Abnormal
Sl. Name of Capacit Make YOM Date of Behaviour(humming
no. GSS
Rating
y outage Last Repair sound/Last DGA report Physical Condition Remarks
etc)
Muzaffarpur Zone
132/33 KV 20 MVA Kanohar 2001 Defects in HV winding Kept on Transformer has been
132/33 KV plinth(missing parts) brought from GSS Nawada.
1 Shahpur
patori This transformer has been
132/33 KV 20 MVA
It is in dismanlte
CGL 1986 DefectiveTransformer brought from GSS
condition Masaurhi.
Burnt Transformer
132/33 KV 20 MVA Telk NA NA NA NA and in Dismantle Very Old
condition
Bhagalpur Zone
Transformer is totally
132/33KV 132/33 KV 20 MVA
12 Kahalgaon NA NA NA NA NA burnt and dismentled
few year ago
132/33 KV Tan delta test between Oil leakage from main LOI has been sent to M/s
14 Banka(new 132/33 KV 50 MVA Telk 1988 16.09.18 Overhauling HV & LV has shown tank and radiator TELK for inspection of
) error transformer
132/33 KV 132/33 KV 20 MVA Dec 2016 Dismantled but not This transformer replaced
15 NA 2001 Not repaired Normal with 50MVA Power
Lakhisarai defective
Transformer in dec 2016.
Only main body lying
It Came from TSD
on ground(no any
16 132/33 KV 132/33 KV 12.5 Romania 1966 NA NA very much rusted. radiator,conservator, Karmnasha in jan
Sheikhpura MVA bushing etd 2005.after inspection it
may be declared obsolete.
available).
Defective since
132/33 KV 10 MVA IMP 2000 19/12/2008 NA NA Defective 19/12/2008 due to
sparking and heavy oil
leakage from tap changer
132/33 KV
20 Khagaria
132/33 KV
20 Khagaria Defective since
19/08/2018 Oil seapage from 19/08/2018 due to
132/33 KV 20 MVA HEL 1967 NA Defective bursting of y-phase bushing
radiator of HV side and heavy oil
thrown out in switchyard.
Patna Zone
BHEL M/s EMCO has suggested
Make, that defective transformer
24 132/33 KV 132/33 KV 20 MVA EMCO NA Repaired Dismantled at Banjari can be repaired
Banjari 22.08.18
repaired at their workshop in
2015 Jalgaon.
220/132/3
25 3 KV Dehri- CGL Make This transformer was sent
on-Sone repaired Repaired in to M/S AVAL in feb 2017 by
220/132K
V 100MVA by M/S 1978 Jul-16 2009 by M/S w.o 24/Tech/TRZ patna
AVAL in AVAL dated 09.12.16 for repair
2009 and is currently still lying.
132/33 KV 15 MVA
Out of service very long.
ELIN 1955 Dismantled
May be declared as scrap
132/33 KV
30 Chandauti
Name Main body only,accessories
132/33 KV plate not NA NA NA NA Dismantled not available(unseviceable
available since long)