PROFESSIONAL PLASTIC AUXILIARY MACHINERY

TECHNICAL PARAMETER

AIR-COOLED CHILLER Model LF5A LF8A LF10A LF12A LF15A LF20A LF25A LF30A LF40A LF50A

50Hz 13 21 26 30 42 55 60 84 111 119


kW/h 16 25 31 36 50 66 71 100 133
Cooling 60Hz 143
Capacity
50Hz 11223 17630 22446 25585 35948 47558 51170 71896 95116 102512
Kcal/h 13488 21156 26935 30702 43138 57070 61404 86258 114139 123015
60Hz
APPLICATION Input Power kW 6 8 10 12 16 20 23 33 41 48

Voltage 3PH-380V-50Hz (Or 200V/220V/415V 50Hz/60Hz)

Name R22 (Or R134a/R407c)


Refrigerant
• Plastic, electronics, electroplating, food,
Control Method
Outside The Balanced Thermal Expansion Valve
medical, chemical, printing, laser,
machining and other industries Types Fully Enclosed Scroll Compressor
Compressor
(kW)
3.73 5.97 7.46 8.95 11.19 14.92 18.64 22.38 29.84 37.28
Power

Types Tank Coil

(m³/h) 2.24 3.52 4.47 5.12 7.20 9.52 10.25 14.39 19.05 20.50
Chilled Water 2.68 4.22 5.37 6.15 8.63 11.42 12.29 17.37 29.86 24.60
Evaporator
(L)
50 120 120 120 200 250 250 250 320 370
Water Tank
SAFETY SYSTEM (Inch)
1 1-1/2 1-1/ 2 2 2 2 2-1/ 2 2-1/2 3 3
Water Pipe

Efficient Aluminum Finned Copper Jacket + Low Noise External Rotor Fan
Types
Condenser
• Compressor Overload Protection
(m³/h)
• Pump Overload Protection 5000 8000 10000 12000 15000 20000 25000 30000 40000 50000
Air Cooling
• Heat-Exchange Fail Protection
(kW)
• Refrigerant Safety Valve 0.37 0.75 0.75 0.75 1.5 2.25 2.25 2.25 3.75 4.5
Pump Power
• Freeze Protection
• High Pressure Protection H (m) 20 22 22 22 24 30 30 30 40 52

• Low Pressure Protection L (MM) 1360 1600 1570 1370 1875 2240 2240 1920 1920 2090
• Phase Failure Protection Dimensions
MOLDE FEATURES W (MM) 645 860 860 940 1100 1100 1110 1650 1650 2020
• Buzzer
H (MM) 1055 1555 1570 1750 1750 1700 1700 2100 2100 2100

Weight
Kg 300 400 450 450 600 880 980 1100 1250 1400
• No need to fit the cooling tower
• Japan Panasonic compressor, high efficiency, low noise, quiet operation Unit Conversion 1KW=860KCAL/HR 1RT=3024KCAL/HR 1BTU/HR=0.252KCAL/HR
• Emerson imported refrigeration parts
• Electrical parts are German SIEMENS genuine, to ensure stable operation of the
• Chilled water range 3-35℃, chilled water inlet temperature difference 3-8℃, cooling water range 18-37℃, cooling water inlet
machine
• Take a large capacity condenser and heat it can run easily temperature 3.5-10℃
• Minimize floor space and ease of installation • Refrigeration capacity is according to, the chilled water inlet and outlet temperature is 12℃/7℃, the cooling water inlet and outlet
• All pipe insulation design, to prevent local convection of the pipeline temperature is 35℃/30℃
• Finned condenser, better heat transfer, faster heat dissipation
• Above parameters are voltage 380v50hz 3 phase,refrigerant R22. Other parameters please call personnel
• Box type evaporator is provided with an automatic water replenishing device

01 SV TECHNOLOGIES SALES@SVTECHS.COM 02
PROFESSIONAL PLASTIC AUXILIARY MACHINERY

TECHNICAL PARAMETER

WATER -C OOLED C H ILLER Model L5W L8W L10W L12W L15W L20W L25W L30W L40W L50W

50Hz 15 24 30 34 49 61 68 97 122 137


kW/h 18 28 36 41 58 72 82 116 146
Cooling 60Hz 164
Capacity
50Hz 12900 20296 25800 29412 41710 52460 58738 83420 104920 117476
Kcal/h 15394 24338 30960 35260 50052 62092 70606 100104 125904 140972
60Hz

