You are on page 1of 35

Page 1 of 35

Cat Electronic Technician 2017A v1.0


Configuration

3/18/2020 4:58 PM

C18 Genset (EST00587)


Parameter Value
Equipment ID NOT PROGRAMMED
Engine Serial Number EST00587
ECM Serial Number 07386486JL
Software Group Part Number 3021866-00
Software Group Release Date DEC06
Software Group Description C18-MEUI-ACERT-A4

Digital Voltage Regulator


Parameter Value
ECM Part Number 3147755-00
ECM Serial Number 07486282GD
Software Group Part Number 3184763-01
Software Group Release Date NOV2007
Software Group Description Regulator Software

EMCP 3.1
Parameter Value
ECM Part Number 3007645-01
ECM Serial Number 0828B161UA
Software Group Part Number 3222117-00
Software Group Release Date NOV2007
Software Group Description L0 8_0 Standard -- English, 2.2 Prod, 7Nov2007

Description Value TT
Automatic Start/Stop
Engine Start Fault Protection Activation Delay Time 30 sec

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 2 of 35

Crank Duration 10 sec


Crank Cycle Rest Interval 10 sec
Engine Purge Cycle Time 0 sec
Maximum Number of Crank Cycles 5
Cooldown Duration 10 min
Start Aid Activation Time 0 sec
Crank Alert Activation Time 0 sec
Crank Terminate RPM 400 rpm
Engine Fuel Type Configuration Diesel
Fuel Shutoff Solenoid Type Configuration Energized to Run
Engine Type Configuration Electronic
Engine Controller J1939 Data Link Support Configuration Proprietary J1939 Support
Engine Cooldown Speed Configuration Low Idle
Engine Operating State Input Configuration Hardwired Input
Fuel Priming Feature Enable Status Disabled
Engine Forced Idle Feature Enable Status Disabled
AVR Desired Voltage Request
Maximum Generator Voltage Output Bias Percentage 5%
Generator Nominal Output Voltage 480 Volts
Battery Voltage Monitor
High Battery Voltage Warning Event Threshold 30.0 Volts
High Battery Voltage Warning Event Notification Delay
30 sec
Time
High Battery Voltage Shutdown Event Threshold 32.0 Volts
High Battery Voltage Shutdown Event Notification Delay
2 sec
Time
Low Battery Voltage Warning Event Threshold 18.0 Volts
Low Battery Voltage Warning Event Notification Delay
10 sec
Time
Low Battery Charging System Voltage Warning Event
25.0 Volts
Threshold
Low Battery Charging System Voltage Warning Event
30 sec
Notification Delay Time
Low Cranking Voltage Warning Event Threshold 0.0 Volts
Low Cranking Voltage Warning Event Notification Delay
2 sec
Time
Digital Inputs
Digital Input #1 Active State Configuration Low
Digital Input #2 Active State Configuration Low

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 3 of 35

Digital Input #3 Active State Configuration Low


Digital Input #4 Active State Configuration Low
Digital Input #5 Active State Configuration Low
Digital Input #6 Active State Configuration Low
Digital Selectors
Digital Selector #1 Source Configuration Input #2
Digital Selector #2 Source Configuration Input #1
Digital Selector #3 Source Configuration Input #3
Digital Selector #4 Source Configuration Input #7
Digital Selector #5 Source Configuration Disabled or Not Installed
Digital Selector #6 Source Configuration Disabled or Not Installed
Digital Selector #7 Source Configuration Disabled or Not Installed
Digital Selector #8 Source Configuration Disabled or Not Installed
Digital Selector #9 Source Configuration Disabled or Not Installed
Digital Selector #10 Source Configuration Disabled or Not Installed
Engine Coolant Temperature Monitor
Engine Coolant Temperature Sensor Configuration Data Link
High Engine Coolant Temperature Warning Event
216 Deg F
Threshold
High Engine Coolant Temperature Warning Event
2 sec
Notification Delay Time
High Engine Coolant Temperature Shutdown Event
225 Deg F
Threshold
High Engine Coolant Temperature Shutdown Event
10 sec
Notification Delay Time
Low Engine Coolant Temperature Warning Event Threshold 70 Deg F
Low Engine Coolant Temperature Warning Event
2 sec
Notification Delay Time
Engine Coolant Temperature Sensor Configuration Code Map #1
Engine Oil Pressure Monitor
Engine Oil Pressure Sensor Configuration Data Link
Low Engine Oil Pressure Warning Event Threshold 35 psi
Low Idle Low Engine Oil Pressure Warning Event Threshold 15 psi
Low Engine Oil Pressure Warning Event Notification Delay
0 sec
Time
Low Engine Oil Pressure Shutdown Event Threshold 30 psi
Low Idle Low Engine Oil Pressure Shutdown Event
10 psi
Threshold
Low Engine Oil Pressure Shutdown Event Notification Delay
0 sec
Time

