500MVA Utility

Ohmic Method:
Base MVA  500MVA
X=0.151 Utility contribution :
ohms
KV 2 13.82
X1    0.381 @ 13.8KV
5000KVA MVAb 500
13.8/2.4KV 13.8KV feeder : X 2  0.151
X=0.055
KV 2 2.4 2
Transformer : X 3  X pu   0.055   0.063
MVAb 500
KV 2 2.4 2
Motor : X 4  X pu   0.16   0.369
F
MVAb 2.5
X 1, 2  X 1  X 2  0.532 @13.8KV
2
 KVLV 
X1,2 @2.4KV side of the transformer  X HV    0.016
2500 KVA
 KV HV 
M X d''  0 .16
X F  X 1, 2  X 3  0.016  0.063  0.079 @2.4KV
KV 2 2.4 2
MVA F @2.4KV bus    72.5 without motor contribution
XF 0.079
XF  X4
X F M   0.0654
XF  X4
KV 2 2.4 2
MVA F M @2.4KV bus    88.13
X F  M 0.0654
MVA fault 88.13
I sc    21.22 KA
3  KV 3  2.4
Powerpoint Templates
Page 24
500MVA Utility
Per Unit Method:
Base MVA  500MVA
Utility contribution :
MVAb 500
X=0.151 ohms X1    1.0 pu
MVASC 500
MVAb 500
13.8KV feeder : X 2  Z f ( actual )   0 .151   0.396 pu
5000KVA
KV 2 13.82
13.8/2.4KV MVAb 500
Transformer : X 3  Z tr ( pu )   0.055   5.5 pu
X=0.055 MVAtr 5
MVAb 500
Motor : X 4  Z M ( pu )   0.16   32 pu
MVAtr 2 .5
X F  X 1  X 2  X 3  1.0  0.396  5.5  6.896 pu
MVAb 500
F MVA F @2.4KV bus    72.5 without motor contribution
XF 6.896
XF  X4
X F M   6.67 pu
XF  X4
MVAb 500
2500 KVA MVA F M @2.4KV bus    88.13
M X F  M 5.67
X d''  0.16
MVA fault 88.13
I sc    21.22 KA
3  KV 3  2.4
or
MVAb 500
Ib    120.42 KA
3  KV 3  2.4
1 pu 1120.42
Powerpoint
I sc  Templates
 Ib   21.22 KA
Z pu total 6.67 Page 25