MANUAL
SEGMENT CHECKER
A UNIVERSAL AND EASY-TO-
USE SEGMENT DESIGN
TOOL FOR FIELDBUS
NETWORKS
Segment Checker
With regard to the supply of products, the current issue of the following document is ap-
plicable: The General Terms of Delivery for Products and Services of the Electrical Indu-
stry, published by the Central Association of the Electrical Industry (Zentralverband
Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the
supplementary clause: "Expanded reservation of proprietorship"
Segment Checker
3 Installation .................................................................................. 6
4 Operation..................................................................................... 7
4.1 Basic Operations.................................................................................. 7
4.1.1 Working with Projects......................................................................... 7
4.1.2 Opening a Project .............................................................................. 8
4.1.3 Saving a Project ................................................................................. 8
4.1.4 Save all projects................................................................................. 9
4.1.5 Display a Print Preview ...................................................................... 9
4.2 Window Overview .............................................................................. 10
4.2.1 Select Segment Type Window ......................................................... 10
4.2.2 The Device Tree Window ................................................................. 11
4.2.3 Property Editor Window ................................................................... 11
4.2.4 The Error Log Window ..................................................................... 12
4.2.5 The Segment Editor Window ........................................................... 13
4.2.6 The Project Report Window ............................................................. 13
4.3 Toolbar Overview ............................................................................... 14
4.4 Device Catalog Editor ........................................................................ 15
4.4.1 Starting the Device Catalog Editor.................................................... 15
4.4.2 Managing Cables............................................................................. 16
4.4.3 Managing Devices ........................................................................... 17
4.4.4 Importing and Exporting of Devices ................................................. 19
4.5 General Settings ................................................................................. 21
4.6 Example: Building a Simple Project ................................................. 22
5 Troubleshooting........................................................................ 27
6 Glossary .................................................................................... 28
6.1 Segment Checker Terms ................................................................... 28
6.2 Fieldbus Entries ................................................................................. 28
7 FAQ............................................................................................. 30
3
Segment Checker
Used Symbols
1 Used Symbols
Safety-relevant Symbols
Danger!
This symbol indicates a warning about an immediate possible danger.
In case of ignoring the consequences may range from personal injury to death.
Warning!
This symbol indicates a warning about a possible fault or danger.
In case of ignoring the consequences may cause personal injury or heaviest property damage.
Caution!
This symbol indicates a warning about a possible fault.
In case of ignoring the devices and any connected facilities or systems may be interrupted or
fail completely.
Informative Symbols
Note!
This symbol brings important information to your attention.
Action
This symbol indicates a paragraph with instructions.
2012-10
4
Segment Checker
Introduction to Segment Checker
Limitations
Segment Checker only audits the selected fieldbus infrastructure for conformity with the
fieldbus standard IEC 61158-2.
Segment Checker does not validate explosion protection. Even when a power supply with
reduced voltage and current levels is applied, the auditing is limited to conformity with the
fieldbus standard.
Segment Checker does not audit for any regional or local regulations.
Segment Checker does not calculate bus cycle time.
Caution!
Danger!
The Segment Checker must not be used for checking of safety data or explosion protection
parameters, the Segment Checker does not replace any stipulated calculations.
2012-10
5
Segment Checker
Installation
3 Installation
Note!
Microsoft .NET Framework 3.5 required
Microsoft .NET Framework 3.5 is required for the installation of the Segment Checker. You can
download the Microsoft .NET Framework from the Internet.
Software Installation
Caution!
Close all running programs before you run the setup tool!
The setup tool cannot replace any files that are used by other programs. In the worst case the
system may become instable or even crash.
2012-10
6
Segment Checker
Operation
4 Operation
4.1 Basic Operations
This section describes basic operations of the Segment Checker Software
7
Segment Checker
Operation
Note!
If one new project is not saved ever, the Save as dialog appears.
9
Segment Checker
Operation
10
Segment Checker
Operation
Note!
If the window is hidden, you can make it visible using the View menu.
Note!
If the window is hidden, you can make it visible using the View menu.
2012-10
11
Segment Checker
Operation
Handheld check
The Handheld checks verifies that if a handheld device is connected to the circuit, if there is still
enough current and voltage on the segment to power the field devices.
Handheld Spur check Checks the supply of the circuit if a handheld is been connected to a
spur in parallel to a field device
Handheld Trunk check Checks the supply of the circuit if a handheld is been connected to
the trunk or a junction box output
Handheld Host check Checks the supply of the circuit if a handheld is been connected in
parallel to the host
Note!
If the window is hidden, you can make it visible using the View menu.
2012-10
12
Segment Checker
Operation
13
Segment Checker
Operation
Displays the Device Catalog Editor. This function is active only if all projects are
closed.
Table 4.2 View Toolbar
14
Segment Checker
Operation
The Device Catalog Editor is a tool which is delivered together with the Segment Checker
Software. It enables you to
■ create your own device types with specific parameters
■ create your own cable types with specific parameters
■ import User Catalog Files (your own or files delivered by other companies)
■ export User Catalog Files (your own or files delivered by other companies)
4.4.1 Starting the Device Catalog Editor
Note!
Before you can run the Device Catalog Editor all projects must be closed.
15
Segment Checker
Operation
3. Change the properties of the cable in the right section of the window.
4. Close the Device Catalog Editor window with the Save button.
The changes are saved.
2012-10
16
Segment Checker
Operation
17
Segment Checker
Operation
Note!
If your new device is similar to a device type which is already existing, copying the exisiting
device type and changing the necessary properties may be easier. Therefore, select the device
type and press the Copy button.
2012-10
18
Segment Checker
Operation
Note!
