Quick Reference
for Remote Countroller
Follower remote
contoroller
Header remote Be sure to set
controller switch 2 to the
DIP switch DIP switch lower osition.
Type Name : RBC-AMT32E
Part No. : 43166011
Substitution : NO
Type of Remote : Wired
Reference : SX-A4EE
Teminal block for
remote controller
wire
Product used : Light commercial
Note : *4-way (4 ser ies)
* Duct ( 2 ser ies)
* Under ceiling ( 2 ser ies)
* High-wall ( 2 ser ies) Remote controller test run setup
1. Push and hold the button for 4 seconds or more
unitil "TEST" appears in the LCD display, then push the
button.
"TEST" appears in LCD display during the test run.
Category Temperature adjustment is not possible while "TEST" is
displayd. The test run applies considerable load on the
DI OK machine; therefore, it is recommended not to use the test
SDI OK mode beyond necessity
MiNi-SMMS OK
120
–1–
Multiple wiring diagram
(Max. 2 remote controllers can be set.)
Remote controller
Master remote controller address connector
Remote controller
Remote controller
check
Secondary
remote
controller
–2–
Part Name
Display section
RBC-AMT21E, RBC-AMT31E, RBC-AMT32E
In the display example, all indicators are displayed for the explanation.
In reality only, the selected contents are indicated.
• When turning on the main power switch and leak breaker at the first time, SETTING flashes on the display part of the
remote controller.
• While this display is flashing, the model is being automatically confirmed.Accordingly, wait for a while after SETTING
display has disappeared, and then use the remote controller.
18 Central control 9 20 19
78 9 8
2 9 2 20 2
CODE No. 1
3 10 1 3 3
SET DATA
45
UNIT No.
10
10 4 17
SETTING TEST R.C. No.
11 4 5
12 6 5 17 6 11
6 13 11 15 16
16 7 12
12 18 14 13
7 14 14 13
<RBC-AMT21E> <RBC-AMT31E> <RBC-AMT32E>
1 SETTING display 13 No function display
Displayed during setup of the timer etc. Displayed if there is no function even if the button
is pushed.
2 Operation mode select display
The selected operation mode is displayed. 14 Air volume select display
The selected air volume mode is displayed.
3 CHECK display
(AUTO) (HIGH)
Displayed while the protective device works or a
trouble occurs. (MED.) (LOW)
15 Louver Number display(exapmle:01, 02, 03, 04)
4 Timer time display (RBC-AMT32E only)
Time of the timer with H mark is displayed.
(When a trouble occurs, the check code is 16 Operation ready display
displayed.) Displayed when cooling or heating operation is
impossible because the outdoor temperature goes
5 Timer SET IN setup display out of the operable range.
When pushing the Timer SET IN button, the display
of the timer is selected in order of [OFF] → 17 Mode select control display
[OFF] repeat OFF timer → [ON] → No (RBC-AMT21E on function)
display. Displayed when pushing “Operation mode select
” button while the operation mode is fixed to
6 Filter display heating or cooling by the system manager of the
If “FILTER ” is displayed, clean the air filter. air conditioner.
7 TEST run display 18 Louver lock display(4-way Air Discharge
Displayed during a test run. Cassette Type 2H series only)
(RBC-AMT32E only)
8 Louver position display(4-way Air Discharge Displayed when there is a louver-locked unit in the
Cassette,2-way Air Discharge Cassette,1-way Air group (including 1 indoor unit by 1 outdoor unit).
Discharge Cassette, Under Ceilingand and High
Wall Type only (2H. 3H)) 19 Unit Number display (RBC-AMT32E only)
Displays louver position. Unit number of the indoor unit selected with the
unit select button or abnormal indication of the
9 SWING display indoor/outdoor unit.
Displayed during up/down movement of the louver.
20 Central control display
10 Set up temperature display (RBC-AMT21E on function)
The selected set up temp. is displayed. Displayed when the air conditioner is used under
11 Remote controller sensor display the central control in combination with a central
control remote controller.
Displayed while the sensor of the remote controller In case the remote controller is disabled by the
is used. central control system, flashes.The button
12 PRE-HEAT display (Heat-pump model only) operation is not accepted.
Displayed when the heating operation starts or Even when you push ON/OFF, MODE, orTEMP.
defrost operation is carried out. button, the button operation is not accepted.
While this indication is displayed, the indoor fan (Settings made by the remote controller vary with
stops or the mode enters in LOW. the central control mode. For details, referto the
Owner’s Manual of the central control remote
controller.)
–3–
Operation section
Push each button to select a desired operation.
• The details of the operation needs to be set up once, afterward, the air conditioner can be used by pushing
(RBC-AMT21E) / ON / OFF button only.
1 8 8
1 8
12 9 TEMP. ON / OFF
9 1 12 9
2 2 10 2 TIMER SET FAN MODE
3 10 TIME SAVE
A VENT
10
4 UNIT FILTER
L 4
5 SET CL
12 5
RESET TEST SET CL SWING/FIX UNIT LOUVER
11
6
11 53 6 7 4 3 7
<RBC-AMT21E> <RBC-AMT31E> <RBC-AMT32E>
–4–
2. Simple WIred Remote Controller How to perform the wiring
of the remote controller
Connectiom diagram
Remote
Terminal block controller
for remote A W
controller wiring B B
on the indoor unit
Earth
SMMS OK The outdoor unit will not operate for approx. 3 minutes
after the power supply has been turned on or the
SHRM OK operation has been stopped.
SMMS-i OK 3. After the test run has finished, push the [CHECK] button
SHRM-i OK again and check "TEST" on the LCD has gone off. (For
this remote controller, a release function of 60 minutes is
provided to prevent consecutive test runs.)
13
60
16
70
–5–
Part Name
• For Cooling Only type, , and are not displayed on LCD.
• Max. 8 indoor units can be operated by a remote controller.
• Once the operational items have been set, you can operate the previous condition by pushing the button only.
The following display is for explanation only and differs from the real display.
89
TEST C
SETTING F
4 12
1 10 TEST C
13
SETTING F
11
2 5 14
3 6
15 16
7
• When turning on the power switch to the remote controller for the first time,
the flashes. While is displayed, the automatic model check is operating.
Operate the remote controller after symbol has disappeared.
–6–
3. WIreless Remote Contoroller How to wire the signal receiving
Connection diagram
Indoor unit Signal receving part
Connection
Connect the wires from the signal receiving part to the
remote controller connection terminal block of the indoor
unit. (The terminals are nonpolar.).
• Clamp the redundant portion of the wires with the
clampers in the electric parts box.
