concrete at an even height.
To accomplish this, use a small level and check from front to back, side to side and diagonally.
These nuts are NOT adjustable after the unit is in place.
The bottom edge of the Code Blue unit will be !-inch above the concrete when
installed.
2.2 Set the Code Blue unit on the anchor bolts. Align the phone plate in the desired direction
and lift the Code Blue unit over the anchor bolts. The
unit may be lifted using the bracket on the inside of the unit. Note that the unit weighs approxi-
mately 200-400 pounds and that the 9 Series does not contain a bracket on the inside of the unit.
Use appropriate lifting materials and
methods to avoid possible injury and/or damage.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 77 of 157
the foundation and the unit to prevent moisture problems.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 78 of 157
Install the Base Gasket
3.0 Access the mounting studs through the access door on the side of the unit.
3.1 Set the gasket on the bolts and cut a small hole where the conduit is located.
Stretch the screen tightly around the conduit pipe. Slide the gasket over the bolts to the base of unit.
3.2 Place the second washer on the anchor bolt and place the nut on top.
Tighten the mounting nuts onto the anchor bolts. This may be more convenient if a long socket, ex-
tension and universal joint is used to tighten the hardware.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 79 of 157
1.1.A.2.1.1.1.2 *For an extra-strong seal, a bead of silicone caulk can be put on the gasket from bolt hole to bolt
hole before setting the gasket into place and around the conduit.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 80 of 157
CB 1 Series Anchor Bolt Installation Instructions
1.0 FOUNDATION
1.1 Conduit – Electrical and telephone line conduit, with a maximum combined diameter of four inches, should be
run up through the center of the foundation hole. A minimum of four
inches and a maximum of six inches of conduit above the finished grade level is required. To ensure proper
grounding, a !-inch x 8-foot copper rod should be inserted in the center of the foundation and tied to the steel
bollard.
NOTE: Follow all national and local codes governing this installation.
1.2 Pour the Foundation – The foundation should be at least 24 inches in diameter and to the correct depth for the
frost line in your area, with a minimum depth of at least three feet (follow local building codes for foundations).
1.3 Set the Anchor Bolts in the Wet Foundation – Four 24-inch L-shaped anchor bolts and an aligning template are
supplied for anchoring the Code Blue unit. The bolts should be set into the foundation so that six inches are left
showing above the finished grade level. The anchor bolts should be aligned, using the supplied template in such
a way that the phone faceplate on the unit will face in the desired direction.
2.0 WIRING
2.1 Pull power and phone line up through the conduits – A minimum of two feet of wire must be
available from the conduit for electrical and communications wiring.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 81 of 157
KEEP
CONDUIT
CONTAIN 4.00 8.00 6.00
ED
WITHIN
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 82 of 157
22 Line Power Installation Instructions
IMPORTANT: All wiring shall comply with national and local codes governing this installation. It is the responsi-
bility of the installer to ensure these conditions are complied with.
1.1 Pulling the power wires – Wire should be a minimum of 14 AWG and be pulled into the unit, leaving a mini-
mum of two feet of wire from the opening of the conduit.
1.2 Pulling the communications wire (if needed) – Communications wire must be shielded phone line. The phone
line must be pulled into the unit using a separate conduit from the power, and be run so as to extend a minimum
of two feet out of the phone opening.
2.1 Make the connections – Locate the grounding lug and connect the ground wire.
2.2 Using 115V AC supply – Connect the colored (hot) wire to the black wire, and connect the
white or gray (neutral) wire to the white wire.
2.3 Higher voltage supply – If the unit was ordered for a higher voltage, a pre-wired power brick will be located on
the top of the electrical panel with a 24 volt secondary to supply the low voltage manifold and power brick to
supply the area light. Connect the colored (hot) wire and the white or gray (neutral) wire to the white wire in the
junction box.
3.0 CONNECT THE PHONE LINE (if required) – See phone Installation Instructions.
4.0 APPLY POWER – The unit should become operational immediately after the power is ener- gized.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 83 of 157
CB 1 Series Deck Mount Installation Instructions
1.0 DECK MOUNT FOUNDATION
1.1 Drill Deck Holes – Drill four holes through the deck or floor for the four 3/4” threaded rods. The holes should be
aligned, using the template provided in such a way that the phone face- plate on the unit will face in the desired
direction (see figure below).
1.2 Drill a fifth hole in the center to accommodate the conduit.
1.3 Position Upper Deck Plate – Position the first plate working from above the deck.
1.3.1 Thread a nut and washer on the end of each rod so that approximately six inches ex- tends beyond the
base of the washer.
1.3.2 Insert each rod through the top side of the plate, plate gasket, and down through the
four holes in the deck.
NOTE: The top of the plate is the side with the tapered edge.
1.4 Position Lower Deck Plate – Position the second plate working from below the deck. Have another worker
hold the upper plate and rods in place from above the deck.
