You are on page 1of 4

ADVANCED AND EVER ADVANCING MITSUBISHI ELECTRIC

1999 No.115E
MITSUBISHI NEW PRODUCT RELEASE
CC-LINK
GENERAL-PURPOSE
PROGRAMMABLE CONTROLLERS
AJ65SBT-RPT type CC-Link System Repeater (T-Branch) Module
New!
T-branch wiring with 10Mbps transmission speed now possible.
Introducing a repeater (T-branch) module which allows extended
transmission distances and T-branch wiring.

[ Features ]
1. T-branch wiring now possible with CC-Link system
By arranging this module between the CC-Link system modules, T-branch wiring can be used in CC-Link
systems for all transmission speeds (10Mbps, 5Mbps, 2.5Mbps, 625kbps, 156kbps).
Master station Repeater Intelligent
(AJ65SBT-RPT) Remote I/O station device station Remote device station

IN OUT

Remote I/O station


T-branch wiring is possible!

2. Realize an extended transmission distance with the CC-Link system


By using this module, a CC-Link system's transmission distance can be extended.
When several of these modules are used, the transmission distance can be extended up to ten stages.
Remote
*1 station
Master station Extend up to 13.2km!!

IN OUT

Remote I/O station Repeater(AJ65SBT-RPT)


IN OUT

IN OUT

*2
IN OUT

IN OUT

IN OUT
*2
*2
*2
1st stage 2nd stage 3rd stage 4th to 10th stage
*1 This indicates the maximum transmission distance when the transmission speed is set to 156kbps.
*2 Although not shown here, other remote stations can be connected between repeaters.
3. Compact module size
The same size as the AJ65SBTB1-8! compact remote I/O module has been achieved.
AJ65SBT-RPT Item Size(mm)
Height 50.0
Width 87.3
Depth 40.0

The Mitsubishi general-purpose programmable controller is manufactured


4. Install in the control panel with either screws or DIN rails at a factory certified for the environment management system standards
(ISO14001) and the quality system standards (ISO9001)
This module can be installed in the control panel with either screws
or DIN rails.
There are no restrictions for the module's orientation, so the module
can be installed at any angle.

–1– EC97J1113
[System configuration]
[Segment] [Segment (1st stage)]

Master station
Remote Repeater Intelligent
Remote I/O station device station (AJ65SBT-RPT) device station

IN OUT

Terminator Terminator Terminator Terminator(mandatory)


(mandatory) (mandatory) (mandatory)
Repeater (AJ65SBT-RPT)
[Segment (1st stage)] IN OUT

Terminator Intelligent Remote device


(mandatory) Remote I/O station device station station

Terminator
(mandatory)
Repeater (AJ65SBT-RPT)
[Segment (2nd stage)] IN OUT
Local station Remote I/O station

Terminator (mandatory)
Terminator (mandatory)

* What is a repeater?
The repeater is a module connected between each segment to expand the CC-Link system.
* What is a segment?
In a CC-Link system using repeaters, the devices between the terminators connected with bridging
wires are called a segment. (The conventional CC-Link system can be called a 1-segment
configuration.)
* The transmission speed of each segment must match the master station's transmission speed.

1. Maximum No. of connected segment stages


When using this module, communication can be carried out with remote stations at up to ten stages from
the master station's segment.

2. Maximum No. of connected modules in CC-Link system


Up to 64 remote I/O stations, remote device stations, local stations, standby master stations, intelligent
device stations and repeaters can be connected in one segment.
Even in a CC-Link system that uses repeaters, the No. of remote stations that can be controlled by one
master station will not change.

3. Conditions for usable master module


Use function version B and above.
When using AJ61BT11, A1SJ61BT11, AJ61QBT11 and A1SJ61QBT11 for the master module, a module
with function version B and above must be used.
The function version can be confirmed on the module's rating nameplate.
Use a module described as "9707 B" or above.
QJ61BT11 can be used regardless of the version.

–2–
[ Performance and Specifications ]
1. AJ65SBT-RPT performance and specifications
Item Specification
Transmission speed (bps) 156k/625k/2.5M/5M/10M selectable
Maximum No. of connected segment
10
stages (stages)
Maximum transmission distance for Differs according to transmission speed.
each segment (Same as normal CC-Link system (system with only one segment).)
Maximum No. of connected modules 64 modules
No. of occupied stations (stations) 0 (none)
Station No. setting No station numbers.
Voltage(V) DC20.4 to DC26.4
Repeater power supply
Current(A) 0.06 (at TYP. 24VDC)
Simulator noise 1500Vp-p
Noise withstand level With noise width 1µs, noise frequency 25 to 60Hz noise simulator
Fast transient/burst noise IEC801-4: 1kV
Withstand voltage 1 minute at 500VAC between DC external terminal batch and grounding
10MΩ or more with 500VDC Megger tester between DC external
Insulation resistance
terminal batch and grounding
Weight(kg) 0.2
Accessories Terminator (110Ω × 2 pcs., 130Ω × 2 pcs.)

