2 . CONTROL SYSTEM
2-1. CONTROL SYSTEM
2-1-1. LINE UP OF CONTROLLERS
Control system that totally controls a pleasant air conditioning environment
Five types of controllers are available to meet the varied needs of the building and the user.
CONTROL
CONTROL
SYSTEM
SYSTEM
Tighter control over the air conditioned environment can be achieved by combining: central
remote controller which can operate all the indoor units at the same time, a wired remote
controller with a weekly or daily schedule, a wireless remote controller and a simple remote controller.
Wireless
Remote Controller
Simple
Remote Controller
(Accessory)
UTB-YRA / UTB-GRA
UTB-TRA
Wired
Remote Controller
UTB-YUB / UTB-GUB
UTB-TUB
Simple
Remote Controller
UTB-YDB / UTB-GDB
- (02 - 01) -
2-1-2. SYSTEM CONFIGURATION
• Wiring system which spans the power source and signal lines improves reliability.
System diagram
CONTROL
CONTROL
SYSTEM
SYSTEM
Separation tube EV kit
Refrigerant piping
Outdoor unit
Indoor unit
Convertor
*) 3 wires : for power source and signal line ; 1 wire : for ground.
2. This wiring system can shorten the wiring length and makes the work easily.
3. Address setting during construction work can be performed using the accessory
wireless remote controller. Therefore, switch setting at each indoor unit like in the
past is unnecessary.
- (02 - 02) -
2-2. CONTROL UNITS
The following types of controllers are available with the J series VRF system.
CONTROL
Group remote controller
SYSTEM
SYSTEM
Individual Control
Wireless Remote Controller
(Accessory)
Wired Simple
Remote Controller Remote Controller
(Option) (Option)
Central Control
Group Remote Controller
(Option)
C
- (02 - 03) -
2-2-1. WIRELESS REMOTE CONTROLLER (Accessory)
Wireless remote controller is an accessory of all indoor units.
FEATURES
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
CONTROL
CONTROL
SYSTEM
SYSTEM
Four kinds of timers. Easy operation.
Can be used jointly with wired remote controllers.
Easy to change transmission code (4 patterns) by button operation.
Built-in timers
Select from four different timer programs (On/Off/Program/Sleep).
Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to
the time setting to prevent excessive cooling and heating while sleeping.
60min.
30min.
60min.
2°C 90min.
1°C
Timer setting
A B C D
Note : Timer setting from a wireless remote controller becomes invaild, if the indoor unit is connected with
a wired or a simple remote controller.
- (02 - 04) -
FUNCTIONS
1 START/STOP button
5
Pressed to start and stop operation
CONTROL
SYSTEM
SYSTEM
Sets the current time and on-off time
Sets R.C. custom code
3 7
3 Master control button/Code change
Selects the operating mode (AUTO 1 , COOL , DRY ,
2 1 , HEAT 2 ).
FAN
9
Start/end R.C. custom code change. (Max. 4 types)
10 11
4 Sleep timer button
1 Pressed to select sleep timer.
8
5 Signal transmitter
6 Timer button
Pressed to select the timer mode. (OFF TIMER, ON TIMER,
PROGRAM TIMER, TIMER RESET)
11 ACL button
Used when replacing batteries or change the code.
16 14 Clock display
14
15 Master control display
16 Timer mode display
17
17 Fan speed display
18 18 Set temperature display
NOTE
1 : "AUTO " and "FAN " cannot be selected for "HEAT PUMP TYPE"
2 : "HEAT " cannot be selected for "COOLING ONLY TYPE"
- (02 - 05) -
SPECIFICATION
Model name -
Size [H x W x D (mm)] 158 x 56 x 20
Weight (g) 70
CONTROL
CONTROL
SYSTEM
SYSTEM
SYSTEM DIAGRAM
Signal receiver
window
Signal transmitter
Control signal might not be recognized in following cases:
(i) A curtain or a wall, etc. exists between transmitter and receiver.
(ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room.
Air conditioner might not work correctly when strong light hits the signal receiver
window. Shut off the direct sunlight and also make illuminator far away from the
receiver window.
PACKING LIST
Name Quantity Application
Remote controller 1 Use for air conditioner operation
Remote controller holder 1 Use as remote controller holder
Tapping screw 2 For remote controller holder installation
Battery
2 For remote controller
[ 1.5V (R03 / LR03 / AAA) x 2 ]
DIMENSION [ Unit : mm ]
20.0 56.0
Front view Side view Bottom view Side view Front view
- (02 - 06) -
2-2-2.WIRED REMOTE CONTROLLER (Option)
Model : UTB - UB ( Market region Y or G or T )
FEATURES Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature
setup can be changed.