Remote controller
connection
terminal block
Remote controller wiress
(Black type) Earth
Indoor unit (procured on site)
Indoor unit No.1 Earth Indoor unit No.2 Earth Indoor unit No.3 Earth Indoor unit No.4
Earth
–7–
Part Name
<RBC-AX31U(W)-E, RBC-AX31U(WS)-E>
• When turning on the power supply for the first time, it will take up to 3 minutes before the [SET DATA] symbol will
flash. This flashing display will last for around 1 minute.
While this display is flashing, the model is being automatically confirmed.
After the minute has passedand the [SET DATA] display has disappeared, you can then use the remote controller.
1
1
5 5
2 2
6 6
7 3
3 8 ADR
4
ADR
9 SET
CL
4 ACL SENSOR 7
10
<Display section> <Operation section>
1 Transmitting indication 1 Operation select button
Displayed while oerating the switches on the remote Selects the desired operation mode.
controller.
2 Fan mode select button
2 Mode display Selects a fan mode.
The selected operation mode is displayed.
[AUTO] mode is displayed on heat recovery type 3 Timer set button
only. TIMER SET button is used when the timer is setup.
–8–
< Hand Unit and Receiver >
RBC-AX31U(W)-E (Except North America)
RBC-AX31U(WS)-E (Except North America)
4
5
RBC-AX31U(W)-E
(White)
6
RBC-AX31U(WS)-E
(Black) Type Name : WH-H1JE2
Part No. : 43166006 1
3
Type Name : Receiver unit
Part No.
NOte
: Not assigned
: All maket
1 Emergency operation button
–9–
Sensor Unit wiring
Indoor unit Sensor unit P.C. board
Terminal block
for remote
controller
wire Indoor unit Indoor unit Indoor unit Indoor unit
No.1 No.2 No.3 No.N
19.5 130
58
65
177
Category
DI OK
SDI OK
MiNi-SMMS OK
SMMS OK
61 SHRM OK
SMMS-i OK
SHRM-i OK
– 10 –
Part Name
Procedure Description
1 The operation is not accepted for 5 minutes when power has been turned on at first time after installation, and
1 minute when power has been turned on at the next time and after. After the specified time has passed,
perform a test operation.
Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button.
2 Then change the fan speed to [High] using [Fan] button.
3 Set temperature to [18˚C] using [Temperature set] Set temperature to [30˚C] using [Temperature set]
button. button.
After checking the receiving sound “Pi”, immediately After checking the receiving sound “Pi”, immediately
4 push [Temperature set] button to set to [19˚C] push [Temperature set] button to set to [29˚C].
After checking the receiving sound “Pi”, immediately After checking the receiving sound “Pi”, immediately
5 push [Temperature set] button to set to [18˚C]. push [Temperature set] button to set to [30˚C].
2 3, 4, 5, 6
2, 7
– 11 –
Part Name
RBC-AX22CE, RBC-AX22CE2
Operation Manual
• When turning on the power supply for the first time, it will take up to 3 minutes before the [SET DATA] symbol will flash.
This flashing display will last for around 1 minute.
While this display is flashing, the model is being automatically confirmed.
After the minute has passed and the [SET DATA] display has disappeared, you can then use the remote controller.
1 1
5
2
5 6
2 6 3
7 ADR
3 8 SET
4
ADR
9 CL
4 ACL SENSOR
10 7
(Display section) (Operation section)
1 Transmitting indication 1 Operation select button
Displayed while operating the switches on the Selects the desired operation mode.
remote controller.
2 Fan mode select button
2 Mode display Selects a fan mode.
The selected operation mode is displayed.
[AUTO] mode is displayed on heat recovery type 3 Timer set button
only. TIMER SET button is used when the timer is setup.
– 12 –
< Hand Unit and Receiver >
RBC-AX22CE2 (Except North America)
P.C.Board (MCC-1504)
43459012
1
4 2
5 6
3
1 Temporary operation button 5 lamp
This lamp goes on when the timer is set.
2 Signal receiving part
The signal sent from the remote controller is 6 lamp
received. • In heating operation this lamp will come on in the
following cases;
3 Display lamp
The operation has started.
One of the displays will flash if afault has occurred. The temp. controller has worked.
4 lamp The unit is under defrost operation.
This lamp goes on during operation. • This lamp will flash when a fault has occurred.
• If a ”beep, beep” sound is heard, the MODE lamp on the display lamp goes on and the lamp and lamp
flash alternately, the operation to perform the desired mode has been unsuccessful.
– 13 –
58 19.5
4.4 x 9.4 long hole
13
83.5
83.5
177
70 4.4 x 5.4 long hole
Wiring diagram
Connector
wire of receiver unit (field supply)
– 14 –
Part Name
TCB-AX21E, TCB-AX21E2
Operation Manual
• When turning on the power supply for the first time, it will take up to 3 minutes before the [SET DATA] symbol will flash.
This flashing display will last for around 1 minute.
While this display is flashing, the model is being automatically confirmed.
After the minute has passed and the [SET DATA] display has disappeared, you can then use the remote controller.
1 1
5
2
5 6
2 6 3
7 ADR
3 8 SET
4
ADR
9 CL
4 ACL SENSOR
10 7
(Display section) (Operation section)
1 Transmitting indication 1 Operation select button
Displayed while operating the switc hes on the Selects the desired operation mode.
remote controller.
2 Fan mode select button
2 Mode display Selects a fan mode.
The selected operation mode is displayed.
[AUTO] mode is displayed on heat recovery type 3 Timer set button
only. TIMER SET button is used when the timer is setup.
– 15 –
< Hand Unit and Receiver >
TCB-AX21E2 (Except North America)
• If a ”beep, beep” sound is heard, the MODE lamp on the display lamp goes on and the lamp and lamp will
flash alternately, the operation to perform the desired mode has been unsuccessful.
– 16 –
Central Remote Countroller
for Schedule timer,
Weekly timer,
Central remote and
ON-OFF Countroller
4. Schedule Timer Multiple wiring diagram
Remote controller
(inside, rear)
DIP switch DIP switch DIP switch DIP switch
120 16
SHRM-i OK 2. Push the TEMP. / buttons, and set code No.14.
3. Push the TIME / buttons, and set the setting
data to 00 00 (factory setting) or 00 01.
4. Push the button. The setting data is entered
successfully if the display stops blinking and lights up.
5. Push the button.
* 00 00 (factory setting):
No settings are sent when the power is restored,
How to wire the remote controller and the scheduled operation is resumed as soon
Connection diagram * AWG20 (Use 0.5 mm2 wire) as the program time is reached after the power has
* Can not use the closed end been restored.
wire joint. * 00 01 :If there was a program which was to have run
* Use UL wires rated 300 V. during the power outage, it is resumed in
Terminal block
for remote Remote controller wiring accordance with what was programmed. If there is
controller wiring (procured on site) no program, operation resumes in accordance with
in indoor unit Remote controller what was being performed prior to the power outage.