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 4 of 35

Low Engine Oil Pressure Step Speed 1200 rpm


Engine Oil Pressure Sensor Configuration Code Map #1
Engine Speed Monitor
Flywheel Teeth 136
Engine Overspeed Setpoint 2124 rpm
Engine Underspeed Warning Event Threshold 1548 rpm
Engine Underspeed Warning Event Notification Delay Time 2.0 sec
Engine Underspeed Shutdown Event Threshold 1476 rpm
Engine Underspeed Shutdown Event Notification Delay
2.0 sec
Time
Engine Speed Sensor Configuration Sensor
Event Input Functions
Event Input Function #1 Suspect Parameter Number Engine Coolant Level
Event Input Function #1 Failure Mode Identifier Condition Exists
Event Input Function #1 Event Notification Delay Time 10 sec
Event Input Function #1 Active State Configuration Low
Event Input Function #2 Suspect Parameter Number Fuel Tank Leak
Event Input Function #2 Failure Mode Identifier Condition Exists
Event Input Function #2 Event Notification Delay Time 0 sec
Event Input Function #2 Active State Configuration High
Event Input Function #3 Suspect Parameter Number Earth Fault
Event Input Function #3 Failure Mode Identifier Condition Exists
Event Input Function #3 Event Notification Delay Time 0 sec
Event Input Function #3 Active State Configuration High
Event Input Function #4 Suspect Parameter Number Fuel Level
Event Input Function #4 Failure Mode Identifier Low Warning
Event Input Function #4 Event Notification Delay Time 0 sec
Event Input Function #4 Active State Configuration High
Event Input Function #5 Suspect Parameter Number Disabled or Not Installed
Event Input Function #5 Failure Mode Identifier Disabled or Not Installed
Event Input Function #5 Event Notification Delay Time Disabled or Not Installed
Event Input Function #5 Active State Configuration Disabled or Not Installed
Event Input Function #6 Suspect Parameter Number Disabled or Not Installed
Event Input Function #6 Failure Mode Identifier Disabled or Not Installed
Event Input Function #6 Event Notification Delay Time Disabled or Not Installed
Event Input Function #6 Active State Configuration Disabled or Not Installed
Event Output Functions
Event Output Function #1 Suspect Parameter Number Engine Oil Pressure

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 5 of 35

Event Output Function #1 Trigger Condition **Disabled


Event Output Function #2 Suspect Parameter Number Disabled or Not Installed
Event Output Function #2 Trigger Condition Disabled or Not Installed
Event Output Function #3 Suspect Parameter Number Disabled or Not Installed
Event Output Function #3 Trigger Condition Disabled or Not Installed
Event Output Function #4 Suspect Parameter Number Disabled or Not Installed
Event Output Function #4 Trigger Condition Disabled or Not Installed
Event Output Function #5 Suspect Parameter Number Disabled or Not Installed
Event Output Function #5 Trigger Condition Disabled or Not Installed
Event Output Function #6 Suspect Parameter Number Disabled or Not Installed
Event Output Function #6 Trigger Condition Disabled or Not Installed
Event Output Function #7 Suspect Parameter Number Disabled or Not Installed
Event Output Function #7 Trigger Condition Disabled or Not Installed
Event Output Function #8 Suspect Parameter Number Disabled or Not Installed
Event Output Function #8 Trigger Condition Disabled or Not Installed
Event Response Configuration - Diagnostic Events
Air Filter Differential Pressure Sensor Diagnostic Response
Activate Warning Condition
Configuration
Air Filter Differential Pressure Sensor Diagnostic Audible
No
Alert
Air Filter Differential Pressure Sensor Diagnostic Breaker
No
#1 Trip
Air Filter Differential Pressure Sensor Diagnostic Breaker
No
#2 Trip
Ambient Air Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Ambient Air Temperature Sensor Diagnostic Audible Alert No
Ambient Air Temperature Sensor Diagnostic Breaker #1
No
Trip
Ambient Air Temperature Sensor Diagnostic Breaker #2
No
Trip
Engine Coolant Level Sensor Diagnostic Response
Activate Warning Condition
Configuration
Engine Coolant Level Sensor Diagnostic Audible Alert No
Engine Coolant Level Sensor Diagnostic Breaker #1 Trip No
Engine Coolant Level Sensor Diagnostic Breaker #2 Trip No
Engine Coolant Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Engine Coolant Temperature Sensor Diagnostic Audible
No
Alert