CONTROL
CONTROL
SYSTEM
SYSTEM
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Easy installation with a slim shape with no bulge in the back.
At the time of heating operation, A room temperature setup of a low
temperature is possible. (10 C )
The room temperature can be controlled by being detective
the temperature accurately with Built-in thermo senser.
Built-in timers
Weekly timer Setback timer
Possible to set ON/OFF time to operate twice each day Possible to set temperature for two time spans and
of the week. for each day of the week.
SU MO TU WE TH FR SA Easy-to-understand time bar display SU MO TU WE TH FR SA
SU MO TU WE TH FR SA
7
7
Screen
3 6 9 12 15 18 21 3 6 9 12 15 18 21
after setup 3 6 9 12 15 18 21
0 3 6 9 12 15 18 21 Time 0 3 6 9 12 15 18 21 Time
European
[ Variable timer control ] switch box
- (02 - 07) -
FUNCTIONS
1 START/STOP button
7 Pressed to start and stop operation.
CONTROL
SYSTEM
SYSTEM
2 1 FAN 1 , HEAT 2 ).
8 DAY 3
4
4 Fan control button
9 CLOCK ADJUST DAY OFF ENERGY THERMO
SET BACK SAVE SENSOR Selects the fan speed (AUTO , HIGH , MED , LOW ).
10 6
11
DELETE SET
5
5 Energy save button
12 14 6 Thermo sensor button
13 15 Selects whether the room temperature is detected at the indoor unit
(remote sensor) or the remote controller.
SU MO TU WE TH FR SA
10 Set back button
Pressed select the set back timer.
11 Set time button
3 6 9 12 15 18 21 Pressed to select the set back timer.
25 26 23 24 22 12 Delete button
The schedule of a weekly timer is deleted.
13 Set button
Sets the date, hour, minute and on-off time.
NOTE
1 : "AUTO " and "FAN " cannot be selected for "HEAT PUMP TYPE"
2 : "HEAT " cannot be selected for "COOLING ONLY TYPE"
- (02 - 08) -
SYSTEM DIAGRAM
1 remote controller 2 remote controllers
Indoor unit Indoor unit
A , B , C : Remote controller cable. Refer to 5-2-1
for detail specification.
A < 500m ; B+C < 500m
A B C
CONTROL
CONTROL
SYSTEM
SYSTEM
Master Slave
PACKING LIST
Name Quantity Application
Wired remote controller 1
1)
Remote controller cable 10m For connecting the remote controller
(Exclude some models)
Tapping screw (M4 x 16mm) 2 For installing the remote controller
For remote controller and remote
Binder 1
controller cable binding
For installing the remote controller
Cord clamper 1
cable to the indoor unit
Tapping screw (M4 x 14mm) 1 For installing the remote controller
cable to the indoor unit
1) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.
DIMENSION
[ Unit : mm ] 30 33.5
120
15.3
17 Hole 23
45.3
SU MO TU WE TH FR SA 8
4.5
63.5
3 6 9 12 15 18 21
83.5
120
120
4.5
DAY
12.5
DELETE SET
6
4.5
REMOTE REMOTE
CONTROLLER CONNECTION CABLE G CONTROLLER CONNECTION CABLE G
G 1 2 3 1(L) 2(N) 3 G 1 2 3 1(L) 2(N) 3
1 2 3 1 2 3 1 2 3 1 (RED) : 12V
G G G 2 (WHITE) : Signal
Master Slave 3 (BLACK) : COM
- (02 - 09) -
2-2-3.SIMPLE REMOTE CONTROLLER (Option) (With MASTER control button)
Model : UTB - PB ( Market region Y or G or T )
FEATURES
Easy operation.
Built-in Back ground Light function.
CONTROL
CONTROL
SYSTEM
SYSTEM
Easy installation with a slim shape with no bulge in the back.
Error indication.(A maximum of 16 error histories are memorizable.)
Can be installed onto SW-BOX. (applies to European and
other country's standard)
User-friendly operation
Provides access to basic operations, such as Start / Stop, Fan control, master control switching,
and temperature setting.
A large Start / Stop button is provided in the centre of the remote controller unit for easy operation.
Following an error display, diagnostics can be carried out on the controller.
Simple installation
Can be mounted on the European mounting Box (installation dimension: 60mm) or
the JIS Built-in Box (installation dimension: 83.5mm).
