1. DESIGN REPORTS OF OPEN R.C.C. LINED DRAIN OF OVERALL WIDTH 4.50 M AND
CLEAR HEIGHT 1.00 M, 1.50 M, 2.00 M, 2.50 M, 3.00 M, 3.50 M AND 4.00 MOF R.C
2. DRAWINGS SHOWING TYPICAL CROSS-SECTION FOR DIMENSIONS AND
REINFORCEMENT DETAILINGS.
3. SCHEDULES OF REINFORCEMENTS FOR OPEN R.C.C. LINED DRAINS.
4. QUANTITY COMPUTATION OF R.C.C., P.C.C., REINFORCEMENTS ETC. FOR R.C.C.
OPEN LINED DRAINS.
5. QUANTITY COMPUTATIONS OF EARTHWORK IN CUTTING AND BACKFILLINGS FOR
R.C.C. OPEN LINED DRAINS.
6. CROSS-SECTION AND QUANTITY COMPUTATION FOR OPEN C.C. MASONARY DRAIN..
OVERALL WIDTH 4.50 M AND
, 3.50 M AND 4.00 MOF R.C
FOR DIMENSIONS AND

NED DRAINS.
RCEMENTS ETC. FOR R.C.C.

NG AND BACKFILLINGS FOR

PEN C.C. MASONARY DRAIN..


STRUCTURAL DESIGN REPORT:

DESIGN OF OPEN R.C.C. LINED DRAIN OF OVERALL WIDTH 4.50 M AND CLEAR HEIGHT
M, 1.50 M, 2.00 M, 2.50 M, 3.00 M, 3.50 M AND 4.00 M

NAME OF WORK: MAINTENANCE OF GUWAHATI BYPASS ON NH-37 FROM JALUKBA


TO KOINADHARA (K.M. 146.000 TO K.M. 163.895) BY P.W.D. (N.
ASSAM.

NAME OF DIVISION: P.W.D., GUWAHATI N.H. DIVISION

Designed By:
Bilal Ahmed Barbhuiya (AFZAL KARIM)
Assistant Engineer, P.W.D. Executive Engineer, P.W.D
Guwahati N.H. Division. Guwahati N.H. Division
0 M AND CLEAR HEIGHT 1.00
ND 4.00 M

N NH-37 FROM JALUKBARI


163.895) BY P.W.D. (N.H),

(AFZAL KARIM)
cutive Engineer, P.W.D
uwahati N.H. Division
SCHEDULE OF REINFORCEMENT
DRAIN TYPE TYPE-1 (3.60 x 4.00)
BAR NO. OF TOTAL
MARK BAR DIA SPACING LENGTH
BAR SHAPE M1 in mm M2 in mm BARS per LENGTH
in mm in mm in mm
rm in 'm'
M1

(1) 20 150 & 300 250 4350 4850 12 58.2


M2

M1

M1
(2) 20 190 250 4400 4900 7 34.3
M1
M2

(3) 12 300 250 4350 4850 10 48.5

M1
M2
(4) M1 M1 12 300 250 4400 4900 5 24.5
M2
(5) M1 M1 10 150 & 300 250 1000 1500 82 123
M2
(6) M1 M1 10 190 250 1000 1500 48 72

M1

(7) 8 300 200 1275 1675 10 16.75

M1

TOTAL QTY. STEEL REQD. PER METER LENGTH OF DRAIN (kgs.)=


SCHEDULE OF REINFORCEME
DRAIN TYPE TYPE-2 (3.75 x 3.50)
BAR
WEIGHT REMARKS BAR DIA SPACING
MARK BAR SHAPE M1 in mm M2 in mm
in kgs. in mm in mm

M1

vert. bar on earth face


144.000 (curtailed above half the (1) 16 150 & 300 200 3775

M2
height)

M1

M1
85.000 bottom bar in slab (2) 20 200 200 4400
M1

M2
43.000 vert. bar water face (3) 10 300 200 3775

M1
M2
22.000 top bar in slab (4) M1 M1 10 300 200 4400
M2
76.000 dist. Bar in walls @ B/F (5) M1 M1 8 150 & 300 200 1000
M2
44.000 dist. Bar in slab @ B/F (6) M1 M1 10 200 200 1000

M1

7.000 haunch bar at bottom corner (7) 8 300 200 1100

M1

421.000 TOTAL QTY. STEEL REQD. PER METER LEN


EINFORCEMENT SCH
E-2 (3.75 x 3.50) DRAIN TYPE
NO. OF TOTAL BAR
LENGTH WEIGHT REMARKS BAR DIA
BARS per LENGTH MARK BAR SHAPE
in mm in kgs. in mm
rm in 'm'
M1

vert. bar on earth face


4175 12 50.1 79.000 (curtailed above half the (1) 16

M2
height)

M1

M1
4800 6 28.8 71.000 bottom bar in slab (2) 16
M1

M2
4175 10 41.75 26.000 vert. bar water face (3) 10

M1
M2
4800 5 24 15.000 top bar in slab (4) M1 M1 10
M2
1400 72 100.8 40.000 dist. Bar in walls @ B/F (5) M1 M1 8
M2
1400 46 64.4 40.000 dist. Bar in slab @ B/F (6) M1 M1 8

M1

1500 10 15 6.000 haunch bar at bottom corner (7) 8

M1

PER METER LENGTH OF DRAIN (kgs.)= 277.000 TOTAL Q


SCHEDULE OF REINFORCEMENT
TYPE-3 (3.80 x 3.00)
NO. OF TOTAL BAR
SPACING LENGTH WEIGHT REMARKS
M1 in mm M2 in mm BARS per LENGTH MARK
in mm in mm in kgs.
rm in 'm'

vert. bar on earth face


150 & 300 175 3250 3600 12 43.2 68.000 (curtailed above half the (1)
height)

190 175 4400 4750 7 33.25 53.000 bottom bar in slab (2)

300 175 3250 3600 10 36 22.000 vert. bar water face (3)

300 175 4400 4750 5 23.75 15.000 top bar in slab (4)

150 & 300 175 1000 1350 72 97.2 38.000 dist. Bar in walls @ B/F (5)

190 175 1000 1350 48 64.8 26.000 dist. Bar in slab @ B/F (6)

300 200 1000 1400 10 14 6.000 haunch bar at bottom corner (7)

TOTAL QTY. STEEL REQD. PER METER LENGTH OF DRAIN (kgs.)= 228.000
SCHEDULE OF REINFORCEMENT
DRAIN TYPE TYPE-4 (3.90 x 2.50)
NO. OF TOTAL
BAR DIA SPACING LENGTH WEIGHT
BAR SHAPE M1 in mm M2 in mm BARS per LENGTH
in mm in mm in mm in kgs.
rm in 'm'
M1

12 150 & 300 150 2700 3000 12 36 32.000


M2

M1

M1
16 225 150 4400 4700 6 28.2 45.000
M1
M2

10 300 150 2700 3000 10 30 19.000

M1
M2
M1 M1 10 300 150 4400 4700 5 23.5 15.000
M2
M1 M1 8 150 & 300 150 1000 1300 72 93.6 37.000
M2
M1 M1 8 225 150 1000 1300 41 53.3 21.000

M1

8 300 200 900 1300 10 13 5.000

M1

TOTAL QTY. STEEL REQD. PER METER LENGTH OF DRAIN (kgs.)= 174.000
SCHEDULE OF REINFORCEMENT
DRAIN TYPE TYPE-5 (4.00 x 2.00)
BAR
REMARKS BAR DIA SPACING LENGTH
MARK BAR SHAPE M1 in mm M2 in mm
in mm in mm in mm