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 6 of 35

Engine Coolant Temperature Sensor Diagnostic Breaker #1


No
Trip
Engine Coolant Temperature Sensor Diagnostic Breaker #2
No
Trip
Engine Oil Level Sensor Diagnostic Response Configuration Activate Warning Condition
Engine Oil Level Sensor Diagnostic Audible Alert No
Engine Oil Level Sensor Diagnostic Breaker #1 Trip No
Engine Oil Level Sensor Diagnostic Breaker #2 Trip No
Engine Oil Pressure Sensor Diagnostic Response
Activate Warning Condition
Configuration
Engine Oil Pressure Sensor Diagnostic Audible Alert No
Engine Oil Pressure Sensor Diagnostic Breaker #1 Trip No
Engine Oil Pressure Sensor Diagnostic Breaker #2 Trip No
Engine Oil Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Engine Oil Temperature Sensor Diagnostic Audible Alert No
Engine Oil Temperature Sensor Diagnostic Breaker #1 Trip No
Engine Oil Temperature Sensor Diagnostic Breaker #2 Trip No
Activate Hard Shutdown
Engine Speed Sensor Diagnostic Response Configuration
Condition
Engine Speed Sensor Diagnostic Audible Alert Yes
Engine Speed Sensor Diagnostic Breaker #1 Trip No
Engine Speed Sensor Diagnostic Breaker #2 Trip No
Exhaust Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Exhaust Temperature Sensor Diagnostic Audible Alert No
Exhaust Temperature Sensor Diagnostic Breaker #1 Trip No
Exhaust Temperature Sensor Diagnostic Breaker #2 Trip No
Right Exhaust Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Right Exhaust Temperature Sensor Diagnostic Audible Alert No
Right Exhaust Temperature Sensor Diagnostic Breaker #1
No
Trip
Right Exhaust Temperature Sensor Diagnostic Breaker #2
No
Trip
Left Exhaust Temperature Sensor Diagnostic Response
Activate Warning Condition
Configuration
Left Exhaust Temperature Sensor Diagnostic Audible Alert No
Left Exhaust Temperature Sensor Diagnostic Breaker #1
No
Trip

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 7 of 35

Left Exhaust Temperature Sensor Diagnostic Breaker #2


No
Trip
Fire Extinguisher Pressure Sensor Diagnostic Response
Activate Warning Condition
Configuration
Fire Extinguisher Pressure Sensor Audible Alert No
Fire Extinguisher Pressure Sensor Breaker #1 Trip No
Fire Extinguisher Pressure Sensor Breaker #2 Trip No
Fuel Filter Differential Pressure Sensor Diagnostic
Activate Warning Condition
Response Configuration
Fuel Filter Differential Pressure Sensor Diagnostic Audible
No
Alert
Fuel Filter Differential Pressure Sensor Diagnostic Breaker
No
#1 Trip
Fuel Filter Differential Pressure Sensor Diagnostic Breaker
No
#2 Trip
Fuel Level Sensor Diagnostic Response Configuration Activate Warning Condition
Fuel Level Sensor Diagnostic Audible Alert No
Fuel Level Sensor Diagnostic Breaker #1 Trip No
Fuel Level Sensor Diagnostic Breaker #2 Trip No
External Tank Fuel Level Sensor Diagnostic Response
Activate Warning Condition
Configuration
External Tank Fuel Level Sensor Diagnostic Audible Alert No
External Tank Fuel Level Sensor Diagnostic Breaker #1
No
Trip
External Tank Fuel Level Sensor Diagnostic Breaker #2
No
Trip
Generator Bearing #1 Temperature Sensor Diagnostic
Activate Warning Condition
Response Configuration
Generator Bearing #1 Temperature Sensor Diagnostic
No
Audible Alert
Generator Bearing #1 Temperature Sensor Diagnostic
No
Breaker #1 Trip
Generator Bearing #1 Temperature Sensor Diagnostic
No
Breaker #2 Trip
Generator Output Sensing System Diagnostic Response
Activate Warning Condition
Configuration
Generator Output Sensing System Diagnostic Audible Alert Yes
Generator Output Sensing System Diagnostic Breaker #1
No
Trip
Generator Output Sensing System Diagnostic Breaker #2
No
Trip