Input Power kW 5 8 10 11 15 20 22 31 39 49

Voltage 3PH-380V-50Hz (Or 200V/220V/415V 50Hz/60Hz)

Name R22 (Or R134a/R407c)


Refrigerant
Control Method Outside The Balanced Thermal Expansion Valve

Types Fully Enclosed Scroll Compressor


Compressor
APPLICATION (kW)
3.73 5.97 7.46 8.95 11.19 14.92 18.64 22.38 29.84 37.28
Power
• Plastic, electronics, electroplating, food,
Types Tank Coil
medical, chemical, printing, laser,
(m³/h) 2.6 4.1 5.2 5.9 8.4 10.0 11.8 16.7 20.6 23.5
machining and other industries 3.2 4.9 6.2 7.1 10.0 12.1 14.1 20.0 24.7 28.2
Chilled Water
Evaporator
(L)
50 120 120 160 200 250 250 265 330 350
Water Tank

(Inch)
1 1- 1/2 1-1/ 2 2 2 2-1/2 2-1/ 2 2-1/2 3 3
Water Pipe

SAFETY SYSTEM Types Shell And Tube

(m³/h) 3.5 5.2 6.8 7.9 10.7 13.9 15.8 20.5 27.8 31.6
Condenser Cooling Water 4.2 6.1 7.4 9.3 11.7 16.3 18.6 22.7 33.4 37.9

(Inch)
• Compressor Overload Protection 1-1/2 1-1/2 1-1/2 1-1/2 2 2 2-1/2 3 3 3
Water Pipe
• Pump Overload Protection
• Heat-Exchange Fail Protection Pump (kW)
0.37 0.75 0.75 0.75 1.5 2.25 2.25 2.25 3.75 4.5
Power
• Refrigerant Safety Valve
• Freeze Protection H (m) 20 22 22 22 24 30 30 30 40 52
• High Pressure Protection
MOLDE FEATURES L (MM) 1070 1300 1300 1300 1880 1880 1835 1880 2100 2200
• Low Pressure Protection Dimensions W (MM) 600 710 710 710 800 800 800 910 1100 1150
• Phase Failure Protection
• Buzzer H (MM) 975 1390 1390 1390 1500 1500 1514 1600 1960 2100
• Japan Panasonic compressor, high efficiency, low noise, quiet operation Weight
Kg 210 300 370 430 700 750 800 950 1200 1300
• Emerson imported refrigeration parts
• High efficiency evaporator and condenser can save more than 30% energy
Unit Conversion 1KW=860KCAL/HR 1RT=3024KCAL/HR 1BTU/HR=0.252KCAL/HR
• Electrical parts are German SIEMENS genuine, to ensure stable operation of
the • Chilled water range 3-35℃, chilled water inlet temperature difference 3-8℃, cooling water range 18-37℃, cooling water inlet
machine
temperature 3.5-10℃
• All pipe insulation design, to prevent local convection of the pipeline
• Refrigeration capacity is according to, the chilled water inlet and outlet temperature is 12℃/7℃, the cooling water inlet and outlet
• Box type evaporator is provided with an automatic water replenishing device
temperature is 35℃/30℃
• Above parameters are voltage 380v50hz 3 phase,refrigerant R22. Other parameters please call personnel

05 SV TECHNOLOGIES SALES@SVTECHS.COM 06
PROFESSIONAL PLASTIC AUXILIARY MACHINERY

WATER MOLD TEMPER ATU R E MA C H IN E

APPLICATION

TECHNICAL PARAMETER
• Precision Injection
• Rubber Machinery
• Plastic Machinery Model M6KWS M9KWS M12KWS M18KWS M24KWS M30KWS M40KWS M60KWS M90KWS M120KWS
• Roller
• Reactor
30-180℃
Temperature Range
• Medical Equipment

