1. DESIGN REPORTS OF OPEN R.C.C. LINED DRAIN OF OVERALL WIDTH 4.50 M AND
CLEAR HEIGHT 1.00 M, 1.50 M, 2.00 M, 2.50 M, 3.00 M, 3.50 M AND 4.00 MOF R.C
2. DRAWINGS SHOWING TYPICAL CROSS-SECTION FOR DIMENSIONS AND
REINFORCEMENT DETAILINGS.
3. SCHEDULES OF REINFORCEMENTS FOR OPEN R.C.C. LINED DRAINS.
4. QUANTITY COMPUTATION OF R.C.C., P.C.C., REINFORCEMENTS ETC. FOR R.C.C.
OPEN LINED DRAINS.
5. QUANTITY COMPUTATIONS OF EARTHWORK IN CUTTING AND BACKFILLINGS FOR
R.C.C. OPEN LINED DRAINS.
6. CROSS-SECTION AND QUANTITY COMPUTATION FOR OPEN C.C. MASONARY DRAIN..
OVERALL WIDTH 4.50 M AND
, 3.50 M AND 4.00 MOF R.C
FOR DIMENSIONS AND
NED DRAINS.
RCEMENTS ETC. FOR R.C.C.
DESIGN OF OPEN R.C.C. LINED DRAIN OF OVERALL WIDTH 4.50 M AND CLEAR HEIGHT
M, 1.50 M, 2.00 M, 2.50 M, 3.00 M, 3.50 M AND 4.00 M
Designed By:
Bilal Ahmed Barbhuiya (AFZAL KARIM)
Assistant Engineer, P.W.D. Executive Engineer, P.W.D
Guwahati N.H. Division. Guwahati N.H. Division
0 M AND CLEAR HEIGHT 1.00
ND 4.00 M
(AFZAL KARIM)
cutive Engineer, P.W.D
uwahati N.H. Division
SCHEDULE OF REINFORCEMENT
DRAIN TYPE TYPE-1 (3.60 x 4.00)
BAR NO. OF TOTAL
MARK BAR DIA SPACING LENGTH
BAR SHAPE M1 in mm M2 in mm BARS per LENGTH
in mm in mm in mm
rm in 'm'
M1
M1
M1
(2) 20 190 250 4400 4900 7 34.3
M1
M2
M1
M2
(4) M1 M1 12 300 250 4400 4900 5 24.5
M2
(5) M1 M1 10 150 & 300 250 1000 1500 82 123
M2
(6) M1 M1 10 190 250 1000 1500 48 72
M1
M1
M1
M2
height)
M1
M1
85.000 bottom bar in slab (2) 20 200 200 4400
M1
M2
43.000 vert. bar water face (3) 10 300 200 3775
M1
M2
22.000 top bar in slab (4) M1 M1 10 300 200 4400
M2
76.000 dist. Bar in walls @ B/F (5) M1 M1 8 150 & 300 200 1000
M2
44.000 dist. Bar in slab @ B/F (6) M1 M1 10 200 200 1000
M1
M1
M2
height)
M1
M1
4800 6 28.8 71.000 bottom bar in slab (2) 16
M1
M2
4175 10 41.75 26.000 vert. bar water face (3) 10
M1
M2
4800 5 24 15.000 top bar in slab (4) M1 M1 10
M2
1400 72 100.8 40.000 dist. Bar in walls @ B/F (5) M1 M1 8
M2
1400 46 64.4 40.000 dist. Bar in slab @ B/F (6) M1 M1 8
M1
M1
190 175 4400 4750 7 33.25 53.000 bottom bar in slab (2)
300 175 3250 3600 10 36 22.000 vert. bar water face (3)
300 175 4400 4750 5 23.75 15.000 top bar in slab (4)
150 & 300 175 1000 1350 72 97.2 38.000 dist. Bar in walls @ B/F (5)
190 175 1000 1350 48 64.8 26.000 dist. Bar in slab @ B/F (6)
300 200 1000 1400 10 14 6.000 haunch bar at bottom corner (7)
TOTAL QTY. STEEL REQD. PER METER LENGTH OF DRAIN (kgs.)= 228.000
SCHEDULE OF REINFORCEMENT
DRAIN TYPE TYPE-4 (3.90 x 2.50)
NO. OF TOTAL
BAR DIA SPACING LENGTH WEIGHT
BAR SHAPE M1 in mm M2 in mm BARS per LENGTH
in mm in mm in mm in kgs.
