Technical catalogue Low-voltage current-limiting

649294/011 en
moulded-case circuit-breakers
June '98
SACE Isomax S

Annex to SACE Isomax S technical catalogue 649240 690 V • 125-630 A • 200 kA (380/415 V)

ABB SACE L.V.


GENERAL INDEX

Presentation Main Characteristic Overall Ordering codes


SACE Isomax S current- characteristics curves dimensions and SACE Isomax S3X 48
limiting circuit-breakers: Electrical and general Current-limiting circuit diagrams SACE Isomax S4X 52
more solutions for every characteristics of SACE curves 24 SACE Isomax
possible need 2 Isomax S current- S3X-S4X 30 SACE Isomax S6X 54
limiting circuit-breakers Specific let-through
Efficiency and flexibility energy curves 26 SACE Isomax S6X 38 Accessories 56
in very application 4 in accordance with IEC
947-2 standard 6 Required distances 46
Overcurrent releases 8 Circuit diagrams 46
Versions and
connections 10
Accessories 14
Construction
characteristics 16
Conditions of use and
power loss values 18
Backup protection
(backup table) 20
CONTENTS

Presentation

on
ntati
e
Pres
]
[V~ Main characteristics

s
ristic
[m] , Ue
ude e [A]
Altit oltag
Iu
ce v

racte
e rvi urrent,
ed s pted
c
Rat rru

Cha
te
ed unin
Ra t

Characteristic curves

es
Curv
Overall dimensions
and circuit diagrams

ons
ensi
Dim

I u (4 e
c o d es
ol
3p
50 e d Ordering codes
11
PR2 79
467
2 82
S4X o c e s s o r - b a
s 467
80
I 467
00 783
rop
r In=1 LI 46
M i c se 781
I 46
a 60 84
rele P
In=1 467
es

WM LI
4 X 250 M P
I
S 50 W MP
Cod

2 50
S4 X W In=2 LI
250 P
S4X 50 W M
X 2 M P
S 4 W
4 X 250 M P
S
X 250 W
S4
tion
SACE Isomax S current-limiting circuit-breakers:
enta

more solutions for every possible need


Pres

SACE Isomax S3X, S4X and S6X The circuit-breakers comply with the IEC 947-2
current-limiting circuit-breakers standards and are available in three and four-pole
The SACE S3X - S4X - S6X models form a new range fixed, plug-in and withdrawable versions.
of current limiting circuit-breakers, developed within The function of a current-limiting circuit-breaker is to
the SACE Isomax S series of moulded-case circuit- the “limit” the specific let-through energy to a mini-
breakers. mum in the event of short-circuits, protecting the cir-
These units are characterised by a rated service cuits and equipment downstream.
voltage Ue of 690 V a.c., rated uninterrupted cur- The breaking system adopted, which features two
rents of 125 A to 630 A, service currents up to 630 A fixed contacts for each pole, makes it possible to
Three models of circuit- and a rated limit short-circuit breaking capacity of provide extremely fast breaking for very high short-
breakers conforming to 200 kA at 380/415 V a.c. and 75 kA at 690 V a.c. circuit currents.
the IEC 947- 2 international In addition, the special shape of the breaking com-
product standards
ponents makes it possible to limit the peak fault cur-
rent to values that are significantly lower than those
of the short-circuit current in the point of installation.
GSIL9101

2
enta
Pres
The high opening speed significantly reduces the that differ from those used for the corresponding au-
electrodynamic stresses to which the circuit-break- tomatic circuit-breakers and are listed in the chapter
ers downstream are exposed in the event of a fault. entitled “Ordering codes”.
Conversely, the fixed parts of plug-in and withdraw-
Integration with the SACE Isomax S able current-limiting circuit-breakers can be used
family both for the current-limiting circuit-breakers them-
This range of current-limiting circuit-breakers has selves and for the corresponding SACE S3 - S4 - S6
been conceived as a dedicated product for a spe- automatic circuit-breakers.
cific use while at the same time being integrated in The same applies to the accessories. The S3X, S4X
the general SACE Isomax S design. and S6X current-limiting circuit-breakers can use the
This brings the user significant benefits, enabling same accessories as the corresponding automatic
them to optimise stocks, standardise their support circuit-breakers, which naturally retain the same elec-
and installation structures and rationalise circuit- trical characteristics.
breaker selection thanks to a versatility that makes it The only exceptions are as follows:
possible to cover all their low-voltage application – the mechanical interlock plate for two vertically-
requirements. installed circuit-breakers
The new current-limiting circuit-breakers offer the – the bracket for mounting on a DIN channel.
same benefits of modular construction as the SACE The circuit diagrams for the SACE S3X, S4X and S6X
Isomax S series. circuit-breakers are the same as the corresponding
All the other versions can be created from the “ba- SACE S3, S4 and S6 automatic circuit-breakers.
sic” version using special conversion kits. The current-limiting circuit-breakers share the fol-
The conversion of the current-limiting circuit-breaker lowing characteristics with the automatic circuit- The increased contact
breakers: the same standardised depth of 103.5 mm, opening speed, dynamic
from a fixed part to a moving part for a plug-in or hiss action exerted by the
withdrawable circuit-breaker uses conversion kits the same standardised widths of 105 (S3X-S4X) / 210 magnetic field and the
(S6X) mm for the three-pole versions and 140 (S3X- structure of the arcing
S4X) / 280 (S6X) mm for the four-pole versions, the chamber contribute to
extinguishing the arc in
same mounting holes for the plug-in and withdraw- the shortest possible time,
able versions and the same mounting holes on the limiting the specific let-
compartment door for all versions and all accesso- through energy I2t and the
current peak
ries.

Short-
circuit
current

ited
Lim gh
throu
let- t ctiv
e
n
curr
e spe it
Pro -circu
ho rt
s t
ren
ISIS0001

cur

3
tion
Efficiency and flexibility in every application
enta
Pres

Applications
These current-limiting circuit-breakers are suitable
for installation in all types of civil, industrial and serv-
ice sector installations, as well as for electrical in-
stallations on board ships, in mines or on oil rigs, as
well as, generally speaking, in any installations where
high power generators and transformers make it pos-
sible for very high short-circuit currents of up to 200kA
at 380/415 V~, 180 kA at 440 V~ and 75 kA at 690 V~
to occur.

The circuit-breakers can be positioned downstream


of the power supply either to provide general protec-
tion (installations, multi-user systems and electrical
lines) or for protecting electrical equipment (motors,
generators, transformers and capacitors).
They can also be fitted in systems where back-up
protection is required that allows the use of circuit-
GSIL9103

breakers downstream which have a lower breaking


capacity than the prospective short-circuit current in
The construction characteristics of these circuit-breakers the point of installation.
enable them to offer outstanding reliability, an essential
requisite to guarantee continuity of service under even The breaking capacities of the SACE Isomax S cur-
the most severe installation conditions. rent-limiting circuit-breakers are higher than the best
values achieved by other units of this type.
GSIL9104

GSIL9105

LN 160 S3X 200

SACE Limitor SACE Isomax S

LN 100 / LN 125 S3X 125

LN 160 / LN 200 S3X 200

LN 320 (setting 250 A) S4X 250

LN 320 S6X 400

LN 500 / LN 630 S6X 630

The electrical characteristics of SACE Isomax S


current-limiting circuit-breakers make it
possible to establish equivalents and
comparisons with the circuit-breakers in the old
GSIL9102

SACE Limitor series to determine replacements


for the latter when upgrading an installation.

4
CONTENTS

racte
Main characteristics

Cha
Electrical and general characteristics of
SACE Isomax S - IEC 947-2 current-limiting circuit-breakers 6

Overcurrent releases 8

Versions and connections 10

Accessories 14

Construction characteristics 16

Conditions of use and power loss values 18

Backup protection 20

5
s
ristic
SACE Isomax S - IEC 947-2
racte

current-limiting circuit-breakers
Cha

Rated uninterrupted current, Iu [A]

Number of poles No.

Rated service voltage, Ue (a.c.) 50-60 Hz [V~]

Rated impulse withstand voltage, Uimp [kV]

Rated insulation voltage, Ui [V]

Test voltage at industrial frequency for 1 minute [V]

Rated limit short-circuit breaking capacity, Icu

(a.c.) 50-60 Hz 220/230 V~ [kA]

(a.c.) 50-60 Hz 380/415 V~ [kA]

(a.c.) 50-60 Hz 440 V~ [kA]

(a.c.) 50-60 Hz 500 V~ [kA]

(a.c.) 50-60 Hz 690 V~ [kA]

Rated duty short-circuit breaking capacity, Ics (1) %Icu

Rated short-circuit making capacity (415 V~), Icm [kA]

Tripping time (440 V~ / 180 kA) [ms]

Use category (EN 60947-2)

Isolation behaviour

IEC 947-2, EN 60947-2

Releases thermomagnetic M fixed 10 lth, T adjustable (0.7 ... 1Ith)

magnetic only (3) M only, adjustable (4 ... 12 Ith)

microprocessor-based PR211/P (I - LI)

PR212/P (LSI - LSIG)

PR212/MP (LRIU)(3)(4)

Interchangeability

Terminals (5) F - fixed

P - plug-in

W - withdrawable (6)

Mechanical life No. operations / Operations per hour No.

Electrical life (415 V~) No. operations / Operations per hour No.

Basic dimensions F - fixed Width (3 / 4 poles) [mm]

Depth [mm]

Height [mm]

Weights F - fixed 3 / 4 poles [kg]

P - plug-in 3 / 4 poles [kg]

W - withdrawable 3 / 4 poles [kg]

Notes
1) The value of Ics is 25% lower at 500/690 V (excluding S3X with setting R 32).
2) For S3X with setting R 32, Icu (690 V~) = 50 kA and Ics = 100%Icu.
3) For three-pole circuit-breakers only.
4) Please ask for the related technical catalogue if you require further information on the motor-protection
circuit-breakers with PR212/MP releases.

6
racte
Cha
CSIL9106

CSIL9107

CSIL9108
S3X S4X S6X
125 - 200 250 400 - 630
3-4 3-4 3-4
690 690 690
8 8 8
800 800 800
3000 3000 3000

300 300 300


200 200 200
180 180 180
150 150 150
75 (2) 75 75
100% 100% 100%
440 440 440
3.5 3.5 3.5
A A A

— —
— —



yes yes yes
F - EF - ES - FC Cu - FC CuAl - R - RC F - EF - ES - FC Cu - FC CuAl - R - RC F - EF - FC CuAl - R - RC

EF - R EF - R —
EF - R EF - R EF - HR - VR
25000 / 120 20000 / 120 20000 / 120
10000(125A) - 8000(200A) / 120 8000 / 120 7000 / 60
105 / 140 105 / 140 210 / 280
103.5 103.5 103.5
255 339 406
3.6 / 4.8 5/7 15 / 20
6.3 / 8.7 8.2 / 10.7 –
7.1 /9.5 9 / 11.5 25.4 / 33.8

5) Please see pages 10-11 if you require further information on the types of terminals.
6) Withdrawable circuit-breakers must be fitted with the front flange for the operating lever mechanism or
the accessories which are an alternative to it such as the rotary handle operating mechanism or motor
operator.