60mm
European
switch box
83.5mm
JIS box
- (02 - 10) -
FUNCTIONS
1 START/STOP button
Pressed to start and stop operation
2 Display background light
Lights during operation.
3 Operation lamp
Lights during operation.
CONTROL
CONTROL
2
SYSTEM
SYSTEM
3 4 Fan control button
1 Selects the fan speed (AUTO , HIGH ,MED ,LOW ).
4 5 Set temperature button
5 Selects the setting temperature.(18-30 C[COOL], 16-30 C[HEAT])
6
6 Master control button
Selects the operating mode (AUTO 1 , COOL , DRY ,
FAN 1 , HEAT 2 ).
7 Standby display
Indicates during the oil recovery and defrosting operation.
8 Power source display
Indicates the main power ON.
9 Central control display
Indicates when function is locked from central remote controller
Display panel or PC controller.
8 13 9
10 Fan speed display
7
11 Set temperature
Indicates Error history number. 4)
Indicates Indoor unit address. 5)
10 11 12 Operation mode display
13 (Upper) Indicates the error code 3) 4) / the refrigerant
system address. 5)
12 (Lower) Indicates the remote controller address. 3) 4) 5)
3)
during self Diagnosis mode.
4)
during Error code history display mode.
5)during address display mode.
NOTE
1 : "AUTO " and "FAN " cannot be selected for "HEAT PUMP TYPE"
2 : "HEAT " cannot be selected for "COOLING ONLY TYPE"
SPECIFICATIONS
Model name UTB - PB
Size [H x W x D (mm)] 120 x 75 x 14
Weight (g) 90
SYSTEM DIAGRAM
1 remote controller 2 remote controllers
Indoor unit Indoor unit
A , B , C : Remote controller cable. Refer to 5-2-1
for detail specifications.
A < 500m ; B+C < 500m
A B C
Master Slave
- (02 - 11) -
PACKING LIST
Name Quantity Application
Simple remote controller 1
6)
Remote controller cable 10m For connecting the remote controller
(Exclude some models)
CONTROL
CONTROL
Tapping screw(M4x16mm) 2 For installing the remote controller
SYSTEM
SYSTEM
For remote controller and remote
Binder 1
controller cable binding
6) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.
DIMENSION
[ Unit : mm ]
75
49 14
hole x 2 11
39
18
6
9
47.5
23.5
60
120
12.5
83.5
4.5
8
hole x 2
Front View
Rear View
ELECTRICAL WIRING
1 remote controller 2 remote controllers
Indoor unit Indoor unit
REMOTE REMOTE
CONTROLLER CONNECTION CABLE G CONTROLLER CONNECTION CABLE G
G 1 2 3 1(L) 2(N) 3 G 1 2 3 1(L) 2(N) 3
1 2 3 1 2 3 1 2 3 1 (RED) : 12V
G G G 2 (WHITE) : Signal
Master Slave 3 (BLACK) : COM
- (02 - 12) -
2-2-4.SIMPLE REMOTE CONTROLLER (Option) (Without MASTER control button)
Model : UTB - RA ( Market region Y or G or T )
FEATURES
Easy operation.
CONTROL
CONTROL
SYSTEM
SYSTEM
Built-in Back Light function.
Easy installation with a slim shape with no bulge in the back.
Error indication.(A maximum of 16 error histories are memorizable.)
Can be installed onto SW-BOX. (applies to European and
other country's standard)
Concentrates on the basic operations such as On/Off, Fan Control,
and Temperature Setting.
User-friendly operation
Provides access to basic operations, such as Start / Stop, Fan Control, and Temperature Setting.
A large Start / Stop button is provided in the centre of the remote controller unit for easy operation.
Following an error display, diagnostics can be carried out on the controller.
Simple installation
Can be mounted on the European mounting Box (installation dimension: 60mm) or
the JIS Built-in Box (installation dimension: 83.5mm).
60mm
European
switch box
83.5mm
JIS box
- (02 - 13) -
FUNCTIONS
1 START/STOP button
Pressed to start and stop operation
2 Display background light
Lights during operation.
3 Operation lamp
Lights during operation.
CONTROL
CONTROL
SYSTEM
SYSTEM
2
4 Fan control button
3 Selects the fan speed (AUTO , HIGH ,MED ,LOW ).
1
4
5 Set temperature button
5 Selects the setting temperature.(18-30 C[COOL], 16-30 C[HEAT])
6 Standby display
Indicates during the oil recovery and defrosting operation.
7 Power source display
Indicates the main power ON.
8 Central control display
Indicates when function is locked from central remote controller
or PC controller.