M1

vert. bar on earth face


(curtailed above half the (1) 10 150 & 300 125 2150 2400

M2
height)

M1

M1
bottom bar in slab (2) 12 175 125 4400 4650
M1

M2
vert. bar water face (3) 8 300 125 2150 2400

M1
M2
top bar in slab (4) M1 M1 8 300 125 4400 4650
M2
dist. Bar in walls @ B/F (5) M1 M1 8 300 125 1000 1250
M2
dist. Bar in slab @ B/F (6) M1 M1 8 300 125 1000 1250

haunch bar at bottom corner (7)

TOTAL QTY. STEEL REQD. PER METER LENGTH OF DR


EMENT SCHEDULE O
2.00) DRAIN TYPE
NO. OF TOTAL BAR
WEIGHT REMARKS BAR DIA SPACING
BARS per LENGTH MARK BAR SHAPE
in kgs. in mm in mm
rm in 'm'
M1

vert. bar on earth face


12 28.8 18.000 (curtailed above half the (1) 10 150 & 300

M2
height)

M1

M1
7 32.55 29.000 bottom bar in slab (2) 12 250
M1

M2
10 24 9.000 vert. bar water face (3) 8 300

M1
M2
5 23.25 9.000 top bar in slab (4) M1 M1 8 300
M2
96 120 47.000 dist. Bar in walls @ B/F (5) M1 M1 8 300
M2
31 38.75 15.000 dist. Bar in slab @ B/F (6) M1 M1 8 300

(7)

R LENGTH OF DRAIN (kgs.)= 127.000 TOTAL QTY. STEEL


SCHEDULE OF REINFORCEMENT
TYPE-6 (4.10 x 1.50)
NO. OF TOTAL REMARKS
LENGTH WEIGHT
M1 in mm M2 in mm BARS per LENGTH
in mm in kgs.
rm in 'm'

vert. bar on earth face


125 1600 1850 12 22.2 14.000 (curtailed above half the
height)

125 4400 4650 5 23.25 21.000 bottom bar in slab

80 1600 1760 10 17.6 7.000 vert. bar water face

80 4400 4560 5 22.8 9.000 top bar in slab

80 1000 1160 96 111.36 44.000 dist. Bar in walls @ B/F

80 1000 1160 31 35.96 14.000 dist. Bar in slab @ B/F

TAL QTY. STEEL REQD. PER METER LENGTH OF DRAIN (kgs.)= 109.000
Design dimensions and reinforcments of R.C.C. Open Drain :

1. R.C.C Drain Clear Span= 3.60m, Clear Height= 4.00m

Clear thick. in Reinforcemnt


Member
Opening mm earth face water face distribution bar. b
wall 450 T20 @ 150 & 300 c/c T12 @300 c/c T10 @ 150 & 300
3.60 x 4.00
base-slab 450 T20 @ 190 c/c T12 @ 300 c/c T10 @190 c/c

2. R.C.C Drain Clear Span= 3.75m, Clear Height= 3.50 m

Clear thick. in Reinforcemnt


Member
Opening mm earth face water face distribution bar. b
wall 375 T16 @ 150 & 300 c/c T10 @ 300 c/c T8 @ 150 & 300 c
3.75 x 3.5
base-slab 375 T20 @ 200 c/c T10 @ 300 c/c T10 @ 200 c/c

3. R.C.C Drain Clear Span= 3.80m, Clear Height= 3.00 m

Clear thick. in Reinforcemnt


Member
Opening mm earth face water face distribution bar. b
wall 350 T16 @ 150 & 300 c/c T10 @ 300 c/c T8 @ 150 & 300 c
3.80 x 3.0
base-slab 350 T16 @ 190 c/c T10 @ 300 c/c T 8 @ 190 c/c

4. R.C.C Drain Clear Span= 3.90m, Clear Height= 2.50 m

Clear thick. in Reinforcemnt


Member
Opening mm earth face water face distribution bar. b
wall 300 T12 @ 150 & 300 c/c T10 @ 300 c/c T8 @ 150 & 300 c
3.90 x 2.5
base-slab 300 T16 @ 225c/c T10 @ 300 c/c T8 @ 225 c/c

5. R.C.C Drain Clear Span= 4.00m, Clear Height= 2.00 m

Clear thick. in Reinforcemnt


Member
Opening mm earth face water face distribution bar. b
wall 250 T10 @ 150 & 300 c/c T8 @ 300 c/c T8 @ 300 c/c
4.00 x 2.0
base-slab 250 T12 @ 175 c/c T8@ 300 c/c T8 @ 300 c/c

6. R.C.C Drain Clear Span= 4.10m, Clear Height= 1.50 m

Clear thick. in Reinforcemnt


Member
Opening mm earth face water face distribution bar. b
wall 200 T10 @ 150 & 300 c/c T8 @ 300 c/c T8 @ 300 c/c
4.10 x 1.50
4.10 x 1.50
base-slab 200 T12 @ 250 c/c T8 @ 300 c/c T8 @ 300 c/c

7. R.C.C Drain Clear Span= 4.10m, Clear Height= 1.50 m

Clear thick. in Reinforcemnt


Member
Opening mm earth face water face distribution bar. b
wall 175 T10 @ 250 c/c T8 @ 300 c/c T8 @ 300 c/c
4.15 x 1.00
base-slab 175 T10 @ 250 c/c T8 @ 300 c/c T8 @ 300 c/c
distribution bar. b/f
T10 @ 150 & 300 c/c
T10 @190 c/c

distribution bar. b/f


T8 @ 150 & 300 c/c
T10 @ 200 c/c

distribution bar. b/f


T8 @ 150 & 300 c/c
T 8 @ 190 c/c

distribution bar. b/f


T8 @ 150 & 300 c/c
T8 @ 225 c/c

distribution bar. b/f


T8 @ 300 c/c
T8 @ 300 c/c

distribution bar. b/f


T8 @ 300 c/c
T8 @ 300 c/c

distribution bar. b/f


T8 @ 300 c/c
T8 @ 300 c/c
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 4.00 m, overall width=4.50m)

f f

a
b

e
TYPICAL CROSS-SECTION

1.0 Design Data

1.1 Preliminary Dimensions :

Clear Span 'b' = 3.70


Clear Height 'a' = 4.00
Wall Thickness 'f' = 0.400
Base Thickness 'e' = 0.400
Overall height 'H' = 4.40
Overall width 'W' = 4.50

1.2 Material Properties

Density of backfill soil γs = 20


Density of Concrete γc = 25
S.B.C. of Soil qs = 100
Angle of Internal friction for back fill ∅ = 30
friction angle between wall & backfill δ = 20
Angle of Inclination of back of wall α = 0
Slope of backfill with horizontal i 0
Permissible Settlement = 40.00
Height of surcharge = 1.20

1.3 Design Parameters


Grade of Concrete = M25
Grade of Steel = Fe500
Clear Cover for earth face structural component = 50
Clear Cover for inside face structural component = 50
Clear Cover for bottom slab = 50
Permissible direct comp. strength of Concrete (scc) = 6.25
Permissible flexural comp. strength of Concrete (scb) = 8.33
Permissible tensile strength of Concrete ( sct ) = 0.61
Permissible tensile strength of Steel ( sst ) = 240

Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981

2.0 Load Calculation

2.10 Dead Load of the Structure 'DL'

U.D.L on vertical wall = 40


U.D.L on base slab = 10

2.20 Dead Load on Bottom Slab due to Soil Silting

Thickness of earth fill due to silting = 0.3


Load (UDL) on bottom slab = 0.3 * 20 = 6

2.30 Horizontal Earth Pressure

Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ  α)
Co-efficient of Active Earth Pressure= (Ka)stat ic 
 sin(δ  φ)sin(φ i
cos2αcos(δ  α)  1 
 cos(δ  α)cos(α
= 0.297

Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.