Remote controller
terminal block
* Terminals A and B are non-polar
Remote
controller wire
Terminal block for (procured on site)
remote controller wiring
Indoor
Earth unit
– 18 –
Part Name
All display are shown lighted only for the purposes of description
31 1 2 3 4 5 6 7 8 9 10
30 11
29
28 12
27
26 13
25 24 23 22 21 20 19 18 17 16 15 14
(Display section)
1 Operation mode display 14 Indoor temperature
This indicates the mode of operation which is This appears when the intake temperature is
currently selected. displayed on the numeric display.
2 Air direction 15 Set temperature
This indicates the air direction which has been This appears when the set temperature is
selected. displayed on the numeric display.
3 Fixed louvers 16 Central control
This appears when the louvers are fixed. This appears when key operation limits are being
* It also appears when the remote controller function enforced by the central controller or other unit or
has been selected. when key operation limits have been set in the
program for the scheduled operation currently
4 Filter being executed.
This appears when it is time to inspect the filter.
17 Save operation
5 Grille up/down This appears while a save operation is being set or
This appears when the grille is goes up or goes executed.
down.
18 Ventilation operation
6 Self-cleaning operation This appears while the ventilation fan is operating.
This appears while self-cleaning is underway.
19 Numeric display
7 Defrosting The numbers of the indoor units or numbers of the
This appears while defrosting is underway during a scheduled operation programs are displayed here.
heating operation.
20 Air speed display
8 Ready This indicates the selected air speed.
This display appears on some models.
21 TEST
9 Heating ready (indoor fan stops while this is This appears while a test run operation is being
displayed) performed.
This appears before a heating operation starts or
while defrosting. 22 SETTING
This appears when the clock time, a program or
10 No function the timer is being set.
This appears when a button is pushed but there is
no corresponding function. 23 ERROR
This appears when there is an error in the program
11 FROST PROTECT operation setting input.
This appears during a frost protection operation.
24 Servicing
12 Numeric display This appears during servicing.
This displays the numeric value of the temperature,
the numerical order of the trouble history events or 25 Inspect
the code numbers when the functions are set. This appears when trouble has occurred.
13 Remote control sensor 26 Timer function display
This appears when the remote control sensor is This indicates the function whose operation has
used. been scheduled when a scheduled operation or
timer operation has been set.
– 19 –
27 Numeric display 29 Days of the week display
This indicates the present clock time, program
operation time or timer execution time.
30 Special holiday
This appears for a day of the week which has been
28 Operation reservation set as a special holiday.
This appears for the days of the week on which
programs have been set.
31 Day arrow
This indicates the current day of the week or day
on which a program is set.
50 32
49
33
48
34
47 35
46 36
45
37
44 43 42 41 40 39 38
(Operation section)
32 ON/OFF button 42 SET button
Shortly after this button is pushed, operation starts, Use this when entering the settings of the program
and operation stops shortly after the button is (for a scheduled operation or timer operation)
pushed again. which is being set.
33 FAN button 43 TEST button
Use this to select the desired air speed mode. Use this for servicing.
* This button is not normally used.
34 MODE button
Use this to select the desired operation mode. 44 FLT.RESET button
Use this to reset (extinguish) the filter display.
35 VENT button
Use this when a ventilation fan or other unit, 45 DAY button
purchased on the market, has been connected. Use this to select the targeted day of the week
when setting the clock or setting a program.
36 LOUVER button
Use this to select the louvers when setting the air 46 PROGRAM button
direction for each louver or when fixing the louvers Use this when starting and ending the program
in place. settings for scheduled operations.
37 UNIT button 47 Grille button
Use this to select the indoor unit to be operated Use this to raise or lower the grille.
when operating a multiple number of indoor units
using one remote controller. 48 SCHEDULE button
Use this when executing or releasing scheduled
38 SAVE button operations or when selecting ON or OFF for timer
Use this when performing save operations. operations.
39 SWING/FIX button 49 TEMP buttons
Use this to select the desired air direction or swing Push and to set the temperature to the
operation. desired value.
40 TIME buttons * These buttons are also used to raise or lower the
grille when the grille function is used.
Use this to set the clock or adjust the time when
the operating time is set. 50 ON lamp
41 CL button This lights during operation. It blinks when trouble
has occurred or when a protection operation is
Use this when clearing the setting of the program
performed.
(for a scheduled operation or timer operation)
which is being set.
– 20 –
5. Weekly schedule Timer Basic diagram
64 system central remote controller or
Wiring ON-OFF controller
specifications (1) Refrigerant system 1 Refrigerant system 3
(S-MMS) (S-MMS)
To power terminal
Refrigerant system 2
To communication
(SDI/DI)
P1 Indoor unit Outdoor unit
terminal
(Header unit) (Header unit)
U3 U4 Outdoor unit
U1 U2 U1 U2 U3 U4 U1 U2 U3 U4
L1
Schedule timer *1
TCC-LINK
adapter
L3 L2 L4
U3 U4 P1
P1 U1 U2 U1 U2 U1 U2
To communication
To communication
To power terminal
To power terminal
Indoor Indoor Indoor Indoor
unit unit unit unit
terminal
terminal
Type Name : TCB-EXS21TLE Remote Remote Remote Remote
Part No. : Not assigned Schedule controller controller controller Schedule controller
timer *2 timer *3
Substitution : NO Wiring specifications (2) Wiring specifications (2)
4
Inter-unit control wiring
U1 Clamp filter
U2
Field supply Communication
wiring
(blue + pink)
120
Schedule timer
16 Wiring procedures
120 Connect the provided connecting wire to the power
terminal (4P connector) of the schedule timer.
Category The terminal attached to the clamp filter must be
DI OK connected to the schedule timer.
SDI OK
MiNi-SMMS OK Wiring specifications (2)
If a 64 system central remote controller (or ON-OFF
SMMS OK controller) is not installed (power is supplied from the
SHRM OK indoor unit):
SMMS-i OK
SHRM-i OK Indoor unit control PCB
Wire joint
(Not used) Power terminal
System diagram (4P connector)
Communication
: Terminal board : Connector terminal (3P connector)
DC12V Wired Schedule timer
Schedule Indoor Outdoor
remote
timer unit unit
4 wires controller
The length of the power wiring must be no more
than 100 m.
– 21 –
Part Name
A: PROGRAM button
E: HOLIDAY button
B: PROG. COPY buttons
F: CANCEL button
C: CLEAR button
G: TIMER OFF button
D: Setting buttons
A: PROGRAM button Use to start setting programs and to enter program settings.
B: PROG. COPY buttons Use to copy programs to specific days in a schedule.
The button is not used.
C: CLEAR button Press to clear the settings of the currently displayed program.
• The current program is not cleared unless the button is pressed
after pressing the CLEAR button.
D: Setting buttons Use to make program settings and to set the present time.
Press to set groups for programmed operation.
