2 . CONTROL SYSTEM
2-1. CONTROL SYSTEM
2-1-1. LINE UP OF CONTROLLERS
Control system that totally controls a pleasant air conditioning environment

Five types of controllers are available to meet the varied needs of the building and the user.
CONTROL

CONTROL
SYSTEM

SYSTEM
Tighter control over the air conditioned environment can be achieved by combining: central
remote controller which can operate all the indoor units at the same time, a wired remote
controller with a weekly or daily schedule, a wireless remote controller and a simple remote controller.

Wireless
Remote Controller

Simple
Remote Controller

(Accessory)

UTB-YRA / UTB-GRA
UTB-TRA
Wired
Remote Controller

UTB-YUB / UTB-GUB
UTB-TUB

Simple
Remote Controller

Group UTB-YPB / UTB-GPB


Remote Controller UTB-TPB

UTB-YDB / UTB-GDB

- (02 - 01) -
2-1-2. SYSTEM CONFIGURATION

• Wiring system which spans the power source and signal lines improves reliability.

System diagram
CONTROL

CONTROL
SYSTEM

SYSTEM
Separation tube EV kit
Refrigerant piping

Power source Power source/signal line *)

Outdoor unit
Indoor unit
Convertor

Group Simple Wired Wireless Wired Simple


remote controller remote controller remote controller remote controller remote controller remote controller
+ +
Simple Wireless
remote controller remote controller

*) 3 wires : for power source and signal line ; 1 wire : for ground.

2-1-3. FEATURES OF CONTROL SYSTEM


1. FGL system can install by wiring from equipment to equipment in the wiring work.

2. This wiring system can shorten the wiring length and makes the work easily.

3. Address setting during construction work can be performed using the accessory
wireless remote controller. Therefore, switch setting at each indoor unit like in the
past is unnecessary.

4. 2 remote controller are connectable for 1 indoor unit.

- (02 - 02) -
2-2. CONTROL UNITS
The following types of controllers are available with the J series VRF system.

Wireless remote controller


Wired remote controller
Simple remote controller
CONTROL

CONTROL
Group remote controller
SYSTEM

SYSTEM
Individual Control
Wireless Remote Controller
(Accessory)

Wired Simple
Remote Controller Remote Controller
(Option) (Option)

Central Control
Group Remote Controller
(Option)
C

- (02 - 03) -
2-2-1. WIRELESS REMOTE CONTROLLER (Accessory)
Wireless remote controller is an accessory of all indoor units.

FEATURES

Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
CONTROL

CONTROL
SYSTEM

SYSTEM
Four kinds of timers. Easy operation.
Can be used jointly with wired remote controllers.
Easy to change transmission code (4 patterns) by button operation.

Built-in timers
Select from four different timer programs (On/Off/Program/Sleep).

Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.

Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to
the time setting to prevent excessive cooling and heating while sleeping.

Cooling operation/dry operation Heating operation


When the sleep timer is set, the set temperature When the sleep timer is set, the set temperature
automatically rises 1°C every hour. The set automatically drops 1°C every 30 minutes. The
temperature can rise up to a maximum of 2°C. set temperature can drop to a maximum of 4°C.

Timer setting 1°C 2°C


3°C 4°C

60min.
30min.

60min.
2°C 90min.
1°C
Timer setting

Easy installation and operation System addressing


After code change
• During installation work, system addressing can be
Mixed-up A B C D
performed using the wireless remote controller, thus
eliminating manual switch setting.
Transmission line

A B C D

Outdoor unit Indoor unit


• Code selector switch eliminates unit • Wide and precise
being wrongly switched. transmitting range.
(Up to 4 codes can be set.) Wireless
remote controller

Note : Timer setting from a wireless remote controller becomes invaild, if the indoor unit is connected with
a wired or a simple remote controller.