rm in 'm'
M1
M1
M1
16 225 150 4400 4700 6 28.2 45.000
M1
M2
M1
M2
M1 M1 10 300 150 4400 4700 5 23.5 15.000
M2
M1 M1 8 150 & 300 150 1000 1300 72 93.6 37.000
M2
M1 M1 8 225 150 1000 1300 41 53.3 21.000
M1
M1
TOTAL QTY. STEEL REQD. PER METER LENGTH OF DRAIN (kgs.)= 174.000
SCHEDULE OF REINFORCEMENT
DRAIN TYPE TYPE-5 (4.00 x 2.00)
BAR
REMARKS BAR DIA SPACING LENGTH
MARK BAR SHAPE M1 in mm M2 in mm
in mm in mm in mm
M1
M2
height)
M1
M1
bottom bar in slab (2) 12 175 125 4400 4650
M1
M2
vert. bar water face (3) 8 300 125 2150 2400
M1
M2
top bar in slab (4) M1 M1 8 300 125 4400 4650
M2
dist. Bar in walls @ B/F (5) M1 M1 8 300 125 1000 1250
M2
dist. Bar in slab @ B/F (6) M1 M1 8 300 125 1000 1250
M2
height)
M1
M1
7 32.55 29.000 bottom bar in slab (2) 12 250
M1
M2
10 24 9.000 vert. bar water face (3) 8 300
M1
M2
5 23.25 9.000 top bar in slab (4) M1 M1 8 300
M2
96 120 47.000 dist. Bar in walls @ B/F (5) M1 M1 8 300
M2
31 38.75 15.000 dist. Bar in slab @ B/F (6) M1 M1 8 300
(7)
TAL QTY. STEEL REQD. PER METER LENGTH OF DRAIN (kgs.)= 109.000
Design dimensions and reinforcments of R.C.C. Open Drain :
f f
a
b
e
TYPICAL CROSS-SECTION
Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981
Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ α)
Co-efficient of Active Earth Pressure= (Ka)stat ic
sin(δ φ)sin(φ i
cos2αcos(δ α) 1
cos(δ α)cos(α
= 0.297
Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.
The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra
40 40
4.10
16
23.76
24.95 7.13 7.13
LOAD DIAGRAM
4 3
8 7
5 9 10 11 12 13 14 6
1 2
4. Design of Drain
Distribution reinforcement :
Moment = 0.20*DL Moment
= 24.00 kN-m
Area of Steel required = 280.54 mm2
Min. area of Steel both face = 540.00 mm2
0.25 of provided main reinf. = 523.33 mm2
Area of steel provided on each face = 523.33 mm2
Bar dia provided = 10 mm
Spacing required = 150 mm
Spacing upto half the ht. from base = 150 mm
Spacing for remaining ht. = 300 mm
Cuttailed Area of Steel provided = 393 mm2
Provide TOR 10 @ 150 c/c for bottom half and 300 c/c for remaning half on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 66 kN
Shear Stress = 0.169 Mpa
% of Steel provided = 0.54
permissible shear stress = 0.322 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at wall face = 136 kN-m
Effective Depth required = 372 mm
Overall depth proposed = 400 mm
Clear Cover = 50 mm
Effective cover = 60 mm
Hence Effective depth = 340 mm < required.