2.40 Live Load Surcharge


Equivalent height = 1.20
Uniform Intensity of loading = = 7.13

3.0 Structural Analysis

The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra

40 40

4.10

16

23.76
24.95 7.13 7.13
LOAD DIAGRAM

4 3

8 7
5 9 10 11 12 13 14 6
1 2

Figure: STADD Discretisation of BOX Geometry.

Spring Constant= 2500 kN/m2 per m width


Nos. of springs provided= 10

Spring constant at end supports 1,2= 250 kN/m per m width


Spring constant at penultimate supports 5,6= 910.714 kN/m per m width
Spring constant atintermediate supports 9 to 14= 1321.43 kN/m per m width

4. Design of Drain

a) Design of Vertical wall


Design for flexure due to (EP+DL) combination :
Max. Moment at the face of bott. Slab = 120.4 kN-m
Required Effective Depth = 350 mm
Overall depth proposed = 400 mm
Clear Cover = 50 mm
Effective cover = 60 mm
Hence Effective depth = 340 mm < required
Effective depth provided = 390 mm
Hence overall depth = 450 mm

Tension reinforcement on outer/ earth face


Area of Steel required = 1407.36 mm2
min. area of steel=0.12% of bD = 540.00 mm2
Main Bar dia provided = 20 mm
Spacing required = 223.10 mm
Spacing upto half the ht. from base = 150.00 mm
Spacing for remaining ht. = 300.00 mm
Actual Area of Steel provided = 2093.33 mm2
Curtailed area of steel = 1570 mm2
Provide TOR 20 @ 150 c/c for bottom half and 300 c/c for remaning half

Vertical Reinforcement: inner face


min. area of steel=0.12% of bD = 540.00 mm2
Area of steel provided = 270.00 mm2
Dia of bar considerd = 12 mm
Spacing required = 419 mm
Spacing provided = 300 mm
Actual Area of Steel provided = 377 mm2
Provide TOR 12 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 24.00 kN-m
Area of Steel required = 280.54 mm2
Min. area of Steel both face = 540.00 mm2
0.25 of provided main reinf. = 523.33 mm2
Area of steel provided on each face = 523.33 mm2
Bar dia provided = 10 mm
Spacing required = 150 mm
Spacing upto half the ht. from base = 150 mm
Spacing for remaining ht. = 300 mm
Cuttailed Area of Steel provided = 393 mm2
Provide TOR 10 @ 150 c/c for bottom half and 300 c/c for remaning half on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 66 kN
Shear Stress = 0.169 Mpa
% of Steel provided = 0.54
permissible shear stress = 0.322 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at wall face = 136 kN-m
Effective Depth required = 372 mm
Overall depth proposed = 400 mm
Clear Cover = 50 mm
Effective cover = 60 mm
Hence Effective depth = 340 mm < required.
Effective depth provided = 390 mm
Hence Overall depth 450 mm

Tension reinforcement at bottom face


Area of Steel required = 1589.71 mm2
min. area of stell=0.12% of bD = 540.00 mm2
Main Bar dia provided = 20 mm
Spacing required = 197.52 mm
Spacing provided = 190.00 mm
Area of Steel provided = 1652.6 mm2
Provide TOR 20 @ 190 c/c

Reinforcement: top face


min. area of steel=0.12% of bD = 540.00 mm2
Area of steel provided = 270.00 mm2
Dia of bar considerd = 12 mm
Spacing required = 419 mm
Spacing provided = 300 mm
Actual Area of Steel provided = 376.8 mm2
Provide TOR 12 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 27.00 kN-m
Area of Steel required = 315.60 mm2
Min. area of Steel both face = 540.00 mm2
0.25 of provided main reinf. = 413.16
Area of Steel provided = 413.16 mm2
Bar dia provided = 10 mm
Spacing required = 190.00 mm
Spacing provided = 190.00 mm
Provide TOR 10 @ 190 c/c on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 37 kN
Shear Stress = 0.095 Mpa
% of Steel provided = 0.42
permissible shear stress = 0.286 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

Design dimensions and reinforcments :

Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face

wall 450 T20 @ 150 & 300 c/c T12 @300 c/c
3.60 x 4.00
base-slab 450 T20 @ 190 c/c T12 @ 300 c/c

Curtailment of wall Reinforcement:


50% vertical bars of earth face & distribution bars on both face is curtailed due to reducing moment a
below.

0.00

3600
1800
4000

22.18
.0 0

09
00
3600
1800

4000
22.18

1 3 6 .0 0

8 5 .0 9
2000
120.4 B.M.D. BASE-SLAB

B.M.D. of Wall
erall width=4.50m)

m
m
m
m
m
m

kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2

N/mm2

kN/m
kN/m

m
KN/m

rth pressure

os2 (φ  α)
2
sin(δ  φ)sin(φ i) 
 
cos(δ  α)cos(α i) 

oad diagram below.

m
KN/m2

esign software ''STAAD.ProV8i " by


are adopted which are applied at
on modulus of subgrade reaction.
4.2

23.76
24.95
N/m per m width
N/m per m width
N/m per m width

(from analysis output)

mm < required
alf on each face

(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

(from analysis output)

mm < required.
(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

cemnt

distribution bar. b/f

T10 @ 150 & 300 c/c


T10 @190 c/c

e to reducing moment as shown


.0 0
SE-SLAB
1 3 6 .0 0
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 3.50 m, overall width=4.50m)

f f

a
b

e
TYPICAL CROSS-SECTION

1.0 Design Data

1.1 Preliminary Dimension Detail

Clear Span 'b' = 3.75


Clear Height 'a' = 3.50
Wall Thickness 'f' = 0.375
Base Thickness 'e' = 0.425
Overall height 'H' = 3.925
Overall width 'W' = 4.50

1.2 Material Properties

Density of backfill soil γs = 20


Density of Concrete γc = 25
S.B.C. of Soil qs = 100
Angle of Internal friction for back fill ∅ = 30
friction angle between wall & backfill δ = 20
Angle of Inclination of back of wall α = 0
Slope of backfill with horizontal i 0
Permissible Settlement = 40.00
Height of surcharge = 1.20

1.3 Design Parameters


Grade of Concrete = M25
Grade of Steel = Fe500
Clear Cover for earth face structural component = 50
Clear Cover for inside face structural component = 50
Clear Cover for bottom slab = 50
Permissible direct comp. strength of Concrete (scc) = 6.25
Permissible flexural comp. strength of Concrete (scb) = 8.33
Permissible tensile strength of Concrete ( sct ) = 0.61
Permissible tensile strength of Steel ( sst ) = 240

Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981

2.0 Load Calculation

2.10 Dead Load of the Structure 'DL'

U.D.L on vertical wall = 32.813


U.D.L on base slab = 10.625

2.20 Dead Load on Bottom Slab due to Soil Silting

Thickness of earth fill due to silting = 0.3


Load (UDL) on bottom slab = 0.3 * 20 = 6

2.30 Horizontal Earth Pressure

Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ  α)
Co-efficient of Active Earth Pressure= (Ka)static 
 sin(δ  φ)sin(φ i
cos2αcos(δ  α)  1 
 cos(δ  α)cos(α
= 0.297

Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.