- (02 - 04) -
FUNCTIONS

1 START/STOP button
5
Pressed to start and stop operation

4 6 2 Set temp./Set time buttons/Set remote controller


Display
custom code buttons
Sets the indoor temp.(From 18-30 C [Cool] , 16-30 C [Heat] )
CONTROL

CONTROL
SYSTEM

SYSTEM
Sets the current time and on-off time
Sets R.C. custom code

3 7
3 Master control button/Code change
Selects the operating mode (AUTO 1 , COOL , DRY ,
2 1 , HEAT 2 ).
FAN
9
Start/end R.C. custom code change. (Max. 4 types)
10 11
4 Sleep timer button
1 Pressed to select sleep timer.
8
5 Signal transmitter
6 Timer button
Pressed to select the timer mode. (OFF TIMER, ON TIMER,
PROGRAM TIMER, TIMER RESET)

7 Fan control button


Selects the fan speed (AUTO , HIGH ,MED ,LOW ).

8 Battery compartment lid


TEST
RUN 12
9 Air flow direction button
Used to set the desired air flow direction & swing function.

10 Time adjust button


Sets the current time.

11 ACL button
Used when replacing batteries or change the code.

12 Test run button


Display panel Used when testing the air conditioner after installation.
13
13 Transmit indicator

16 14 Clock display
14
15 Master control display
16 Timer mode display
17
17 Fan speed display
18 18 Set temperature display

15 19 19 Timer set indicator


20 20 Temperature set indicator

NOTE
1 : "AUTO " and "FAN " cannot be selected for "HEAT PUMP TYPE"
2 : "HEAT " cannot be selected for "COOLING ONLY TYPE"

- (02 - 05) -
SPECIFICATION
Model name -
Size [H x W x D (mm)] 158 x 56 x 20
Weight (g) 70
CONTROL

CONTROL
SYSTEM

SYSTEM
SYSTEM DIAGRAM

Signal receiver
window

Signal transmitter
Control signal might not be recognized in following cases:
(i) A curtain or a wall, etc. exists between transmitter and receiver.
(ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room.

Air conditioner might not work correctly when strong light hits the signal receiver
window. Shut off the direct sunlight and also make illuminator far away from the
receiver window.

PACKING LIST
Name Quantity Application
Remote controller 1 Use for air conditioner operation
Remote controller holder 1 Use as remote controller holder
Tapping screw 2 For remote controller holder installation
Battery
2 For remote controller
[ 1.5V (R03 / LR03 / AAA) x 2 ]

DIMENSION [ Unit : mm ]

Holder Controller 158.0

20.0 56.0

Front view Side view Bottom view Side view Front view

- (02 - 06) -
2-2-2.WIRED REMOTE CONTROLLER (Option)
Model : UTB - UB ( Market region Y or G or T )
FEATURES Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature
setup can be changed.
CONTROL

CONTROL
SYSTEM

SYSTEM
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Easy installation with a slim shape with no bulge in the back.
At the time of heating operation, A room temperature setup of a low
temperature is possible. (10 C )
The room temperature can be controlled by being detective
the temperature accurately with Built-in thermo senser.

Powerful features and compact size


Wired
Thermo Weekly Setback
sensor timer timer = remote
controller

Accurate and comfortable Sensor part


Indoor temperature can be detected accurately by the inclusion of
a thermo sensor in the body of the wired controller. Thermo sensor
display
Our system can correspond to various scenes.
This new wired remote controller and the optional remote sensor Control part for
allows flexibility in sensor location, suitable for all requirements. changing the
thermo sensor

Built-in timers
Weekly timer Setback timer
Possible to set ON/OFF time to operate twice each day Possible to set temperature for two time spans and
of the week. for each day of the week.
SU MO TU WE TH FR SA Easy-to-understand time bar display SU MO TU WE TH FR SA

SU MO TU WE TH FR SA

7
7
Screen
3 6 9 12 15 18 21 3 6 9 12 15 18 21
after setup 3 6 9 12 15 18 21

Setup screen example Setup screen example


(Set to Wednesday: 8:00 to 20:00.) (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
24°C 28°C

0 3 6 9 12 15 18 21 Time 0 3 6 9 12 15 18 21 Time

At "Weekly timer" + "Set back timer" setup


28°C
24°C
24 C 28 C 24 C
0 3 6 9 12 15 18 21 Time

Easy-to-understand operation Simple installation


Components are compatible with standard
switch boxes. Flat back construction allows
Timer Operation equipment to be installed wherever it is
area area
needed.