Effective depth provided = 390 mm
Hence Overall depth 450 mm
Distribution reinforcement :
Moment = 0.20*DL Moment
= 27.00 kN-m
Area of Steel required = 315.60 mm2
Min. area of Steel both face = 540.00 mm2
0.25 of provided main reinf. = 413.16
Area of Steel provided = 413.16 mm2
Bar dia provided = 10 mm
Spacing required = 190.00 mm
Spacing provided = 190.00 mm
Provide TOR 10 @ 190 c/c on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 37 kN
Shear Stress = 0.095 Mpa
% of Steel provided = 0.42
permissible shear stress = 0.286 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face
wall 450 T20 @ 150 & 300 c/c T12 @300 c/c
3.60 x 4.00
base-slab 450 T20 @ 190 c/c T12 @ 300 c/c
0.00
3600
1800
4000
22.18
.0 0
09
00
3600
1800
4000
22.18
1 3 6 .0 0
8 5 .0 9
2000
120.4 B.M.D. BASE-SLAB
B.M.D. of Wall
erall width=4.50m)
m
m
m
m
m
m
kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2
N/mm2
kN/m
kN/m
m
KN/m
rth pressure
os2 (φ α)
2
sin(δ φ)sin(φ i)
cos(δ α)cos(α i)
m
KN/m2
23.76
24.95
N/m per m width
N/m per m width
N/m per m width
mm < required
alf on each face
mm < required.
(from analysis output)
cemnt
f f
a
b
e
TYPICAL CROSS-SECTION
Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981
Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ α)
Co-efficient of Active Earth Pressure= (Ka)static
sin(δ φ)sin(φ i
cos2αcos(δ α) 1
cos(δ α)cos(α
= 0.297
Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.
The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra
32.813 32.813
4.125
16.625
20.79
22.05 7.13 7.13
LOAD DIAGRAM
4 3
8 7
5 9 10 11 12 13 14 6
1 2
4. Design of Drain
Distribution reinforcement :
Moment = 0.20*DL Moment
= 18.00 kN-m
Area of Steel required = 258.85 mm2
Min. area of Steel both face = 450.00 mm2
0.25 of provided main reinf. = 334.93 mm2
Bar dia provided = 8 mm
Spacing required = 150 mm
Spacing upto half the ht. from base = 150 mm
Spacing for remaining ht. = 300 mm
Cuttailed Area of Steel provided = 251 mm2
Provide TOR 8 @ 150 c/c for bottom half and 300 c/c for remaning half on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 53 kN
Shear Stress = 0.167 Mpa
% of Steel provided = 0.42
permissible shear stress = 0.285 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at wall face = 100 kN-m
Effective Depth required = 319 mm
Overall depth considered = 425 mm
Clear Cover = 50 mm
Effective cover = 60 mm
Effective depth = 365 mm > required.
Effective depth considered = 325 mm
Revise overall depth 375 mm
Distribution reinforcement :
Moment = 0.20*DL Moment
= 20.00 kN-m
Area of Steel required = 280.54 mm2
Min. area of Steel both face = 450.00 mm2
0.25 of provided main reinf. = 392.50 mm2
Area of Steel provided = 392.50 mm2
Bar dia provided = 10 mm
Spacing required = 200.00 mm
Spacing provided = 200.00 mm
Provide TOR 10 @ 200 c/c on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 21.263 kN
Shear Stress = 0.065 Mpa
% of Steel provided = 0.48
permissible shear stress = 0.305 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face
wall 375 T16 @ 150 & 300 c/c T10 @ 300 c/c
3.75 x 3.5
base-slab 375 T20 @ 200 c/c T10 @ 300 c/c
50% vertical bars of earth face & distribution bars on both face is curtailed due to reducing moment.
0.00
3750
1875
3500
17.00
1 0 0 .0 0
7 1 .0 0
1750
B.M.D. BASE-SLAB
3500
17.00
1 0 0 .0 0
7 1 .0 0
1750
B.M.D. BASE-SLAB
88.00
B.M.D. of Wall
erall width=4.50m)
m
m
m
m
m
m
kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2
N/mm2
kN/m
kN/m
m
KN/m
rth pressure
os2 (φ α)
2
sin(δ φ)sin(φ i)
cos(δ α)cos(α i)
m
KN/m2
20.79
22.05
N/m per m width
N/m per m width
N/m per m width
mm > required
lf on each face
mm > required.
(from analysis output)
cemnt
e to reducing moment.