7
s
ristic
Thermomagnetic or magnetic only
racte

overcurrent releases
Cha

The characteristics of the thermomagnetic, magnetic Ith - rated current of the thermomagnetic release at
only and microprocessor-based electronic overcur- a room temperature of 40°C
GSIL9109

rent releases are the same as those described in the Im - magnetic trip current
technical catalogue for the SACE Isomax S circuit- In - rated current of the electronic release
SACE S3X circuit-breaker breakers (code number 649240).
with thermomagnetic The tables below show the values for the following
overcurrent release parameters for the different types of releases:

Thermomagnetic overcurrent releases


Circuit-breaker Phases L1 - L2 - L3 Neutral

S3X 125 S3X 200 Setting Thermal adjustment [A] Magnetic tripping [A] Setting
[A] 0.7 ... 1 x Ith Im = 10 x Ith - min. 500 A [A]

R 32 19 ... 32 500 R 32

R 50 30 ... 50 500 R 50

R 80 48 ... 80 800 R 80

R 100 70 ... 100 1000 R 100

R 125 87.5 ... 125 1250 R 80

R 160 112 ... 160 1600 R 100

R 200 140 ... 200 2000 R 125

Magnetic only overcurrent releases (for three-pole circuit-breakers only)


Circuit-breaker Phases L1 - L2 - L3

S3X 125 S3X 200 Setting Magnetic adjustment [A]


[A] Im = 4 ... 12 x Ith

R3 12 ... 36

R5 20 ... 60

R 10 40 ... 120

R 25 100 ... 300

R 50 200 ... 600

R 100 400 ... 1200

R 125 500 ... 1500

R 160 640 ... 1920

R 200 800 ... 2400

8
Microprocessor-based electronic

racte
overcurrent releases

Cha
SACE PR211/P - PR212/P microprocessor-based electronic overcurrent releases
Circuit-breaker Rated current Phases L1 - L2 - L3 Neutral (1)
S4X 250 S6X 400 S6X 630 of release L S I G
In [A] I1 [A] I2 [A] I3 [A] I4 [A] [A]

100 40 ... 100 100 ... 1000 150 ... 1200 20 ... 100 20 ... 50

160 64 ... 160 160 ... 1600 240 ... 1920 32 ... 160 32 ... 80

250 100 ... 250 250 ... 2500 375 ... 3000 50 ... 250 50 ... 125

320 128 ... 320 320 ... 3200 480 ... 3840 64 ... 320 64 ... 160

400 160 ... 400 400 ... 4000 600 ... 4800 80 ... 400 80 ... 200

630 252 ... 630 630 ... 6300 945 ... 7560 126 ... 630 126 ... 315

L = Overload protection function with related setting current (I1 = 0.4-0.5-0.6-0.7-0.8-0.9-0.95-1 x In)
S = Short-circuit protection function with time-delay trip and related setting current (I2 = 1-2-3-4-6-8-10 x In - t2 = 0.05 ... 0.5 s)
I = Short-circuit protection function with instantaneous trip and related setting current (I3 = 1.5-2-4-6-8-10-12 x In)
G = Earth fault protection function with time-delay trip and related setting current (I4 = 0.2-0.3-0.4-0.6-0.8-0.9-1 x In - t4 = 0.1 ... 0.8 s)
(1) Available upon request: neutral protection to 100% of phase L protection (ordering code 1SDA0 37505 R1).

SACE PR212/MP (2) microprocessor-based electronic motor-protection


overcurrent releases (for three-pole circuit-breakers only)
Circuit-breaker Rated current Phases L1 - L2 - L3

GSIL9110
S4X 250 S6X 400 S6X 630 of release L R I U
In [A] I1 [A] I5 [A] I3 [A] Iu [A]

100 50 ... 100 600 ... 1300


SACE S4X, S6X circuit-
160 80 ... 160 960 ... 2080 breakers with SACE
PR211/P, PR212/P or
SACE PR212/MP
200 100 ... 200 1200 ... 2600 microprocessor-based
3 ... 10 x I1 0,4 x I1 overcurrent releases
320 160 ... 320 1920 ... 4160

400 200 ... 400 2400 ... 5200

630 315 ... 630 3780 ... 8190

L = Overload protection function with related setting current (I1 = 0.5-0.6-0.7-0.8-0.85-0.9-0.95-1 x In)
R = Motor lock protection function with related setting current (I5 = 3-4-5-6-7-8-10 x I1 - t5 = 1-4-7-10 s)
I = Short-circuit protection with related setting current (I3 = 6-7-8-9-10-11-12-13 x In)
U = Phase failure or unbalance protection function with related setting current (Iu = 0.4 x I1 - t = 4 s)
(2) Please ask for the related technical catalogue if you require further information on the motor-protection circuit-breakers with SACE
PR212/MP releases.

9
s
ristic
Versions and connections
racte
Cha

SACE S3X, S4X and S6X current-limiting circuit-break- These terminal covers form part of the circuit-break-
ers are available in three-pole and four-pole fixed er’s standard equipment.
(F), plug-in (P) and withdrawable (W) versions. It In particular, low terminal covers are always required
should be noted that the fixed parts in the plug-in and for:
withdrawable versions are the same as the corre- – the fixed parts of plug-in or withdrawable circuit-
sponding S3, S4 and S6 automatic circuit-breakers. breakers
In addition, as with the latter, the withdrawable cir- – fixed circuit-breakers with threaded rear terminals
cuit-breakers are always fitted with the front flange or spreaded extended front terminals,
for locks with a lever operating mechanism or, alter- and high terminal covers for:
natively, with a rotary handle operating mechanism – fixed circuit-breakers with rear terminals for Cu/Al
or motor operator. cables.
The current-limiting circuit-breakers are character- The table below shows the basic version (fixed cir-
ised by a varied range of terminals that enable the cuit-breaker with front terminals) and the various types
circuit-breaker to be connected to the installation in of terminals available with their related terminal cov-
the manner best suited to the installation require- ers.
ments. If the terminal covers are not specified they must be
For some versions and type of terminals the supply ordered separately.
foresees the fitting of terminal covers (high or low).

F EF ES FC Cu

front (1) extended spreaded front


front (2) extended for Cu cables
front (4)

fixed (F) LTC

SACE S3X plug-in (P) LTC

withdrawable (W) LTC

fixed (F) LTC

SACE S4X plug-in (P) LTC

withdrawable (W) LTC

fixed (F)
SACE S6X
withdrawable (W) (3)LTC
HTC = high terminal covers, LTC = low terminal covers
(1) Basic version of the fixed circuit-breaker
(2) Basic version of fixed part for plug-in or withdrawable circuit-breakers

10
racte
Cha
GSIL9111

GSIL9112

GSIL9113
F P W
FIXED PLUG-IN WITHDRAWABLE

SACE S3X
SACE S4X
SACE S6X —

FC CuAI R RC HR VR

front threaded rear horizontal flat bar vertical flat bar


for Cu/Al cables rear for Cu/Al cables rear rear

LTC HTC

LTC

LTC

LTC HTC

LTC

LTC

LTC HTC

LTC LTC
3
( ) The extended front terminals can only be fitted on the bottom of the fixed part of the withdrawable S6X circuit-breaker.
(4) The terminal covers supplied for fixed S3X and S4X circuit-breakers with spreaded extended front terminals are always
supplied complete with separating partitions between the phases.

11
s
ristic
Versions and connections
racte
Cha

The different types of terminals, which can be com- nals for connecting bare wires directly. The informa-
bined in different ways with one another (top of one tion required to make the connections is summa-
type, bottom of another), enable one to connect the rised for each type of terminal. Different flat bar di-
circuit-breaker to the installation in the most suitable mensions and compositions are recommended for
way to meet the installation’s requirements. busbar connections. The minimum depth required
We can distinguish between: of flat bars with different compositions from those rec-
– front terminals that allow one to connect cables ommended are also specified. For bare cable con-
or busbars, working directly from the front of the nections, the minimum and maximum cable cross-
circuit-breaker. section areas that can be clamped in the terminals
– rear terminals which enable the circuit-breakers are shown together with the terminal diameter.
to be installed in switchboards with rear access to The tightening torque values for the screws on cable
either cable or busbar connections. terminals and the screws for connecting busbars to
Terminals are available for connecting busbars or flat bar terminals are also shown.
cables terminated with cable terminals, as are termi-

S3X-S4X S6X S3X-S4X S6X S3X-S4X

Front terminals, extended front terminals and spreaded


front terminals
Enable busbars or cables terminated with cable terminals to be connected.

versions flat bar tightening


pieces width [mm] thickness [mm] Ø [Nm]
S3X 125 F-P-W 1 20 6 M8 9
S3X 200 F-P-W 1 20 6 M8 9
S4X 250 F-P-W 1 20 6 M8 9
S6X 400 F-W 2 40 5 (minimum) M10 9
S3X-S4X (fixed part) S6X (fixed part)
S6X 630 F-W 2 40 5 (minimum) M10 9

Front terminals for copper cables


Enable bare copper cables to be connected directly to the circuit-breaker.
versions cross-section area of cable terminal Ø tightening
cables [mm 2] [mm] [Nm]
S3X 125 F 1 6 ... 185 18 16
S3X 200 F 1 6 ... 185 18 16
S4X 250 F 1 6 ... 185 18 16
S3X-S4X

12
racte
Cha
Front terminals for copper or aluminium cables
Enable copper or aluminium cables to be connected directly to the circuit-breaker.
versions cross-section area of cable terminal Ø tightening
cables [mm2] [mm] [Nm]
S3X 125 F 1 35 ... 95 13.5 13.5
S3X 200 F 1 25 ... 150 17 31
S4X 250 F 1 25 ... 150 17 31
S6X 400 F 2 120 ... 240 21.5 31 S3X-S4X S6X
S6X 630 F 2 120 ... 240 21.5 31

Rear terminals for copper or aluminium cables


Enable copper or aluminium cables to be connected directly to the circuit-breaker.
versions cross-section area of cable terminal Ø tightening
cables min÷max [mm2] [mm] [Nm]
S3X 125 F 1 50 ... 120 16 31
S3 X200 F 1 50 ... 120 16 31
S4X 250 F 1 50 ... 120 16 31
S6X 400 F 2 50 ... 150 21 31
S3X-S4X S6X
S6X 630 F 2 50 ... 150 21 31