Importing Devices
Note!
A PFD-file may contain many devices. You are able to choose only the devices you actually
want to import. Above all it is possible to update the data of devices which are already in your
Device Tree.
19
Segment Checker
Operation
20
Segment Checker
Operation
Note!
Before you can run the Device Catalog Editor all projects must be closed.
21
Segment Checker
Operation
22
Segment Checker
Operation
23
Segment Checker
Operation
Note!
The Error Log window displays not only error messages. It also displays some hints to build
the basic structure of the network.
Adding Devices
To add the devices, proceed as follows:
1. Add a power supply device: Expand the folder Power Supplies in the Device Tree window.
Move a power supply, e. g. the HD2-FBCL-1.500, via Drag & Drop into the Segment Editor
window.
The power supply is added to the project and the properties of the devices are shown in the
Property Editor window.
2. Enter a device name and a description for the power supply in the Property Editor window.
The HD2-FBCL-1.500 power supply contains a detachable terminator. For our purpose,
ensure that the check box Terminator is activated.
3. Add a host device: Expand the folder Hosts in the Device Tree window. Move a host, e. g.
the Gen. Host, via Drag & Drop into the Segment Editor window nearby the power supply.
The host is added to the project and connected to the power supply.
2012-10
24
Segment Checker
Operation
4. Enter a device name and a description for the host in the Property Editor window.
5. Add a distribution device, e. g. a segment protector: Expand the folder Segment
Protectors in the Device Tree window. Move a segment protector, e. g. the F2-JB-4.xx, via
Drag & Drop into the Segment Editor window nearby the power supply.
The segment protector is added to the project and connected to the other devices.
6. Enter a device name and a description for the segment protector in the Property Editor
window. The F2-JB-4.xx power segment protector contains a detachable terminator. For our
purpose, ensure that the check box Terminator is activated.
7. Add a field device: Expand the folder Field Devices in the Device Tree window. Move a
field device, e. g. the LTC series, via Drag & Drop into the Segment Editor window nearby
the segment protector.
The field device is added to the project and connected to the segment protector.
2012-10
25
Segment Checker
Operation
8. Enter a device name and a description for the field device in the Property Editor window.
Note!
If the Error Log window displays no messages, the fieldbus network is valid.
2. Change the desired cross-sectional area and cable length. For example, choose a cross-
sectional area of AWG 16 and a cable length of 10 meters.
The cross-sectional area and the cable length are stored. The values depending on the
cables are updated.
2012-10
26
Segment Checker
Troubleshooting
5 Troubleshooting
This chapter describes errors that may be displayed in the .
27
Segment Checker
Glossary
6 Glossary
6.1 Segment Checker Terms
Device Tree
The Device Tree contains all the available fieldbus devices classiefied in a folder structure.
Error Log
The Error Log displays all errors occured in the current Segment Checker project.
Property Editor
In the Property Editor all the properties of devices an cables can be displayed an changed.
Field Barrier
A field barrier provides intrinsically safe connection of the .
Fieldbus
A fieldbus is an industrial network system for real-time distributed control, more precisely a
digital, two-way, multi-drop communication link among intelligent measurement and control
devices. It serves as a Local Area Network (LAN) for advanced process control, remote
input/output and high speed factory automation applications.
Field Device
A field device is a component interacting directly with the process, usually remote I/O, sensors,
actuators, transducers. A field device is located in the field, whereas an instrument need not
be.
FOUNDATION fieldbus™
FOUNDATION fieldbus™ is the Fieldbus Foundation’s official product/service trade name.
Host
A host is generally a computer connected to a network. Within PROFIBUS a computing device
that "hosts" a DP master class 1 with at least one PROFIBUS segment and its DP slaves.
Junction box
A junction box connect the to the by individual , thus allowing easy disconnection and
maintenance.
Segment
A segment or bus segment is a closed part of a serial bus system. The bus line between two
termination resistors forms a segment. A segment contains 0 to 32 bus participants.
2012-10
28
Segment Checker
Glossary
Segment Protector
A segment protector distributes and prevents from communication break-downs caused by
short-circuits at any connected .
Spur
A spur is a branch line connecting a sub segment to the main segment of a fieldbus network.
Only one field device shall be connected to the end of the spur.
Surge Protector
A surge protector allows to incorporate protection concepts against power surges and lightning
strikes.
Terminator
A terminator is a resistor connecting conductor pairs at both ends of a wire medium segment to
prevent reflections from occurring at the ends of cables. Ideally it should be the wave
impedance of the wire medium.
Trunk
The trunk is the main communication line of a fieldbus network. From the trunk, the go off
which connect the field devices to the fieldbus.
2012-10
29
Segment Checker
FAQ
7 FAQ
I downloaded the Segment Checker software. How do I install it on my
computer?
Please read our installation instructions see chapter 3.
How do I get an instrument from the Device Tree into my project layout?
In order to build a network, simple drag and drop or double-click methods can be used to build
the structure. Simply drag the icon to the Segment Editor window and drop it. To add the next
element, just drag it close to the intended interconnecting element. The software will then make
the connection automatically with the same type of trunk cable that was defined earlier in the
basic parameter setup. Please be aware that you will need to connect elements when using the
double-click method see chapter 4.6.
2012-10
30
Segment Checker
FAQ
What is the difference in the Icon and Bitmap within the Device Editor?
The Icon is the image associated with the created instrument that will appear under your
Device Tree. The Bitmap is the image displayed in a project once it is connected to an interface
product.
What are the import and export functions within the Device Editor?
The import function allows you to incorporate instrument libraries of various field device
instruments. The export function allows you to save created field devices and share them with
other people, or transfer to another computer.