0
1 0 0 .0 0
SE-SLAB
SE-SLAB
1 0 0 .0 0
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 3.00 m, overall width=4.50m)
f f
a
b
e
TYPICAL CROSS-SECTION
Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981
Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ α)
Co-efficient of Active Earth Pressure= (Ka)static
sin(δ φ)sin(φ i
cos2αcos(δ α) 1
cos(δ α)cos(α
= 0.297
Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.
The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra
27.781 27.781
4.150
14.75
17.82
18.86 7.13 7.13
LOAD DIAGRAM
4 3
8 7
5 9 10 11 12 13 14 6
1 2
4. Design of Drain
Distribution reinforcement :
Moment = 0.20*DL Moment
= 12.00 kN-m
Area of Steel required = 187.34 mm2
Min. area of Steel both face = 420.00 mm2
0.25 of provided main reinf. = 334.93 mm2
Bar dia provided = 8 mm
Spacing required = 150 mm
Spacing upto half the ht. from base = 150 mm
Spacing for remaining ht. = 300 mm
Cuttailed Area of Steel provided = 251 mm2
Provide TOR 8 @ 150 c/c for bottom half and 300 c/c for remaning half on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 41 kN
Shear Stress = 0.140 Mpa
% of Steel provided = 0.46
permissible shear stress = 0.297 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at face of wall = 67.62 kN-m
Effective Depth required = 263 mm
Overall depth considered = 350 mm
Clear Cover = 50 mm
Effective cover = 58 mm
Hence Effective depth = 292 mm > required.
Effective depth provided = 292 mm
Overall depth provided 350 mm
Distribution reinforcement :
Moment = 0.20*DL Moment
= 14.00 kN-m
Area of Steel required = 218.57 mm2
Min. area of Steel both face = 420.00 mm2
0.25 of provided main reinf. = 264.42 mm2
Area of Steel provided = 264.42 mm2
Bar dia provided = 8 mm
Spacing required = 190.00 mm
Spacing provided = 190.00 mm
Provide TOR 8 @ 190 c/c on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 22.11 kN
Shear Stress = 0.076 Mpa
% of Steel provided = 0.36
permissible shear stress = 0.266 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face
wall 350 T16 @ 150 & 300 c/c T10 @ 300 c/c
3.80 x 3.0
base-slab 350 T16 @ 190 c/c T10 @ 300 c/c
50% vertical bars of earth face & distribution bars on both face is curtailed due to reducing moment.
0.00
3800
1900
3000
12.00
6 7 .6 2
3 9 .0 0
1500
30
6 7 .6 2
3 9 .0 0
1500
59.00 B.M.D. BASE-SLAB
B.M.D. of Wall
erall width=4.50m)
m
m
m
m
m
m
kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2
N/mm2
kN/m
kN/m
m
KN/m
rth pressure
os2 (φ α)
2
sin(δ φ)sin(φ i)
cos(δ α)cos(α i)
m
KN/m2
17.82
18.86
7
6
2
etry.
N/m per m width
N/m per m width
N/m per m width
mm > required
lf on each face
mm > required.
(from analysis output)
cemnt
e to reducing moment.
00
6 7 .6 2
ASE-SLAB
6 7 .6 2
ASE-SLAB
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 2.50 m, overall width=4.50m)
f f
a
b
e
TYPICAL CROSS-SECTION
Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981
Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ α)
Co-efficient of Active Earth Pressure= (Ka)static
sin(δ φ)sin(φ i
cos2αcos(δ α) 1
cos(δ α)cos(α
= 0.297
Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.
The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra
19.875 19.875
4.200
13.5
14.85
4 3
8 7
5 9 10 11 12 13 14 6
1 2
4. Design of Drain
Distribution reinforcement :
Moment = 0.20*DL Moment
= 8.00 kN-m
Area of Steel required = 149.47 mm2
Min. area of Steel both face = 360.00 mm2
0.25 of provided main reinf. = 188.40 mm2
Area of Steel provided = 188.40 mm2
Bar dia provided = 8 mm
Spacing required = 267 mm
Spacing upto half the ht. from base = 150 mm
Spacing for remaining ht. = 300 mm
Cuttailed Area of Steel provided = 251 mm2
Provide TOR 8 @ 150 c/c for bottom half and 300 c/c for remaning half on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 32.11 kN
Shear Stress = 0.132 Mpa
% of Steel provided = 0.23
permissible shear stress = 0.224 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at face of wall = 43.46 kN-m
Effective Depth required = 210 mm
Overall depth proposed = 300 mm
Clear Cover = 50 mm
Effective cover = 58 mm
Effective depth = 242 mm > required.