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 8 of 35

Engine Oil Filter Differential Pressure Sensor Diagnostic


Activate Warning Condition
Response Config
Engine Oil Filter Differential Pressure Sensor Diagnostic
No
Audible Alert
Engine Oil Filter Differential Pressure Sensor Diagnostic
No
Breaker #1 Trip
Engine Oil Filter Differential Pressure Sensor Diagnostic
No
Breaker #2 Trip
Primary Data Link Diagnostic Response Configuration Activate Warning Condition
Primary Data Link Diagnostic Audible Alert No
Primary Data Link Diagnostic Breaker #1 Trip No
Primary Data Link Diagnostic Breaker #2 Trip No
Starting Air Pressure Sensor Diagnostic Response
Activate Warning Condition
Configuration
Starting Air Pressure Sensor Diagnostic Audible Alert No
Starting Air Pressure Sensor Diagnostic Breaker #1 Trip No
Starting Air Pressure Sensor Diagnostic Breaker #2 Trip No
Battery Charger Failure Diagnostic Response Configuration Activate Warning Condition
Battery Charger Failure Diagnostic Audible Alert Yes
Engine Controller Not Responding Diagnostic Response
Activate Warning Condition
Configuration
Engine Controller Not Responding Diagnostic Audible Alert No
Engine Controller Not Responding Diagnostic Breaker #1
No
Trip
Engine Controller Not Responding Diagnostic Breaker #2
No
Trip
Event Response Configuration - Engine Protection
Events
Hard Shutdown & Active Only
Air Damper Closed Event Response Configuration
Condition
Air Damper Closed Event Audible Alert Yes
High Air Filter Differential Pressure Warning Event
Activate Warning Condition
Response Configuration
High Air Filter Differential Pressure Warning Event Audible
Yes
Alert
High Air Filter Differential Pressure Warning Event Breaker
No
#1 Trip
High Air Filter Differential Pressure Warning Event Breaker
No
#2 Trip
High Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 9 of 35

High Air Filter Differential Pressure Shutdown Event


Yes
Audible Alert
High Air Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
High Air Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Air Filter Differential Pressure Warning Event
Activate Warning Condition
Response Configuration
Low Air Filter Differential Pressure Warning Event Audible
Yes
Alert
Low Air Filter Differential Pressure Warning Event Breaker
No
#1 Trip
Low Air Filter Differential Pressure Warning Event Breaker
No
#2 Trip
Low Air Filter Differential Pressure Warning Event Fault
Yes
Protection Timer
Low Air Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Low Air Filter Differential Pressure Shutdown Event Audible
Yes
Alert
Low Air Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
Low Air Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Air Filter Differential Pressure Shutdown Event Fault
Yes
Protection Timer
Activate Hard Shutdown
Emergency Stop Activated Event Response Configuration
Condition
Emergency Stop Activated Event Audible Alert Yes
Emergency Stop Activated Event Breaker #1 Trip No
Emergency Stop Activated Event Breaker #2 Trip No
High Engine Coolant Level Warning Event Response
Activate Warning Condition
Configuration
High Engine Coolant Level Warning Event Audible Alert Yes
High Engine Coolant Level Warning Event Breaker #1 Trip No
High Engine Coolant Level Warning Event Breaker #2 Trip No
High Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Coolant Level Shutdown Event Audible Alert Yes
High Engine Coolant Level Shutdown Event Breaker #1
No
Trip