European
[ Variable timer control ] switch box

The operation/display sections are zoned accord-


ing to time and operation, enabling variable pro-
gramming to match application. JIS box

- (02 - 07) -
FUNCTIONS
1 START/STOP button
7 Pressed to start and stop operation.

2 Set Temperature button


Display
Selects the setting temperature.(18-30 C[COOL], 10-30 C[HEAT])
SU MO TU WE TH FR SA

3 Master control button


3 6 9 12 15 18 21
16 Selects the operating mode (AUTO 1 , COOL , DRY ,
CONTROL

CONTROL
SYSTEM

SYSTEM
2 1 FAN 1 , HEAT 2 ).
8 DAY 3
4
4 Fan control button
9 CLOCK ADJUST DAY OFF ENERGY THERMO
SET BACK SAVE SENSOR Selects the fan speed (AUTO , HIGH , MED , LOW ).
10 6
11
DELETE SET
5
5 Energy save button
12 14 6 Thermo sensor button
13 15 Selects whether the room temperature is detected at the indoor unit
(remote sensor) or the remote controller.

7 Built-in thermo sensor


Detect room temperature.

8 Timer mode (CLOCK ADJUST) button


Display panel Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.

9 Day (DAY OFF) button


17 20 21 19 18 Temporarily cancels of one day timer.

SU MO TU WE TH FR SA
10 Set back button
Pressed select the set back timer.
11 Set time button
3 6 9 12 15 18 21 Pressed to select the set back timer.

25 26 23 24 22 12 Delete button
The schedule of a weekly timer is deleted.

13 Set button
Sets the date, hour, minute and on-off time.

14 Horizontal air flow direction and swing button


Push for two seconds to change the swing mode.

15 Vertical air flow direction and swing button


Push for two seconds to change the swing mode
16 Operation lamp
Lights during operation and when the timer is on.
17 Timer and clock display
18 Operation mode display
19 Fan speed display
20 Operation lock display
21 Temperature display
Displayed temperature is set temperature.
22 Defrost display
SPECIFICATIONS Indicates during the oil recovery and defrosting operation.
23 Vertical swing display
Model name UTB - UB
Size [H x W x D (mm)] 120 x 120 x 17
24 Horizontal swing display
Weight (g) 160 25 Energy save display
26 Thermo sensor display

NOTE
1 : "AUTO " and "FAN " cannot be selected for "HEAT PUMP TYPE"
2 : "HEAT " cannot be selected for "COOLING ONLY TYPE"

- (02 - 08) -
SYSTEM DIAGRAM
1 remote controller 2 remote controllers
Indoor unit Indoor unit
A , B , C : Remote controller cable. Refer to 5-2-1
for detail specification.
A < 500m ; B+C < 500m
A B C
CONTROL

CONTROL
SYSTEM

SYSTEM
Master Slave

Remote controller Remote controllers

PACKING LIST
Name Quantity Application
Wired remote controller 1
1)
Remote controller cable 10m For connecting the remote controller
(Exclude some models)
Tapping screw (M4 x 16mm) 2 For installing the remote controller
For remote controller and remote
Binder 1
controller cable binding
For installing the remote controller
Cord clamper 1
cable to the indoor unit
Tapping screw (M4 x 14mm) 1 For installing the remote controller
cable to the indoor unit
1) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.

DIMENSION
[ Unit : mm ] 30 33.5
120

15.3
17 Hole 23
45.3

SU MO TU WE TH FR SA 8
4.5

63.5
3 6 9 12 15 18 21

83.5
120
120

4.5
DAY
12.5

CLOCK ADJUST DAY OFF ENERGY THERMO


SET BACK SAVE SENSOR

DELETE SET
6
4.5

Front view Side view HoleX2


HoleX3

ELECTRICAL WIRING Rear view


1 remote controller 2 remote controllers
Indoor unit Indoor unit

REMOTE REMOTE
CONTROLLER CONNECTION CABLE G CONTROLLER CONNECTION CABLE G
G 1 2 3 1(L) 2(N) 3 G 1 2 3 1(L) 2(N) 3

1 2 3 1 2 3 1 2 3 1 (RED) : 12V
G G G 2 (WHITE) : Signal
Master Slave 3 (BLACK) : COM