Effective depth considered = 242 mm
Overall depth provided = 300 mm
Distribution reinforcement :
Moment = 0.20*DL Moment
= 9.00 kN-m
Area of Steel required = 169.54 mm2
Min. area of Steel both face = 360.00 mm2
0.25 of provided main reinf. = 223.29 mm2
Area of Steel provided = 223.29 mm2
Bar dia provided = 8 mm
Spacing required = 225.00 mm
Spacing provided = 225.00 mm
Provide TOR 8 @ 225 c/c on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 16.4 kN
Shear Stress = 0.068 Mpa
% of Steel provided = 0.37
permissible shear stress = 0.268 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face
wall 300 T12 @ 150 & 300 c/c T10 @ 300 c/c
3.90 x 2.5
base-slab 300 T16 @ 225c/c T10 @ 300 c/c
0.00
3900
1950
2500
8.00
4 3 .4 6
2 2 .5 0
1250
2500
8.00
4 3 .4 6
2 2 .5 0
1250
38.00 B.M.D. BASE-SLAB
B.M.D. of Wall
erall width=4.50m)
m
m
m
m
m
m
kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2
N/mm2
kN/m
kN/m
m
KN/m
rth pressure
os2 (φ α)
2
sin(δ φ)sin(φ i)
cos(δ α)cos(α i)
m
KN/m2
14.85
15.74
7
6
2
etry.
N/m per m width
N/m per m width
N/m per m width
mm > required
mm > required
lf on each face
mm > required.
(from analysis output)
cemnt
0
4 3 .4 6
SE-SLAB 4 3 .4 6
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 2.00 m, overall width=4.50m)
f f
a
b
e
TYPICAL CROSS-SECTION
Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981
Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ α)
Co-efficient of Active Earth Pressure= (Ka)static
sin(δ φ)sin(φ i
cos2αcos(δ α) 1
cos(δ α)cos(α
= 0.297
Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.
The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra
11.953 11.953
4.275
12.25
11.88
12.62 7.13 7.13
LOAD DIAGRAM
4 3
8 7
5 9 10 11 12 13 14 6
1 2
4. Design of Drain
Distribution reinforcement :
Moment = 0.20*DL Moment
= 4.00 kN-m
Area of Steel required = 93.99 mm2
Min. area of Steel both face = 300.00 mm2
0.25 of provided main reinf. = 130.83 mm2
Area of Steel considered = 150.00 mm2
Bar dia provided = 8 mm
Spacing required = 335 mm
spacing provided = 300 mm
Actual Area of Steel provided = 167 mm2 > required
Provide TOR 8 @ 300 c/c
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 22 kN
Shear Stress = 0.113 Mpa
% of Steel provided = 0.27
permissible shear stress = 0.236 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at face of wall = 25.6 kN-m
Effective Depth required = 162 mm
Overall depth proposed = 250 mm
Clear Cover = 50 mm
Effective cover = 56 mm
Effective depth = 194 mm > required.
Effective depth considered = 194 mm
Overall depth provided = 250 mm
Distribution reinforcement :
Moment = 0.20*DL Moment
= 5.00 kN-m
Area of Steel required = 117.49 mm2
Min. area of Steel both face = 300.00 mm2
0.25 of provided main reinf. = 161.49 mm2
Area of Steel provided = 161.49 mm2
Bar dia provided = 8 mm
Spacing required = 311.00 mm
Spacing provided = 300.00 mm
Provide TOR 8 @ 300 c/c on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 10.775 kN
Shear Stress = 0.056 Mpa
% of Steel provided = 0.33
permissible shear stress = 0.257 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face
0.00
4000
2000
2000
5.00
1 2 .5 5
2 5 .6
1000
B.M.D. of Wall
1 2 .5 5
2 5 .6
1000
22.00 B.M.D. BASE-SLAB
B.M.D. of Wall
erall width=4.50m)
m
m
m
m
m
m
kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2
N/mm2
kN/m
kN/m
m
KN/m
rth pressure
os2 (φ α)
2
sin(δ φ)sin(φ i)
cos(δ α)cos(α i)
11.88
12.62
7
6
2
etry.