2.40 Live Load Surcharge


Equivalent height = 1.20
Uniform Intensity of loading = = 7.13

3.0 Structural Analysis

The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra

32.813 32.813

4.125

16.625

20.79
22.05 7.13 7.13
LOAD DIAGRAM
4 3

8 7
5 9 10 11 12 13 14 6
1 2

Figure: STADD Discretisation of BOX Geometry.

Spring Constant= 2500 kN/m2 per m width


Nos. of springs provided= 10

Spring constant at end supports 1,2= 234.38 kN/m per m width


Spring constant at penultimate supports 5,6= 904.0 kN/m per m width
Spring constant atintermediate supports 9 to 14= 1339.29 kN/m per m width

4. Design of Drain

a) Design of Vertical wall


Design for flexure due to (EP+DL) combination :
Max. Moment at the face of bott. Slab = 88 kN-m
Required Effective Depth = 300 mm
Overall depth proposed = 375 mm
Clear Cover = 50 mm
Effective cover = 58 mm
Hence Effective depth = 317 mm > required
Effective depth provided = 317 mm

Tension reinforcement on outer/ earth face


Area of Steel required = 1265.51 mm2
min. area of steel=0.12% of bD = 450.00 mm2
Main Bar dia provided = 16 mm
Spacing required = 158.80 mm
Spacing upto half height from base = 150.00 mm
Spacing for remaining ht. = 300.00 mm
Actual Area of Steel provided = 1339.73 mm2
Curtailed area of steel = 1004.8 mm2
Provide TOR 16 @ 150 c/c for bottom half and 300 c/c forupper half

Vertical reinforcement: inner face/water face


min. area of steel=0.12% of bD = 450.00 mm2
Area of steel provided = 225.00 mm2
Dia of bar considerd = 10 mm
Spacing required = 348.90 mm
Spacing provided = 300.00 mm
Actual Area of Steel provided = 261.667 mm2
Provide TOR 10 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 18.00 kN-m
Area of Steel required = 258.85 mm2
Min. area of Steel both face = 450.00 mm2
0.25 of provided main reinf. = 334.93 mm2
Bar dia provided = 8 mm
Spacing required = 150 mm
Spacing upto half the ht. from base = 150 mm
Spacing for remaining ht. = 300 mm
Cuttailed Area of Steel provided = 251 mm2
Provide TOR 8 @ 150 c/c for bottom half and 300 c/c for remaning half on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 53 kN
Shear Stress = 0.167 Mpa
% of Steel provided = 0.42
permissible shear stress = 0.285 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at wall face = 100 kN-m
Effective Depth required = 319 mm
Overall depth considered = 425 mm
Clear Cover = 50 mm
Effective cover = 60 mm
Effective depth = 365 mm > required.
Effective depth considered = 325 mm
Revise overall depth 375 mm

Tension reinforcement at bottom face


Area of Steel required = 1402.68 mm2
min. area of steel=0.12% of bD = 450.00 mm2
Main Bar dia provided = 20 mm
Spacing required = 223.86 mm
Spacing provided = 200.00 mm
Area of Steel provided = 1570 mm2
Provide TOR 20 @ 200 c/c

Reinforcement: top face


min. area of steel=0.12% of bD = 450.00 mm2
Area of steel provided = 225.00 mm2
Dia of bar considerd = 10 mm
Spacing required = 349 mm
Spacing provided = 300 mm
Actual Area of Steel provided = 261.667 mm2
Provide TOR 10 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 20.00 kN-m
Area of Steel required = 280.54 mm2
Min. area of Steel both face = 450.00 mm2
0.25 of provided main reinf. = 392.50 mm2
Area of Steel provided = 392.50 mm2
Bar dia provided = 10 mm
Spacing required = 200.00 mm
Spacing provided = 200.00 mm
Provide TOR 10 @ 200 c/c on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 21.263 kN
Shear Stress = 0.065 Mpa
% of Steel provided = 0.48
permissible shear stress = 0.305 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

Design dimensions and reinforcments :

Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face

wall 375 T16 @ 150 & 300 c/c T10 @ 300 c/c
3.75 x 3.5
base-slab 375 T20 @ 200 c/c T10 @ 300 c/c

Curtailment of wall Reinforcement:

50% vertical bars of earth face & distribution bars on both face is curtailed due to reducing moment.

0.00

3750
1875
3500

17.00
1 0 0 .0 0

7 1 .0 0
1750

B.M.D. BASE-SLAB
3500
17.00

1 0 0 .0 0

7 1 .0 0
1750
B.M.D. BASE-SLAB
88.00

B.M.D. of Wall
erall width=4.50m)

m
m
m
m
m
m

kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2

N/mm2

kN/m
kN/m

m
KN/m

rth pressure

os2 (φ  α)
2
sin(δ  φ)sin(φ i) 
 
cos(δ  α)cos(α i) 

oad diagram below.

m
KN/m2

esign software ''STAAD.ProV8i " by


are adopted which are applied at
on modulus of subgrade reaction.
3.713

20.79
22.05
N/m per m width
N/m per m width
N/m per m width

(from analysis output)

mm > required
lf on each face

(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

(from analysis output)

mm > required.
(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

cemnt

distribution bar. b/f

T8 @ 150 & 300 c/c


T10 @ 200 c/c

e to reducing moment.

0
1 0 0 .0 0

SE-SLAB
SE-SLAB
1 0 0 .0 0
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 3.00 m, overall width=4.50m)

f f

a
b

e
TYPICAL CROSS-SECTION

1.0 Design Data

1.1 Preliminary Dimensions :

Clear Span 'b' = 3.80


Clear Height 'a' = 3.00
Wall Thickness 'f' = 0.350
Base Thickness 'e' = 0.350
Overall height 'H' = 3.350
Overall width 'W' = 4.50

1.2 Material Properties

Density of backfill soil γs = 20


Density of Concrete γc = 25
S.B.C. of Soil qs = 100
Angle of Internal friction for back fill ∅ = 30
friction angle between wall & backfill δ = 20
Angle of Inclination of back of wall α = 0
Slope of backfill with horizontal i 0
Permissible Settlement = 40.00
Height of surcharge = 1.20

1.3 Design Parameters


Grade of Concrete = M25
Grade of Steel = Fe500
Clear Cover for earth face structural component = 50
Clear Cover for inside face structural component = 50
Clear Cover for bottom slab = 50
Permissible direct comp. strength of Concrete (scc) = 6.25
Permissible flexural comp. strength of Concrete (scb) = 8.33
Permissible tensile strength of Concrete ( sct ) = 0.61
Permissible tensile strength of Steel ( sst ) = 240

Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981

2.0 Load Calculation

2.10 Dead Load of the Structure 'DL'

U.D.L on vertical wall = 27.781


U.D.L on base slab = 8.75

2.20 Dead Load on Bottom Slab due to Soil Silting

Thickness of earth fill due to silting = 0.3


Load (UDL) on bottom slab = 0.3 * 20 = 6

2.30 Horizontal Earth Pressure

Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ  α)
Co-efficient of Active Earth Pressure= (Ka)static 
 sin(δ  φ)sin(φ i
cos2αcos(δ  α)  1 
 cos(δ  α)cos(α
= 0.297

Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.

