The document provides the guaranteed technical particulars for a 36kV circuit breaker manufactured by ABB India Ltd. Some key specifications include:
- Rated voltage of 33kV and maximum continuous service voltage of 36kV
- Short circuit breaking capacity of 25kA for 3 seconds and making capacity of 66kA
- Total break time and arcing time of 45+/-15ms and <15ms respectively
- One minute power frequency and impulse withstand test voltages of 70kV rms and 170kV peak respectively
- Three poles, one break per phase, with butt type main contacts and spring-spring operating mechanism
The document provides the guaranteed technical particulars for a 36kV circuit breaker manufactured by ABB India Ltd. Some key specifications include:
- Rated voltage of 33kV and maximum continuous service voltage of 36kV
- Short circuit breaking capacity of 25kA for 3 seconds and making capacity of 66kA
- Total break time and arcing time of 45+/-15ms and <15ms respectively
- One minute power frequency and impulse withstand test voltages of 70kV rms and 170kV peak respectively
- Three poles, one break per phase, with butt type main contacts and spring-spring operating mechanism
The document provides the guaranteed technical particulars for a 36kV circuit breaker manufactured by ABB India Ltd. Some key specifications include:
- Rated voltage of 33kV and maximum continuous service voltage of 36kV
- Short circuit breaking capacity of 25kA for 3 seconds and making capacity of 66kA
- Total break time and arcing time of 45+/-15ms and <15ms respectively
- One minute power frequency and impulse withstand test voltages of 70kV rms and 170kV peak respectively
- Three poles, one break per phase, with butt type main contacts and spring-spring operating mechanism
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 36 KV
CIRCUIT BREAKERS 1. Name of Manufacturer. M/s ABB India Ltd., Nashik 2. Manufacturer’s type designation. VBF 3. Rated Voltage. - 33 KV 4. Maximum (continuous) service rated Voltage 36 KV 5. Normal current rating. a) Under normal conditions. 1250A b) Under site conditions. 1250A
6. Short time current rating for seconds (rms) 25 KA for 3 Sec.
7. Maximum temperature rise over ambient. As per relevant IS/IEC 8. Breaking capacity. 25 KA for 3 Sec 9. Making capacity. 66 KA 10. Total break time in ms. a) at 10% rated interrupting capacity - 45+/- 15/-10ms (approx.) b) at rated interrupting capacity - 45+/- 15/-10ms (approx.) 11. Arcing time. - <15 ms (approx.) 12. Make time. - 65+/-15ms (approx.) 13. Minimum reclosing time at full rated - As per relevant IS/IEC Interrupting MVA from the instant of Trip coil energization. 14. Minimum dead time for 3 phase reclosing.- As per relevant IS/IEC 15. Whether restricting free. - Yes/No 16. One minute dry power frequency Withstanding test voltage (KV rms) Between line terminal and ground objects. - 70 KV rms. Between terminals with breaker contacts open. 70KV rms. 17. 1.2/50micros full wave impulse withstand test voltage for the two cases above. i) Between line terminal & grounded objects. - 170KV(Peak) ii) Between terminal with breaker Contacts open. 170KV(Peak) 18. Busing or Insulators : i) Type of bushing. Porcelain ii) Dry 1 minute power frequency 70KV rms withstand test voltage. iii) Dry flashover value. 70KV rms. iv) Wet flashover value. 70KV rms. V) 1.2/50 impulse withstand 170KV(Peak) vi) Creepage distance. 900 mm vii) Puncture value of bushing. As per relevant IS/IEC viii) Weight of bushing. As per manufactures standard 19. Minimum clearance in air. i) Between phases. As per GA drawing ii) Live parts to earth. As per GA drawing iii) Live parts to ground level As per GA drawing iv) Between live parts & grounded object. As per GA drawing 20. Number of poles of circuit breaker. Three 21. Number of breaks per phase. One 22. Total length of break per phase. 24 mm 23. Type of main contacts. Butt Type 24. Type of Aux. Contacts. As per manufacturers standard 25. Materials of auxiliary contacts. Copper 26. Contacts silver plated or not. No 27. Thickness of silver plating. N.A. 28. Contact pressure. 2700 N at no load (approx.) 29. Voltage distribution between breaker. As per relevant IS/IEC 30. Type of device if any, used to limit NA the rate of rise or restricting voltage. 31. Voltage grading device if any used. NA 32. Number of auxiliary contacts provided. i) Those closed when breaker is closed. 8 ii) These open when breaker is closed. 8 iii) Those adjustable with respect to NA the position of main contacts. 33. Type of operating mechanism. i) Opening Spring-Spring ii) Closing. Spring-Spring 34. Control circuit voltage. 110V DC 35. Power required for trip coil 250 Watts (approx.) As per Drawings approval. 36. Power required for close coil As per drawings approval - 250 Watts (approx.) 37. Frequency at which contacts are NA To be replaced. 38. Steel support structure galvanized - Yes Whether with foundation – Nuts & Bolts to be provided 39. Circuit Breaker weight. 450 Kg (approx)