SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 36 KV


CIRCUIT BREAKERS
1. Name of Manufacturer. M/s ABB India Ltd., Nashik
2. Manufacturer’s type designation. VBF
3. Rated Voltage. - 33 KV
4. Maximum (continuous) service rated Voltage 36 KV
5. Normal current rating.
a) Under normal conditions. 1250A
b) Under site conditions. 1250A

6. Short time current rating for seconds (rms) 25 KA for 3 Sec.


7. Maximum temperature rise over ambient. As per relevant IS/IEC
8. Breaking capacity. 25 KA for 3 Sec
9. Making capacity. 66 KA
10. Total break time in ms.
a) at 10% rated interrupting capacity - 45+/- 15/-10ms (approx.)
b) at rated interrupting capacity - 45+/- 15/-10ms (approx.)
11. Arcing time. - <15 ms (approx.)
12. Make time. - 65+/-15ms (approx.)
13. Minimum reclosing time at full rated - As per relevant IS/IEC
Interrupting MVA from the instant of Trip
coil energization.
14. Minimum dead time for 3 phase reclosing.- As per relevant IS/IEC
15. Whether restricting free. - Yes/No
16. One minute dry power frequency
Withstanding test voltage (KV rms)
Between line terminal and ground objects. - 70 KV rms.
Between terminals with breaker contacts open. 70KV rms.
17. 1.2/50micros full wave impulse withstand test
voltage for the two cases above.
i) Between line terminal & grounded objects. - 170KV(Peak)
ii) Between terminal with breaker Contacts open. 170KV(Peak)
18. Busing or Insulators :
i) Type of bushing. Porcelain
ii) Dry 1 minute power frequency 70KV rms
withstand test voltage.
iii) Dry flashover value. 70KV rms.
iv) Wet flashover value. 70KV rms.
V) 1.2/50 impulse withstand 170KV(Peak)
vi) Creepage distance. 900 mm
vii) Puncture value of bushing. As per relevant IS/IEC
viii) Weight of bushing. As per manufactures standard
19. Minimum clearance in air.
i) Between phases. As per GA drawing
ii) Live parts to earth. As per GA drawing
iii) Live parts to ground level As per GA drawing
iv) Between live parts & grounded object. As per GA drawing
20. Number of poles of circuit breaker. Three
21. Number of breaks per phase. One
22. Total length of break per phase. 24 mm
23. Type of main contacts. Butt Type
24. Type of Aux. Contacts. As per manufacturers standard
25. Materials of auxiliary contacts. Copper
26. Contacts silver plated or not. No
27. Thickness of silver plating. N.A.
28. Contact pressure. 2700 N at no load (approx.)
29. Voltage distribution between breaker. As per relevant IS/IEC
30. Type of device if any, used to limit NA
the rate of rise or restricting voltage.
31. Voltage grading device if any used. NA
32. Number of auxiliary contacts provided.
i) Those closed when breaker is closed. 8
ii) These open when breaker is closed. 8
iii) Those adjustable with respect to NA
the position of main contacts.
33. Type of operating mechanism.
i) Opening Spring-Spring
ii) Closing. Spring-Spring
34. Control circuit voltage. 110V DC
35. Power required for trip coil 250 Watts (approx.)
As per Drawings approval.
36. Power required for close coil
As per drawings approval - 250 Watts (approx.)
37. Frequency at which contacts are NA
To be replaced.
38. Steel support structure galvanized - Yes
Whether with foundation – Nuts & Bolts
to be provided
39. Circuit Breaker weight. 450 Kg (approx)