2.40 Live Load Surcharge


Equivalent height = 1.20
Uniform Intensity of loading = = 7.13

3.0 Structural Analysis

The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra

27.781 27.781

4.150

14.75

17.82
18.86 7.13 7.13
LOAD DIAGRAM

4 3

8 7
5 9 10 11 12 13 14 6
1 2

Figure: STADD Discretisation of BOX Geometry.

Spring Constant= 2500 kN/m2 per m width


Nos. of springs provided= 10

Spring constant at end supports 1,2= 218.75 kN/m per m width


Spring constant at penultimate supports 5,6= 897.3 kN/m per m width
Spring constant atintermediate supports 9 to 14= 1357.1 kN/m per m width

4. Design of Drain

a) Design of Vertical wall


Design for flexure due to (EP+DL) combination :
Max. Moment at the face of bott. Slab = 58.82 kN-m
Required Effective Depth = 245 mm
Overall depth proposed = 350 mm
Clear Cover = 50 mm
Effective cover = 58 mm
Hence Effective depth = 292 mm > required
Effective depth provided = 292 mm

Tension reinforcement on outer/ earth face


Area of Steel required = 918.3 mm2
min. area of steel=0.12% of bD = 420.00 mm2
Main Bar dia provided = 16 mm
Spacing required = 218.80 mm
Spacing upto half height from base = 150.00 mm
Spacing for remaining ht. = 300.00 mm
Actual Area of Steel provided = 1339.73 mm2
Curtailed area of steel = 1004.8 mm2
Provide TOR 16 @ 150 c/c for bottom half and @ 300 c/c for upper half

Vertical reinforcement: inner face/water face


min. area of steel=0.12% of bD = 420.00 mm2
Area of steel provided = 210.00 mm2
Dia of bar considerd = 10 mm
Spacing required = 373.80 mm
Spacing provided = 300.00 mm
Actual Area of Steel provided = 261.667 mm2
Provide TOR 10 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 12.00 kN-m
Area of Steel required = 187.34 mm2
Min. area of Steel both face = 420.00 mm2
0.25 of provided main reinf. = 334.93 mm2
Bar dia provided = 8 mm
Spacing required = 150 mm
Spacing upto half the ht. from base = 150 mm
Spacing for remaining ht. = 300 mm
Cuttailed Area of Steel provided = 251 mm2
Provide TOR 8 @ 150 c/c for bottom half and 300 c/c for remaning half on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 41 kN
Shear Stress = 0.140 Mpa
% of Steel provided = 0.46
permissible shear stress = 0.297 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at face of wall = 67.62 kN-m
Effective Depth required = 263 mm
Overall depth considered = 350 mm
Clear Cover = 50 mm
Effective cover = 58 mm
Hence Effective depth = 292 mm > required.
Effective depth provided = 292 mm
Overall depth provided 350 mm

Tension reinforcement at bottom face


Area of Steel required = 1055.69 mm2
min. area of stell=0.12% of bD = 420.00 mm2
Main Bar dia provided = 16 mm
Spacing required = 190.36 mm
Spacingprovided = 190.00 mm
Area of Steel provided = 1057.68 mm2
Provide TOR 16 @ 190 c/c

Reinforcement: top face


min. area of steel=0.12% of bD = 420.00 mm2
Area of steel provided = 210.00 mm2
Dia of bar considerd = 10 mm
Spacing required = 374 mm
Spacing provided = 300 mm
Actual Area of Steel provided = 261.667 mm2
Provide TOR 10 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 14.00 kN-m
Area of Steel required = 218.57 mm2
Min. area of Steel both face = 420.00 mm2
0.25 of provided main reinf. = 264.42 mm2
Area of Steel provided = 264.42 mm2
Bar dia provided = 8 mm
Spacing required = 190.00 mm
Spacing provided = 190.00 mm
Provide TOR 8 @ 190 c/c on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 22.11 kN
Shear Stress = 0.076 Mpa
% of Steel provided = 0.36
permissible shear stress = 0.266 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

Final design dimensions and reinforcment of the drain:

Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face

wall 350 T16 @ 150 & 300 c/c T10 @ 300 c/c
3.80 x 3.0
base-slab 350 T16 @ 190 c/c T10 @ 300 c/c

Curtailment of wall Reinforcement:

50% vertical bars of earth face & distribution bars on both face is curtailed due to reducing moment.

0.00

3800
1900
3000

12.00
6 7 .6 2

3 9 .0 0
1500

59.00 B.M.D. BASE-SLAB


12.00

30

6 7 .6 2

3 9 .0 0
1500
59.00 B.M.D. BASE-SLAB

B.M.D. of Wall
erall width=4.50m)

m
m
m
m
m
m

kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2

N/mm2

kN/m
kN/m

m
KN/m

rth pressure

os2 (φ  α)
2
sin(δ  φ)sin(φ i) 
 
cos(δ  α)cos(α i) 

oad diagram below.

m
KN/m2

esign software ''STAAD.ProV8i " by


are adopted which are applied at
on modulus of subgrade reaction.
3.175

17.82
18.86

7
6
2

etry.
N/m per m width
N/m per m width
N/m per m width

(from analysis output)

mm > required
lf on each face

(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

(from analysis output)

mm > required.
(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

cemnt

distribution bar. b/f

T8 @ 150 & 300 c/c


T 8 @ 190 c/c

e to reducing moment.

00
6 7 .6 2

ASE-SLAB
6 7 .6 2
ASE-SLAB
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 2.50 m, overall width=4.50m)

f f

a
b

e
TYPICAL CROSS-SECTION

1.0 Design Data

1.1 Preliminary Dimensions :

Clear Span 'b' = 3.90


Clear Height 'a' = 2.50
Wall Thickness 'f' = 0.300
Base Thickness 'e' = 0.300
Overall height 'H' = 2.800
Overall width 'W' = 4.50

1.2 Material Properties

Density of backfill soil γs = 20


Density of Concrete γc = 25
S.B.C. of Soil qs = 100
Angle of Internal friction for back fill ∅ = 30
friction angle between wall & backfill δ = 20
Angle of Inclination of back of wall α = 0
Slope of backfill with horizontal i 0
Permissible Settlement = 40.00
Height of surcharge = 1.20

1.3 Design Parameters


Grade of Concrete = M25
Grade of Steel = Fe500
Clear Cover for earth face structural component = 50
Clear Cover for inside face structural component = 50
Clear Cover for bottom slab = 50
Permissible direct comp. strength of Concrete (scc) = 6.25
Permissible flexural comp. strength of Concrete (scb) = 8.33
Permissible tensile strength of Concrete ( sct ) = 0.61
Permissible tensile strength of Steel ( sst ) = 240

Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981

2.0 Load Calculation

2.10 Dead Load of the Structure 'DL'

U.D.L on vertical wall = 19.875


U.D.L on base slab = 7.5

2.20 Dead Load on Bottom Slab due to Soil Silting

Thickness of earth fill due to silting = 0.3


Load (UDL) on bottom slab = 0.3 * 20 = 6

2.30 Horizontal Earth Pressure

Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ  α)
Co-efficient of Active Earth Pressure= (Ka)static 
 sin(δ  φ)sin(φ i
cos2αcos(δ  α)  1 
 cos(δ  α)cos(α
= 0.297

Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.

2.40 Live Load Surcharge


Equivalent height = 1.20
Uniform Intensity of loading = = 7.13

3.0 Structural Analysis

The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra

19.875 19.875

4.200

13.5

14.85

15.74 7.13 7.13


LOAD DIAGRAM

4 3

8 7
5 9 10 11 12 13 14 6
1 2

Figure: STADD Discretisation of BOX Geometry.