1.4.1 Place the second plate gasket and then the second plate over the threaded rods.
1.4.2 Secure the second plate with nuts and washers provided. If required, readjust the nuts so that six inches of
the rods are above the top of the upper plate (see figure below).
1.5 Secure Lower Nuts – To prevent tampering, it is advisable to tack weld the lower nuts to the threaded rod.
2.0 WIRING
2.1 Pull power and phone line through conduits – A minimum of two feet of wire must be avail- able from the
conduit for electrical and communications wiring.
2.2 Conduit – Electrical and telephone line conduit is run through the deck and the center open- ings (two-inch di-
ameter) of the upper and lower deck plates. A minimum of four inches and a maximum of six inches of conduit
above the upper plate is required.
Ø14.00
DECK
B PLATE
P B
HO
NE
FAC
EPL
ATE
D
I
R
E
C
MIT Design Standards | Campus Safety and Security Services Thematic Folder
T
I Page 84 of 157
O
N ALLO
Ø8.00
W 1/2"
GAP FOR BOLT CIRCLE
3/4" THREADED ROD OF
CB 2 Series
Administrator Guide
Download Information
Code Blue now has a centralized location where you can find Installation, Setup, Information, Configuration and Operation instruc-
tions.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 85 of 157
CB 2 Series
Administrator Guide
For Legacy IA3100 Information:
www.codeblue.com/support/resources
These Guides should contain all the information needed for your application. If further information is required, please contact
customerservice@codeblue.com
CB 2 Se-
ries
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 86 of 157
CB 2-a CB 2-e
CB 2 Series
Administrator Guide
CB 2-e with AED Housing CB 2-e with Public
Address
CB 2-s
WARNING
ONLY QUALIFIED PERSONNEL SHOULD INSTALL THESE UNITS. THE INSTALLATION SHOULD
CONFORM TO ALL LOCAL CODES. IN SOME COUNTRIES, A CERTIFIED ELECTRI- CIAN MAY BE
REQUIRED.
NOTICE TO USERS
Copyright © Code Blue Corporation. All rights reserved. This guide or software described herein, in whole or part, shall
not be reproduced, translated or reduced to any machine-readable form without prior written approval from Code Blue
Corporation.
CODE BLUE CORPORATION PROVIDES NO WARRANTY WITH REGARD TO THIS GUIDE, THE
SOFTWARE OR OTHER INFORMATION CONTAINED HEREIN AND HEREBY EXPRESSLY DIS- CLAIMS
ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICU- LAR PURPOSE
WITH REGARD TO THIS GUIDE, THE SOFTWARE OR SUCH OTHER INFORMA- TION. IN NO EVENT
SHALL CODE BLUE CORPORATION BE LIABLE FOR ANY INCIDENTAL, CONSEQUENTIAL, OR SPECIAL
DAMAGES, WHETHER BASED ON TORT, CONTRACT, OR OTHERWISE, ARISING OUT OF OR IN
CONNECTIONS WITH THIS GUIDE, THE SOFTWARE OR OTHER INFORMATION CONTAINED HEREIN OR
THE USE THEREOF.
Code Blue Corporation reserves the right to make any modifications to this guide or the information contained herein at
any time without notice. The software described herein may also be governed by the terms of a separate user license
agreement.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 87 of 157
CB 2 Series
Administrator Guide
Code Blue® is a registered trademark of Code Blue Corporation.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 88 of 157
Getting Started
1. EIA/TIA, ANSI, CSA and BICSI cabling or similar standards shall be adhered to for proper operation of Code
Blue communication devices connected to copper or fiber infrastructures. Communications cable and electrical
cable in the same conduit is not an acceptable instal- lation and shall not be supported. Analog phones require a
minimum of 23mA for proper operation (26-29mA recommended).
2. Each analog speakerphone requires its own phone line or PBX extension. Multiple units shall not be sup-
ported.
3. Speakerphones require programming before operation. Consult the User Guide or Administrator Guide
enclosed with the unit or visit www.codeblue.com > Support > Downloads to read or download manu-
als.
4. If you are installing IP speakerphones, please read the appropriate manuals and consult with your Network
Administrator.
Tools Required
CB 2 Series
1. Drill and security bit for removing and inserting security screws on phone and access plate
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 89 of 157
CB 2-e with Public Address
Part Part Number
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 90 of 157
Power Requirements
(The following power requirements include the 2 Series and also ALL OTHER Code Blue units.)
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 91 of 157
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 92 of 157
CB 2-e High Voltage Exploded View
4 2
4
3
1
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 93 of 157
5
10 4
DISCLAIMER: Product design and component use subject to change without notice. Product shown reasonably represents current of-
fering and is intended to assist in component identification. Reference the model and serial number from the unit ID tag and contact
manufacturer to confirm replacement part version and availabilit
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 94 of 157
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 95 of 157
16 CB 2-e with Public Address Installation Instructions
1.0 PRE-INSTALLATION
1.1 Electrical preparation – The unit may have supply wires run from either (a) behind the unit through the wall,
or (b) below the unit using an external conduit through the bottom of the unit. Holes in the back and bottom of the
unit have been provided for this purpose.