Threaded rear terminals


Enable busbars to be connected from behind.
versions length studs thread max flat bar cross-section area tightening
[mm] [mm] width [mm] thickness [mm] A [Nm] B [Nm]
S3X 125 F 55 100 M12 20 6 10 20
P-W 48 100 M12 20 6 10 20
S3X 200 F 55 100 M12 20 6 10 20
S3X-S4X
P-W 48 100 M12 20 6 10 20
S4X 250 F 55 100 M12 20 6 10 20 A S3X-S4X (fixed part)
P-W 48 100 M12 20 6 10 20 B
S6X 400 F 68 68 M24 x 2 40 2x5 60 120
S6X 630 F 68 68 M24 x 2 40 2x5 60 120

S6X

Horizontal and vertical flat bar rear terminals


flat bar tightening
versions pieces width [mm] thickness [mm] Ø [Nm]
S6X 400 W 2 40 5 M12 30
S6X 630 W 2 40 5 M12 30

S6X (fixed part)

13
s
ristic
Accessories
racte
Cha

The SACE Isomax S3X - S4X - S6X current-limiting


circuit-breakers can be fitted with all the accesso-
ries available for the corresponding SACE Isomax
S3 - S4 - S6 circuit-breakers described in the related
technical catalogue (code 649240). The only excep-
tions are the mechanical interlock plate for two verti-
cally-installed circuit-breakers and the bracket for
mounting on a DIN rail.
GSSC0402

14
15
Cha
racte
s
ristic
Construction characteristics
racte
Cha

SACE S3X, S4X and S6X current-limiting circuit-break-


ers offer the highest standards of safety and operat-
ing reliability. Thanks to ABB SACE’s extensive expe-
rience in the field of L.V. moulded-case circuit-break-
ers and the tried and tested characteristics of the
SACE Isomax S series from which the current-limit-
ing circuit-breakers have been developed.
The main construction characteristics of the current-
limiting circuit-breakers are listed below.

GSIL9114
CSIS9027

Easy to inspect, simply requiring one to remove the


cover with the circuit-breaker out of service, reduc-
ing operating times and installation down times.
Double insulation with total segregation of the power
circuits and auxiliary circuits.
GSIL9115

CSIS9031

Microprocessor-based electronic releases (for types Circuit-breaker can be racked in and out with the
S4X and S6X) that meet the European Directives on compartment door closed, offering maximum opera-
electromagnetic compatibility (EMC). tor safety and the possibility of building internal-arc-
proof switchboards.

16
racte
Cha
CSIL9116

CSIL9117

Conces. S.M.A. N° 12/137 P.H. EDY COLOR Monfalcone

Isolation behaviour. In the open position, the circuit- Vibration resistance and possibility of using the cir-
breaker guarantees isolation of the circuit in compli- cuit-breaker for naval and aseismatic installations.
ance with IEC Standard 947-2.
The insulation distances are ample, ensuring there The rated characteristics of the circuit-breaker re-
are no leakage currents and guaranteeing the di- main unchanged irrespective of its installation posi-
electric strength against any overvoltages across the tion.
input and output.
CSIL9118

CSIS9112

A fibreglass-reinforced synthetic resin moulded in- Protection grade IP20 for all versions (excluding the
sulating case, corrosion-proofed main metal com- terminals) and IP30 for the front parts of circuit-break-
ponents and appropriate galvanising enable use in ers installed in switchboards.
damp - saline climates. Possibility of achieving protection grade IP54 for cir-
cuit-breakers installed in switchboards with compart-
ment door-mounted crank handle operating mecha-
nisms by using special seals available to order.

17
s
ristic
Conditions of use and power loss values
racte
Cha

Operating temperature
CSIL9119

SACE Isomax S3X - S4X - S6X current-limiting circuit- with changes in temperature. But one does need to
breakers can be used in ambient conditions in which reduce the maximum overload protection setting (L)
the temperature of the surrounding atmosphere is to take into account the phenomena that occur in the
between -25 °C and +70 °C. copper parts of the circuit breakers through which
Circuit-breakers fitted with a thermomagnetic over- the phase current passes (moving contacts, fixed
current release have the thermal element set for a contacts and connection terminals) and which lead
reference temperature of +40 °C. to a fall in the rated uninterrupted current.
The thermal tripping threshold for a given setting falls Circuit-breaker performance is not guaranteed for
at temperatures between +40 °C and +70 °C due to temperatures above +70 °C.
the behaviour of the release’s bimetal strip in relation In order to ensure continuity of operation for an in-
to temperature. stallation, one needs to carefully evaluate how to
Conversely, one needs to take an increase in the keep the temperature within acceptable levels for
thermal tripping threshold into account for tempera- the operation of all the various devices concerned
tures below +40 °C (see table). and not just the circuit breakers by, for example, us-
The microprocessor-based electronic overcurrent re- ing forced ventilation in the switchboards and in the
leases do not undergo any changes in performance rooms where they are installed.

Temperature performance of S3X circuit-breaker

R [A] 10 °C 20 °C 30 °C 40 °C 50 °C 60 °C 70 °C
R 32 26 … 43 24 … 39 22 … 36 19 … 32 16 … 27 14 … 24 11 … 21
R 50 37 … 62 35 … 58 33 … 54 30 … 50 27 … 46 25 … 42 22 … 39
R 80 59 … 98 55 … 92 52 … 86 48 … 80 44 … 74 40 … 66 32 … 58
R 100 83 … 118 80 … 113 74 … 106 70 … 100 66 … 95 59 … 85 49 … 75
R 125 103 … 145 100 … 140 94 … 134 88 … 125 80 … 115 73 … 105 63 … 95
R 160 130 … 185 124 … 176 118 … 168 112 … 160 106 … 150 100 … 140 90 … 130
R 200 162 … 230 155 … 220 147 … 210 140 … 200 133 … 190 122 … 175 107 … 160

18
racte
Cha
Altitude

SACE S3X - S4X - S6X circuit-breakers do not undergo any change in their rated
performance up to a height of 2000 m.
As the height increases, changes occur in the properties of the atmosphere
regarding its composition, dielectric capacity, cooling power and pressure.
The performance of the circuit-breakers therefore undergoes derating that can
essentially be measured in terms of the changes in the main parameters such as
the maximum rated operating voltage and rated uninterrupted current.

Altitude [m] 2000 3000 4000

Rated service voltage, Ue [V~] 690 600 500

Rated uninterrupted current, Iu %Iu 100% 95% 90%


CSIL9120

Power loss and voltage drop values

Circuit-breaker Setting Current Power Voltage drop


loss per pole
[A] [W] [mV]

SACE S3X
with thermomagnetic R 125 125 30.8 82
release R 200 200 48 80

SACE S4X
with PR211/LI R 250 250 60 80
electronic release

SACE S6X
with PR211/LI R 400 400 80.4 67
electronic release R 630 630 126.6 67

Note
The values indicated in the table refer to balanced loads, with a current flow equal to the Iu and to both three-pole and
four-pole fixed version apparatus. For the latter, the current of the neutral is nil by definition.

19
s
ristic
Backup protection
racte

(backup table at Ue = 400 V~) Backup protection is required by CEI EN Standards


Cha

60947-2, Annex A. Coordination can be used when


there are no selectivity requirements, enabling sav-
ings to be made (above all by using current-limiting
circuit-breakers upstream) with sizing the circuit-
breakers downstream.

CIRCUIT-BREAKER UPSTREAM
S270 S280/20 S280/25 S290 S500 LNA S1B S2B S1N S2N S3N S4N S5N S6N S2S S6S
In [A] < 32/63/100 125 160 125 160 250 250 630 800 160 800
Icu [kA] 15 20 25 15 50 50 16 16 25 35 35 35 35 35 50 50

CIRCUIT-BREAKER DOWNSTREAM
10 S240 S240 S240 S240 S240
S240 S240
15
S250 S250
16 S250 S250 S250 S250
S240 S250 S250 S270 S1B S1B S250 S1B
20 S250 S2B S2B S2B
S270
S240 S270 S270 S270 S280/20 S270
S250 S280/20 S280/20 S1B
25
S270 S280/25 S2B
S1B
S240 S240 S280/20 S280/25 S280/25 S280/20
30
S280/25 S1B S1N S1N S1N S280/25
S1B S1N
35
S1N S2B
S2B
S250 S250 S1N

40

S270 S270 S1B S2N


S280/20 S280/20 S1N S3N
50 S280/25 S280/25 S2B S4N
S1B S1B S2N S5N
S1N S1N

65

85

100

130

150
170

200

20
racte
The table below shows the backup protection avail- In the interest of facilitating clear representation, the latter
must be read using the follow key:

Cha
able, with the related breaking capacities for the rated
voltage Ue=400 V~, between ABB moulded-case and S250:: S250, S260, S270K
S270:: S270 (B-C-D), S280 (In = 3 ... 8 A),
air low voltage circuit-breakers (SACE Isomax S, S280 (In = 50 ... 63 A), S290
SACE Limitor LNA and SACE Emax) and pro M sys- S280/20:: S280 (In = 32 ... 40 A)
tem modular circuit-breakers. S280/25:: S280 (In = 10... 25 A)

S7S S3H S4H S5H S6H S7H S3L S4L S5L S6L S7L S3X S3X S4X S6X E2L E3L
1600 250 250 630 800 1600 250 250 630 800 1600 125 200 250 630 1600 2500
50 65 65 65 65 65 85 100 100 100 100 200 200 200 200 130 130

S240

S250 S250 S250 S250


S270 S1B S1B S270 S1B S1B S250 S250 S250 S1B
S2B S2B S2B S2B S2B

S270 S280/20 S270 S280/20 S270 S270 S270


S280/20 S280/20 S280/20 S280/20

S280/25 S280/25 S280/25 S280/25 S280/20 S280/25


S1B
S2B S280/25 S280/25

S3N S1B S1N S1N S3N S1B S1N S1N S3N S5N S6N
S4N S2B S4N S2B S4N
S5N S5N S5N
S6N S6N
S1N S2B S6N S1N S6N
S1B

S1N S2N S2N S2N S2N S2N S1B S6S


S2N S2S S2S S2S S3N S3N S2B
S2S S3N S3N S3N S4N S4N
S3N S4N S4N
S5N
S1N S1N S5N S5H S1B
S2N S6S
S2S S6H
S3N
S3H
S2N S2S S2S S2B S2N S5H S6H
S2S S3H S3H S3N S6S S7S
S3N S3L S3L S4N S6H S7H
S3H S4H S4H S7S
S3L S5H S7H
S1B S1N S2S S5L S6L
S2B S6L S7L
S7L
S1N
S1N S5N
S500 S500 LNA S3H
LNA LNA S2N S3L
S2N S2N S2S S4H
S2S S2S S3N S4L
S3N S3H S5H
S3H S3L S5L
S3L S6S
S6H
S6L