Remote controller Remote controllers

- (02 - 09) -
2-2-3.SIMPLE REMOTE CONTROLLER (Option) (With MASTER control button)
Model : UTB - PB ( Market region Y or G or T )

FEATURES
Easy operation.
Built-in Back ground Light function.
CONTROL

CONTROL
SYSTEM

SYSTEM
Easy installation with a slim shape with no bulge in the back.
Error indication.(A maximum of 16 error histories are memorizable.)
Can be installed onto SW-BOX. (applies to European and
other country's standard)

User-friendly operation
Provides access to basic operations, such as Start / Stop, Fan control, master control switching,
and temperature setting.
A large Start / Stop button is provided in the centre of the remote controller unit for easy operation.
Following an error display, diagnostics can be carried out on the controller.

Back ground light


Backlight enables easy operation in a darkened room.
Backlight activates during all button operations, and lasts 10 seconds
in operating mode and 5 seconds in stop mode after a button is pressed.

Simple installation
Can be mounted on the European mounting Box (installation dimension: 60mm) or
the JIS Built-in Box (installation dimension: 83.5mm).

60mm
European
switch box
83.5mm

JIS box

- (02 - 10) -
FUNCTIONS
1 START/STOP button
Pressed to start and stop operation
2 Display background light
Lights during operation.
3 Operation lamp
Lights during operation.
CONTROL

CONTROL
2
SYSTEM

SYSTEM
3 4 Fan control button
1 Selects the fan speed (AUTO , HIGH ,MED ,LOW ).
4 5 Set temperature button
5 Selects the setting temperature.(18-30 C[COOL], 16-30 C[HEAT])
6
6 Master control button
Selects the operating mode (AUTO 1 , COOL , DRY ,
FAN 1 , HEAT 2 ).

7 Standby display
Indicates during the oil recovery and defrosting operation.
8 Power source display
Indicates the main power ON.
9 Central control display
Indicates when function is locked from central remote controller
Display panel or PC controller.

8 13 9
10 Fan speed display
7
11 Set temperature
Indicates Error history number. 4)
Indicates Indoor unit address. 5)
10 11 12 Operation mode display
13 (Upper) Indicates the error code 3) 4) / the refrigerant
system address. 5)
12 (Lower) Indicates the remote controller address. 3) 4) 5)
3)
during self Diagnosis mode.
4)
during Error code history display mode.
5)during address display mode.

NOTE
1 : "AUTO " and "FAN " cannot be selected for "HEAT PUMP TYPE"
2 : "HEAT " cannot be selected for "COOLING ONLY TYPE"

SPECIFICATIONS
Model name UTB - PB
Size [H x W x D (mm)] 120 x 75 x 14
Weight (g) 90

SYSTEM DIAGRAM
1 remote controller 2 remote controllers
Indoor unit Indoor unit
A , B , C : Remote controller cable. Refer to 5-2-1
for detail specifications.
A < 500m ; B+C < 500m
A B C

Master Slave

Remote controller Remote controllers

- (02 - 11) -
PACKING LIST
Name Quantity Application
Simple remote controller 1
6)
Remote controller cable 10m For connecting the remote controller
(Exclude some models)
CONTROL

CONTROL
Tapping screw(M4x16mm) 2 For installing the remote controller
SYSTEM

SYSTEM
For remote controller and remote
Binder 1
controller cable binding
6) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.

DIMENSION
[ Unit : mm ]
75
49 14
hole x 2 11
39

18
6

9
47.5
23.5

60
120

12.5
83.5

4.5
8

hole x 2
Front View
Rear View

ELECTRICAL WIRING
1 remote controller 2 remote controllers
Indoor unit Indoor unit

REMOTE REMOTE
CONTROLLER CONNECTION CABLE G CONTROLLER CONNECTION CABLE G
G 1 2 3 1(L) 2(N) 3 G 1 2 3 1(L) 2(N) 3

1 2 3 1 2 3 1 2 3 1 (RED) : 12V
G G G 2 (WHITE) : Signal
Master Slave 3 (BLACK) : COM

Remote controller Remote controllers

- (02 - 12) -
2-2-4.SIMPLE REMOTE CONTROLLER (Option) (Without MASTER control button)
Model : UTB - RA ( Market region Y or G or T )

A part of the function is limited. It is recommended to use it together


with other type controller.

