Connect your laptop to the smartpack located above the rectifiers using the usb cable in the
port shown in the figure.
MD4 External Alarms Configuration
Make sure that the two Ethernet cables are punched down in the DDF module using this order:
1st Ethernet cable:
o Blue
o White/blue
o Green
o White/green
o Orange
o White/orange
o Brown
o White/brown
nd
2 Ethernet cable:
o Green
o Black/green
o Brown
o Black brown
o Grey
o Black/green
o Yellow
o Yellow/blue
MD4 External Alarms Configuration
Start the powrsuite program using this icon shown in the desktop.
A small window will pop up for connection, click on find COM-port #, and insert the number
shown in the small box next to it in the communication port box, as shown in the figure.
NB: for the password: 0003
MD4 External Alarms Configuration
From the top menu click on tools and then Import/Export Configuration (XML file)
MD4 External Alarms Configuration
Select the file Model_site_alarms and click open.
MD4 External Alarms Configuration
Then Click on next till it starts uploading like shown in the following figures.
MD4 External Alarms Configuration
Open the NEM and from the top menu choose allocate configuration rights.
Again click on configurations from the top menu and then Commissioning wizard.
Click on next till you reach the external alarms tab (click ok if you pass by any error)
MD4 External Alarms Configuration
o Site on Battery
o Rectifier Down
o Over Temperature
o Door Alarm
o Rectifier Major –Fan-
o Fan Fail
o Battery Deep Discharge
o Battery Low
Site on Batteries
Temperature Alarm 60 C
Door Open
Fan Failure-Rectifier
Click on the upper next and set all the 8 alarms on inactive mode.
MD4 External Alarms Configuration
Check the alarms tab and make sure that you don’t have contact alarms other than the Door
Alarm.
Close the Door while connected to see that the Door Alarm was cleared.
TEST OF ALARMS
MD4 External Alarms Configuration
1. You can use a magnetic object to make contact with the door magnet, this will deactivate door
alarm, and start fan if fan is ok.
2. Mains breaker on top right corner can be switched off, to test for Site on Battery alarm
3. Battery low and Battery Deep Discharge will lead to site going down, after it’s been on battery
for some time.
MD4 External Alarms Configuration