Split-range control is used when a single controller is employed to control two final-control elements

(two valves for example).

In such a system, the controller struggle to keep one controlled variable at the set point using two
manipulated variables.

Typically, split-range control is found in temperature control applications, but split-range control
applications extend far beyond temperature control.

Split Range Control Working Principle


The concept of split-range control is easier to understand when illustrated using applications such as
a temperature control.

In such an application, the process needs to be heated or cooled depending of the product
temperature.

The below figure shows how the temperature transmitter, the controller, and the two control valves
are connected for split-range control in a typical temperature control application.

In the diagram above, the 0% to 100% range of the controller output is split in two between the two
valves. If the controller output is between 0% and 50%, it is the cooling valve that operates.

This valve is fully open when the controller output is 0% and fully closed when the controller output is
50%. If the controller output is between 50% and 100%, it is the heating valve that is in operation.

At 50%, the heating valve starts to open and it is fully open at 100% of the controller output.
In a split-range control installation, there are different ways to connect the valves so that they
operate on two different ranges.

In the example above, the current to pressure converters are used to split the controller output in two
ranges.

The first converter responds to a current from 4 mA to 12 mA, while the other operates in a range
from 12 mA to 20 mA.

When using this type of wiring, no special controller or configuration is required for split-range
control.

Split Range Control Using Pneumatic Signals


The below figure shows a setup that performs the same split-range control but, in this case, the
signal from controller is a pneumatic signal. In such a setup, the two valves are mechanically
different.

The spring/diaphragm actuators of the two valves are selected so that their ranges of operation are
different.

The spring of the cooling valve is selected to allow the valve to open and close over a range of 20.7
kPa (3 psi) to 55.2 kPa (8 psi), while the heating valve closes and opens over a range of 55.2 kPa 8
psi to 89.6 kPa (13 psi).
The opening and closing of the valves follow the same rules for both of the setups shown above.

The graph shows the relationship between the opening of the valves and the controller output.

Dead band for split range control


The examples above are some of the simplest setups for split-range control. Of course, a controller
supporting split-range control may support more complex setups and correct some of the flaws
inherent to split-range control.

One problem that may arise with the setups detailed above is that the system may switch
continuously between cooling and heating when the controller output is around 50%.

To avoid continuous oscillation between the cooling and heating modes, a dead band is usually
added between the two ranges. A dead band can be added, for example, by setting a range of 0% to
49% for the cooling valve and a range of 51% to 100% for the heating valve.
Using split-range to control the input and output of a
reactor
The below figure shows another example of split-range control. In this example, chemical reactants
come into a reactor via a first control valve that limits the input flow.

Another control valve limits the output flow of the reactor. To ensure a high-efficiency chemical
reaction and a uniform product, the pressure inside the reactor must be kept above a given level.

A pressure transmitter reads the pressure in the reactor and a controller, connected for split-range
control, changes its output to control the pressure inside the reactor.

If the pressure is too low, the controller opens the input valve. If the pressure is still low, the
controller closes the output valve.

The below graph shows the opening of the control valves as a function of the controller output.
For this installation, the controller could also be configured so that the opening of the control valves
overlap at 50% of the controller output, as shown in below Figure.

In this case, the output valve is fully open when the controller output is 0%, both valves are 50%
open when the controller output is 50% and, finally, the input valve is fully open and the output valve
is fully closed when the controller output is 100%.
<img

Split-range control for a flare application


Gas flares are common in refinery and chemical plants. These devices are mainly used to burn the
excess of flammable gas in a vessel and prevent an eventual explosion of due to over-pressure.
When something goes wrong, the flare system is the insurance against disaster.

Many flare systems rely on split-range control for the evacuation of the gas.

The below figure shows a typical split-range arrangement for a flare application.


In a flare application, a fluid or a gas is processed in a vessel. The chemical reaction or the physical
condition to which the fluid is exposed allows obtaining the desired product plus an (undesired)
excess of flammable gas.

In the example above, it is a pressure transmitter that determines if the product is ready and if there is
a gas excess.

The below figure shows the opening of the control valves as a function of the controller output for
this flare application. If the pressure is low, the controller output is 0% and both valves are closed to
allow pressure to build up in the vessel and the formation of the product.

As the pressure increases, the control valve allowing the product to exit the vessel and go to the gas
compressor opens. This valve continues to open until the controller output reaches 50%.

At this point, the valve is fully open while the flare valve is still closed. If the pressure still increases,
it indicates to the controller that there is an excess of gas that must be evacuated.

Thus, the controller increases its output and the flare valve starts to open to evacuate the gas and
burn it. When the controller output reaches 100% both valves are fully open.