N/m per m width
N/m per m width
N/m per m width
mm > required
mm2 > required
mm > required.
(from analysis output)
cemnt
T8 @ 300 c/c
T8 @ 300 c/c
2 5 .6
E-SLAB
2 5 .6
E-SLAB
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 2.00 m, overall width=4.50m)
f f
a
b
e
TYPICAL CROSS-SECTION
Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981
Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ α)
Co-efficient of Active Earth Pressure= (Ka)static
sin(δ φ)sin(φ i
cos2αcos(δ α) 1
cos(δ α)cos(α
= 0.297
Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.
The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra
8.000 8.000
4.300
11.00
8.91
9.50 7.13 7.13
LOAD DIAGRAM
4 3
8 7
5 9 10 11 12 13 14 6
1 2
4. Design of Drain
Distribution reinforcement :
Moment = 0.20*DL Moment
= 2.00 kN-m
Area of Steel required = 62.88 mm2
Min. area of Steel both face = 240.00 mm2
0.25 of provided main reinf. = 130.83 mm2
Area of Steel considered = 130.83 mm2
Bar dia provided = 8 mm
Spacing required = 384 mm
spacing provided = 300 mm
Actual Area of Steel provided = 167 mm2 > required
Provide TOR 8 @ 300 c/c
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 15.129 kN
Shear Stress = 0.104 Mpa
% of Steel provided = 0.36
permissible shear stress = 0.265 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at face of wall = 13.18 kN-m
Effective Depth required = 116 mm
Overall depth proposed = 200 mm
Clear Cover = 50 mm
Effective cover = 56 mm
Hence Effective depth = 144 mm > required.
Effective depth considered = 144 mm
Overall depth provided = 200 mm
Distribution reinforcement :
Moment = 0.20*DL Moment
= 3.00 kN-m
Area of Steel required = 94.97 mm2
Min. area of Steel both face = 240.00 mm2
0.25 of provided main reinf. = 113.04 mm2
Area of Steel provided = 120.00 mm2
Bar dia provided = 8 mm
Spacing required = 419.00 mm
Spacing provided = 300.00 mm
Provide TOR 8 @ 300 c/c on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 8.638 kN
Shear Stress = 0.060 Mpa
% of Steel provided = 0.31
permissible shear stress = 0.250 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)
Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face
wall 200 T10 @ 150 & 300 c/c T8 @ 300 c/c
4.10 x 1.50
base-slab 200 T12 @ 250 c/c T8 @ 300 c/c
0.00
4100
2050
1500
2.4
7 .5 0
750
B.M.D. BASE-SLAB
11.36
B.M.D. of Wall
1
7 .5 0
750
B.M.D. BASE-SLAB
11.36
B.M.D. of Wall
erall width=4.50m)
m
m
m
m
m
m
kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2
N/mm2
kN/m
kN/m
m
KN/m
rth pressure
os2 (φ α)
2
sin(δ φ)sin(φ i)
cos(δ α)cos(α i)
m
KN/m2
8.91
9.50
7
6
2
etry.
N/m per m width
N/m per m width
N/m per m width
mm > required
mm2 > required
mm > required.
(from analysis output)
cemnt
distribution bar. b/f
T8 @ 300 c/c
T8 @ 300 c/c
0
1 3 .1 8
SE-SLAB
SE-SLAB
1 3 .1 8
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 1.00 m, overall width=4.50m)
f f
a
b
e
TYPICAL CROSS-SECTION
1.1 Dimensions :
Provide TOR 10 @ 250 c/c for base slab and walls outer face (tension face)
Provide TOR 8 @ 300 c/c as secondary reinforcemnts.
Reinforcemnt
Clear thick. in
Member
Opening mm earth face water face
m
m
m
m
m
m
kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
mm
mm
cemnt
T8 @ 300 c/c
T8 @ 300 c/c