Professional Documents
Culture Documents
■ Definitions
1 MW =modular width 18 mm Mounting depth 70 mm =
N-type =Device mounting Device mounting depth 70 mm
depth 55 mm
■ Protection against hazardous shock currents according to DIN VDE 0100 Part 410
Application
• Protection against indirect 10 mA 30 mA
10000 Range 1
AI2-6158d
contact (indirect personnel Usually, the effect
protection). Protection is pro- ms
is not perceived.
t
vided by disconnecting haz-
2000 Range 2
ardous high touch voltages Usually, there are
caused by a short circuit to ex- 1000 no noxious effects.
posed conductive parts of 500
equipment. 1 2 3 4 Range 3
• When using RCCBs with 200 Usually, no danger
I∆n ≤ 30 mA, protection from of heart fibrillation.
100
direct contact (direct person-
nel protection) is also provid- 50
Range 4
ed. Supplementary protection Heart fibrillation
20
measure by disconnection 0,1 0,2 0,5 1 2 5 10 20 50 100 200 500 1000 mA 10000
danger.
when live parts are touched. Current ranges acc. to IEC 479 M: Shock current
M
t : Duration
Protective action
RCCB
RCCB
RCCB
I2-7557
the magnetizing effects of cur- for the test function is 100 V AC
rent carrying conductors cancel that the full protective function (5SM series).
2 4 6 N 2 4 6 N
each other out in accordance of the RCCB is maintained, even
with Kirchhoff’s law. There is no in the event of a supply fault, 3 x 230 V AC + N 3 x 230 V AC
residual magnetic field which e.g. if a phase conductor fails or 3 x 400 V AC + N 3 x 400 V AC
could induce a voltage in the the neutral conductor is inter-
secondary winding. rupted.
■ Use
RCCBs may be used in all three TN network
L1 TT network L1
IT network (conditional) L1
distribution network types (DIN L2 L2 L2
L3 L3 L3
VDE 0100 Teil 410) and in an IT N N AI2-6155d
network system provided that PEN PE AI2-6154e
RCCB
RCCB RCCB
to ground is sufficient to allow a
fault current to flow which has L1
the same level as the rated fault N PE
L2 PE PE
L3
current. N
The IT network can still be mon- TN-C TN-S
itored using an insulation moni-
tor. Both protective systems do
not mutually interfere with one
another.
■ Current types
When using electronic compo- RCCBs which trip on both sinu-
nents in household appliances soidal AC fault currents as well Current type Tripping
current
and in industrial plants for as on pulsating DC fault cur-
equipment with a protective rents have the symbol . 1 AC fault current 0.5 ... 1 I∆n
ground conductor (protection 2 Pulsating DC fault currents 0.35 ... 1.4 I∆n
class I), non-sinusoidal fault Half-wave current
currrents may flow through an (pos. and neg. half-waves)
RCCB in case of an insulation
Phased half-wave currents:
fault. Phase control angle 90°el 0.25 ... 1.4 I∆n
The specifications and regula- 135°el 0.11 ... 1.4 I∆n
tions for RCCBs include add-
3 Half-wave current with superim- max. 1.4 I∆n+
tional requirements and test posed smooth 6 mA DC current 6 mA
specifications for fault currents
which, within a supply frequen- Tripping currents for RCCBs defined according to DIN VDE 0664 Part 1
cy period, reach zero or ap-
proach zero.