21
Cha
racte
ristic

22
s
CONTENTS

es
Curv
Characteristic curves

Current-limiting curves 24

Specific let-through energy curves 26

Note
For the time-current curves of SACE S3X - S4X - S6X in the technical catalogue for SACE Isomax S circuit-
current-limiting circuit-breakers please see the breakers (code number 649240).
information for the corresponding S3 - S4 - S6 types

23
Current-limiting curves
es
Curv

The current-limiting and specific let-through energy – the peak value Ip [kA] of the limited current in
curves are shown below. relation to the prospective symmetrical short-cir-
The characteristic of an automatic current-limiting cuit current Is
circuit-breaker is represented by two distinct curves – the value of the specific let-through energy I2t [A2s]
that indicate the following respectively: let through by the circuit-breaker in relation to the
uninterrupted symmetrical short-circuit current

Current-limiting curves at 440 V~ for SACE Isomax S3X-S4X-S6X circuit-breakers

Ip [ kA]

Prospective
peak
current

100

S6X

S4X
S3X R160, R200
S3X R80, R100, R125

S3X R50
S3X R32

10

1
1 10 100 Is [ kA]
CSIL8003

24
es
Curv
Current-limiting curves at 690 V~ for SACE Isomax S3X-S4X-S6X circuit-breakers

Ip [ kA]

Prospective
peak
current

100

S6X

S4X
S3X R160, R200
S3X R80, R100, R125
S3X R50
S3X R32

10

1
1 10 100 Is [ kA]
CSIL8004

25
Specific let-through energy curves
es
Curv

Specific let-through energy curves at 440 V~ for SACE Isomax S3X-S4X-S6X circuit-breakers

I2t [A2s]

S6X

10 7

S4X

S3X R160, R200

S3X R80, R100, R125

10 6 S3X R50

S3X R32

10 5
1 10 100 Is [ kA]
CSIL8001

26
es
Curv
Specific let-through energy curves at 690 V~ for SACE Isomax S3X-S4X-S6X circuit-breakers

I2t [A2s]

S6X

10 7

S4X

S3X R160, R200

S3X R80, R100, R125

S3X R50

S3X R32

10 6

10 5
1 10 100 Is [ kA]
CSIL8002

27
Curv
es

28
CONTENTS

o
ensi
Overall dimensions and circuit diagrams

Dim
SACE Isomax S3X - S4X 30

SACE Isomax S6X 38

Required distances 46

Note
The information provided in the technical catalogue S6X current-limiting circuit-breakers and the circuit
for SACE Isomax S circuit-breakers (code number diagrams for connecting the releases and
649240) also applies for the circuit and power accessories.
diagrams for the corresponding SACE S3X - S4X -

29
ons
Overall dimensions
ensi

SACE S3X - S4X


Dim

Fixed circuit-breaker
Y
117 Mounting on sheet metal Terminal covers
B (4 POL)
135 (to order when not included in the supply)
= A = (3 POL)
≥3 101.5 2.5
Z
25
V 4 H
46
F

1
D

G
C =
I on I o I o
X 161 105 X
O off = O ff O ff

1 H
Low High

4
E E E 5
105 103.5
107 2
Y Spreaded extended front
Terminals Front for flat bars Front for cables Y
140
Y
5 min. 25 M 101,5
105 45 45 45
H
30 ø8.5

12.5
M8 3 3 5 45 5
155

155
55.5

56.5
ø 8.5

60
4

2 2
I I 52.5

5 J J G
1 1
=

20
161

161

X X X X
=

1 Flange for compartment door included in the supply


60

K K
155

2 Low terminal covers included in the supply


155

12.5

50 50 30
3 Separator plates between the phases 117 105
= 117 =
4 Tightening torque 2 Nm 130 = =
165
Y 65
5 High terminal covers included in supply
101,5
Y

3 6 Threaded rear View A


5
O N P 25 12.5 25
13.5
L A
46 33.5 S
2
E E E
U
R
D Q
I I I

I on
X X
CSIL0100

O off
T
For rear Cu/Al cables Front extended

A B C D E F G H I J K L M N O P Q R S T U V Z

S3X 105 140 255 172.25 35 ø8 228 10 158.75 260 56.5 ø16 18x18 20 ø8.5 83 81.5 36.5 55 100 M12 24 17.5

S4X 105 140 339 210.25 35 ø8 307.5 11 196.75 344 52 ø16 18x18 20 ø8.5 83 81.5 36.5 55 100 M12 24 17.5

30
o
ensi
Dim
Mounting parts for fixed circuit-breaker

Template for drilling sheet metal


(minimum thickness of sheet metal: 3 mm)

For terminals: For terminals for rear Cu/Al For rear threaded terminals
Front for flat bars, cables
Extended front,
Front for cables,
Spreaded extended front
Y Y
Y
Y A A A
A (3 POL) A A
A (3 POL) B (4 POL)
M M M5/ø5.5
B (4 POL) E

D L L D
F D
D

X C X X C G X X N C A X X N C X
E
M5/ø5.5 H

E A
(3 POL) M5/ø5.5 (4 POL)
B (3 POL) B
Y I (4 POL) Y
Y
Y

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)
Y
112
= =
80
= =

= =

X 112 142 X
=
=

ø7

Y
CSIL0101

A B C D E F G H I L M N

S3X 35 70 224 156.75 17.5 179.75 270 R15 105 158.5 ø24 228

S4X 35 70 303,5 194.75 17.5 218 350 R15 105 196.75 ø24 307.5

31
ons
Overall dimensions
ensi

SACE S3X - S4X


Dim

Plug-in circuit-breaker - withdrawable circuit-breaker

Plug-in Withdrawable
Y Y
≥3
117 B (4 POL)
27.5 Isolating distance
B (4 POL)
≥3 A (3 POL)
A (3 POL) 2 = =
= = 3
2
4

3 1
1
D 3 D
C G = C G
5 = = 5
I o
X 105 161 X
X 161 105 X
ø5.5 1.75
O off = =
=

5 5

167
E E E E E E
153 2 F
F 190
2
156.5 H
Y
195.5 74 96
184.5
Y

1 Fixed part

2 Moving part complete with IP20 protection class terminal covers


3 Flange for compartment door included in supply
4 Lock for compartment door (available upon request)
5 Tightening torque 1,1 Nm

Plug-in - withdrawable terminals

Front for flat bars (up to 400 A) Threaded rear

I M A
P
L

N
View A
Q
31

Note
The withdrawable circuit-breaker must be completed with
one of the following accessories:
- front flange for lever operating mechanism 83
- rotary handle operating mechanism S
- motor operator
CSIL0102

A B C D E F G H I L M N O P Q R S

S3X 105 140 260 174.5 35 52.5 228 84 10 17.5 ø8.2 20 5 16 48 M12 100

S4X 105 140 344 212.75 35 52.5 307.5 84 10 13 ø8.2 20 5 20.5 48 M12 100

32
o
ensi
Dim
Mounting parts for plug-in circuit-breaker - withdrawable circuit-breaker

Template for drilling sheet metal support


(minimum thickness of sheet metal: 3 mm)

For extended front For rear threaded


terminals terminals

Y
A (3 POL)
Y B (4 POL)

A (3 POL)

B (4 POL)
F

G
D
D

X C C H X

F E

N I
E

Y L (3 POL)

M (4 POL)

Template for drilling compartment door and fitting flange


(thickness of sheet metal: 2 mm)
ø4

80°

Y
Y
112 135
= =
80 63
= = 45 Nr. 5 ø7

= = 72.5 94 =
=
X 112 142 X X 126 142 X
27.5
= = 16 =
=

81
ø7 125
R min. 200
Y
Y

For plug-in circuit-breaker For withdrawable circuit-breaker


CSIL0103

A B C D E F G H I L M N

S3X 70 105 100 52.25 25 M4-ø5 73.75 143 35 70 105 R14

S4X 82 117 135 65.75 41 M4-ø5 107.25 218 35 70 105 R14

33
ons
Overall dimensions
ensi

SACE S3X - S4X


Dim

Accessories

Motor operator for fixed circuit-breaker


Y
2 A
220
= B = 1 Flange for compartment door included
C in supply
Y 2 Dimensions with connectors
1 112 3
= =
80 3 Drilling of compartment door
= =
2 Note
=
= = See the different versions for the
X 161 112 142 X circuit-breaker mounting holes
=
= =

A B C
ø7
= =
Y
225.5
103.5 117
S3X-S4X 140 105 58
Y

Motor operator for plug-in circuit-breaker


Isolating distance Y
27.5
A
2 B
269.5 = = 1 Flange for compartment door included
C in supply
Y 2 Dimensions with connectors
112 3
1 = =
80 3 Drilling of compartment door
= =
2 Note
=
= = = See the different versions for the
X 105 161 112 142 X circuit-breaker mounting holes
= =
= =

A B C
ø7
= =
117 Y
275
S3X-S4X 140 105 58
Y

Motor operator for withdrawable circuit-breaker


Y
74 96
27.5 Isolating distance
A 1 Flange for compartment door included
2 269.5
= B = in supply
C
2 Lock for compartment door (available
upon request)
Y
3 Drilling of compartment door
135
1
2 63
Nr. 5 ø7 Note
See the different versions for the
= 1.75
=
72.5 = 94 = circuit-breaker mounting holes
X 105 161 126 142 X
27.25
= ø5.5 = 16 =
=

81
167
Y 3 125 A B C
R min. 200
CSIL0104

275 Y
S3X-S4X 140 105 84

34
o
ensi
Dim
Interlock between two horizontally-installed circuit-breakers

Y
A
Y
B B B C B B B
M
N P N

F
E
G L Q
105
X D X I R X
O

3
H
5 1 4 2
ø7

Y
65

103.5

275

Y Interlock device for S3-S4 circuit-breakers.