FEATURES
Easy operation.
CONTROL

CONTROL
SYSTEM

SYSTEM
Built-in Back Light function.
Easy installation with a slim shape with no bulge in the back.
Error indication.(A maximum of 16 error histories are memorizable.)
Can be installed onto SW-BOX. (applies to European and
other country's standard)
Concentrates on the basic operations such as On/Off, Fan Control,
and Temperature Setting.

User-friendly operation
Provides access to basic operations, such as Start / Stop, Fan Control, and Temperature Setting.
A large Start / Stop button is provided in the centre of the remote controller unit for easy operation.
Following an error display, diagnostics can be carried out on the controller.

Back ground light


Backlight enables easy operation in a darkened room.
Backlight activates during all button operations, and lasts 10 seconds
in operating mode and 5 seconds in stop mode after a button is pressed.

Simple installation
Can be mounted on the European mounting Box (installation dimension: 60mm) or
the JIS Built-in Box (installation dimension: 83.5mm).

60mm
European
switch box
83.5mm

JIS box

- (02 - 13) -
FUNCTIONS
1 START/STOP button
Pressed to start and stop operation
2 Display background light
Lights during operation.
3 Operation lamp
Lights during operation.
CONTROL

CONTROL
SYSTEM

SYSTEM
2
4 Fan control button
3 Selects the fan speed (AUTO , HIGH ,MED ,LOW ).
1
4
5 Set temperature button
5 Selects the setting temperature.(18-30 C[COOL], 16-30 C[HEAT])
6 Standby display
Indicates during the oil recovery and defrosting operation.
7 Power source display
Indicates the main power ON.
8 Central control display
Indicates when function is locked from central remote controller
or PC controller.
9 Fan speed display
10 Set temperature
Display panel Indicates Error history number. 2)
Indicates Indoor unit address. 3)
6 7 12 8
11 Operation mode display
12 (Upper) Indicates the error code 1) 2) / the refrigerant
system address. 3)
9 10 1) 2) 3)
(Lower) Indicates the remote controller address.
1) during self Diagnosis mode.
2) during Error code history display mode.
3) during address display mode.
11

SPECIFICATIONS
Model name UTB - RA
Size [H x W x D (mm)] 120 x 75 x 14
Weight ( g ) 90

SYSTEM DIAGRAM
1 remote controller 2 remote controllers
Indoor unit Indoor unit
A , B , C : Remote controller cable. Refer to 5-2-1
for detail specifications.
A < 500m ; B+C < 500m
A B C

Master Slave

Remote controller Remote controllers

PACKING LIST
Name Quantity Application
Simple remote controller 1
4)
Remote controller cable 10m For connecting the remote controller
(Exclude some models)
Tapping screw(M4x16mm) 2 For installing the remote controller
For remote controller and remote
Binder 1
controller cable binding
4) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.

- (02 - 14) -
DIMENSION
[ Unit : mm ]
75
49 14
hole x 2 11
39

18
CONTROL

CONTROL
6
SYSTEM

SYSTEM
9
47.5
23.5
60

120 4

12.5
83.5

4.5
8

Front View hole x 2

Rear View

ELECTRICAL WIRING
1 remote controller 2 remote controllers
Indoor unit Indoor unit

REMOTE REMOTE
CONTROLLER CONNECTION CABLE G CONTROLLER CONNECTION CABLE G
G 1 2 3 1(L) 2(N) 3 G 1 2 3 1(L) 2(N) 3

1 2 3 1 2 3 1 2 3 1 (RED) : 12V
G G G 2 (WHITE) : Signal
Master Slave 3 (BLACK) : COM