Spring Constant= 2500 kN/m2 per m width


Nos. of springs provided= 10

Spring constant at end supports 1,2= 187.50 kN/m per m width


Spring constant at penultimate supports 5,6= 883.9 kN/m per m width
Spring constant atintermediate supports 9 to 14= 1392.9 kN/m per m width

4. Design of Drain

a) Design of Vertical wall


Design for flexure due to (EP+DL) combination :
Max. Moment at the face of bott. Slab = 37.756 kN-m
Required Effective Depth = 196 mm
Overall depth proposed = 300 mm
Clear Cover = 50 mm
Effective cover = 56 mm
Hence Effective depth = 244 mm > required
Effective depth considerd = 244 mm > required

Tension reinforcement on outer/ earth face


Area of Steel required = 705.405 mm2
min. area of steel=0.12% of bD = 360.00 mm2
Main Bar dia provided = 12 mm
Spacing required = 160.20 mm
Spacing upto half height from base = 150.00 mm
Spacing for remaining ht. = 300.00 mm
Actual Area of Steel provided = 753.6 mm2
Curtailed area of steel = 565.2 mm2
Provide TOR 12 @ 150 c/c for bottom half and @ 300 c/c for upper half

Reinforcement: inner face/water face


min. area of steel=0.12% of bD = 360.00 mm2
Area of steel provided = 180.00 mm2
Dia of bar considerd = 10 mm
Spacing required = 436.10 mm
Spacing provided = 300.00 mm
Actual Area of Steel provided = 261.667 mm2
Provide TOR 10 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 8.00 kN-m
Area of Steel required = 149.47 mm2
Min. area of Steel both face = 360.00 mm2
0.25 of provided main reinf. = 188.40 mm2
Area of Steel provided = 188.40 mm2
Bar dia provided = 8 mm
Spacing required = 267 mm
Spacing upto half the ht. from base = 150 mm
Spacing for remaining ht. = 300 mm
Cuttailed Area of Steel provided = 251 mm2
Provide TOR 8 @ 150 c/c for bottom half and 300 c/c for remaning half on each face
Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 32.11 kN
Shear Stress = 0.132 Mpa
% of Steel provided = 0.23
permissible shear stress = 0.224 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at face of wall = 43.46 kN-m
Effective Depth required = 210 mm
Overall depth proposed = 300 mm
Clear Cover = 50 mm
Effective cover = 58 mm
Effective depth = 242 mm > required.
Effective depth considered = 242 mm
Overall depth provided = 300 mm

Tension reinforcement at bottom face


Area of Steel required = 818.685 mm2
min. area of stell=0.12% of bD = 360.00 mm2
Main Bar dia provided = 16 mm
Spacing required = 245.47 mm
Spacing provided = 225.00 mm
Area of Steel provided = 893.156 mm2
Provide TOR 16 @ 225 c/c

Reinforcement: top face


min. area of steel=0.12% of bD = 360.00 mm2
Area of steel provided = 180.00 mm2
Dia of bar considerd = 10 mm
Spacing required = 436 mm
Spacing provided = 300 mm
Actual Area of Steel provided = 261.667 mm2
Provide TOR 10 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 9.00 kN-m
Area of Steel required = 169.54 mm2
Min. area of Steel both face = 360.00 mm2
0.25 of provided main reinf. = 223.29 mm2
Area of Steel provided = 223.29 mm2
Bar dia provided = 8 mm
Spacing required = 225.00 mm
Spacing provided = 225.00 mm
Provide TOR 8 @ 225 c/c on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 16.4 kN
Shear Stress = 0.068 Mpa
% of Steel provided = 0.37
permissible shear stress = 0.268 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

Final design dimensions and reinforcment of the drain:

Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face

wall 300 T12 @ 150 & 300 c/c T10 @ 300 c/c
3.90 x 2.5
base-slab 300 T16 @ 225c/c T10 @ 300 c/c

0.00

3900
1950
2500

8.00
4 3 .4 6

2 2 .5 0
1250
2500
8.00

4 3 .4 6

2 2 .5 0
1250
38.00 B.M.D. BASE-SLAB

B.M.D. of Wall
erall width=4.50m)

m
m
m
m
m
m

kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2

N/mm2

kN/m
kN/m

m
KN/m

rth pressure

os2 (φ  α)
2
sin(δ  φ)sin(φ i) 
 
cos(δ  α)cos(α i) 

oad diagram below.

m
KN/m2

esign software ''STAAD.ProV8i " by


are adopted which are applied at
on modulus of subgrade reaction.
2.650

14.85

15.74

7
6
2

etry.
N/m per m width
N/m per m width
N/m per m width

(from analysis output)

mm > required
mm > required
lf on each face

(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

(from analysis output)

mm > required.
(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

cemnt

distribution bar. b/f

T8 @ 150 & 300 c/c


T8 @ 225 c/c

0
4 3 .4 6
SE-SLAB 4 3 .4 6
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 2.00 m, overall width=4.50m)

f f

a
b

e
TYPICAL CROSS-SECTION

1.0 Design Data

1.1 Preliminary Dimensions :

Clear Span 'b' = 4.05


Clear Height 'a' = 2.00
Wall Thickness 'f' = 0.225
Base Thickness 'e' = 0.250
Overall height 'H' = 2.250
Overall width 'W' = 4.50

1.2 Material Properties

Density of backfill soil γs = 20


Density of Concrete γc = 25
S.B.C. of Soil qs = 100
Angle of Internal friction for back fill ∅ = 30
friction angle between wall & backfill δ = 20
Angle of Inclination of back of wall α = 0
Slope of backfill with horizontal i 0
Permissible Settlement = 40.00
Height of surcharge = 1.20

1.3 Design Parameters


Grade of Concrete = M25
Grade of Steel = Fe500
Clear Cover for earth face structural component = 50
Clear Cover for inside face structural component = 50
Clear Cover for bottom slab = 50
Permissible direct comp. strength of Concrete (scc) = 6.25
Permissible flexural comp. strength of Concrete (scb) = 8.33
Permissible tensile strength of Concrete ( sct ) = 0.61
Permissible tensile strength of Steel ( sst ) = 240

Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981

2.0 Load Calculation

2.10 Dead Load of the Structure 'DL'

U.D.L on vertical wall = 11.953


U.D.L on base slab = 6.25

2.20 Dead Load on Bottom Slab due to Soil Silting

Thickness of earth fill due to silting = 0.3


Load (UDL) on bottom slab = 0.3 * 20 = 6

2.30 Horizontal Earth Pressure

Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ  α)
Co-efficient of Active Earth Pressure= (Ka)static 
 sin(δ  φ)sin(φ i
cos2αcos(δ  α)  1 
 cos(δ  α)cos(α
= 0.297

Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.

2.40 Live Load Surcharge


Equivalent height = 1.20
Uniform Intensity of loading = = 7.13

3.0 Structural Analysis

The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra

11.953 11.953

4.275

12.25

11.88
12.62 7.13 7.13
LOAD DIAGRAM

4 3

8 7
5 9 10 11 12 13 14 6
1 2

Figure: STADD Discretisation of BOX Geometry.