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 10 of 35

High Engine Coolant Level Shutdown Event Breaker #2


No
Trip
Low Engine Coolant Level Warning Event Response
Activate Warning Condition
Configuration
Low Engine Coolant Level Warning Event Audible Alert Yes
Low Engine Coolant Level Warning Event Breaker #1 Trip No
Low Engine Coolant Level Warning Event Breaker #2 Trip No
Low Engine Coolant Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Coolant Level Shutdown Event Audible Alert Yes
Low Engine Coolant Level Shutdown Event Breaker #1 Trip No
Low Engine Coolant Level Shutdown Event Breaker #2 Trip No
High Engine Coolant Temperature Warning Event
Activate Warning Condition
Response Configuration
High Engine Coolant Temperature Warning Event Audible
Yes
Alert
High Engine Coolant Temperature Warning Event Breaker
No
#1 Trip
High Engine Coolant Temperature Warning Event Breaker
No
#2 Trip
High Engine Coolant Temperature Warning Event Fault
Yes
Protection Timer
High Engine Coolant Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Engine Coolant Temperature Shutdown Event Audible
Yes
Alert
High Engine Coolant Temperature Shutdown Event Breaker
No
#1 Trip
High Engine Coolant Temperature Shutdown Event Breaker
No
#2 Trip
High Engine Coolant Temperature Shutdown Event Fault
Yes
Protection Timer
Low Engine Coolant Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Engine Coolant Temperature Warning Event Audible
Yes
Alert
Low Engine Coolant Temperature Warning Event Breaker
No
#1 Trip
Low Engine Coolant Temperature Warning Event Breaker
No
#2 Trip
No
Low Engine Coolant Temperature Warning Event Fault

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 11 of 35

Protection Timer
Engine Failure To Start Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Engine Failure To Start Shutdown Event Audible Alert Yes
Engine Failure To Start Shutdown Event Breaker #1 Trip No
Engine Failure To Start Shutdown Event Breaker #2 Trip No
High Engine Oil Level Warning Event Response
Activate Warning Condition
Configuration
High Engine Oil Level Warning Event Audible Alert Yes
High Engine Oil Level Warning Event Breaker #1 Trip No
High Engine Oil Level Warning Event Breaker #2 Trip No
High Engine Oil Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Oil Level Shutdown Event Audible Alert Yes
High Engine Oil Level Shutdown Event Breaker #1 Trip No
High Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Level Warning Event Response
Activate Warning Condition
Configuration
Low Engine Oil Level Warning Event Audible Alert Yes
Low Engine Oil Level Warning Event Breaker #1 Trip No
Low Engine Oil Level Warning Event Breaker #2 Trip No
Low Engine Oil Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Oil Level Shutdown Event Audible Alert Yes
Low Engine Oil Level Shutdown Event Breaker #1 Trip No
Low Engine Oil Level Shutdown Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Engine Oil Pressure Warning Event Audible Alert Yes
Low Engine Oil Pressure Warning Event Breaker #1 Trip No
Low Engine Oil Pressure Warning Event Breaker #2 Trip No
Low Engine Oil Pressure Warning Event Fault Protection
Yes
Timer
Low Engine Oil Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Engine Oil Pressure Shutdown Event Audible Alert Yes
Low Engine Oil Pressure Shutdown Event Breaker #1 Trip No
Low Engine Oil Pressure Shutdown Event Breaker #2 Trip No
Low Engine Oil Pressure Shutdown Event Fault Protection
Yes
Timer

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 12 of 35

High Engine Oil Temperature Warning Event Response


Activate Warning Condition
Configuration
High Engine Oil Temperature Warning Event Audible Alert Yes
High Engine Oil Temperature Warning Event Breaker #1
No
Trip
High Engine Oil Temperature Warning Event Breaker #2
No
Trip
High Engine Oil Temperature Warning Event Fault
No
Protection Timer
High Engine Oil Temperature Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Engine Oil Temperature Shutdown Event Audible
Yes
Alert
High Engine Oil Temperature Shutdown Event Breaker #1
No
Trip
High Engine Oil Temperature Shutdown Event Breaker #2
No
Trip
High Engine Oil Temperature Shutdown Event Fault
No
Protection Timer
Low Engine Oil Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Engine Oil Temperature Warning Event Audible Alert Yes
Low Engine Oil Temperature Warning Event Breaker #1
No
Trip
Low Engine Oil Temperature Warning Event Breaker #2
No
Trip
Low Engine Oil Temperature Warning Event Fault
Yes
Protection Timer
Low Engine Oil Temperature Shutdown Event Response
Disable Condition
Configuration
Low Engine Oil Temperature Shutdown Event Audible Alert No
Low Engine Oil Temperature Shutdown Event Breaker #1
No
Trip
Low Engine Oil Temperature Shutdown Event Breaker #2
No
Trip
Low Engine Oil Temperature Shutdown Event Fault
No
Protection Timer
Unexpected Engine Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Unexpected Engine Shutdown Event Audible Alert Yes
Unexpected Engine Shutdown Event Breaker #1 Trip No