±0.1℃
Temperature Control Accuracy

Voltage 3PH-380V-50Hz
SAFETY SYSTEM
MOLDE FEATURES Heat Transfer Media
Water

Direct Cooling
Cooling method

kW 6 9 12 18 24 30 40 60 90 120
Heating Capacity

0.37 0.37 0.75 0.75 0.75 1.50 1.50


kW 4.00 4.50 4.50
Pump Power 0.75 0.75 1.50 1.50 1.50 2.24 2.24

42 42 56 56 56 110 110
L/min 367 400 400
Max Pump Flow 56 56 110 110 110 140 140

2.8 2.8 3.8 3.8 3.8 6.0 6.0


Kg/cm² 4.0 5.2 5.2
• P.I.D. control temperature, temperature difference error is 0.1 degree, System Pressure 3.8 3.8 6.0 6.0 6.0 8.5 8.5

constant temperature time, high efficiency, energy saving


• Start automatic Exhaust Inch 3/4 3/4 3/4 3/4 3/4 1 1 1 1 1
• LCD screen directly displays the measured temperature and set the Cooling Water Pipe
temperature • Shutdown Automatic Cooling
• Internal use of stainless steel, corrosion resistant, high pressure Inch 3/4 Χ 2 3/4 Χ 2 3/4 Χ 4 3/4 Χ 4 3/4 1 1 1 1 1
• Pump Overload Protection Circulation Water Pipe
explosionproof,
• Overheating Protection L (mm) 715 715 715 715 895 895 1010 1010 1500 1500
long temperature, high thermal efficiency
• High quality and high efficiency pump, which can adapt to the • Phase Failure Protection W (mm) 340 340 340 340 400 400 540 540 840 840
Dimensions
temperature H (mm) 650 650 650 650 710 710 670 670 1500 1500
control requirements of various molds
Weight Kg 65 90 105 138 168 198 218 288 658 688
• Beautiful appearance, save space

09 SV TECHNOLOGIES SALES@SVTECHS.COM 10
PROFESSIONAL PLASTIC AUXILIARY MACHINERY

OIL MOLD TEMPER ATU R E MA C H IN E

APPLICATION

• Precision Injection TECHNICAL PARAMETER


• Rubber Machinery
• Plastic Machinery
• Roller Model M6KWY M9KWY M12KWY M18KWY M24KWY M30KWY M40KWY M60KWY M90KWY M120KWY
• Reactor
• Medical Equipment Temperature Range
30-300℃

Temperature Control Accuracy


±0.1℃

MOLDE FEATURES Voltage 3PH-380V-50Hz


SAFETY SYSTEM Heat Transfer Media
Conduction Oil

Cooling method
Indirect cooling

Heating Capacity
kW 6 9 12 18 24 30 40 60 90 120

Pump Power 0.37 0.37 0.75 0.75 0.75 1.50 1.50


kW 4.00 4.50 4.50
0.75 0.75 1.50 1.50 1.50 2.24 2.24

Max Pump Flow 42 42 56 56 56 110 110


L/min 367 400 400
56 56 110 110 110 140 140
• P.I.D. control temperature, temperature difference error is 0.1 degree,
constant temperature time, high efficiency, energy saving System Pressure 2.8 2.8 3.8 3.8 3.8 6.0 6.0
Kg/cm² 4.0 5.2 5.2
3.8 3.8 6.0 6.0 6.0 8.5 8.5
• LCD screen directly displays the measured temperature and set the • Start automatic Exhaust
temperature Cooling Water Pipe
• Shutdown Automatic Cooling Inch 3/4 3/4 3/4 3/4 3/4 1 1 1 1 1
• Internal use of stainless steel, corrosion resistant, high pressure
explosionproof, • Pump Overload Protection
Circulation Water Pipe
Inch 3/4 Χ 2 3/4 Χ 2 3/4 Χ 4 3/4 Χ 4 3/4 1 1 1 1 1
long temperature, high thermal efficiency • Overheating Protection
• High quality and high efficiency pump, which can adapt to the
• Phase Failure Protection L (mm) 715 715 715 715 895 895 1010 1010 1500 1500
temperature
Dimensions
W (mm) 340 340 340 340 400 400 540 540 840 840
control requirements of various molds
• Beautiful appearance, save space H (mm) 650 650 650 650 710 710 670 670 1500 1500

Weight Kg 65 90 105 138 168 198 218 288 658 688

11 SV TECHNOLOGIES SALES@SVTECHS.COM 12