1
It can also be used for horizontally-installed
Isolating distance 27.5 S3X-S4X circuit-breakers in fixed version with
front terminals or plug-in/withdrawable version
with rear terminals

2 Template for drilling mounting holes in sheet


metal
3 Drilling template for all versions with rear
terminals

4 Dimensions with four-pole withdrawable


version mounted on right

5 Tightening torque 3,7 Nm


Note
See the different versions for the
dimensions of the circuit-breakers
CSIL0105

A B C D E F G H I L M N O P Q R

S3X 350 35 66 265 135 172 255 12 227.5 116 324 95 R30 76 80.5 155

S4X 350 35 66 350 173.5 210 339 12 315 156 324 95 R30 76 113.5 230

35
ons
Overall dimensions
ensi

SACE S3X - S4X


Dim

Accessories

Rotary handle operating mechanism on fixed or plug-in circuit-breaker


Y

105
= = Circuit-breaker-mounted rotary handle
1
operating mechanism
2 Lock for compartment door (available
ø4 80° upon request)
5
Y 3 Drilling of compartment door
45
Dimensions with connector for early
== 4 auxiliary contact for undervoltage
=
= = 72.5 release
X 105 161 X 142 112 X 5 Flange for compartment door included
= = =
in supply
ø7
80
= =
112 3
= =
=
117
=
R min 200 4 A
A Y
Y Note
S3X-S4X III 58
See the different versions for the circuit-
breaker mounting holes S3X-S4X IV 93

Compartment door-mounted rotary handle operating mechanism with adjustable depth for fixed or
plug-in circuit-breaker

Y
105

2
11.5

X 105 X X
90°
52.5

26 46.5

Y Support for depths of up to


26 1 Transmission assembly 6 500mm
5
2 Rotary handle assembly with door 66...300 mm
lock device 7
= 11.5 (with IP54 protection min. 90)
4 46
X = X 3 Padlock device for open position Distance (7) +2 mm
8
R min 200
33 (maximum 3 padlocks max. ø 6 (shaft length)
mm to be provided by user)
Y 27
4 Minimum radius of rotation for 9 301...500 mm
opening door
54
5 10
Distance (9) +2 mm
R min 200 Drilling of door (shaft length)
Y
Note
CSIL0106

See the different versions for the circuit-breaker mounting holes

36
o
ensi
Dim
Rotary handle operating mechanism on withdrawable circuit-breaker
Y
170
105
= =
2 38.5 22

ø4 80°

2 Circuit-breaker-mounted
Y 1 rotary handle operating
135
63 mechanism
45 Nr. 5 ø7
2 Lock for compartment door
= 27.25 = (available upon request)
72.5 = 94
X 105 161 X 126 142 X
= 57.1 5.5ø = 16 = Padlock device for open
3 position (maximum 3 padlocks
3 81 “Ø 6 mm to be provided by
125 user)
1
R min. 200
Note
Y
See the different versions for
35 35 37 the circuit-breaker mounting
42.5 holes
Y

Front flange for operating lever mechanism


Y
105 37 2
= = 1 Front flange for operating lever
mechanism
ø4 80° 2 Lock for compartment door (available
4 2 upon request)
3
Y Drilling of compartment door
45
== 4 Flange for compartment door included in
= =
= 72.5
supply
=
X 105 161 X X 142 112 X 5 Dimensions with connector for
= =
= undervoltage release early contact
=
1 ø7
80
= =
5
112 3 A
= =

=
117
= Y S3X-S4X III 58
A

Y 42.5 S3X-S4X IV 93

External neutral for SACE S4X circuit-breaker Note


50 76.5 See the different versions for the circuit-
breaker mounting holes
25 4
36.25

=
=

=
In 5 6 Line
100
160 Load
120 66 40 200 95
250
320
400

=
=
1 4 5 6

X3
CSIL0107

11

37
ons
Overall dimensions
ensi

SACE S6X
Dim

Fixed circuit-breaker

Y
105
280 (4 POL) 107 2 Terminal covers
210 (3 POL) -3 (available upon request when not included in the supply)
1 140
101.5
= = 2
12

241.75
263.25 Low High
47
=
2.5
X 406 161 379 105 X
=

16.5

14 9
1 Flange for compartment door
103.5
= = (included in the supply)
152
159
Y Mounting on sheet metal 2 Tightening torque 2 Nm

Terminals
Front extended Front for Cu/Al cables
70 70 70 41.5
ø21.5
40 ø11 5 15
47
32
48.5 62 47

Front
For rear Cu/Al cables 40
22.5 ±0.1 23 5 min.
(IP20 high terminal covers included in the supply)
ø6.5

ø21 12
19.5
12

Threaded rear
(low terminal covers included in the supply)
73
70 70 70 2.5 44

M24x2
CSIL0108

38
o
ensi
Dim
Mounting parts for fixed circuit-breaker

Template for drilling sheet metal support


(minimum thickness of sheet metal: 3 mm)

For terminals: For terminals for rear Cu/Al cables


Front for flat bars,
Front extended,
Front for cables Y

Y 70
(3 POL)
70 140
(3 POL) (4 POL)
140 35
(4 POL)

247.75 279.75
247.75

109.75 109.75
439
X 375 X X 375 X
M5/ø5.5
M5/ø5.5 R18

35 84

168 (3 POL)
Y 238
(4 POL)

Template for drilling


compartment door and
fitting flange
For threaded rear terminals (thickness of sheet metal: 2 mm)

Y
3 POL Y 4 POL
70 70 70

Y
105 35 147
= =
115
= =
247.75 249.75 247.75 249.75

109.75 379 109.75 379 =


70 =
X 375 375 X X 112 142 X
=
=
70 70
8 8

M5/ø5.5 ø35 M5/ø5.5 ø35 ø7

Y
Y Y
CSIL0109

39
ons
Overall dimensions
ensi

SACE S6X
Dim

Withdrawable circuit-breaker

280 (4 POL)
210 (3 POL)
70 70 70
27.5 Isolating distance

1 Fixed part
4 2 1 2
Moving part complete with IP20
protection class terminal covers
260 3
3 Flange for compartment door
included in supply
133 411
89.5
= 58 4 Lock for compartment door
ø5.5
X 140 208 196 X
(available upon request)
14.5 145 295
= 5 Tightening torque 9 Nm
5

167
91.5 131
2 190 123.5 136.5

195.5 193.5

Terminals Front extended (bottom only)

X X

162
187

25
20 ø14
10 31 3 70 70 70
40

Y
Horizontal or vertical flat bar rear terminals

≥3 80.5

20 ø14

40

X X

10
CSIL0110

40
o
ensi
Dim
Mounting parts for withdrawable circuit-breaker

Template for drilling sheet metal support Template for drilling compartment door and
(minimum thickness of sheet metal: 3 mm) fitting flange (thickness of sheet metal: 2 mm)
Y

140 (3 POL) ø4

210 80°
(4 POL
70
Y
170
80.5
77.5 45
Nr. 7 ø7
==

57.5 90 =
45.5 9
X X X 161 177 X
120
39
ø8.5 (M8) =
86.5

19.75
16
101
77.5 162.5
121
R min 200
Y
107
214
(3 POL)
284 (4 POL)

CSIL0111

41
ons
Overall dimensions
ensi

SACE S6X
Dim

Accessories

Interlock between two horizontally-installed circuit-breakers


Y
= =
650
55 70 70 70 120 70 70 70 55
Y

87 46
284

1 Interlock device
274.5

30
= 101 =
2 Drilling template for fitting

R
411
interlock plate
X 350 331 X
375 3 Drilling template for fixed
=
ø9
= version with rear terminals

Drilling template for withdrawable


4 version with rear terminals
= =
525
Dimensions with withdrawable
5 version mounted on right
2 4
Y Tightening torque 9 Nm
6 10.5 6
1 5 46 284
3
65
Note
73
See the different versions for
103.5
30 dimensions of the circuit-breakers
R
288 ø9
233

27.5
X 350 X
Isolating distance
92.5

Y 73

525

2 Y

CSIL0112

42
o
ensi
Dim
Motor operator for fixed circuit-breaker
Y
2
222.5
91.5 1 198.5 23.5 Y
81.25±0.1 81.25±0.1
19.75
Nr. 7 ø8

263.25
192.25

270 338 304 319


R8
72.25
X X
159.5
102.25 94.75
111.75 22.75

174
122±0.1 2
= 140 = R. min.200
215.5 96.5
210 Y Flange for compartment door
285.5 3 1 included in supply
Y Template for drilling
Note 2 compartment door
See the different versions for the circuit-
breaker mounting holes 3 Dimensions with connectors

Motor operator for withdrawable circuit-breaker


Y

222.5
27.5 91.5

1 Y
81.25±0.1 81.25±0.1
19.75
Nr. 7 ø8

186.5
338
270
304 319
411 R
72.25
X X
159.5
83.5 102.25 94.75
22.75
117.75

151
174
122±0.1 2
R. min.200
= =
140
23.5 123.5 Y
247.5
2 193.5
Y 1 Flange for compartment door
included in supply
Note
2 Template for drilling compartment
See the different versions for the circuit-breaker
CSIL0113

door
mounting holes

43
ons
Overall dimensions
ensi

SACE S6X
Dim

Accessories

Rotary handle operating


Y
mechanism on fixed circuit breaker
104.75
152
6
2 44.5 22
140

2 ø4 80°
1 Rotary handle operating
5 257.5 mechanism on circuit-breaker
Y
45
2 Lock for compartment door
(available upon request)
406 = = =
196 90 3
140 177 147 X
Drilling of compartment door
= = = 4 Drilling template for mounting
ø7 circuit-breaker on sheet metal
115 3 Flange for compartment door
1 = = 5
147 included in supply
= =
42.5 R min 200
Y 6 Tightening torque 2 Nm
Drilling only required for version with rear terminals
Y
3 POL 4 POL 70 70 70
4 Note
See the different versions for the
244 circuit-breaker mounting holes
70
244
105 35
104 104 379
X 375 379 375 X
70 70
133 133
8 8

M5/ø5.5 ø35 M5/ø5.5 ø35


Y Y

Compartment door-mounted rotary handle operating mechanism with adjustable depth for fixed circuit-
breaker 105 7
41.5 31 103.5 63 22
23

5 1 Transmission assembly
Y
2 41.5 Rotary handle assembly with
257.5 5 2 door lock device
19
406 1
= Padlock device (maximum 3 padlocks
46 3 max Ø 6mm to be provided by the
105 28 28 = customer only for circuit-breaker open
X X
36 33 position)
3 4 Minimum radius of rotation for fulcrum
2 of door
8 27

54 5 Template for drilling compartment door


168 R min 200
Drilling template for mounting circuit-
6
breaker on sheet metal
4 Y

7
72 ... 506 mm
R min 200 (with IP54 protection class min 90)
Drilling only required for version with rear terminals
Y
3 POL 4 POL 70 70 70 8 Distance (7) -4 mm
4 (shaft length)

70 244
244 Note
105 35
104 104 379 See the different versions for the
X 375 379 375 X
70 70 circuit-breaker mounting holes
133 133
8 8
CSIL0114

M5/ø5.5 ø35 M5/ø5.5 ø35


Y Y

44
o
ensi
Dim
Rotary handle operating mechanism on withdrawable circuit-breaker
Y