Spring Constant= 2500 kN/m2 per m width
Nos. of springs provided= 10

Spring constant at end supports 1,2= 140.63 kN/m per m width


Spring constant at penultimate supports 5,6= 863.8 kN/m per m width
Spring constant atintermediate supports 9 to 14= 1446.4 kN/m per m width

4. Design of Drain

a) Design of Vertical wall


Design for flexure due to (EP+DL) combination :
Max. Moment at the face of bott. Slab = 22.18 kN-m
Required Effective Depth = 150 mm
Overall depth proposed = 225 mm
Clear Cover = 50 mm
Effective cover = 56 mm
Hence Effective depth = 169 mm
Effective depth considerd = 194 mm > required
Overall depth considered = 250 mm

Tension reinforcement on outer/ earth face


Area of Steel required = 521.198 mm2
min. area of steel=0.12% of bD = 300.00 mm2
Main Bar dia provided = 10 mm
Spacing required = 150.60 mm
Spacing upto half height from base = 150.00 mm
Spacing for remaining ht. = 300.00 mm
Actual Area of Steel provided = 523.333 mm2
Curtailed area of steel = 392.5 mm2
Provide TOR 10 @ 150 c/c for bottom half and @ 300 c/c for upper half

Reinforcement: inner face/water face


min. area of steel=0.12% of bD = 300.00 mm2
Area of steel provided = 150.00 mm2
Dia of bar considerd = 8 mm
Spacing required = 334.90 mm
Spacing provided = 300.00 mm
Actual Area of Steel provided = 167.467 mm2
Provide TOR 8 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 4.00 kN-m
Area of Steel required = 93.99 mm2
Min. area of Steel both face = 300.00 mm2
0.25 of provided main reinf. = 130.83 mm2
Area of Steel considered = 150.00 mm2
Bar dia provided = 8 mm
Spacing required = 335 mm
spacing provided = 300 mm
Actual Area of Steel provided = 167 mm2 > required
Provide TOR 8 @ 300 c/c

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 22 kN
Shear Stress = 0.113 Mpa
% of Steel provided = 0.27
permissible shear stress = 0.236 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at face of wall = 25.6 kN-m
Effective Depth required = 162 mm
Overall depth proposed = 250 mm
Clear Cover = 50 mm
Effective cover = 56 mm
Effective depth = 194 mm > required.
Effective depth considered = 194 mm
Overall depth provided = 250 mm

Tension reinforcement at bottom face


Area of Steel required = 601.563 mm2
min. area of stell=0.12% of bD = 300.00 mm2
Main Bar dia provided = 12 mm
Spacing = 187.91 mm
Spacing provided = 175.00 mm
Area of Steel provided = 645.943 mm2
Provide TOR 12 @ 175 c/c

Reinforcement: top face


min. area of steel=0.12% of bD = 300.00 mm2
Area of steel provided = 150.00 mm2
Dia of bar considerd = 8 mm
Spacing required = 335 mm
Spacing provided = 300 mm
Actual Area of Steel provided = 167.467 mm2
Provide TOR 8 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 5.00 kN-m
Area of Steel required = 117.49 mm2
Min. area of Steel both face = 300.00 mm2
0.25 of provided main reinf. = 161.49 mm2
Area of Steel provided = 161.49 mm2
Bar dia provided = 8 mm
Spacing required = 311.00 mm
Spacing provided = 300.00 mm
Provide TOR 8 @ 300 c/c on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 10.775 kN
Shear Stress = 0.056 Mpa
% of Steel provided = 0.33
permissible shear stress = 0.257 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

Final design dimensions and reinforcment of the drain:

Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face

wall 250 T10 @ 150 & 300 c/c T8 @ 300 c/c


4.00 x 2.0
base-slab 250 T12 @ 175 c/c T8@ 300 c/c

0.00

4000
2000
2000

5.00
1 2 .5 5
2 5 .6
1000

22.00 B.M.D. BASE-SLAB

B.M.D. of Wall
1 2 .5 5
2 5 .6
1000
22.00 B.M.D. BASE-SLAB

B.M.D. of Wall
erall width=4.50m)

m
m
m
m
m
m

kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2

N/mm2

kN/m
kN/m

m
KN/m

rth pressure

os2 (φ  α)
2
sin(δ  φ)sin(φ i) 
 
cos(δ  α)cos(α i) 

oad diagram below.


m
KN/m2

esign software ''STAAD.ProV8i " by


are adopted which are applied at
on modulus of subgrade reaction.
2.125

11.88
12.62

7
6
2

etry.
N/m per m width
N/m per m width
N/m per m width

(from analysis output)

mm > required
mm2 > required

(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

(from analysis output)

mm > required.
(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

cemnt

distribution bar. b/f

T8 @ 300 c/c
T8 @ 300 c/c
2 5 .6

E-SLAB
2 5 .6
E-SLAB
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 2.00 m, overall width=4.50m)

f f

a
b

e
TYPICAL CROSS-SECTION

1.0 Design Data

1.1 Preliminary Dimensions :

Clear Span 'b' = 4.10


Clear Height 'a' = 1.50
Wall Thickness 'f' = 0.200
Base Thickness 'e' = 0.200
Overall height 'H' = 1.700
Overall width 'W' = 4.50

1.2 Material Properties

Density of backfill soil γs = 20


Density of Concrete γc = 25
S.B.C. of Soil qs = 100
Angle of Internal friction for back fill ∅ = 30
friction angle between wall & backfill δ = 20
Angle of Inclination of back of wall α = 0
Slope of backfill with horizontal i 0
Permissible Settlement = 40.00
Height of surcharge = 1.20

1.3 Design Parameters


Grade of Concrete = M25
Grade of Steel = Fe500
Clear Cover for earth face structural component = 50
Clear Cover for inside face structural component = 50
Clear Cover for bottom slab = 50
Permissible direct comp. strength of Concrete (scc) = 6.25
Permissible flexural comp. strength of Concrete (scb) = 8.33
Permissible tensile strength of Concrete ( sct ) = 0.61
Permissible tensile strength of Steel ( sst ) = 240

Design Costants:
Modular Ratio m = 10
Netral axis depth factor n = 0.258
Lever arm factor j = 0.914
moment of resistance factor Q = 0.981

2.0 Load Calculation

2.10 Dead Load of the Structure 'DL'

U.D.L on vertical wall = 8.000


U.D.L on base slab = 5

2.20 Dead Load on Bottom Slab due to Soil Silting

Thickness of earth fill due to silting = 0.3


Load (UDL) on bottom slab = 0.3 * 20 = 6

2.30 Horizontal Earth Pressure

Critical loading condition will be the situation when box will be subjected to earth pressure
due to saturated backfill and there will be no water inside the box.
cos2 (φ  α)
Co-efficient of Active Earth Pressure= (Ka)static 
 sin(δ  φ)sin(φ i
cos2αcos(δ  α)  1 
 cos(δ  α)cos(α
= 0.297

Earth-pressure at a depth 'h' from the top of vertical wall=Ka. γ s.h kN/sq.m
Horizontal force on wall due to Earth pressure at variuos level is shown in the load diagram below.

2.40 Live Load Surcharge


Equivalent height = 1.20
Uniform Intensity of loading = = 7.13

3.0 Structural Analysis

The structure is analysed for variuos load acting on it using structural-design software ''STAAD
modelling it along the center lines of walls and slab. Spring type supports are adopted which a
various nodes along bottom slab. Stiffness of the support are calculated based on modulus of subgra

8.000 8.000

4.300

11.00

8.91
9.50 7.13 7.13
LOAD DIAGRAM

4 3

8 7
5 9 10 11 12 13 14 6
1 2

Figure: STADD Discretisation of BOX Geometry.