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 13 of 35

Unexpected Engine Shutdown Event Breaker #2 Trip No


Engine Overspeed Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Engine Overspeed Shutdown Event Audible Alert Yes
Engine Overspeed Shutdown Event Breaker #1 Trip No
Engine Overspeed Shutdown Event Breaker #2 Trip No
Engine Underspeed Warning Event Response Configuration Activate Warning Condition
Engine Underspeed Warning Event Audible Alert Yes
Engine Underspeed Warning Event Breaker #1 Trip No
Engine Underspeed Warning Event Breaker #2 Trip No
Engine Underspeed Warning Event Fault Protection Timer Yes
Engine Underspeed Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Engine Underspeed Shutdown Event Audible Alert Yes
Engine Underspeed Shutdown Event Breaker #1 Trip No
Engine Underspeed Shutdown Event Breaker #2 Trip No
Engine Underspeed Shutdown Event Fault Protection Timer Yes
High Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
High Exhaust Temperature Warning Event Audible Alert Yes
High Exhaust Temperature Warning Event Breaker #1 Trip No
High Exhaust Temperature Warning Event Breaker #2 Trip No
High Exhaust Temperature Warning Event Fault Protection
No
Timer
High Exhaust Temperature Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Exhaust Temperature Shutdown Event Audible Alert Yes
High Exhaust Temperature Shutdown Event Breaker #1
No
Trip
High Exhaust Temperature Shutdown Event Breaker #2
No
Trip
High Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Exhaust Temperature Warning Event Audible Alert Yes
Low Exhaust Temperature Warning Event Breaker #1 Trip No
Low Exhaust Temperature Warning Event Breaker #2 Trip No
Low Exhaust Temperature Warning Event Fault Protection
Yes
Timer

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 14 of 35

Low Exhaust Temperature Shutdown Event Response


Disable Condition
Configuration
Low Exhaust Temperature Shutdown Event Audible Alert No
Low Exhaust Temperature Shutdown Event Breaker #1
No
Trip
Low Exhaust Temperature Shutdown Event Breaker #2
No
Trip
Low Exhaust Temperature Shutdown Event Fault
Yes
Protection Timer
High Right Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
High Right Exhaust Temperature Warning Event Audible
Yes
Alert
High Right Exhaust Temperature Warning Event Breaker
No
#1 Trip
High Right Exhaust Temperature Warning Event Breaker
No
#2 Trip
High Right Exhaust Temperature Warning Event Fault
No
Protection Timer
High Right Exhaust Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Right Exhaust Temperature Shutdown Event Audible
Yes
Alert
High Right Exhaust Temperature Shutdown Event Breaker
No
#1 Trip
High Right Exhaust Temperature Shutdown Event Breaker
No
#2 Trip
High Right Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Right Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Right Exhaust Temperature Warning Event Audible
Yes
Alert
Low Right Exhaust Temperature Warning Event Breaker
No
#1 Trip
Low Right Exhaust Temperature Warning Event Breaker
No
#2 Trip
Low Right Exhaust Temperature Warning Event Fault
Yes
Protection Timer
Low Right Exhaust Temperature Shutdown Event
Disable Condition
Response Configuration
Low Right Exhaust Temperature Shutdown Event Audible

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 15 of 35

Alert No
Low Right Exhaust Temperature Shutdown Event Breaker
No
#1 Trip
Low Right Exhaust Temperature Shutdown Event Breaker
No
#2 Trip
Low Right Exhaust Temperature Shutdown Event Fault
No
Protection Timer
High Left Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
High Left Exhaust Temperature Warning Event Audible
Yes
Alert
High Left Exhaust Temperature Warning Event Breaker #1
No
Trip
High Left Exhaust Temperature Warning Event Breaker #2
No
Trip
High Left Exhaust Temperature Warning Event Fault
No
Protection Timer
High Left Exhaust Temperature Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Left Exhaust Temperature Shutdown Event Audible
Yes
Alert
High Left Exhaust Temperature Shutdown Event Breaker
No
#1 Trip
High Left Exhaust Temperature Shutdown Event Breaker
No
#2 Trip
High Left Exhaust Temperature Shutdown Event Fault
No
Protection Timer
Low Left Exhaust Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Left Exhaust Temperature Warning Event Audible
Yes
Alert
Low Left Exhaust Temperature Warning Event Breaker #1
No
Trip
Low Left Exhaust Temperature Warning Event Breaker #2
No
Trip
Low Left Exhaust Temperature Warning Event Fault
Yes
Protection Timer
Low Left Exhaust Temperature Shutdown Event Response
Disable Condition
Configuration
Low Left Exhaust Temperature Shutdown Event Audible
No
Alert
Low Left Exhaust Temperature Shutdown Event Breaker