210

ø4 80°
1 Rotary handle operating
2 44.5 22 mechanism on circuit-breaker
Y Lock for compartment door
2
2 170 (available upon request)
80.5
45 3
Padlock device for open
7 fori ø7
== position (maximum 3 padlocks
max Ø 6mm to be provided by
411
90 9 = X the customer)
X 196 X 161 177
39
=
Note
3 See the different versions
151 19.75
16 for the circuit-breaker
101 mounting holes
1 162.5
121
R min 200
37
222.5 Y
42.5
91.5 131
123.5 136.5

Front flange for operating lever mechanism


104.75
152 103.5 37 2
140
= = 6
1 Front flange for operating lever mechanism
Lock for compartment door
ø4 80° 2 (available upon request)
5
257.5
2 Drilling of compartment door
Y 3
45
Drilling template for mounting circuit-breaker
4 on sheet metal
= = = = 2.75 90
Flange for compartment door included in
X 140 196 177 147 X 5 supply
= = =
= Tightening torque 2 Nm
ø7
6
115 3
= =
1 147
= = Note
Y 42.5 Y See the different versions for the circuit-
3 POL breaker mounting holes
Drilling only
required for version
4 with rear terminals
244 External neutral
379 115
104 70 75
X 375 X 40 10
70 70 52.5
133 =
8
25
ø35 =
M5/ø5.5

Y
4 POL 70 70 70 =
4 5 6 Line
In
100 A
160 A
115
185 77 49 200 A
250 A

320 A
400 A

Load

244 =
375 105 35 379
104
X X
=
6

25
5

133 X
4

8
1

=
CSIL0115

M5/ø5.5 ø35 11
Y

45
ons
Required distances
ensi
Dim

Installation of current-limiting circuit-breakers in compartment

A F
E E

B Circuit-breaker A B C D E F
3 POLE 4 POLE
I o

O off S3X 161 196 340 51 30 25.5 112


S4X 161 196 430 58 29 25.5 112
S6X 275 345 500 60 30 30.5 152
CSIL0116

D A-B-F = Distances outside compartment


C-D-E = Distances inside compartment walls

46
CONTENTS

es
Cod
Ordering codes

SACE Isomax S3X 48

SACE Isomax S4X 52

SACE Isomax S6X 54

Accessories 56

47
Ordering codes
es

SACE Isomax S3X


Cod

circuit-breaker

F = FIXED S3X 125 Iu (40 °C) = 125 A • Icu (415 V) = 200 kA

Thermomagnetic Im code 1SDA0 R1


release 3 poles 4 poles
F = Front terminals
S3X 125 F F R 32 Im 500A 45197 45207
S3X 125 F F R 50 Im 500A 45199 45209
S3X 125 F F R 80 Im 800A 45201 45211
S3X 125 F F R 100 Im 1000A 45203 45213
S3X 125 F F R 125 Im 1250A 45205 45215
CSIL9106

EF = Extended front
terminals
S3X 125 F EF R 32 Im 500A 45217 45267
S3X 125 F EF R 50 Im 500A 45219 45269
S3X 125 F EF R 80 Im 800A 45221 45271
S3X 125 F EF R 100 Im 1000A 45223 45273
S3X 125 F EF R 125 Im 1250A 45225 45275
FC Cu = Front terminals
for copper cables
S3X 125 F FC Cu R 32 Im 500A 45227 45277
S3X 125 F FC Cu R 50 Im 500A 45229 45279
S3X 125 F FC Cu R 80 Im 800A 45231 45281
S3X 125 F FC Cu R 100 Im 1000A 45233 45283
S3X 125 F FC Cu R 125 Im 1250A 45235 45285
FC CuAl = Front terminals
for copper/aluminium cables
S3X 125 F FC CuAl R 32 Im 500A 45237 45287
S3X 125 F FC CuAl R 50 Im 500A 45239 45289
S3X 125 F FC CuAl R 80 Im 800A 45241 45291
S3X 125 F FC CuAl R 100 Im 1000A 45243 45293
S3X 125 F FC CuAl R 125 Im 1250A 45245 45295
R = Threaded rear
terminals
S3X 125 F R R 32 Im 500A 45257 45307
S3X 125 F R R 50 Im 500A 45259 45309
S3X 125 F R R 80 Im 800A 45261 45311
S3X 125 F R R 100 Im 1000A 45263 45313
S3X 125 F R R 125 Im 1250A 45265 45315
RC = Rear terminals
for cables
S3X 125 F RC R 32 Im 500A 45247 45297
S3X 125 F RC R 50 Im 500A 45249 45299
S3X 125 F RC R 80 Im 800A 45251 45301
S3X 125 F RC R 100 Im 1000A 45253 45303
S3X 125 F RC R 125 Im 1250A 45255 45305

Magnetic only Im code 1SDA0 R1


release 3 poles
F = Front terminals
S3X 125 F F R3 Im 12 ... 36A 45384
S3X 125 F F R5 Im 20 ... 60A 45385
S3X 125 F F R 10 Im 40 ... 120A 45386
S3X 125 F F R 25 Im 100 ... 300A 45387
S3X 125 F F R 50 Im 200 ... 600A 45388
S3X 125 F F R 100 Im 400 ... 1200A 45389
S3X 125 F F R 125 Im 500 ... 1500A 45390

Note
The S3X circuit-breaker with magnetic only release in the plug-in and withdrawable version are taken from the corresponding fixed version by
means of the conversion kits indicated on page 60 and cannot be ordered configured directly.

48
Ordering codes

es
SACE Isomax S3X

Cod
circuit-breaker

F = FIXED S3X 200 Iu (40 °C) = 200 A • Icu (415 V) = 200 kA

Thermomagnetic Im code 1SDA0 R1


release 3 poles 4 poles
F = Front terminals
S3X 200 F F R 125 Im 1250A 46039 46045
S3X 200 F F R 160 Im 1600A 46041 46047
S3X 200 F F R 200 Im 2000A 46043 46049
EF = Extended front
terminals
CSIL9106

S3X 200 F EF R 125 Im 1250A 46051 46081


S3X 200 F EF R 160 Im 1600A 46053 46083
S3X 200 F EF R 200 Im 2000A 46055 46085
FC Cu = Front terminals
for copper cables
S3X 200 F FC Cu R 125 Im 1250A 46057 46087
S3X 200 F FC Cu R 160 Im 1600A 46059 46089
S3X 200 F FC Cu R 200 Im 2000A 46061 46091
FC CuAl = Front terminals
for copper/aluminium cables
S3X 200 F FC CuAl R 125 Im 1250A 46063 46093
S3X 200 F FC CuAl R 160 Im 1600A 46065 46095
S3X 200 F FC CuAl R 200 Im 2000A 46067 46097
R = Threaded rear
terminals
S3X 200 F R R 125 Im 1250A 46075 46105
S3X 200 F R R 160 Im 1600A 46077 46107
S3X 200 F R R 200 Im 2000A 46079 46109
RC = Rear terminals
for cables
S3X 200 F RC R 125 Im 1250A 46069 46099
S3X 200 F RC R 160 Im 1600A 46071 46101
S3X 200 F RC R 200 Im 2000A 46073 46103

Magnetic only Im code 1SDA0 R1


release 3 poles
F = Front terminals
S3X 200 F F R 125 Im 500 ... 1500A 46135
S3X 200 F F R 160 Im 640 ... 1920A 48659
S3X 200 F F R 200 Im 800 ... 2400A 48660

Note
The S3X circuit-breaker with magnetic only release in the plug-in and withdrawable version are taken from the corresponding fixed version by
means of the conversion kits indicated on page 60 and cannot be ordered configured directly.

49
Ordering codes
es

SACE Isomax S3X


Cod

circuit-breaker

P = PLUG-IN Moving part


S3X 125 Iu (40 °C) = 125 A • Icu (415 V) = 200 kA

Thermomagnetic Im code 1SDA0 R1


release 3 poles 4 poles
S3X 125 P MP R32 Im 500A 45317 45327
S3X 125 P MP R50 Im 500A 45319 45329
S3X 125 P MP R80 Im 800A 45321 45331
CSIL9106

S3X 125 P MP R100 Im 1000A 45323 45333


S3X 125 P MP R125 Im 1250A 45325 45335

S3X 200 Iu (40 °C) = 200 A • Icu (415 V) = 200 kA

Thermomagnetic Im code 1SDA0 R1


release 3 poles 4 poles
S3X 200 P MP R125 Im 1250A 46111 46117
S3X 200 P MP R160 Im 1600A 46113 46119
S3X 200 P MP R200 Im 2000A 46115 46121

Fixed parts
code 1SDA0 R1
3 poles 4 poles
EF = Extended front
terminals
S3 P FP EF 13539 13548
R = Threaded rear
terminals
S3 P FP R 13547 13554
CSIL9022

50
Ordering codes

es
SACE Isomax S3X

Cod
circuit-breaker

W = WITHDRAWABLE Moving part


S3X 125 Iu (40 °C) = 125 A • Icu (415 V) = 200 kA

Thermomagnetic Im code 1SDA0 R1


release 3 poles 4 poles
S3X 125 W MP R32 Im 500A 45337 45347
S3X 125 W MP R50 Im 500A 45339 45349
S3X 125 W MP R80 Im 800A 45341 45351
CSIL9121

S3X 125 W MP R100 Im 1000A 45343 45353


S3X 125 W MP R125 Im 1250A 45345 45355

S3X 200 Iu (40 °C) = 200 A • Icu (415 V) = 200 kA

Thermomagnetic Im code 1SDA0 R1


release 3 poles 4 poles
S3X 200 W MP R125 Im 1250A 46123 46129
S3X 200 W MP R160 Im 1600A 46125 46131
S3X 200 W MP R200 Im 2000A 46127 46133

Fixed parts
Im Max code 1SDA0 R1
3 poles 4 poles
EF = Extended front
terminals
S3 W FP EF 13555 13564
R = Threaded rear
terminals
S3 W FP R 13563 13572
CSIL9021

51
Ordering codes
es

SACE Isomax S4X


Cod

circuit-breaker

F = FIXED S4X 250 Iu (40 °C) = 250 A • Icu (415 V) = 200 kA

Microprocessor-based PR211 code 1SDA0 R1 PR212 code 1SDA0 R1


release 3 poles 4 poles 3 poles 4 poles
F = Front terminals
S4X 250 F F In=100 I 46582 46592 LSI 46586 46596
LI 46584 46594 LSIG 46588 46598
S4X 250 F F In=160 I 46583 46593 LSI 46587 46597
LI 46585 46595 LSIG 46589 46599
S4X 250 F F In=250 I 46524 46528 LSI 46526 46530
CSIL9111