Press to set today’s day and days of programmed operation.
Press to set the present time and times used in programmed operation.
Use to start/stop indoor units via the timer.
Not used.
Use to set programmed operation trigger time.
• Program settings are not entered unless the button is pressed at
the end of setting operations.
E: HOLIDAY button Press to set and cancel holidays during a scheduled week of operation.
F: CANCEL button Press to cancel the current program setting operation, copying operation or
holiday setting operation. When the CANCEL button is held down for 2
seconds, the current setting operation or copying operation is canceled and
the normal display returns.
G: TIMER OFF button Press to turn the timer OFF when timer operation will not be used for a long
period of time. When this button is held down for 2 seconds,
appears on the display. Programs cannot be run until the button is again held
down for 2 seconds.
• Some of these buttons are disabled when SDI/DI is used with the schedule
timer in the conventional weekly timer mode. If any of the disabled buttons is
pressed, appears on the display. For more information, contact your dealer.
– 22 –
Display
A B C D E
F
G
H I
B: Program schedule Appears under days that are scheduled for program operation.
indication ( )
F: (Disabled Feature) Displayed if the selected feature was disabled during installation.
indication
G: TIMER OFF indication Displayed when the timer has been turned OFF.
H: Copy mode indication Displayed when copying a program into a day of the schedule.
I: Present time Displays the present time on a 24-hour clock. Also, displays settings
in the various setting modes.
– 23 –
6. Central Remote Controller
Up to 64 units *
ALL ALL
160 21 69
6 148 (6) central control remote control
6
ZONE 1
Remote controller Remote controller
ZONE 1 ZONE 1
115
121
160
148
ZONE 2
121 Remote controller Remote controller
(6)
Category
DI OK
13
ZONE 3
47
36
SDI OK ZONE 3
Remote controller Remote controller
128
SMMS OK
SHRM OK ZONE 4
SMMS-i OK Remote controller Remote controller
Z-view ZONE 4 ZONE 4 Group1 Group2 Group16
SHRM-i OK central control remote control
ALL
– 24 –
Part Name
A: ALL/ZONE/GR B: ZONE select C: GROUP select
SELECT button button buttons
F: Operation
lamp
D: ON button
E: OFF button
G: MODE
button
H: Temperature
setting
buttons
A: ALL/ZONE/GR SELECT button Use this button to select one of the following:
ALL
ZONE1 ZONE2
ALL: Used for turning all the air conditioners on and off.
GR1 GR1
UNIT UNIT
UNIT UNIT
UNIT
ZONE: Used for turning all the air conditioners of each zone on and
GR2 GR2 off.
UNIT UNIT
GR3 GR3 GROUP: Used for turning all the air conditioners of each group on and
UNIT UNIT
off.
B: ZONE select button Use this button to select a zone (1 to 4) to operate individually.
C: GROUP select buttons Use these buttons to select a group (1 to 16) to operate individually.
– 25 –
Functions of buttons (Continued)
D: ON button This button is for turning the selected air conditioner on.
E: OFF button This button is for turning the selected air conditioner off.
F: Operation lamp This lamp lights when the unit is turned on.
G: MODE button Use this button to select one of the following five operations:
(AUTO) : Used to automatically set cooling or heating operation.
Some models are not provided with a mode for automatically
setting the cooling or heating operation.
(temperature range: 18 to 29 C)
(HEAT) : Used for normal heating operation.
For heat pump type, heat recovery type
(temperature range: 18 to 29 C)
(DRY) : Used for dehumidifying without changing the room tempe rature.
(temperature range: 18 to 29 C)
(COOL) : Used for normal cooling operation.
(temperature range: 18 to 29 C)
(FAN) : Used to run the fan only, without heating or cooling operation.
NOTE When the indication is displayed, you cannot change the mode from
and or to or and . To change the mode, turn off all
units once then select the mode again.
H: Temperature setting : Press this button to increase the temperature setting.
buttons
: Press this button to decrease the temperature setting.
I: FAN SPEED button
(AUTO) : The air conditioner automatically decides the fan speed.
(HI.) : High fan speed.
(MED.) : Medium fan speed.
(LO.) : Low fan speed.
J: FLAP button 1. Use this button to set the airflow direction to a specific angle.
The airflow direction is displayed on the remote control unit.
Operation mode Number of airflow direction settings
(COOL) or (DRY) 3
(HEAT) or (FAN) 5
(AUTO)
Cooling mode: 3
Heating mode: 5
• In the cool mode and dry mode, when the flaps are set in a
CAUTION downward position, condensation may form and drip around
the vent.
Do not move the flap with your hands.
NOTE This function is available only for 4-Way air discharge cassette type and
Under ceiling type.
( ) 2. Use this button to make the airflow direction sweep up and down
automatically.
Press this button several times until the ( ) symbol appears on
the display.
NOTE 1) The flap setting can be performed only for units that have no remote
controllers.
2) In the ALL or ZONE modes, no flap settings can be performed. If
necessary, you should select the GR mode and use the FLAP button.
– 26 –
Functions of buttons (Continued)
K: CHECK button This button is used only when servicing the air conditioner.
L: CENTRAL CTRL button Use this button to inhibit the individual operation by a remote controller
as follows:
O: VENTILATION button Use this button when you installed a fan available in the market.
Pressing this button turns the fan on and off.
When turning off the air conditioner, the fan will also turn off. While
the fan is operating, will appear in the display.
If is displayed when pressing the ventilation button, no fans are
installed.
– 27 –
Display
B H
G C
E J
K
D
I
A
Description
A: When the unit is in the heating standby mode, the indicator appears.
B: The currently selected operation mode is displayed.
C: The currently selected FAN SPEED, Airflow Direction and SWEEP settings are
displayed.
D: This indication appears when the filter needs cleaning.
E: This indication appears only when an abnormality occurs within a unit.
F: The currently selected mode (ALL, ZONE or GROUP), ZONE number and GROUP
number are displayed.
GROUP number display (no figure: no number registered)
GROUP state display ( : registered group, : currently selected
group)
Operation state display ( : on, no sign: off, : alarm)
– 28 –
How to start group operation
To start group operation
Stop
2
1 3
9 6
7
8
Power Turn the power supply switch on more than 12 hours before starting operation.
2 Select the ZONE No. including the group to be operated by pressing ZONE button.
6 Set the desired temperature by pressing one of the temperature setting buttons .
7 Set the desired fan speed by pressing the FAN SPEED button.
AUTO Depending on the difference between the temperature setting and the room temperature,
Operation heating and cooling alternate automatically so that a uniform room temperature is maintained.
Some models are not provided with a mode for automatically setting the cooling or heating
operation.
Stop Confirming the GROUP No. to be selected, press the OFF button.
NOTE The flap setting can be performed only for units that have no remote controllers.