9 Fan speed display
10 Set temperature
Display panel Indicates Error history number. 2)
Indicates Indoor unit address. 3)
6 7 12 8
11 Operation mode display
12 (Upper) Indicates the error code 1) 2) / the refrigerant
system address. 3)
9 10 1) 2) 3)
(Lower) Indicates the remote controller address.
1) during self Diagnosis mode.
2) during Error code history display mode.
3) during address display mode.
11
SPECIFICATIONS
Model name UTB - RA
Size [H x W x D (mm)] 120 x 75 x 14
Weight ( g ) 90
SYSTEM DIAGRAM
1 remote controller 2 remote controllers
Indoor unit Indoor unit
A , B , C : Remote controller cable. Refer to 5-2-1
for detail specifications.
A < 500m ; B+C < 500m
A B C
Master Slave
PACKING LIST
Name Quantity Application
Simple remote controller 1
4)
Remote controller cable 10m For connecting the remote controller
(Exclude some models)
Tapping screw(M4x16mm) 2 For installing the remote controller
For remote controller and remote
Binder 1
controller cable binding
4) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.
- (02 - 14) -
DIMENSION
[ Unit : mm ]
75
49 14
hole x 2 11
39
18
CONTROL
CONTROL
6
SYSTEM
SYSTEM
9
47.5
23.5
60
120 4
12.5
83.5
4.5
8
Rear View
ELECTRICAL WIRING
1 remote controller 2 remote controllers
Indoor unit Indoor unit
REMOTE REMOTE
CONTROLLER CONNECTION CABLE G CONTROLLER CONNECTION CABLE G
G 1 2 3 1(L) 2(N) 3 G 1 2 3 1(L) 2(N) 3
1 2 3 1 2 3 1 2 3 1 (RED) : 12V
G G G 2 (WHITE) : Signal
Master Slave 3 (BLACK) : COM
- (02 - 15) -
2-2-5.GROUP REMOTE CONTROLLER (Option)
Model : UTB - DB [ Market region Y or G ] ( GROUP REMOTE CONTROLLER)
UTR - YGCA ( NETWORK CONVERTOR)
Only one group remote controller can be used in a system.
When it is used, network convertor (an optional parts UTR-YGCA) is necessary.
CONTROL
CONTROL
SYSTEM
SYSTEM
FEATURES
Up to 8 indoor units can be controlled with a single controller.
On/off, operation mode, set temperature, timer control and air flow can be
controlled/monitored centrally or individually.
Easy installation with a slim shape with no bulge in the back.
One-touch ON/OFF operation of each indoor unit is possible. All the indoor
units can also be easily operated by pressing an ALL ON, ALL OFF, or
ALL TIMER ON/OFF button.
ON
ON OFF ON OFF ON OFF OFF
28°C 24°C 26°C OFF
- (02 - 16) -
FUNCTIONS
TIMER and Clock Indoor units operation
Display and setting display, control
Transmitting
Setting Display Operation Lock Display
CONTROL
CONTROL
Day Display Operation Lamp
SYSTEM
SYSTEM
Timer and Fan Speed Display
Clock Display C
Temperature Display
Timer Mode Display Operation Mode Display
All ON
All Timer Mode
All OFF
Timer Mode
Start/Stop Button
(DELETE) Button
Select Button
DAY Button
Set Time Button Fan Control Button
PROGRAM 1 2
(CLOCK ADJUST) Button Master Control Button
ENTER Button Set Temperature Button
NOTE
1 : "AUTO " and "FAN " cannot be selected for "HEAT PUMP TYPE"
2 : "HEAT " cannot be selected for "COOLING ONLY TYPE"
SPECIFICATION
Group remote controller (UTB - DB)
Size [H x W x D (mm) ] 120 x 120 x 17
Weight (g) 160
- (02 - 17) -
PACKING LIST
Group remote controller (UTB - DB)
Name Quantity Application
Group remote controller 1
Use this for writing the names of the indoor
Label 4
units that have been registered.
CONTROL
CONTROL
SYSTEM
SYSTEM
Tapping screw(M4x16mm) 2 For installing the remote controller
For remote controller and remote
Binder 1
controller cable binding
DIMENSION
GROUP REMOTE CONTROLLER
MODEL NAME : UTB - DB [ Unit : mm ]
30 33.5
120
15.3
17 Hole 23
45.3
8
4.5
63.5
83.5
4.5
120
12.5
6
4.5
HoleX2
Name plate HoleX3
(84 x 21)
Front View Rear View
- (02 - 18) -
DIMENSION
NETWORK CONVERTOR
MODEL NAME : UTR - YGCA 85
18
CONTROL
CONTROL
SYSTEM
SYSTEM
35
27.5
44.5
313
300
37.5
37.5
172
216
1 12V 1 L
RC Line
AC Line
AC Line
Outdoor
Indoor Indoor unit
1.12V unit unit
2.Signal or
3.COM
UTB- DB
1 2 3
- (02 - 19) -
2-2-6. IR RECEIVER UNIT (Accessory)
IR receiver unit is an accessory of duct units.
FEATURES
CONTROL
CONTROL
SYSTEM
SYSTEM
Duct type indoor unit can be controlled with wireless remote controller
if the IR receiver unit is used.
FUNCTIONS
OPERATION LAMP
TIMER LAMP
MANUAL AUTO
SIGNAL RECEIVER
[Unit : mm]
DIMENSIONS 13.6 57.4 13.6
11.5
8.5 18.5
7.2 7.2
90
22.9
57.6
118.4
60
145
17
.5
72.4
83
ATTACHMENT RANGE
1)
L L
1)
- (02 - 20) -
SIGNAL ANGLE
120
CONTROL
CONTROL
SYSTEM
SYSTEM
120
5m 5m
ELECTRICAL WIRING
Control box
PCB
Connected to
CN13 of PCB
Connection cable A (L = 1m)...Standard parts
Connection cable B (L = 5m)...Optional service parts
Connection cable C (L = 10m)...Optional service parts 60mm x 120mm hole
Connected to
IR Receiver unit
- (02 - 21) -
2-2-7.EXTERNAL SWITCH CONTROLLER [Option]
UTR-YESA
FEATURES
Air conditioner switching can be controlled by connecting other sensor switches.
CONTROL
CONTROL
ON/OFF, Temperature, Fan speed and Operating mode can be switched by a
SYSTEM
SYSTEM
combination with Card-key switch equipped in facilities such as hotel room.
SYSTEM DIAGRAM
A B
Indoor Unit
shorter than 50m shorter than 25m
External External switch Remote B + C < 500m
SW
input cable controller controller cable Remote
C
controller cable
Remote controller
SPECIFICATIONS
Power supply DC 12V
Size (H x W x D) (mm) 120 x 75 x 30
Weight (g) 90
PACKING LIST
Name Quantity Application
External switch controller 1
Tapping screw(M4x16mm) 2 For installing the external switch controller
For external switch controller and
Binder 5
cable binding
DIMENSIONS
30 75 60
7x5 18 (Unit: mm)
21
19.5 19.5
83.5
120
19.5
19.5
21
- (02 - 22) -
ELECTRICAL WIRING
CONTROL
CONTROL
SYSTEM
SYSTEM
G G
Non voltage
Open circuit voltage : 12 (V) +- 2 (V).
External contact 1
SW1 Short circuit current : <
= 2 (mA).
Short circuit detection resistance (RON) : <
= 1 (kilo-ohm).
SW2
External contact 2
Open circuit detection resistance (ROFF) : >
= 50 (kilo-ohm).
COM
Terminal
WIRING SPECIFICATIONS
Use Size Wire type Remarks
EXAMPLE
Application Setting Wiring Operation example
- (02 - 23) -
EXAMPLE
Application Setting Wiring Operation example
CONTROL
controlling P1 : Arbitrary operation unit
SW1 ON
SYSTEM
SYSTEM
operation by state
ON or OFF of P2 : Arbitrary operation External P2 P1
SW controller OFF
an external state
contact switch
Operation state ON
Others setting are
arbitrary. External COOL
contact 1 OFF 26 °C
- (02 - 24) -
2-2-8.COMPARISON TABLE OF CONTROLLER
Table 1 List of Controller Functions
CONTROL
(UTB- UB) (UTB- PB) (UTB- RA) (UTB- DB)
SYSTEM
SYSTEM
Max. controllable indoor units 1 1 1 1 8
Air conditioning control function
On / Off
Operation mode setting -
Fan speed setting
Room temp. setting
Test operation - -
Up/down air direction flap setting - - -
Right/left air direction flap setting - - -
Address display -
Failure -
Defrosting - -
Display
Current time - -
Day of week - - -
Centrally controling - -
Cooling/Heating priority -
Error history -
On/Off timer - - -
Weekly timer - - -
Set back timer - - - -
Sleep timer - - - -
Timer
Program timer - - - -
On/Off per day 1 2 - - 2
On/Off per week - 14 - - 14
Day off - - - -
Min. unit of timer setting 5 30 - - 10
- (02 - 25) -