LI 46525 46529 LSIG 46527 46531


EF = Extended front
terminals
S4X 250 F EF In=100 I 46657 46707 LSI 46663 46713
LI 46660 46710 LSIG 46668 46716
S4X 250 F EF In=160 I 46658 46708 LSI 46664 46714
LI 46661 46711 LSIG 46669 46717
S4X 250 F EF In=250 I 46659 46709 LSI 46665 46715
LI 46662 46712 LSIG 46670 46718
FC Cu = Front terminals
for copper cables
S4X 250 F FC Cu In=100 I 46671 46719 LSI 46677 46725
LI 46674 46722 LSIG 46680 46728
S4X 250 F FC Cu In=160 I 46672 46720 LSI 46678 46726
LI 46675 46723 LSIG 46681 46729
S4X 250 F FC Cu In=250 I 46673 46721 LSI 46679 46727
LI 46676 46724 LSIG 46682 46730
FC CuAl = Front terminals
for copper/aluminium cables
S4X 250 F FC CuAl In=100 I 46830 46842 LSI 46836 46848
LI 46833 46845 LSIG 46839 46851
S4X 250 F FC CuAl In=160 I 46831 46843 LSI 46837 46849
LI 46834 46846 LSIG 46840 46852
S4X 250 F FC CuAl In=250 I 46832 46844 LSI 46838 46850
LI 46835 46847 LSIG 46841 46853
R = Threaded rear
terminals
S4X 250 F R In=100 I 46695 46743 LSI 46701 46749
LI 46698 46746 LSIG 46704 46752
S4X 250 F R In=160 I 46696 46744 LSI 46702 46750
LI 46699 46747 LSIG 46705 46753
S4X 250 F R In=250 I 46697 46745 LSI 46703 46751
LI 46700 46748 LSIG 46706 46754
RC = Rear terminals
for cables
S4X 250 F RC In=100 I 46683 46731 LSI 46689 46737
LI 46686 46734 LSIG 46692 46740
S4X 250 F RC In=160 I 46684 46732 LSI 46690 46738
LI 46687 46735 LSIG 46693 46741
S4X 250 F RC In=250 I 46685 46733 LSI 46691 46739
LI 46688 46736 LSIG 46694 46742

52
Ordering codes

es
SACE Isomax S4X

Cod
circuit-breaker

P = PLUG-IN Moving part


S4X 250 Iu (40 °C) = 250 A • Icu (415 V) = 200 kA

Microprocessor-based PR211 code 1SDA0 R1 PR212 code 1SDA0 R1


release 3 poles 4 poles 3 poles 4 poles
S4X 250 P MP In=100 I 46755 46767 LSI 46761 46773
LI 46758 46770 LSIG 46764 46776
S4X 250 P MP In=160 I 46756 46768 LSI 46762 46774
CSIL9111

LI 46759 46771 LSIG 46765 46777


S4X 250 P MP In=250 I 46757 46769 LSI 46763 46775
LI 46760 46772 LSIG 46766 46778

Fixed parts
code 1SDA0 R1
3 poles 4 poles
EF = Extended front
terminals
S4 P FP EF 13612 13621
R =Threaded rear
terminals
S4 P FP R 13620 13629
CSIL9024

W = WITHDRAWABLE Moving part


S4X 250 Iu (40 °C) = 250 A • Icu (415 V) = 200 kA

Microprocessor-based PR211
PR211 code 1SDA0 R1 PR212
PR212 code 1SDA0 R1
release 3 poles 4 poles 3 poles 4 poles
S4X 250 W MP In=100 I 46779 46791 LSI 46785 46797
LI 46782 46794 LSIG 46788 46800
S4X 250 W MP In=160 I 46780 46792 LSI 46786 46798
CSIL9122

LI 46783 46795 LSIG 46789 46801


S4X 250 W MP In=250 I 46781 46793 LSI 46787 46799
LI 46784 46796 LSIG 46790 46802

Fixed parts
code 1SDA0 R1
3 poles 4 poles
EF = Extended front
terminals
S4 W FP EF 13630 13639
R =Threaded rear
terminals
S4 W FP R 13638 13647
CSIL9023

53
Ordering codes
es

SACE Isomax S6X


Cod

circuit-breaker

F = FIXED S6X 400 Iu (40 °C) = 400 A • Icu (415 V) = 200 kA

Microprocessor-based PR211 code 1SDA0 R1 PR212 code 1SDA0 R1


release 3 poles 4 poles 3 poles 4 poles
F = Front terminals
S6X 400 F F In=320 I 47595 47601 LSI 47597 47603
LI 47596 47602 LSIG 47598 47604
S6X 400 F F In=400 I 46534 46538 LSI 46536 46540
LI 46535 46539 LSIG 46537 46541
EF = Extended front
CSIL9108

terminals
S6X 400 F EF In=320 I 47661 47693 LSI 47665 47697
LI 47663 47695 LSIG 47667 47699
S6X 400 F EF In=400 I 47660 47692 LSI 47664 47696
LI 47662 47694 LSIG 47666 47698
FC CuAl =Front terminals
for copper/aluminium cables
S6X 400 F FC CuAl In=320 I 47669 47701 LSI 47673 47704
LI 47671 47703 LSIG 47675 47707
S6X 400 F FC CuAl In=400 I 47668 47700 LSI 47672 47705
LI 47670 47702 LSIG 47674 47706
R = Threaded rear
terminals
S6X 400 F R In=320 I 47685 47717 LSI 47689 47721
LI 47687 47719 LSIG 47691 47723
S6X 400 F R In=400 I 47684 47716 LSI 47688 47720
LI 47686 47718 LSIG 47690 47722
RC = Rear terminals
for cables
S6X 400 F RC In=320 I 47677 47709 LSI 47681 47713
LI 47679 47711 LSIG 47683 47715
S6X 400 F RC In=400 I 47676 47708 LSI 47680 47712
LI 47678 47710 LSIG 47682 47714

S6X 630 Iu (40 °C) = 630 A • Icu (415 V) = 200 kA

Microprocessor-based PR211 code 1SDA0 R1 PR212 code 1SDA0 R1


release 3 poles 4 poles 3 poles 4 poles
F = Front terminals
S6X 630 F F In=630 I 46560 46564 LSI 46562 46566
LI 46561 46565 LSIG 46563 46567
EF = Extended front
terminals
S6X 630 F EF In=630 I 47724 47744 LSI 47726 47746
LI 47725 47745 LSIG 47727 47747
FC CuAl =Front terminals
for copper/aluminium cables
S6X 630 F FC CuAl In=630 I 47729 47749 LSI 47731 47751
LI 47730 47750 LSIG 47732 47752
R = Threaded rear
terminals
S6X 630 F R In=630 I 47739 47759 LSI 47741 47761
LI 47740 47760 LSIG 47742 47762
RC =Rear terminals
for cables
S6X 630 F RC In=630 I 47734 47754 LSI 47736 47756
LI 47735 47755 LSIG 47737 47757

54
Ordering codes

es
SACE Isomax S6X

Cod
circuit-breaker

W = WITHDRAWABLE Moving part


S6X 400 Iu (40 °C) = 400 A • Icu (415 V) = 200 kA

Microprocessor-based PR211
PR211 code 1SDA0 R1 PR212 code 1SDA0 R1
release 3 poles 4 poles 3 poles 4 poles
S6X 400 W MP In=320 I 47633 47643 LSI 47637 47647
LI 47635 47645 LSIG 47641 47649
S6X 400 W MP In=400 I 47632 47642 LSI 47636 47646
CSIL9123

LI 47634 47644 LSIG 47640 47648

S6X 630 Iu (40 °C) = 630 A • Icu (415 V) = 200 kA

Microprocessor-based PR211
PR211 code 1SDA0 R1 PR212 code 1SDA0 R1
release 3 poles 4 poles 3 poles 4 poles
S6X 630 W MP In=630 I 47650 47655 LSI 47652 47657
LI 47651 47656 LSIG 47653 47658

Fixed parts
Im Max code 1SDA0 R1
3 poles 4 poles
VR = Vertical flat-bar
rear terminals
S6 W FP VR 13972 13981
HR = Horizontal flat-bar
rear terminals
S6 W FP HR 13968 13977
PSIS9619
PSIS9618

55
Ordering codes
es

SACE Isomax S accessories


Cod

Auxiliary releases
Shunt opening releases
Type code 1SDA0 R1
S3X-S4X S6X
12 V d.c. 23403 23404
24 V a.c. / d.c. 13781 14136
CSIS9034

48 V a.c. / d.c. 13782 14137


60 V a.c. / d.c. 23405 23406
110...120 V a.c. - 110...125 V d.c. 13783 14138
220...240 V a.c. - 220...250 V d.c. 13785 14140
380...400 V a.c. 13786 14141
480 V a.c. 37512 37514

Undervoltage releases
Type code 1SDA0 R1
S3X-S4X S6X
24 V a.c. 13842 14188
48 V a.c. 13843 14189
CSIS9033

60 V a.c. 23346 23347


110...127 V a.c. 13844 14190
220...250 V a.c. 13846 14192
380...440 V a.c. 13847 14193
480 V a.c. 37513 37515
24 V d.c. 13833 14179
48 V d.c. 13835 14181
60 V d.c. 13836 14182
110...125 V d.c. 13838 14184
220...250 V d.c. 13839 14185

Time-lag undervoltage releases


Type code 1SDA0 R1
S3X-S4X S6X
110 - 220 V a.c. (release + time-lag device) 13840 14186

Connectors for auxiliary releases


Type code 1SDA0 R1
PSIS9661

S3X-S4X-S6X
for fixed circuit-breaker - L=1m 13865
for fixed circuit-breaker - L=2m 37523
for plug-in or withdrawable circuit-breaker - L=1m 13866
extension for testing auxiliary circuits with the circuit-breaker racked out 25552
PSIS9634

56
Ordering codes

es
SACE Isomax S accessories

Cod
Electrical signalling
Auxiliary contacts
Type code 1SDA0 R1
S3X-S4X S6X
2 open/closed change-over contacts 13856 23366
PSIS9630

1 open/closed change-over contact and 1 tripped release signal 13575 23332


2 open/closed change-over contacts and 1 tripped release signal 25773

Auxiliary contacts for digital signals


Type code 1SDA0 R1
S3X-S4X S6X
2 open/closed change-over contacts 25544 25774
1 open/closed change-over contact and 1 tripped release signal 25545 25775
2 open/closed change-over contacts and 1 tripped release signal 25776

Accept contacts and connectors


Type code 1SDA0 R1
S3X-S4X-S6X
accept contact and connector for undervoltage release 25551

Connectors for auxiliary contacts


PSIS9631

Type code 1SDA0 R1


S3X-S4X-S6X
for fixed circuit-breaker - L=1m 13863
for fixed circuit-breaker - L=2m 37522
for plug-in or withdrawable circuit-breaker - L=1m 13864
extension for testing auxiliary circuits with the circuit-breaker racked out 25553

