Control Valve

Performance
Department Editor: Scott Jenkins

inimizing process variability is an response time and over-

M important component of a plant’s prof-


itability. The performance of control
valves within process control loops has a
shoot for a control valve
response to a step input
change. In this case,
significant impact on maintaining consistent stem position in percent
processes. This refresher outlines some of the of travel is used as the Output
important aspects of control valve perfor- control valve “output.”
mance, including parameters of both the Step-change size. The
static response and the dynamic response. dynamic response of b
a control valve varies a c
d
Static response depending upon the a < resolution ≤ b
A valve’s static response refers to mea- size of the input step
surements that are made with data points change. Four “ranges” c ≤ dead band < d
Input
recorded when the device is at rest. Key of step sizes to help

Amplitude
static-response parameters for control valves understand the static-
include travel gain, dead band and resolu- and dynamic- response
tion (Figure 1). metrics are defined by
Travel gain (Gx). This term represents the ANSI/ISA standards: Time
change in position of the valve closure • Small input steps (Re- Dynamics are not shown
member divided by the change in input gion 1) that result in no
FIGURE 1. Dead band and resolution, illustrated here, are
signal. Both quantities are expressed as measurable movement
of the closure member key static-response parameters for control valves
a percentage of the full valve span. The
within the specified
closure member is part of the valve trim (the wait time 39
combination of flow-control elements inside Initial overshoot to 38.11 = 23% Final steady-state
• Input step changes average values
a valve). Travel gain measures how well the that are large enough input = 37.84, stem = 37.65
valve system positions its closure member to result in some 38 Stem
compared to the input signal it receives. control-valve response
Input, stem %

with each input signal Input


Without signal characterization in the valve
system, the travel gain should be 1.0. [1] change, but the re-
sponse does not satisfy 37 Travel gain = 0.91
Dead band. This term can be defined as Time to steady state, Tss = 18.3 s
the requirements of
the range through which an input signal the specified time and
may be varied, with reversal of direction, 86.5% of response, T86 = 2.06 s
linearity (Region 2) 36
without initiating a response (an observable • Step changes that are
Dead time Td =1.6 s
change in output signal). With respect to large enough to result
control valve performance, if the process in flow coefficient Initial steady state average values, input and stem = 35.67
changes, which sat- 35
controller attempts to reverse the position of 0 10 20 30
the control valve, the valve will not begin isfy both the specified
maximum response Time, s
to move until after the controller output has
time and the specified FIGURE 2. This graph shows the response of a control valve
reversed an amount greater than the dead maximum linearity to a step input (reprinted with permission from EnTech Con-
band. A large dead band will negatively (Region 3) trol Valve Dynamic Speciication V3.0)
impact control performance. • Input steps larger than
Resolution. This term can be defined as the in Region 3 where the specified magnitude- istic refers to the curve relating percentage of
minimum amount of change in valve shaft response linearity is satisfied but the speci- flow to percentage of valve travel. Inherent
position when an input is applied. Resolu- fied response time is exceeded (Region 4) flow characteristic applies when constant
tion will cause the control valve to move Region 1 is directly related to dead band pressure drop is maintained across the valve.
and resolution. Region 2 is a highly nonlinear
in discrete steps in response to small, step Typically linear, quick opening or equal per-
region that causes performance problems and
input changes in the same direction. This should be minimized. Region 3 is the range of centage, this will impact both the magnitude
occurs as the valve travel sticks (when the input movements that are important to control and the consistency of the process gain over
starting friction on the valve shaft is greater performance [1]. the operating range [1]. Good control-valve
than the friction when the shaft is in motion). performance depends on proper valve sizing
Similar to dead band, a larger resolution Process gain and trim characteristics.
will negatively impact control performance. Process gain is the ratio of the change in
a given process variable to the change in References
Dynamic response controller output that caused the change. 1. Beall, James, Improving Control Valve Perfor-
Dynamic response for a control valve is the To achieve effective process control, the pro- mance, Chem. Eng., Oct. 2010, pp. 41–45.
time-dependent response resulting from a cess gain should ideally fall within a certain 2. Emerson Entech, Control Valve Dynamic Specifi-
time-varying input signal. range, and should be consistent throughout cation, Version 3.0, November 1998.
Dead time. This term refers to the time after the operating range of the valve. When the 3. Hoop, Emily, Control Valves: An Evolution in
the initiation of an input change and before process gain is too high, valve non-lineari- Design, Chem. Eng., August 2012, pp. 48–51.
the start of the resulting observable response. ties are amplified by the process gain and 4. Ruel, M., A simple method to determine control
Step response time. This term represents valve performance and its impacts on control
process control performance deteriorates.
loop performance, Top Control Inc., Swanton,
the interval of time between initiation of an When the process gain is too low, the Vt., white paper, 2001.
input-signal step change and the moment range of control is reduced. Changes in the 5. International Society of Automation (ISA) and
that the dynamic response reaches 86.5% process gain over the range of operation American National Standards Institute (ANSI).
of its full, steady-state value [1]. The step result in poorly performing regions in the ANSI-ISA-TR75-25-02-2000, Control Valve Re-
response time includes the dead time before closed-loop controller response. sponse Measurement from Step Inputs, 2000.
the dynamic response. Two control-valve features impact process 6. Neles-Jamesbury Inc., “The Valve Book,” Neles-
Overshoot. This term is the amount by which gain: the size of the valve trim and the inher- Jamesbury, Worchester, Mass., 1990.
a step response exceeds its final, steady-state ent flow characteristic of the valve. If the 7. Skousen, Philip L., Valve Handbook, McGraw
value. Overshoot is usually expressed as a valve trim is oversized, the process gain will Hill, New York, 1998.
percentage of the full change in steady-state be higher than it would be for an appropri- Editor’s note: Portions of this page were adapted
value. Figure 2 shows the dead time, step ately sized valve. The valve’s flow character- from the article in Ref. 1.