2.2 Mark the mounting holes – In order to comply with the Americans with Disabilities Act (ADA) of 1990, the
speakerphone button(s) should be positioned between 34 and 48 inches from grade level. (Consult an ADA spe-
cialist in your area to verify local and federal guidelines.)
2.4 Install the housing – Four anchors of appropriate size and type should be used to fasten the housing to the wall.
IMPORTANT: If wiring is supplied from the back, ensure that the conduit is aligned at this time.
3.1 Ground – The ground (green) wire should be stripped and fastened to the supplied grounding lug.
3.2 24V AC supply – The unit will contain a 5 finger manifold with corresponding fuses per
component. Incoming power is connected to the red and black wires on the manifold.
3.3 120/240V AC supply – The unit will contain a small 120V AC 40VA transformer. The incom- ing power would
run to the two forks coming off of the transformer and power is distributed through the 5 finger manifold.
3.4 120,240,277,347V AC Multi-tap transformer – Incoming power will be connected to the transformer and
wiring will depend on incoming voltage. A wiring diagram depicting each voltage option is located on top of
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 96 of 157
the multi-tap transformer. Power will be distributed through the multiple fingers coming off the transformer.
3.5 PoE Power – The unit will contain a PoE splitter and an IP surge suppressor. The incoming RJ45 connector
would run to the IP surge suppressor inside the unit. A CAT 5 cable from the surge suppressor runs to the PoE
splitter. All power in the unit is distributed through the PoE splitter.
4.1 Have category 3 or higher 4-pair cable terminated to a RJ45 applying TIA/EIA T568-B speci-
fications.
See diagrams next page
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 97 of 157
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 98 of 157
Suggested installation dimensions shown from ground to lower right mounting hole are for single button face- plates.
• For dual button faceplate, deduct 3.25 inches.
• For keypad faceplate, deduct 4.5 inches.
• For wheelchair direct facing access only, deduct 6 inches.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 99 of 157
DISCLAIMER: The dimensions above are intended as guidelines only. For specific installation requirements,
reference your local codes.
All wiring must be installed and connected by experienced and certified personnel to meet
local and national electrical codes, and will include a service disconnect.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 100 of 157
Download Information
Code Blue now has a centralized location where you can find Installation, Setup, Information,
Configuration and Operation instructions.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 101 of 150
APPENDIX N: Camera Equipment
Section 1 – Exterior Cameras
Axis Communications – Q6055-E PTZ
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 102 of 150
Fixed Camera
Axis Communications – P3375-LVE
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 103 of 150
Mounts
Wall
Axis Communications – T91B61 Wall Mount
Use pendant kit for exterior cameras
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 104 of 150
Axis Communications – P33-VE Pendant Kit
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 105 of 150
Pole
Axis Communications – T91A67 Pole Bracket. Pendant kit is required for this bracket. See below.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 106 of 150
(Axis Communications – P33-VE Pendant Kit)
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 107 of 150
Ceiling
Axis Communications – P33-VE 3/4" NPS Conduit Adapter and P33-VE Mounting Bracket
Roof
Pelco, Parapet Rooftop Mount
Pelco, Parapet Wall Mount
Pendant kit is required for this bracket.
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 108 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 109 of 150
Axis Communications – T94A01D Pendant Kit
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 110 of 150
Section 2 – Interior Cameras
Axis Communications – P3375-LV Interior Camera,
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 111 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 112 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 113 of 150
Axis Communications – T94H05L Recessed Ceiling Kit
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 114 of 150
Section 3 – Specialty Cameras
Axis Communications – F41 Main Unit
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 115 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 116 of 150
Axis Communications – F1005-E Sensor Unit
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 117 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 118 of 150
Axis Communications – F8212 Trim Ring
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 119 of 150
Installation Instructions
Section 1 – Exterior
Axis Communications – Q6055-E PTZ
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 120 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 121 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 122 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 123 of 150
Axis Communications – P3375-LVE
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 124 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 125 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 126 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 127 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 128 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 129 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 130 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 131 of 150
Pendant Kit
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 132 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 133 of 150
Wall Mount
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 134 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 135 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 136 of 150
Pole Mount
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 137 of 150
Rooftop Mounts
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 138 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 139 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 140 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 141 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 142 of 150
Axis POE Midspan 60W
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 143 of 150
Section 2 – Interior
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 144 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 145 of 150
Recessed Ceiling Kit
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 146 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 147 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 148 of 150
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 149 of 150
APPENDIX O: Camera Viewing Minimum System Requirements
Genetec Security Center Software
A maximum of 20 cameras can be displayed at a single time using the below computer configurations.
End of Document
MIT Design Standards | Campus Safety and Security Services Thematic Folder Page 150 of 150