– 29 –
How to start collective operation
To start collective operation (ALL or ZONE)
Stop
2 5
Power Turn the power supply switch on 12 hours or more before starting operation.
5 Set the desired temperature by pressing one of the temperature setting buttons .
6 Set the desired fan speed by pressing the FAN SPEED button.
Stop Confirming the ZONE No. to be selected or ALL indication, press the OFF button.
NOTE In the ALL or ZONE mode, no flap settings can be performed. If necessary, you should
select the GR mode and use the FLAP button.
– 30 –
7. ON-OFF Controller
Basic wiring
Clamp for electrical wiring
Type Name : TCB-CC163TLE / TCB-CC163TLE2
Part No. : Not assigned
Connector (CN02)
Substitution : TCB-CC163TLE2
for weekly timer
Type of Remote : ON-OFF controller (optional)
Reference : NO
Product used : VRF
Note :
CN02
Earth for
NO LONGER AVAILABLE power N
U1/U3
PCB
wiring L
U2/U4
C3
B3 B2 B1 A3 A2 A1
C4
116
N:
Power supply ( 50 Hz/60 Hz, 220 . 240 V)
L:
• Power supply wire specification: Cable 3-core,
160
in conformance with Design 60245 IEC 57.
6 148 (6) 14 69 • Fix the wires with cord clamp.
6
U1/U3:
Central control wiring. (Low voltage)
U2U4:
Z C3: Auxiliary
115
121
160
148
122
47
SMMS OK
128
80
– 31 –
Part Name
A : ON/OFF button
B : ALL ON button
B: All ON button Press this to start up all the air conditioners at the same time.
– 32 –
8. Function Selecting Item (DN)
Table 1. Setting data (CODE No. table (example))
Concealed Concealed Under High High Medium
DN Item Setting data Factory-set value 4-way 2-way 1-way duct duct high ceiling wall static duct static duct Slim duct
standard standard
01 Filter sign lighting time Depending on Type
02 Filter pollution level 0000: standard
03 Central control address 0099: Not determined
04 Specific indooor unit priority 0000: No priority
06 Heating suction temperature shift 0002: +2˚C (flooring installation type: 0)
0C PREPARING indication selection 0000: Normal
0d Existence of [AUTO] mode 0000: Not provided
0E Follows operation mode of header 0000: Not provided
0F Cooling only 0000: Heat pump
10 Type Depending on model type
11 Indoor unit capacity Depending on capacity type
12 System address 0099: Not determined
13 Indoor unit address 0099: Not determined
14 Group address 0099: Not determined
19 Louver type (wind direction adjustment) Depending on Type.
1E Temperature range of cooling/heating automatic SW control point 0003: 3 deg (Ts ± 1.5)
28 Power failure automatic recovery 0000: None
29 Operation condition of humidifier 0000: Usual
2A Option/Abnormal input (CN70) SW 0002: Humidifier
2b Thermo output SW (T10 ) 0000: Thermo ON
2E HA terminal (T10-1) selection 0000: Operation input
30 Automatic elevating grille 0000: Unavailable
31 Ventilation fan (standalone) 0000: Not available
32 Sensor SW (Selection of static pressure) 0000: Body sensor
33 Temperature unit select 0000: ˚C
40 Humidifier control (+ drain pump control) 0003: Humidifier ON + Pump OFF
5d High ceiling SW 0000: Standard
60 Timer setting (wired remote controller) 0000: Available
62 Anti-ceiling smudging control 4- way Air discharge cassette type only
69 Louver setting for cooling 0000: Normal
8b Correction of feeling of strong heating 0000: Not provided
C2 Demand setting (outdoor unit current demand) 0075: 75 %
d0 Remote controller operation save function 0001: Enable
d1 Frost protection function 0000: None
d3 Rotation number of the self-clean operation 0001: 210ypm(at self-clean operation)
F0 Swing mode 0001: Standard
F1 Louver fixing position (Flap No. 1) 0000: Not fixed
F2 Louver fixing position (Flap No. 2) 0000: Not fixed
F3 Louver fixing position (Flap No. 3) 0000: Not fixed
F4 Louver fixing position (Flap No. 4) 0000: Not fixed
– 33 –
SDI (4Series example)
Function selection item No. (DN) list
0000: Standard
02 Filter stain level 0000: Standard
0001: Heavy stain (Half of standard time)
11 Indoor unit capacity 0000: Undecided 0001 to 0034 According to capacity type
12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Undecided
13 Indoor unit address 0001: No.1 unit to 0064: No.64 unit 0099: Undecided
28 Automatic reset of power failure 0000: None 0001: Provided 0000: None
0000: No control
Humidifier control 0001: Humidifier + Vaporizing type (Pump ON)
0003: Humidifier ON
40 (+Drain pump control) 0002: Humidifier + Supersonic type
Pump OFF
(This function is not provided.) (Pump ON when specified time elapsed)
0003: Humidifier + Natural drain type (Pump OFF)
C2 Current demand X% to outdoor unit 0050: 50% to 0100: 100% 0075: 75%
– 34 –
MiNi-SMMS
DN Item Description At shipment
Filter display delay timer 0000: None 0001: 150H According to type
01 0002: 2500H 0003: 5000H
0004: 10000H
Dirty state of filter 0000: Standard 0000: Standard
02
0001: High degree of dirt (Half of standard time)
Central control address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
03
0099: Unfixed
Specific indoor unit 0000: No priority 0001: Priority 0000: No priority
04
priority
Heating temp shift 0000: No shift 0001: +1 ˚C 0002: +2 ˚C
06 0002: +2 ˚C to 0010: +10 ˚C (Floor type 0000: 0 ˚C)
(Up to +6 recommended)
Existence of [AUTO] 0000: Provided 0001: Not provided
0d
mode 0001: Not provided (Automatic selection from connected outdoor unit)
Cooling only 0000: Heat pump 0000: Heat pump
0F
0001: Cooling only (No display of [AUTO] [HEAT])
Type 0001: 4-way Air Cassette Depending on model
10
type
Indoor unit capacity 0000: Unfixed 0001 to 0034 According to capacity
11
type
12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Unfixed
13 Indoor unit address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
Group address 0000: Individual 0001: Outdoor unit of group 0099: Unfixed
14
0002: Follower unit of group
Louver type 0000: No louver 0001: Swing only According to type
(Air direction 0002: (1-way Air Cassette type, Ceiling type)
19 adjustment)
0003: (2-way Air Cassette type)
0004: (4-way Air Cassette type)
Temp difference of 0000: 0 deg to 0010: 10 deg 0003: 3 deg
[AUTO] mode selection (For setup temperature, reversal of COOL / HEAT by ± (Data value) / 2) (Ts±1.5)
1E
COOL → HEAT,
HEAT → COOL
Automatic restart of 0000: None 0001: Restart 0000: None
28
power failure
Selection of option / error 0000: Filter input 0001: Alarm input (Air washer, etc.) 0002: None
2A
input (CN70) 0002: None
31 Ventilating fan control 0000: Unavailable 0001: Available 0000: Unavailable
32 TA sensor selection 0000: Body TA sensor 0001: Remote controller sensor 0000: Body TA sensor
33 Temperature unit select 0000: ˚C (factory default) 0001: ˚F 0000: ˚C
Swing mode 0001: Standard 0002: Dual swing 0001: Standard
F0
0003: Cycle swing
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F1
