OVERCURRENT PROTECTION PART 1
For the circuit shown, with a pickup setting of 1.2, will it TRIP or not?
A
1200A 1600 2000
1200
800
400
P1 S1
1200/5 51 0
P2 S2
OVERCURRENT PROTECTION PART 1
For the fault shown, show the direction of currents for all of the feeders /
incomers and identify which circuit breakers need to trip
1600A
1600A A
P1
1600/1
P2 1600A
800
= 1.2 * 1200A = 1,440A
400
P1 S1
1200/5 51 0
THE BREAKER WILL TRIP
P2 S2
OVERCURRENT PROTECTION PART 1
ANSWER : For the fault shown, show the direction of currents for all of the
feeders / incomers and identify which circuit breakers need to trip
1600A