Remote controller Remote controllers

- (02 - 15) -
2-2-5.GROUP REMOTE CONTROLLER (Option)
Model : UTB - DB [ Market region Y or G ] ( GROUP REMOTE CONTROLLER)
UTR - YGCA ( NETWORK CONVERTOR)
Only one group remote controller can be used in a system.
When it is used, network convertor (an optional parts UTR-YGCA) is necessary.
CONTROL

CONTROL
SYSTEM

SYSTEM
FEATURES
Up to 8 indoor units can be controlled with a single controller.
On/off, operation mode, set temperature, timer control and air flow can be
controlled/monitored centrally or individually.
Easy installation with a slim shape with no bulge in the back.
One-touch ON/OFF operation of each indoor unit is possible. All the indoor
units can also be easily operated by pressing an ALL ON, ALL OFF, or
ALL TIMER ON/OFF button.

High performance and compact size


ON/OFF, operation mode, set temperature and air flow can be controlled /
monitored centrally or individually.

Central ON/OFF Weekly


control control timer

Built-in weekly timers


The WEEKLY TIMER is provided as a standard function.
1. The timer can be set up for up to 4 times/day. (On/Off, set temperature)
2. Allows separate settings for each day of the week.

ON/OFF switching Temperature switching Stop setting

ON
ON OFF ON OFF ON OFF OFF
28°C 24°C 26°C OFF

- (02 - 16) -
FUNCTIONS
TIMER and Clock Indoor units operation
Display and setting display, control
Transmitting
Setting Display Operation Lock Display
CONTROL

CONTROL
Day Display Operation Lamp
SYSTEM

SYSTEM
Timer and Fan Speed Display
Clock Display C
Temperature Display
Timer Mode Display Operation Mode Display

All ON
All Timer Mode
All OFF
Timer Mode
Start/Stop Button
(DELETE) Button
Select Button
DAY Button
Set Time Button Fan Control Button
PROGRAM 1 2
(CLOCK ADJUST) Button Master Control Button
ENTER Button Set Temperature Button

NOTE
1 : "AUTO " and "FAN " cannot be selected for "HEAT PUMP TYPE"
2 : "HEAT " cannot be selected for "COOLING ONLY TYPE"

SPECIFICATION
Group remote controller (UTB - DB)
Size [H x W x D (mm) ] 120 x 120 x 17
Weight (g) 160

Network convertor (UTR - YGCA)


Size [H x W x D (mm) ] 85 x 216 x 313
Weight (g) 1800
Power source AC 208V-240V 50/60Hz
Power consumption 2.0W
Temperature (°C) 0 - 46
Operating
Humidity RH (%) 10 - 90
Environment
Temperature (°C) -10 - 60
Packaged
Humidity RH (%) 10 - 90
Necessary if group remote controller is used.

- (02 - 17) -
PACKING LIST
Group remote controller (UTB - DB)
Name Quantity Application
Group remote controller 1
Use this for writing the names of the indoor
Label 4
units that have been registered.
CONTROL

CONTROL
SYSTEM

SYSTEM
Tapping screw(M4x16mm) 2 For installing the remote controller
For remote controller and remote
Binder 1
controller cable binding

Network convertor (UTR - YGCA)


Name Quantity Application
Network convertor 1
Tapping screw(M4x16mm) 4 For installing the remote controller
For remote controller and remote
Binder (Push mount) 4
controller cable binding
Cord bushing 2

DIMENSION
GROUP REMOTE CONTROLLER
MODEL NAME : UTB - DB [ Unit : mm ]

30 33.5
120

15.3
17 Hole 23
45.3

8
4.5

63.5

83.5
4.5
120

12.5

6
4.5

HoleX2
Name plate HoleX3
(84 x 21)
Front View Rear View

- (02 - 18) -
DIMENSION
NETWORK CONVERTOR
MODEL NAME : UTR - YGCA 85

18
CONTROL

CONTROL
SYSTEM

SYSTEM
35

27.5
44.5
313
300

37.5
37.5
172

216

Refer the installation manual for mounting condition.