Motor operating mechanism


Direct action
Type code 1SDA0 R1
S3X-S4X
24 V d.c. 13873
48...60 V d.c. 13874
PSIS9632

100...127 V a.c. - 100...125 V d.c. 13875


220...240 V a.c. - 220...250 V d.c. 13876
380 V a.c. 13877
440 V a.c. 14545

Stored energy
Type code 1SDA0 R1
S6X
24 V d.c. 14029
48 V d.c. 14030
60 V d.c. 23348
PSIS9633

110 V a.c. / d.c. 23349


120...127 V a.c. / d.c. 14031
220...250 V a.c. / d.c. 14032
380 V a.c. 14033

Connectors for motor operating mechanism and auxiliary contacts


Type code 1SDA0 R1
S3X-S4X-S6X
for fixed circuit-breaker - L=1m 13857
for fixed circuit-breaker - L=2m 37524
PSIS9629

for plug-in or withdrawable circuit-breaker - L=1m 13858


extension for testing auxiliary circuits with the circuit-breaker racked out 25554

57
Ordering codes
es

SACE Isomax S accessories


Cod

Operating mechanism and locks

Direct-mounted rotary-handle operating mechanism


Type code 1SDA0 R1
S3X-S4X S6X
PSIS9635

for fixed/plug-in circuit breakers 13867 14026


for withdrawable circuit breakers 13868 14027
emergency for fixed or withdrawable circuit-breakers 13870

Rotary handle operating mechanism with transmission


Type code 1SDA0 R1
S3X-S4X S6X
compartment door, adjustable depth (Lmax= 300 mm) for fixed or plug-in 13869
compartment door, adjustable depth (Lmax= 500 mm) for fixed or withdrawable 14028
compartment door, emergency, adjustable depth (Lmax= 300 mm) for fixed or plug-in 13871
PSIS9636

compartment door, emergency, adjustable depth (Lmax= 500 mm) for fixed 46569
remote transmission rod with adjustable depth (Lmax= 500 mm) 25427

Front flange for operating lever mechanism


Type code 1SDA0 R1
S3X-S4X S6X
for fixed or plug-in 13889 14035
for withdrawable 13890 14036
PSIS9637

Key lock for locking in the open position


Type code 1SDA0 R1
S3X-S4X S6X
for motor operating mechanism - a different key for each circuit-breaker 13883 13885
for motor operating mechanism - the same key for sets of circuit-breakers 13884 13886
for motor operating mechanism against manual operation
(a different key for each circuit-breaker) 36245
for front flange / rotary handle - a different key for each circuit-breaker 13881 13881
for front flange / rotary handle - the same key for sets of circuit-breakers 13882 13882
PSIS9645

Locks
Type model code 1SDA0 R1

Compartment door lock for front flange for locks / rotary handle oper. mech. S3X-S4X-S6X 13880
Tamper-proof lock for thermal releases S3X 25548

Mechanical interlock across two circuit-breakers


PSIS9640

Type model code 1SDA0 R1

for horizontal installation (excluded ES terminals) S3X 23330


for horizontal installation (excluded ES terminals) S4X 13690
for horizontal installation (excluded ES terminals) S6X 14024

58
Ordering codes

es
SACE Isomax S accessories

Cod
Connection terminals
Type code 1SDA0 R1
3 pieces 4 pieces 6 pieces 8 pieces
EF = Extended front terminals
S3X-S4X 23353 23359 13596 13597
S6X 23379 23389 13920 13921
ES = Spreaded extended front terminals
PSIS9663

S3X-S4X 46517 46518 46515 46516


FC Cu = Front terminals for copper cables
S3X-S4X 23354 23360 13598 13599
FC CuAl = Front terminals for copper - aluminium cables
S3X 125 (1x95 mm2) 23356 23362 13602 13603
S3X 200 - S4X 250 (1x150 mm2) 23357 23363 20293 20294
S6X (2x240 mm2) 23380 23390 13922 13923
R = Threaded rear terminals
S3X-S4X 23352 23365 13606 13607
S6X 23382 23392 13960 13961
R Res.Cur. = Threaded rear terminals for residual-current release in vertical installation
PSIS9641

S3X 25543
RC = Rear terminals for copper or aluminium cables
S3X-S4X (1x120 mm2) 23358 23364 13604 13605
S6X (2x150 mm2) 23381 23391 13924 13925

Insulating terminal covers


Type code 1SDA0 R1
3 poles 4 poles
high for fixed
PSIS9642

S3X-S4X 13695 13696


S6X 14040 14041
low for fixed and moving part of plug-in or withdrawable
S3X-S4X 13693 13694
S6X 14038 14039

Screws for sealing terminal covers


Type code 1SDA0 R1
PSIS9643

S3X-S4X-S6X 13699
PSIS9632

59
Ordering codes
es

SACE Isomax S accessories


Cod

Accessories for microprocessor-based


overcurrent release
Type model code 1SDA0 R1

Signalling unit SACE PR212/K S4X 13854


Signalling unit SACE PR212/K S6X 14200
PSIS9648

Dialog unit SACE PR212/D + Actuator unit SACE PR212/T S4X 48003
Dialog unit SACE PR212/D + Actuator unit SACE PR212/T S6X 48004

Current transformer for neutral conductor outside circuit-breaker S4X (In = 100A) 37114
Current transformer for neutral conductor outside circuit-breaker S4X (In = 160A) 37115
Current transformer for neutral conductor outside circuit-breaker S4X (In = 250A) 37117
Current transformer for neutral conductor outside circuit-breaker S6X (In = 630A) 25777

X3 connector for tripped release signal


and neutral protection for fixed circuit-breaker with PR211/P, PR212/P - LSI S4X-S6X 13702
PSIS9650

X3, X4 connector for tripped release signal


and neutral protection for fixed circuit-breaker with PR212/P - LSIG S4X-S6X 13704
X3 connector for tripped release signal and neutral protection
for plug-in or withdrawable circuit-breaker with PR211/P, PR212/P - LSI S4X-S6X 13703
X3, X4 connector for tripped release signal and neutral protection
for plug-in or withdrawable circuit-breaker with PR212/P - LSIG S4X-S6X 13705
SACE TT1 test unit S4X-S6X 37121

Conversion kits (for current-limiting circuit-breakers only)


PSIS9649

Kit for converting from fixed circuit-breaker to moving part of


plug-in circuit-breaker
Type code 1SDA0 R1
3 poles 4 poles
S3X 46519 46520
S4X 46511 46512

Kit for converting from fixed circuit-breaker to moving part of


PSIS9647

withdrawable circuit-breaker
Type code 1SDA0 R1
3 poles 4 poles
S3X 46521 46522
S4X 46514 46513
S6X 47619 47620

Notes
– The contact isolators on the fixed parts of S3-S4 circuit-breakers (plug-in and withdrawable versions) have been modified (during 1997) to
make them suitable for the moving parts of S3X-S4X current-limiting circuit-breakers.
PSIS9651

The “new” contact isolators are supplied in the conversion kit for S3X-S4X models (used for converting them into moving parts). The operation
is simple to perform and can be carried out by the user with the help of the instructions supplied. It enables one to maintain the compatibility
of S3X-S4X models and S3-S4 fixed parts that are already stored in the warehouse or installed.
The modification is not required on S3X or S4X current-limiting circuit-breakers that are supplied complete with fixed parts or on fixed parts
purchased after February 1998.
The contact isolators can be supplied as spare parts if required.
– The existing fixed parts for S3-S4 circuit-breakers are not compatible with current-limiting apparatus if they are fitted with front terminals for
copper cables FC Cu.
PSIS9652

60
Ordering codes

es
SACE Isomax S accessories

Cod
Accessories for fixed part of plug-in or withdraw-
able circuit-breakers

Rails
Type code 1SDA0 R1
S3X-S4X
Rail for preparing the fixed part of a plug-in circuit-breaker for use
as the fixed part of a withdrawable circuit-breaker 13692

Terminals for the fixed parts of plug-in or withdrawable circuit-


breakers
Type code 1SDA0 R1
3 pieces 4 pieces
EF = Extended front terminals
S3X-S4X 13650 13651
PSIS9655

S6X (with terminals mounted only below) 13984 13985


R = Threaded rear terminals
S3X-S4X 13654 13655
HR = Horizontal flat-bar rear terminals
S6X 13986 13987
VR = Vertical flat-bar rear terminals
S6X 13988 13989

Position contacts
PSIS9654

Type code 1SDA0 R1


S3X-S4X-S6X
contacts for signalling circuit-breaker racked out 13859
contacts for signalling circuit-breaker racked out for digital signals 25546
contacts for signalling circuit-breaker racked in 13860
contacts for signalling circuit-breaker racked in for digital signals 25547

Lock for fixed part of withdrawable circuit-breakers


Type code 1SDA0 R1
PSIS9656

S3X-S4X-S6X
key lock for locking in racked in / out position - different key for each c.b. 25434
key lock for locking in racked in / out position - same key for sets of c.bs. 25435
padlock device 13872
PSIS9664

61
Ordering codes
es

SACE Isomax S accessories


Cod

Installation accessories

Bracket for mounting on DIN rail


Type code 1SDA0 R1
3 poles 4 poles
For DIN rail DIN EN 50023 (complete with DIN front flange H=45 mm)
S3X 13576 13577
S4X 13700 13701

IP54 protection
Type code 1SDA0 R1
S3X-S4X-S6X
PSIS9657

for adjustable-depth rotary handle operating mechanism on door 13891

Residual-current releases

SACE RC211, SACE RC212


Type code 1SDA0 R1
PSIS9659

RC211/3 RC212/3
For S3X circuit-breaker (horizontal installation) 20288 20290
For S3X circuit-breaker (vertical installation) 20289 20291

SACE RCQ
Type code 1SDA0 R1

release and closed toroid - diameter 60 mm 37388


release and closed toroid - diameter 110 mm 37389
PSIS9665

release and opening toroid - diameter 110 mm 37390


release and opening toroid - diameter 180 mm 37391
release and opening toroid - diameter 230 mm 37392

release only 37393

closed toroid only - diameter 60 mm 37394


closed toroid only - diameter 110 mm 37395
opening toroid only - diameter 110 mm 37396
opening toroid only - diameter 180 mm 37397
opening toroid only - diameter 230 mm 37398
PSIS9660

62
es
Cod

Due to possible developments of standards as well as of materials, the characteristics and dimensions specified in the present
catalogue may only be considered binding after confirmation by ABB SACE L.V.

63
ITSLV 649294/011 en 6/'98

ABB SACE L.V. SPA Obtained from: