Date Serial No.

Project Name Revision


Customer Engineer

LG Air Cooled Scroll Chiller

LG Air Cooled Scroll Chiller


Model Combination ACAH050HETB + ACAH050HETB +ACAH040HETB

Unit Specification Performance data


Model ACAH140HETB Total Compressor Power 134.9 kW
Quantity 1 Total Fan Motor Power 14.4 kW
Refrigerant Type R410A Total Unit Power(without pump) 149.3 kW
475.8 kW EER 10.88 BTU/Whr
Cooling Capacity
135.3 usRT kW/RT 1.103
Power Supply 3Ph 460 V 60 Hz
Compressor Others
Type Hermetic scroll (VSD) Length 84.8 in
Quantity of Comp. 16 Dimension Width 240.6 in
Starter Type Inverter Height 86.6 in
Oil PVE Weight 8,990 lb
Oil Charged 1400 × 16 cc Refrigerant Charged 229 lb
Sump Heater 600 × 16 W

EVAPORATOR / CONDENSER
Item Evaporator Item Condenser
Heat Exchanger Structure Shell and Tube Heat Exchanger Structure Fin and Tube
Fluid Type Fresh Water Material Al / Cu
Nozzle Connection Size 65A × 3 Fin Type Wide Louver PLUS
Fouling Factor 0.0001 (hr-sqft-F)/BTU Fluid Type Ambient Air
Entering Temp 54.0 ℉ Altitude 1521 ft
Leaving Temp 44.0 ℉ Number of Fans 16
Flowrate 324.3 gpm Total Fan Air Flow 138,999 CFM
Pressure Drop 12.3 ft H2O Entering Air Temperature 92.0 ℉
Max. Water Pressure 335 ft H2O Fan Motor Type BLDC

IPLV.IP (EER)
%Load 100 75 50 25
Capacity (usRT) 134.2 100.7 67.1 33.6
Ambient Air Temp. (℉) 95.0 80.0 65.0 55.0
EER (BTU/Whr) 10.62 15.25 20.99 19.74
Power Input (kW) 151.6 79.2 38.4 20.4