Test Report No.

7191073545-MEC13/01-EAH
dated 07 Nov 2013

Note: This report is issued subject to the Testing and Certification Regulations of the TÜV SÜD Group and the
General Terms and Conditions of Business of TÜV SÜD PSB Pte Ltd. In addition, this report is governed by the
terms set out within this report.

SUBJECT:

Impact performance, surface compression, fragmentation test and dimensional tolerance


measurements on tempered glass submitted by Da Di Glass (Singapore) Pte Ltd.

TESTED FOR:

Da Di Glass Singapore Pte Ltd


14 Sungei Kadut Avenue
Singapore 729650

Attn: Mr Marcus Lim

TEST METHOD:

SS 341 : 2001 Specification for safety glazing materials for use in buildings (human impact considerations)

DESCRIPTION OF SAMPLE:

1) 4 pieces of 6 mm thick clear tempered glass of nominal size 1900 x 860 x 6 mm were received for
impact test.

2) 1 piece of 6 mm thick clear tempered glass of nominal size 1900 x 860 x 6 mm was received for
dimensional measurements, thickness and squareness, overall bow and warpage test.

3) 1 piece of 6 mm thick clear tempered glass of nominal size 300 x 300 x 6 mm was received for surface
compression test.

4) 1 piece of 6 mm thick clear tempered glass of nominal size 700 x 500 x 6 mm was received for
fragmentation test.

Logo on glass specimen

Ng Lai Huat
Higher Associate Engineer Eng Aik How
Engineer
Building
Mechanical Centre

Laboratory: Phone : +65-6885 1333 Regional Head Office:


TÜV SÜD PSB Pte. Ltd. Fax : +65-6776 8670 TÜV SÜD Asia Pacific Pte. Ltd.
No.1 Science Park Drive E-mail: testing@tuv-sud-psb.sg 3 Science Park Drive, #04-01/05
Singapore 118221 www.tuv-sud-psb.sg The Franklin, Singapore 118223
Co. Reg : 199002667R Page 1 of 4
Test Report No. 7191073545-MEC13/01-EAH
dated 07 Nov 2013

RESULTS OF IMPACT TEST:

1. Measured thickness of glass = 5.96 mm


2. Weight of glass = 24.3 kg
3. Tabulation of results;

Impact test with Requirements in accordance to SS 341 : 2001


Observation
drop heights of Clause A.5 (g)
Shall comply with any of the following requirements
after impact:
4 pcs of glass did not break
300 mm 1) It has remained unbroken; or
Complied with item (1)

2) It has broken and numerous cracks or


fissures appear but no shear or opening
3 pcs of glass broke safely develops within the body of the glazing
Complied with item (3) material through which a 76 mm diameter
450 mm sphere can be passed freely; additionally, if
1 pc of glass did not break fragments are detached from the test piece up
Complied with item (1) to 3 min after impact, they shall, in total, weigh
no more than the mass equivalent to 10 000
mm² of the original test piece and the largest
single fragment shall weigh less than the mass
1 pc of glass did not break equivalent to 4400 mm² of the original test
600 mm
Complied with item (1) piece; or

3) It has broken and disintegration occurs but


the 10 largest crack-free fragments selected 3
min after impact, together weigh no more than
1 pc of glass broke safely the mass equivalent to 6500 mm² of the original
750 mm test piece; or
Complied with item (3)

4) It has broken and the breakage results in


several separate pieces, which may or may not
be retained in the frame. Those pieces that are
exposed after the impact shall be in
900 mm - accordance with one or both of the following:
a) The perimeter shall not be sharp.
b) Where any pointed protrusion occurs in
any perimeter, the length of the chord
between the two points which are
established when an arc of radius 25 mm,
1200 mm - whose centre is at the apex of the
protrusion, crosses the perimeter on each
side of the apex shall not be less 25 mm.

1500 mm -

Remark: The results of the impact performance test for the submitted tempered glass meet the Grade A
requirements of SS 341: 2001 up to maximum drop height of 750 mm.

Page 2 of 4
Test Report No. 7191073545-MEC13/01-EAH
dated 07 Nov 2013

RESULTS OF MEASUREMENTS:

Sample SS 341 : 2001


Test Measurement Result
Size Requirement for Glass
Dimensional Width (mm) 861 860 Pass (Clause 4.9)
Measurements Height (mm) 1900 1900 Pass ± 3 mm

SS 341 : 2001
Test Measurement Average Result
Requirement for Glass
1 5.968
(Clause 4.5)
2 5.983
Thickness (mm) 5.96 Pass Minimum 5.8 mm
3 5.935
Maximum 6.2 mm
4 5.956
Flatness – Localized 1 0.1
(Clause 4.10)
warp over any 200 mm 2 0.1 0.1 Pass
± 1 mm
span (mm) 3 0.1
Flatness – Overall bow 1 0.1
(Clause 4.10)
and warpage over any 2 0.1 0.1 Pass
± 1 mm
300 mm span (mm) 3 0.1

Measurement SS 341 : 2001


Difference between
Test of opposite Result Requirement for Glass
diagonals of glass
diagonals (Clause 4.8)
1 2088 Difference between the
Squareness
2 Pass two diagonals does not
(mm) 2 2086 exceed 10 mm.

RESULTS OF SURFACE COMPRESSION TEST;

Sample Stress Measurement Average SS 341 : 2001 (Clause 5.4)


Reference Points (MPa) (MPa) Requirement for Tempered Glass
1 115.20
2 115.20 Classification of tempered glass:
1 3 109.23 114.0
Thickness 8 mm and below - 79 MPa minimum
4 115.20
5 115.20
Note: The results of the surface compression test comply to SS 341 : 2001 requirement for tempered
glass.

RESULTS OF FRAGMENTATION TEST;

Sample SS 341 : 2001 (Clause 5.3)


Position No. of Particles Average
Reference Requirement for Tempered Glass

1 130 Minimum particle count of 40 per square


1 2 123 119 of 50 mm side for glass of nominal
105 thickness 6 mm.
3
Note:The results of the fragmentation test comply to SS 341 : 2001 requirement for tempered glass.

Page 3 of 4
Test Report No. 7191073545-MEC13/01-EAH
dated 07 Nov 2013

Please note that this Report is issued under the following terms :

1. This report applies to the sample of the specific product/equipment given at the time of its testing/calibration. The results are not used to
indicate or imply that they are applicable to other similar items. In addition, such results must not be used to indicate or imply that TÜV SÜD
PSB approves, recommends or endorses the manufacturer, supplier or user of such product/equipment, or that TÜV SÜD PSB in any way
“guarantees” the later performance of the product/equipment. Unless otherwise stated in this report, no tests were conducted to determine
long term effects of using the specific product/equipment.

2. The sample/s mentioned in this report is/are submitted/supplied/manufactured by the Client. TÜV SÜD PSB therefore assumes no
responsibility for the accuracy of information on the brand name, model number, origin of manufacture, consignment or any information
supplied.

3. Nothing in this report shall be interpreted to mean that TÜV SÜD PSB has verified or ascertained any endorsement or marks from any other
testing authority or bodies that may be found on that sample.

4. This report shall not be reproduced wholly or in parts and no reference shall be made by the Client to TÜV SÜD PSB or to the report or results
furnished by TÜV SÜD PSB in any advertisements or sales promotion.