2. Connection cable specifications


Use a CC-Link dedicated cable with the CC-Link system or else the system's performance cannot be
guaranteed.
Refer to the User's Manual of the master module in use for the CC-Link dedicated cable's specifications
and for purchasing information.

3. Maximum transmission distance

Local station Local station


Remote I/O station Master station Remote I/O station RemRemote I/O station Standby master station Standby master station RemRemote I/O station
Remote device Station Remote device Station Remote device Station Intelligent Intelligent Remote device Station
Repeater Repeater Repeater device station device station Repeater

Maximum transmission distance

Conditions Details
The maximum transmission distance in one segment is the same as the normal CC-
Link system (system with only one segment).
The maximum transmission distance within one segment will differ according to the
Transmission speed transmission speed.
Refer to the User's Manual of the master module in use for
details. (Handling of the cable between repeater stations is the same as for the
remote I/O station.)
When one connection stage is added, the maximum transmission distance for one
No. of connected segment stages
segment will be added.

–3–
[ Outside dimensions ]

40(1.57)

87.3(3.44)
78.3 +10 (installation pitch)
2-4.5 x 5.1 installation hole
(M4 installation screw)
16.(0.65)

PW TEST ERR. SD1 RD1 SD2 RD2 B RATE


TEST
RESET 4 2 1

IN OUT ON

AJ65SBT-RPT

(0.30)
7.5
DA1 DG1 +24V 24G DA2 DG2 NC NC
50(1.97)

IN DB1 SLD (FG) DB2 SLD (FG)


OUT

7.9(0.31)
DIN rail
(0.16)
4

Unit: mm(inch)

[ Manual ]
Manual name Manual shipment type IB No. Type code
AJ65SBT-RPT type CC-Link System Repeater
Enclosed with product IB-0800078 13JQ81
(T-branch) Module User's Manual

Country/Region Sales office Tel/Fax


U.S.A Mitsubishi Electric Automation Inc. Tel :1-847-478-2100
500 Corporate Woods Parkway Vernon Hills, IL 60061 FAX :1-847-478-0328
Brazil MELCO-TEC Rep. Com.e Assessoria Tecnica Ltda. Tel :55-21-221-8343
Av. Rio Branco, 123-15 ,and S/1507, Rio de Janeiro, RJ CEP 20040-005, Brazil FAX :55-21-221-9388
U.K Mitsubishi Electric Europe B.V. UK Branch Tel :44-1707-276100
Travellers Lane, Hatfield, Herts., AL10 8XB,UK FAX :44-1707-278695
Germany Mitsubishi Electric Europe B.V. German Branch Tel :49-2102-486-0
Gothaer Strasse 8 D-40880 Ratingen, GERMANY FAX :49-2102-486-717
South Africa MSA Manufacturing (Pty) Ltd. Tel :27-11-444-8080
P O Box 39733 Bramley 201 8 Johannesburg, South Africa FAX :27-11-444-8304
India Messung Systems Put,Ltd. Tel :91-212-793130
Electronic Sadan NO:111 Unit No15, M.I.D.C BHOSARI,PUNE-411026 FAX :91-212-798108
Singapore Mitsubishi Electric Asia Pte, Ltd. Tel :65-470-2480
307 ALEXANDRA ROAD #05-01/02, MITSUBISHI ELECTRIC BUILDING SINGAPORE 159943 FAX :65-476-7439
Indonesia P.T. Autoteknindo SUMBER MAKMUR Tel :62-21-336292
Kompleks Agung Sedayu Propertindo (Harco Mangga Dua) FAX :62-21-330378
Blok H No.4 JI Mangga Dua Raya Jakarta Pusat 10730-Indonesia.
Thailand F. A. Tech Co.,Ltd. Tel :66-2-295-2861
1138/33-34 Rama 3 Road, Yannawa, Bangkok 10120, Thailand FAX :66-2-295-2865
Hong Kong Ryoden International Ltd. Tel :852-2887-8870
10th Floor, Manulife Tower, 169 Electric Road, North Point, HongKong FAX :852-2887-7984
China Ryoden International Shanghai Ltd. Tel :86-21-6475-3228
3F Block5 Building Automation Instrumentation Plaza 103 Cao Bao Rd. Shanghai 200233 FAX :86-21-6484-6996
China
Taiwan Setsuyo Enterprise Co., Ltd. Tel :886-2-2299-2499
6F., No.105 Wu-Kung 3rd.RD, Wu-Ku Hsiang, Taipei Hsine, Taiwan R.O.C. FAX :886-2-2299-2509
Australia Mitsubishi Electric Australia Pty. Ltd. Tel :61-2-9684-7777
348 Victoria Road, PostalBag, No 2, Rydalmere, N.S.W 2116, Australia FAX :61-2-9684-7245
MITSUBISHI ELECTRIC CORPORATION
HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI. TOKYO 100-0005. TELEX J24532 CABLE MELCO TOKYO

99 (MEE) Specifications subject to change without notice.


Printed in Japan on recycled paper.