(Louver No.1) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F2
(Louver No.2) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F3
(Louver No.3) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F4
(Louver No.4) 0005: Downward discharge position
– 35 –
DN Item Description At shipment
High-ceiling adjustment 1-way air cassette (SH) 0000: Standard
(Air flow selection) Value Type AP015, AP018 AP024
0000 Standard (factory default) 3.5 m or less 3.8 m or less
0001 High-ceiling (1) 4.0 m or less 4.0 m or less
0003 High-ceiling (3) 4.2 m or less 4.2 m or less
Ceiling
Value Type AP015~AP056
0000 Standard (factory default) 3.5 m or less
0001 High-ceiling (1) 4.0 m or less
– 36 –
SMMS
DN Item Description At shipment
01 Filter sign lighting 0000 : None 0001 : 150H According to type
time 0002 : 2500H 0003 : 5000H
0004 : 10000H
02 Dirty state of filter 0000 : Standard 0001 : High degree of dirt 0000 : Standard
(Half of standard time)
03 Central control 0001 : No.1 unit to 0064 : No.64 unit 0099 : Unfixed
address 0099 : Unfixed
04 Specific indoor unit 0000 : No priority 0001 : Priority 0000 : No priority
priority
06 Heating temp shift 0000 : No shift 0001 : +1˚C 0002 : +2˚C
0002 : +2˚C to 0010 : +10˚C (Floor type 0000 : 0˚C)
(Up to +6 recommended)
0d Existence of 0000 : Provided 0001 : Not provided 0001 : Not provided
automatic cool/heat (Automatic selection from
mode connected outdoor unit)
0F Cooling only 0000 : Heat pump 0001 : Cooling only 0000 : Heat pump
(No display of [AUTO] [HEAT])
12 Line address 0001 : No.1 unit to 0030 : No.30 unit 0099 : Unfixed
13 Indoor unit address 0001 : No.1 unit to 0064 : No.64 unit 0099 : Unfixed
14 Group address 0000 : Individual 0001 : Header unit of group 0099 : Unfixed
0002 : Follower unit of group
19 Flap type 0000 : Not provided 0001 : Swing only According to type
(Adjustment of air 0004 : [4-way Air Discharge Cassette type] and [Under Ceiling type]
direction)
1E Temp difference of 0000 : 0 deg to 0010 : 10 deg 0003 : 3 deg
automatic cooling/ (For setup temperature, reversal of COOL/HEAT by ± (Data value)/2) (Ts±1.5)
heating mode
selection COOL →
HEAT, HEAT
→ COOL
28 Automatic restart of 0000 : None 0001 : estart 0000 : None
power failure
2A Selection of option/ 0000 : Filter input 0001 : Alarm input (Air washer, etc.) 0002 : Humidifier
error input (CN70) 0002 : Humidifier input
2E HA terminal (CN61) 0000 : Usual 0001 : Leaving-ON prevention control 0000 : Usual
select (HA terminal)
30 Automatic elevating 0000 : Unavailable 0001 : Available 0000 : Unavailable
grille (Standard, (Auto grille, Oil guard,
Oil guard panel) Auto grille panel)
31 Ventilating fan 0000 : Unavailable 0001 : Available 0000 : Unavailable
control
32 TA sensor selection 0000 : Body TA sensor 0001 : Remote controller sensor 0000 : Body TA sensor
33 Temperature unit 0000 : ˚C (at factory shipment) 0001 : ˚F 0000 : ˚C
select
40 Control for humidifier 0000 : None 0001 : Humidifier + Vaporizing system 0003 : Humidifier ON,
(+ drain pump (Pump ON) Pump OFF
control) 0002 : Humidifier + Ultrasonic system
(Pump ON after specified time passed) (Unused)
0003 : Humidifier + Natural drain system (Pump OFF)
5d High ceiling selection [4-way Air Discharge Cassette type] and [Under Ceiling type] 0000 : Standard
(Air volume selection) 0000 : Standard filter
0001 : Super-long life
[Concealed Duct Standard type]
0000 : Standard static pressure 0001 : High static pressure 1
(40Pa) (70Pa)
0003 : High static pressure 2 0005 : Correspond to quiet sound
(100Pa) 0006 : Low static pressure (20Pa)
60 Timer set 0000 : Available (Operable) 0001 : Unavailable (Operation prohibited) 0000 : Available
(Wired remote
controller)
62 Smudging-proof 0000 : Clear 4-way Air Discharge
control clear Cassette type only
92 Outside interlock 0000 : Operation stop 0001 : Release communication signal 0000 : Operation stop
release condition receive
– 37 –
SMMS-i
DN Item Description At shipment
Filter display delay timer 0000: None 0001: 150H According to type
01 0002: 2500H 0003: 5000H
0004: 10000H
Dirty state of filter 0000: Standard 0000: Standard
02
0001: High degree of dirt (Half of standard time)
Central control address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
03
0099: Unfixed
Specific indoor unit 0000: No priority 0001: Priority 0000: No priority
04
priority
Heating temp shift 0000: No shift 0001: +1˚C 0002: +2˚C
06 0002: +2˚C to 0010: +10˚C (Floor type 0000: 0˚C)
(Up to +6 recommended)
Existence of [AUTO] 0000: Provided 0001: Not provided
0d
mode 0001: Not provided (Automatic selection from connected outdoor unit)
Cooling only 0000: Heat pump 0000: Heat pump
0F
0001: Cooling only (No display of [AUTO] [HEAT])
Type 0001: 4-way Air Discharge Cassette Depending on model
10
type
Indoor unit capacity 0000: Unfixed 0001 to 0034 According to capacity
11
type
12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Unfixed
13 Indoor unit address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
Group address 0000: Individual 0001: Header unit of group 0099: Unfixed
14
0002: Follower unit of group
Louver type 0000: No louver 0001: Swing only According to type
(Air direction 0002: (1-way Air Discharge Cassette type, Under Ceiling type)
19 adjustment)
0003: (2-way Air Discharge Cassette type)
0004: (4-way Air Discharge Cassette type)
Temp difference of 0000: 0 deg to 0010: 10 deg 0003: 3 deg
[AUTO] mode selection (For setup temperature, reversal of COOL/HEAT by ± (Data value)/2) (Ts±1.5)
1E
COOL → HEAT,
HEAT → COOL
Automatic restart of 0000: None 0001: Restart 0000: None
28
power failure
Selection of option/error 0000: Filter input 0001: Alarm input (Air washer, etc.) 0002: None
2A
input (CN70) 0002: None
31 Ventilating fan control 0000: Unavailable 0001: Available 0000: Unavailable
32 TA sensor selection 0000: Body TA sensor 0001: Remote controller sensor 0000: Body TA sensor
33 Temperature unit select 0000: ˚C (at factory shipment) 0001: ˚F 0000: ˚C
Swing mode 0001: Standard 0002: Dual swing 0001: Standard
F0
0003: Cycle swing
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F1
(Louver No.1) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F2
(Louver No.2) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F3
(Louver No.3) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F4
(Louver No.4) 0005: Downward discharge position
– 38 –
SHRM
DN Item Description At shipment
01 Filter sign lighting 0000 : None 0001 : 150H According to type
time 0002 : 2500H 0003 : 5000H
0004 : 10000H
02 Dirty state of filter 0000 : Standard 0001 : High degree of dirt 0000 : Standard
(Half of standard time)
03 Central control 0001 : No.1 unit to 0064 : No.64 unit 0099 : Unfixed