ELECTRICAL WIRING (UTB- DB, UTR-YGCA)

1 12V 1 L
RC Line

AC Line
AC Line

2 Signal Ext In RC Line (L)(N) (G) 2 N


3 GND 123 123 G 1 2 3 4 3 Signal
4 G
UTR-YGCA

Outdoor
Indoor Indoor unit
1.12V unit unit
2.Signal or
3.COM
UTB- DB
1 2 3

CONNECTION CABLE CONNECTION


1(L) 2(N) 3 1(L) 2(N) 3
G G
G

Group remote controller cable


(Field supply) cross-section 0.33 mm2
Polar 3 - core,Shield.

- (02 - 19) -
2-2-6. IR RECEIVER UNIT (Accessory)
IR receiver unit is an accessory of duct units.
FEATURES
CONTROL

CONTROL
SYSTEM

SYSTEM
Duct type indoor unit can be controlled with wireless remote controller
if the IR receiver unit is used.

FUNCTIONS

OPERATION LAMP
TIMER LAMP

MANUAL AUTO
SIGNAL RECEIVER

[Unit : mm]
DIMENSIONS 13.6 57.4 13.6
11.5
8.5 18.5
7.2 7.2
90
22.9
57.6

118.4
60
145

17
.5

72.4
83

ATTACHMENT RANGE
1)
L L
1)

1) Connection cable length L


Cable A (Standard parts) : 1 m
Cable B (Optional service parts) : 5 m
Cable C (Optional service parts) : 10m

- (02 - 20) -
SIGNAL ANGLE

120
CONTROL

CONTROL
SYSTEM

SYSTEM
120

5m 5m

ELECTRICAL WIRING
Control box
PCB
Connected to
CN13 of PCB
Connection cable A (L = 1m)...Standard parts
Connection cable B (L = 5m)...Optional service parts
Connection cable C (L = 10m)...Optional service parts 60mm x 120mm hole

Connected to
IR Receiver unit

PACKING LIST OPTIONAL SERVICE PARTS


Please use the parts number shown below to order
Name Quantity the cable from your sales representative.
Select shielded type conncetion cable in accordance
Holder (PCB) 1
with the standard of the country.
PCB assy 1

Bracket (Holder) 1 Parts name Type Parts No.


Holder cover 1 Non-shielded 9378143005
Connection cable B
Screw 4 Shielded 9378143029
Connection cable A (1m) 1 Non-shielded 9378143012
Connection cable C
Shielded 9378143036

- (02 - 21) -
2-2-7.EXTERNAL SWITCH CONTROLLER [Option]
UTR-YESA

FEATURES
Air conditioner switching can be controlled by connecting other sensor switches.
CONTROL

CONTROL
ON/OFF, Temperature, Fan speed and Operating mode can be switched by a
SYSTEM

SYSTEM
combination with Card-key switch equipped in facilities such as hotel room.

Card-key or other sensor switches are available as a field supplied parts.

SYSTEM DIAGRAM
A B
Indoor Unit
shorter than 50m shorter than 25m
External External switch Remote B + C < 500m
SW
input cable controller controller cable Remote
C
controller cable

Remote controller

SPECIFICATIONS
Power supply DC 12V
Size (H x W x D) (mm) 120 x 75 x 30
Weight (g) 90

PACKING LIST
Name Quantity Application
External switch controller 1
Tapping screw(M4x16mm) 2 For installing the external switch controller
For external switch controller and
Binder 5
cable binding

DIMENSIONS
30 75 60
7x5 18 (Unit: mm)
21
19.5 19.5

83.5
120

19.5
19.5
21

Left view Front view Rear view

- (02 - 22) -
ELECTRICAL WIRING
CONTROL

CONTROL
SYSTEM

SYSTEM
G G

Connection to external contacts

Non voltage
Open circuit voltage : 12 (V) +- 2 (V).
External contact 1
SW1 Short circuit current : <
= 2 (mA).
Short circuit detection resistance (RON) : <
= 1 (kilo-ohm).
SW2
External contact 2
Open circuit detection resistance (ROFF) : >
= 50 (kilo-ohm).
COM
Terminal

External switch controller

WIRING SPECIFICATIONS
Use Size Wire type Remarks

Remote controller cable (mm 2 ) Shielded Polar 3 core


0.33 (22AWG)
Twisted pair
Polar 2 core
External input cable (mm 2 ) 0.33 (22AWG) Shielded
Twisted pair