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 16 of 35

#1 Trip No
Low Left Exhaust Temperature Shutdown Event Breaker
No
#2 Trip
Low Left Exhaust Temperature Shutdown Event Fault
No
Protection Timer
High Fuel Filter Differential Pressure Warning Event
Activate Warning Condition
Response Configuration
High Fuel Filter Differential Pressure Warning Event
Yes
Audible Alert
High Fuel Filter Differential Pressure Warning Event
No
Breaker #1 Trip
High Fuel Filter Differential Pressure Warning Event
No
Breaker #2 Trip
High Fuel Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Config Condition
High Fuel Filter Differential Pressure Shutdown Event
Yes
Audible Alert
High Fuel Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
High Fuel Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Warning Event
Activate Warning Condition
Response Configuration
Low Fuel Filter Differential Pressure Warning Event Audible
Yes
Alert
Low Fuel Filter Differential Pressure Warning Event Breaker
No
#1 Trip
Low Fuel Filter Differential Pressure Warning Event Breaker
No
#2 Trip
Low Fuel Filter Differential Pressure Warning Event Fault
Yes
Protection Timer
Low Fuel Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Low Fuel Filter Differential Pressure Shutdown Event
Yes
Audible Alert
Low Fuel Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
Low Fuel Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Fuel Filter Differential Pressure Shutdown Event Fault
Yes
Protection Timer
High Fuel Level Warning Event Response Configuration Activate Warning Condition

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 17 of 35

High Fuel Level Warning Event Audible Alert Yes


High Fuel Level Warning Event Breaker #1 Trip No
High Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
High Fuel Level Shutdown Event Response Configuration
Condition
High Fuel Level Shutdown Event Audible Alert Yes
High Fuel Level Shutdown Event Breaker #1 Trip No
High Fuel Level Shutdown Event Breaker #2 Trip No
Low Fuel Level Warning Event Response Configuration Activate Warning Condition
Low Fuel Level Warning Event Audible Alert Yes
Low Fuel Level Warning Event Breaker #1 Trip No
Low Fuel Level Warning Event Breaker #2 Trip No
Activate Hard Shutdown
Low Fuel Level Shutdown Event Response Configuration
Condition
Low Fuel Level Shutdown Event Audible Alert Yes
Low Fuel Level Shutdown Event Breaker #1 Trip No
Low Fuel Level Shutdown Event Breaker #2 Trip No
External Tank High Fuel Level Warning Event Response
Activate Warning Condition
Configuration
External Tank High Fuel Level Warning Event Audible Alert Yes
External Tank High Fuel Level Warning Event Breaker #1
No
Trip
External Tank High Fuel Level Warning Event Breaker #2
No
Trip
External Tank High Fuel Level Shutdown Event Response Activate Hard Shutdown
Configuration Condition
External Tank High Fuel Level Shutdown Event Audible
Yes
Alert
External Tank High Fuel Level Shutdown Event Breaker #1
No
Trip
External Tank High Fuel Level Shutdown Event Breaker #2
No
Trip
External Tank Low Fuel Level Warning Event Response
Activate Warning Condition
Configuration
External Tank Low Fuel Level Warning Event Audible Alert Yes
External Tank Low Fuel Level Warning Event Breaker #1
No
Trip
External Tank Low Fuel Level Warning Event Breaker #2
No
Trip