address 0099 : Unfixed
04 Specific indoor unit 0000 : No priority 0001 : Priority 0000 : No priority
priority
06 Heating temp shift 0000 : No shift 0001 : +1˚C 0002 : +2˚C
0002 : +2˚C to 0010 : +10˚C (Floor type 0000: 0˚C)
(Up to +6 recommended)
0d Existence of 0000 : Provided 0001 : Not provided 0001 : Not provided
automatic cool/heat (Automatic selection from
mode connected outdoor unit)
0F Cooling only 0000 : Heat pump 0001 : Cooling only 0000 : Heat pump
(No display of [AUTO] [HEAT])
10 Type 0000 : (1-way air discharge cassette) According to model type
0001 : (4-way air discharge cassette) to 0037
11 Indoor unit capacity 0000 : Unfixed 0001 to 0034 According to capacity type
12 Line address 0001 : No.1 unit to 0030 : No.30 unit 0099 : Unfixed
13 Indoor unit address 0001 : No.1 unit to 0064 : No.64 unit 0099 : Unfixed
14 Group address 0000 : Individual 0001 : Header unit of group 0099 : Unfixed
0002 : Follower unit of group
19 Flap type 0000 : Not provided 0001 : Swing only According to type
(Adjustment of air 0004 : [4-way Air Discharge Cassette type] and [Under Ceiling type]
direction)
1E Temp difference of 0000 : 0 deg to 0010 : 10 deg 0003 : 3 deg
automatic cooling/ (For setup temperature, reversal of COOL/HEAT by ± (Data value)/2) (Ts±1.5)
heating mode
selection COOL →
HEAT, HEAT →COOL
28 Automatic restart of 0000 : None 0001 : Reset 0000 : None
power failure
29 Operation condition 0000 : Usual 0001 : Condition ignored 0000 : Usual
of humidifier (Detection control for heat exchanger temperature)
2A Selection of option/ 0000 : Filter input 0001 : Alarm input (Air washer, etc.) 0002 : Humidifier
error input (CN70) 0002 : Humidifier input
2E HA terminal (CN61) 0000 : Usual 0001 : Leaving-ON prevention control 0000 : Usual
select (HA terminal)
30 Automatic elevating 0000 : Unavailable 0001 : Available 0000 : Unavailable
grille (Standard, (Auto grille, Oil guard,
Oil guard panel) Auto grille panel)
31 Ventilating fan 0000 : Unavailable 0001 : Available 0000 : Unavailable
control
32 TA sensor selection 0000 : Body TA sensor 0001 : Remote controller sensor 0000 : Body TA sensor
33 Temperature unit 0000 : ˚C (at factory shipment) 0001 : ˚F 0000 : ˚C
select
40 Control for humidifier 0000 : None 0001 : Humidifier + Vaporizing system 0003 : Humidifier ON,
(+ drain pump control) (Pump ON) Pump OFF
0002 : Humidifier + Ultrasonic system
(Pump ON after specified time passed) (Unused)
0003 : Humidifier + Natural drain system (Pump OFF)
5d High ceiling selection [4-way Air Discharge Cassette type] and [Under Ceiling type] 0000 : Standard
(Air volume selection) 0000 : Standard filter
0001 : Super-long life
[Concealed Duct Standard type]
0000 : Standard static pressure 0001 : High static pressure 1
(40Pa) (70Pa)
0003 : High static pressure 2 0005 : Correspond to quiet sound
(100Pa) 0006 : Low static pressure (20Pa)
60 Timer set 0000 : Available (Operable) 0001 : Unavailable (Operation prohibited) 0000 : Available
(Wired remote
controller)
62 Smudging-proof 0000 : Clear 4- way Air Discharge
control clear Cassette type only
92 Outside interlock 0000 : Operation stop 0001 : Release communication signal 0000 : Operation stop
release condition receive
– 39 –
SHRM-i
DN Item Description At shipment
Filter display delay timer 0000: None 0001: 150H According to type
01 0002: 2500H 0003: 5000H
0004: 10000H
Dirty state of filter 0000: Standard 0000: Standard
02
0001: High degree of dirt (Half of standard time)
Central control address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
03
0099: Unfixed
Specific indoor unit 0000: No priority 0001: Priority 0000: No priority
04
priority
Heating temp shift 0000: No shift 0001: +1 C 0002: +2 C
06 0002: +2 C to 0010: +10 C (Floor type 0000: 0 C)
(Up to +6 recommended)
Existence of [AUTO] 0000: Provided 0001: Not provided
0d
mode 0001: Not provided (Automatic selection from connected outdoor unit)
FS unit 0000: Standard (1 FS unit : 1 indoor unit) 0000:Standard
0E Connection set of multiple 0001: Multiple units connected ((1 FS unit : Multiple indoor units)
indoor units
Cooling only 0000: Heat pump 0000: Heat pump
0F
0001: Cooling only (No display of [AUTO] [HEAT])
Type 0001: 4-way Cassette Depending on model
10
type
Indoor unit capacity 0000: Unfixed 0001 to 0050 According to capacity
11
type
12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Unfixed
13 Indoor unit address 0001: No.1 unit to 0048: No.48 unit 0099: Unfixed
Group address 0000: Individual 0001: Header unit of group 0099: Unfixed
14
0002: Follower unit of group
Group address 0000: No louver 0001: Swing only According to type
19 0002: (1-way Cassette type, Ceiling type)
0003: (2-way Cassette type)
0004: (4-way Cassette type)
Temp difference of 0000: 0 deg to 0010: 10 deg 0003: 3 deg
1E [AUTO] mode selection (Ts ±1.5)
COOL → HEAT, (For setup temperature, reversal of COOL/HEAT by } (Data value)/2)
HEAT → COOL
Automatic restart of 0000: None 0001: Restart 0000: None
28
power failure
Selection of option/error 0000: Filter input 0001: Alarm input (Air washer, etc.) 0002: None
2A
input (CN70) 0002: None
HA terminal (CN61) 0000: Usual 0001: Leaving-ON prevention control 0000: Usual
2E
select 0002: Fire alarm input (HA terminal)
31 Ventilating fan control 0000: Unavailable 0001: Available 0000: Unavailable
32 TA sensor selection 0000: Body TA sensor 0001: Remote controller sensor 0000: Body TA sensor
33 Temperature unit select 0000: C (at factory shipment) 0001: F 0000: C
Swing mode 0001: Standard 0002: Dual swing 0001: Standard
F0
0003: Cycle swing
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F1
(Louver No.1) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F2
(Louver No.2) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F3
(Louver No.3) 0005: Downward discharge position
Louver fixed position 0000: Release 0001: Horizontal discharge position 0000: Not fixed
F4
(Louver No.4) 0005: Downward discharge position
– 40 –
DN Item Description At shipment
High-ceiling adjustment 1-way cassette (SH) 0000: Standard
(Air flow selection)
Value Type AP015, AP018 AP024
0000 Standard (factory default) 3.5 m or less 3.8 m or less
0001 High-ceiling (1) 4.0 m or less 4.0 m or less
0003 High-ceiling (3) 4.2 m or less 4.2 m or less
2-way cassette
Value Type AP007~AP030 AP036~AP056
0000 Standard (factory default) 2.7 m or less 2.7 m or less
0001 High-ceiling (1) 3.2 m or less (*) 3.0 m or less
0003 High-ceiling (3) 3.8 m or less (*) 3.5 m or less
* The high-ceiling installation of model AP007 to AP012 can only be
undertaken when the combined capacity of the indoor units connected is
100% or less than the capacity of the outdoor unit.