EXAMPLE
Application Setting Wiring Operation example

When MODE0 Indoor P1 : ON, COOL, 26°C P2 : OFF


controlling the P1: Arbitrary unit
individual operation state SW1 ON
OFF P1
operation Contact OFF ON External
states with two P2: Arbitrary SW controller SW2 ON
external operation state External
OFF P2
contact 1
contact Contact OFF ON Operation state ON
Others setting are External
COOL
arbitrary. contact 2
OFF 26 °C

- (02 - 23) -
EXAMPLE
Application Setting Wiring Operation example

When MODE1 Indoor P1 : OFF P2 : ON, COOL, 26°C


CONTROL

CONTROL
controlling P1 : Arbitrary operation unit
SW1 ON
SYSTEM

SYSTEM
operation by state
ON or OFF of P2 : Arbitrary operation External P2 P1
SW controller OFF
an external state
contact switch
Operation state ON
Others setting are
arbitrary. External COOL
contact 1 OFF 26 °C

When operating in MODE1 or 0 MODE1, P1 : SETBACK P2 : ON, COOL, 26°C


the state set when P1 : SETBACK Indoor
an external P2 : Arbitrary unit SW1 ON
contact switch operation state
was set to ON and Others setting are External OFF P2 P1
SW controller
returning to the arbitrary.
original operation Operation state ON
state when the COOL COOL COOL
switch was set to External
contact 1 OFF 23°C 26 °C 23 °C
OFF

When operated MODE1 or 0 MODE1, P1 : ON, COOL, 26°C


Indoor
in the state P1 : Arbitrary P2 : When SETBACK
unit
when an operation state
SW1 ON
external P2 : SETBACK External P1 P2
contact switch Others setting are SW controller OFF
was set to OFF arbitrary.
and returned to
Operation state ON
original External COOL COOL COOL
operation state contact 1 23°C 26 °C 23 °C
OFF

When a MODE2 Indoor P1 : ON, COOL, 26°C


temperature P1 : ON, COOL or unit P2 : ON,HEAT, 21°C
sensor switch HEAT SW1 ON
is connected P2 : ON, COOL or P2 P1
and cooling HEAT OFF
and heating Operation conditions
switching is :Unit operationg only Operation state ON
performed. Others setting are COOL HEAT COOL
arbitrary. OFF 23°C 21°C 26°C
Thermal sensor SW
An external switch controller is
connected to all the indoor units
of the same refrigerant system
and cooling and heating are
switched by one temperature
sensor.

When MODE1 Indoor P1 : OFF P2 : ON, COOL, 26 °C


preventing Delay-time setting unit
SW1
chattering noise :Delay
ON P2 P1
within 1 minute P1 : Arbitrary External
of the external operation state SW controller
1min 1min
contact switch. P2 : Arbitrary
operation state Operation state ON
External COOL
Others setting are contact 1 OFF 26 °C
arbitrary.

- (02 - 24) -
2-2-8.COMPARISON TABLE OF CONTROLLER
Table 1 List of Controller Functions

Wireless Wired Simple Simple Group


remote remote remote remote remote
controller controller controller controller controller
CONTROL

CONTROL
(UTB- UB) (UTB- PB) (UTB- RA) (UTB- DB)
SYSTEM

SYSTEM
Max. controllable indoor units 1 1 1 1 8
Air conditioning control function

On / Off
Operation mode setting -
Fan speed setting
Room temp. setting
Test operation - -
Up/down air direction flap setting - - -
Right/left air direction flap setting - - -
Address display -
Failure -
Defrosting - -
Display

Current time - -
Day of week - - -
Centrally controling - -
Cooling/Heating priority -
Error history -
On/Off timer - - -
Weekly timer - - -
Set back timer - - - -
Sleep timer - - - -
Timer

Program timer - - - -
On/Off per day 1 2 - - 2
On/Off per week - 14 - - 14
Day off - - - -
Min. unit of timer setting 5 30 - - 10

- (02 - 25) -