Spring Constant= 2500 kN/m2 per m width


Nos. of springs provided= 10

Spring constant at end supports 1,2= 125.00 kN/m per m width


Spring constant at penultimate supports 5,6= 857.1 kN/m per m width
Spring constant atintermediate supports 9 to 14= 1464.3 kN/m per m width

4. Design of Drain

a) Design of Vertical wall


Moment Max. at the face of bott. Slab = 11.36 kN-m
Required Effective Depth = 108 mm
Overall depth proposed = 200 mm
Clear Cover = 50 mm
Effective cover = 55 mm
Effective depth = 145 mm
Effective depth considerd = 145 mm > required
Overall depth considered = 200 mm

Tension reinforcement on outer/ earth face


Area of Steel required = 357.152 mm2
min. area of steel=0.12% of bD = 240.00 mm2
Main Bar dia provided = 10 mm
Spacing required = 219.80 mm
Spacing upto half height from base = 150.00 mm
Spacing for remaining ht. = 300.00 mm
Actual Area of Steel provided = 523.333 mm2
Curtailed area of steel = 392.5 mm2
Provide TOR 10 @ 150 c/c for bottom half and @ 300 c/c for upper half

Reinforcement: inner face/water face


min. area of steel=0.12% of bD = 240.00 mm2
Area of steel provided = 120.00 mm2
Dia of bar considerd = 8 mm
Spacing required = 418.70 mm
Spacing provided = 300.00 mm
Actual Area of Steel provided = 167.467 mm2
Provide TOR 8 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 2.00 kN-m
Area of Steel required = 62.88 mm2
Min. area of Steel both face = 240.00 mm2
0.25 of provided main reinf. = 130.83 mm2
Area of Steel considered = 130.83 mm2
Bar dia provided = 8 mm
Spacing required = 384 mm
spacing provided = 300 mm
Actual Area of Steel provided = 167 mm2 > required
Provide TOR 8 @ 300 c/c

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 15.129 kN
Shear Stress = 0.104 Mpa
% of Steel provided = 0.36
permissible shear stress = 0.265 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

b) Design of base-slab
Design for flexure due to (EP+DL) combination :
Max. Moment at face of wall = 13.18 kN-m
Effective Depth required = 116 mm
Overall depth proposed = 200 mm
Clear Cover = 50 mm
Effective cover = 56 mm
Hence Effective depth = 144 mm > required.
Effective depth considered = 144 mm
Overall depth provided = 200 mm

Tension reinforcement at bottom face


Area of Steel required = 417.249 mm2
min. area of stell=0.12% of bD = 240.00 mm2
Main Bar dia provided = 12 mm
Spacing = 270.92 mm
Spacing provided = 250.00 mm
Area of Steel provided = 452.16 mm2
Provide TOR 12 @ 250 c/c

Reinforcement: top face


min. area of steel=0.12% of bD = 240.00 mm2
Area of steel provided = 120.00 mm2
Dia of bar considerd = 8 mm
Spacing required = 419 mm
Spacing provided = 300 mm
Actual Area of Steel provided = 167.467 mm2
Provide TOR 8 @ 300 c/c

Distribution reinforcement :
Moment = 0.20*DL Moment
= 3.00 kN-m
Area of Steel required = 94.97 mm2
Min. area of Steel both face = 240.00 mm2
0.25 of provided main reinf. = 113.04 mm2
Area of Steel provided = 120.00 mm2
Bar dia provided = 8 mm
Spacing required = 419.00 mm
Spacing provided = 300.00 mm
Provide TOR 8 @ 300 c/c on each face

Shear Check:
S.F. at a dist. deff. from face of bott. Slab = 8.638 kN
Shear Stress = 0.060 Mpa
% of Steel provided = 0.31
permissible shear stress = 0.250 Mpa > Actual, hence O.K
(Refer IRC:21-2000, Table-12B) (no shear reinf. reqd.)

Final design dimensions and reinforcment of the drain:

Reinforcemnt
Clear (span thick. in
Member
x height) mm earth face water face
wall 200 T10 @ 150 & 300 c/c T8 @ 300 c/c
4.10 x 1.50
base-slab 200 T12 @ 250 c/c T8 @ 300 c/c

0.00

4100
2050
1500

2.4
7 .5 0
750

B.M.D. BASE-SLAB
11.36

B.M.D. of Wall
1

7 .5 0
750
B.M.D. BASE-SLAB
11.36

B.M.D. of Wall
erall width=4.50m)

m
m
m
m
m
m

kN/m3
kN/m3
kN/m2
degree
degree
degree
degree
mm
m
mm
mm
mm
N/mm2
N/mm2
N/mm2
N/mm2

N/mm2

kN/m
kN/m

m
KN/m

rth pressure

os2 (φ  α)
2
sin(δ  φ)sin(φ i) 
 
cos(δ  α)cos(α i) 

oad diagram below.

m
KN/m2

esign software ''STAAD.ProV8i " by


are adopted which are applied at
on modulus of subgrade reaction.
1.600

8.91
9.50

7
6
2

etry.
N/m per m width
N/m per m width
N/m per m width

(from analysis output)

mm > required
mm2 > required

(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

(from analysis output)

mm > required.
(from analysis output)

pa > Actual, hence O.K.


no shear reinf. reqd.)

cemnt
distribution bar. b/f
T8 @ 300 c/c
T8 @ 300 c/c

0
1 3 .1 8

SE-SLAB
SE-SLAB

1 3 .1 8
DESIGN OF R.C.C. OPEN DRAIN ( clear height= 1.00 m, overall width=4.50m)

f f

a
b

e
TYPICAL CROSS-SECTION

1.0 Design Data

1.1 Dimensions :

Clear Span 'b' = 4.15


Clear Height 'a' = 1.00
Wall Thickness 'f' = 0.175
Base Thickness 'e' = 0.175
Overall height 'H' = 1.175
Overall width 'W' = 4.50

1.2 Material Properties

Density of backfill soil γs = 20


Density of Concrete γc = 25
S.B.C. of Soil qs = 100
Angle of Internal friction for back fill ∅ = 30
friction angle between wall & backfill δ = 20
Angle of Inclination of back of wall α = 0
Slope of backfill with horizontal i 0
Grade of Concrete = M25
Grade of Steel = Fe500
Clear Cover for earth face structural component = 50
Clear Cover for inside face structural component = 50
Clear Cover for bottom slab = 50
4. Design of Drain

a) Design of Vertical wall & Slab:

Tension reinforcement on outer/ earth face

Nominal reinf. @ 0.12 % gross-concrete Area is provided to cater bending reinforcement


Overall depth proposed = 175 mm
Clear Cover = 50 mm
Effective cover = 55 mm
Effective depth = 120 mm
min. area of steel=0.12% of bD = 210.00 mm2
Main Bar dia provided = 10 mm
Spacing required = 373.80 mm
Spacing provided = 250.00 mm
Actual Area of Steel provided = 314 mm2

Provide TOR 10 @ 250 c/c for base slab and walls outer face (tension face)
Provide TOR 8 @ 300 c/c as secondary reinforcemnts.

Design dimensions and reinforcment of the drain:

Reinforcemnt
Clear thick. in
Member
Opening mm earth face water face

wall 175 T10 @ 250 c/c T8 @ 300 c/c


4.15 x 1.00
base-slab 175 T10 @ 250 c/c T8 @ 300 c/c
erall width=4.50m)

m
m
m
m
m
m

kN/m3
kN/m3
kN/m2
degree
degree
degree
degree

mm
mm
mm
cemnt

distribution bar. b/f

T8 @ 300 c/c
T8 @ 300 c/c