Do not proceed with high-ceiling installation if this limit is exceeded.
4-way cassette
Type AP009~AP012 AP015~AP018
Value
Air flow at outlet 4 directions 3 directions 2 directions 4 directions 3 directions 2 directions
Standard
0000 2.7 m 2.8 m 3.0 m 2.8 m 3.2 m 3.5 m
(factory default)
0001 High-ceiling (1) — — — 3.2 m 3.5 m 3.8 m
0003 High-ceiling (3) — — — 3.5 m 3.8 m —
Type AP024~AP030 AP036~AP056
5d Value
Air flow at outlet 4 directions 3 directions 2 directions 4 directions 3 directions 2 directions
Standard
0000 3.0 m 3.3 m 3.6 m 3.0 m 3.3 m 3.6 m
(factory default)
0001 High-ceiling (1) 3.3 m 3.5 m 3.8 m 3.3 m 3.5 m 3.8 m
0003 High-ceiling (3) 3.6 m 3.8 m — 3.6 m 3.8 m —
Ceiling
Value Type AP015~AP056
0000 Standard (factory default) 3.5 m or less
0001 High-ceiling (1) 4.0 m or less
– 41 –
Codes (DN codes) for changing settings (Necessary for local advanced control)
– 42 –
9. Montor Function of Remote Controller Switch
<Produre> (RBC-AMT21E)
1 Push + buttons simultaneously for 4 seconds or more to call up the service monitor mode.
2 Pushing button returns the display to the normal display.
CODE No.
UNIT No.
2 2
2
TIMER SET FAN MODE
TIMER SET FAN MODE
1
FILTER RESET TEST SET CL SWING/FIX UNIT LOUVER
3
RESET TEST SET CL UNIT
1 1
1 3
(RBC-AMT31E, RBC-AMT32E)
1
CL TEST
Push + buttons simultaneously for 4 seconds or more to call up the service monitor mode.
The service monitor goes on, and temperature of the item code 00 is firstly displayed.
2 Push the temperature setup / buttons to select the CODE NO. (DN code) to be monitored.
For displayed codes, refer to the table below.
3 Push (
UNIT
RBC-AMT32E) button to change the item to one to be monitored.
UNIT LOUVER
Then monitor the indoor unit and sensor temperature or operation status in the corresponding
refrigerant line.
4
TEST
Pushing button returns the display to the normal display.
(Note 1) In the group connection, only data of the (Note 4) Upper girder of CODE No. indicates the
header indoor unit isdisplayed. outdoor unit No.
(Note 2) 01: Only compressor 1 is ON. 1: Header unit (A)
10: Only compressor 2 is ON. 2: Followe run it (B)
11: Both compressor 1 and 2 are ON. 3: Follower unit (C)
(Note 3) For the CODE No., an example of header unit 4: Follower unit (D)
is described. (RBC-AMT32E Not used)
– 43 –
10. Indoor Unit Function DN Code
1 , and
seconds.
The unit No. displayed first is the address of the header indoor unit in 2
group control. Then the fan and louver of the selected indoor unit move. 3 and
2 Each time the “Select unit” side of the button is pressed, one of
UNIT LOUVER
4 and
the indoor unit Nos. under group control is displayed in turn.
Then the fan and louver of the selected indoor unit move. 5
3 Use the button to select the CODE No. (DN code) of the
TEMP.
6
desired function.
4 Use the button to select the desired SET DATA associated with
TIME
<RBC-AMT31E button>
the selected function.
5 Push the button. (The display changes from flashing to steady.)
SET
2 UNIT
– 44 –
11. Specific Indoor Unit Priority Mode
– 45 –
SMMS, MiNi-SMMS, SMMS-i, SHRM. SHRM-i Series
<RBC-AMT21E> <RBC-AMT31E> <RBC-AMT32E>
When pushing the + + buttons at the same time for 4 seconds or more, as shown in the figure, the
display section flashes and after a short period of time the following confirmation code should be displayed [ ].
1 • When the item code is one other than [ ], push the button to
eliminate the display and then repeat the procedure from the first step.
(The remote controller operation is not accepted for approx. 1 minute
after pushing the button.)
(In a group control, the indoor unit with its number displayed first is set to
the header unit.)
For every push of the , the indoor unit numbers in the group control are successively displayed.
Select the indoor unit of which setup is to be changed.
2 In this time, the fan and louver of the selected indoor unit will operate allowing you to
identify the position of the indoor unit of which the setup is to be changed.
Push the button. In this time, the setup operation finishes when the display changes from flashing to
5 lighting.
After setup operation has finished, push the button. (Setup is determined.)
6 When pushing the button, the display disappears and the status returns
to the usual stop status.
(The remote controller operation is not accepted for approx. 1 minute.)
2
UNIT LOUVER
– 46 –
TOSHIBA CARRIER CORPORATION