■ DC fault currents
In industrial electrical equip- Thus, electrical equipment Three-phase star connection
ment, circuits are being increas- which generates fault currents bridge connection
N L1 L2 L3
ingly used where smooth DC such as these when faults oc- -six pulse
L1 L2 L3
fault currents or fault currents cur, may not be operated to- IB
with a low residual ripple may gether with pulsating current-
flow in the event of a fault condi- sensitive RCCBs on electrical IB
tion. This is shown on the follow- supply networks.
ing diagram with the example of Alternative protective measures
AI2-6161b
a piece of elecrical equipment can, for instance, include pro-
with a three-phase rectifier cir- tective separation, which, how-
cuit. Electrical equipment such ever, can only be implemented
as this includes, for example, using heavy and expensive AI2-6160b ID
AC drive converters, medical transfromers. A technically opti- I
equipment (e.g. X-ray equip- mum and cost-effective solution
ment and CT systems) as well is obtained by using the new Load current Fault current
as UPS systems. AC/DC-sensitive RCCBs. This IB I
Pulsating current-sensitive type of RCCB has been includ-
RCCBs cannot detect such DC ed in prEN 50 178 (replacing
fault currents and cannot trip. DIN VDE 0160) “Equipment for
Further, this has a negative im- power plants with electronic
AI2-6162b
pact on their tripping function. equipment“. t t
Block diagram with fault location
■ Circuit design
When designing and installing
electrical systems, it must be
ensured that electric devices,
which can generate smooth DC
fault currents when a fault de-
velops, have their own circuit
Wh
with an AC/DC-sensitive RCCB.
It is not permissible to branch
AI2-6164b
circuits with these types of elec-
tric devices after pulsating
currrent-sensitive RCCBs. De-
vices, which can generate DC I n =300 mA
RCCB
fault currents under fault condi- S
tions, would then diminish the
tripping capability of the pulsat- A
ing current-sensitive RCCBs.
The tripping conditions accord-
ing to DIN VDE 0664 also apply I n =30 mA I n =10 mA I n =30 mA
to the AC/DC-sensitive RCCB. RCCB RCCB RCCB RCCB RCCB
I n =30 mA
To trip in the event of smooth
DC fault currents, they have S
been extended, corresponding
to the current compatibility
characteristics according to
IEC 479, so that tripping must
be realized at a tripping current
of 0.50 to 2 × I∆n.
AC/DC-sensitive RCCBs have
the symbol . This new protective device has Note: RCBBs into the building man-
a monitoring symbol from VDE If you use the available auxiliary agement systems with instabus
with VDE Register No. 5342. contacts, you can integrate the EIB and AS-i-Bus or PROFIBUS.
■ Selective tripping
Residual current operated cir- Further, selective RCCBs ac- Main Sub distribution
cuit-breakers normally have an cording to DIN VDE 0664 must distribution board RCCB
instantaneous release. This have an increased surge board
means that a series circuit of strength of at least 3 kA. Sie-
such residual current operated mens devices have a surge
circuit-breakers with the aim to strength of ≥ 5 kA. S RCCB
provide selective tripping will Selective RCCBs have the sym-
not operate correctly when a bol î. Selective version RCCB
fault occurs. To achieve selec-
tivity when RCCBs are connect- The table opposite shows a
ed in series, the devices possible grading of RCCBs for
For undelayed undelayed
connected in series must be selective tripping when the disconnection
graded both with regard to the RCCBs are connected in series
without time delay. ID n = 300 mA 10 mA or 30 mA
tripping time as well as with re-
gard to the rated fault current. ID = 500 mA 10 mA or 30 mA
n
Selective RCCBs have a trip-
ping delay. ID n = 1000 mA 10 mA or 30 mA 0,3; 0,5
AI2-6168d
■ Surge strength
During thunderstorms, atmos- A surge current of Î = 250 A is % Peak Characteristics of a current impulse acc. to
pheric-related overvoltage con- used for testing with a 100 DIN VDE 0432 Part 2
ditions may enter a system or standardized surge of 8/20 µs. 90 TS front time in s
Front Tail Tr virtual time to half-value on tail in s
plant via the overhead power Siemens pulsating current-sen- I 01 virtual origin
lines in the form of travelling sitive RCCBs have a surge Im peak value
waves and thus the RCCBs are strength of ≥ 1 000 A.
Im
50
tripped. In order to prevent
these undesirable trips, pulsat-
ing current-sensitive RCCBs
must meet the requirements of 10
AI2-6165b
the tests defined to prove the 0
surge strength. 01 TS t
Tr