External Tank Low Fuel Level Shutdown Event Response Activate Hard Shutdown

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 18 of 35

Configuration Condition
External Tank Low Fuel Level Shutdown Event Audible
Yes
Alert
External Tank Low Fuel Level Shutdown Event Breaker #1
No
Trip
External Tank Low Fuel Level Shutdown Event Breaker #2
No
Trip
Fuel Leak Event Response Configuration Activate Warning Condition
Fuel Leak Event Audible Alert Yes
Fuel Leak Event Breaker #1 Trip No
Fuel Leak Event Breaker #2 Trip No
High Engine Oil Filter Differential Pressure Warning Event
Activate Warning Condition
Response Config
High Engine Oil Filter Differential Pressure Warning Event
Yes
Audible Alert
High Engine Oil Filter Differential Pressure Warning Event
No
Breaker #1 Trip
High Engine Oil Filter Differential Pressure Warning Event
No
Breaker #2 Trip
High Engine Oil Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Config Condition
High Engine Oil Filter Differential Pressure Shutdown Event
Yes
Audible Alert
High Engine Oil Filter Differential Pressure Shutdown Event
No
Breaker #1 Trip
High Engine Oil Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Event
Activate Warning Condition
Response Config
Low Engine Oil Filter Differential Pressure Warning Event
Yes
Audible Alert
Low Engine Oil Filter Differential Pressure Warning Event
No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Warning Event
No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Warning Fault
Yes
Protection Timer
Low Engine Oil Filter Differential Pressure Shutdown Event Activate Hard Shutdown
Response Config Condition
Low Engine Oil Filter Differential Pressure Shutdown Event
Yes
Audible Alert

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 19 of 35

Low Engine Oil Filter Differential Pressure Shutdown Event


No
Breaker #1 Trip
Low Engine Oil Filter Differential Pressure Shutdown Event
No
Breaker #2 Trip
Low Engine Oil Filter Differential Pressure Shutdown Fault
Yes
Protection Timer
High Starting Air Pressure Warning Event Response
Activate Warning Condition
Configuration
High Starting Air Pressure Warning Event Audible Alert Yes
High Starting Air Pressure Warning Event Breaker #1 Trip No
High Starting Air Pressure Warning Event Breaker #2 Trip No
High Starting Air Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Starting Air Pressure Shutdown Event Audible Alert Yes
High Starting Air Pressure Shutdown Event Breaker #1 Trip No
High Starting Air Pressure Shutdown Event Breaker #2 Trip No
Low Starting Air Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Starting Air Pressure Warning Event Audible Alert Yes
Low Starting Air Pressure Warning Event Breaker #1 Trip No
Low Starting Air Pressure Warning Event Breaker #2 Trip No
Low Starting Air Pressure Warning Event Fault Protection
Yes
Timer
Low Starting Air Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Starting Air Pressure Shutdown Event Audible Alert Yes
Low Starting Air Pressure Shutdown Event Breaker #1 Trip No
Low Starting Air Pressure Shutdown Event Breaker #2 Trip No
Low Starting Air Pressure Shutdown Event Fault Protection
Yes
Timer
High Gas Pressure Warning Event Response Configuration Activate Warning Condition
High Gas Pressure Warning Event Audible Alert Yes
High Gas Pressure Warning Event Breaker #1 Trip No
High Gas Pressure Warning Event Breaker #2 Trip No
High Gas Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Gas Pressure Shutdown Event Audible Alert Yes
High Gas Pressure Shutdown Event Breaker #1 Trip No
High Gas Pressure Shutdown Event Breaker #2 Trip No
Low Gas Pressure Warning Event Response Configuration Activate Warning Condition

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 20 of 35

Low Gas Pressure Warning Event Audible Alert Yes


Low Gas Pressure Warning Event Breaker #1 Trip No
Low Gas Pressure Warning Event Breaker #2 Trip No
Activate Hard Shutdown
Low Gas Pressure Shutdown Event Response Configuration
Condition
Low Gas Pressure Shutdown Event Audible Alert Yes
Low Gas Pressure Shutdown Event Breaker #1 Trip No
Low Gas Pressure Shutdown Event Breaker #2 Trip No
Engine Intake Manifold Charge Combustion Event Activate Hard Shutdown
Response Configuration Condition
Engine Intake Manifold Charge Combustion Event Audible
Yes
Alert
Engine Intake Manifold Charge Combustion Event Loss of
No
Utility
Engine Intake Manifold Charge Combustion Event Breaker
No
#1 Trip
Engine Intake Manifold Charge Combustion Event Breaker
No
#2 Trip
Engine Intake Manifold Charge Combustion Event Fault
No
Protection Timer
Event Response Configuration - Generator
Protection Events
High Generator Bearing #1 Temperature Warning Event
Activate Warning Condition
Response Configuration
High Generator Bearing #1 Temperature Warning Event
Yes
Audible Alert
High Generator Bearing #1 Temperature Warning Event
No
Breaker #1 Trip
High Generator Bearing #1 Temperature Warning Event
No
Breaker #2 Trip
High Generator Bearing #1 Temperature Warning Event
No
Fault Protection Timer
High Generator Bearing #1 Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
High Generator Bearing #1 Temperature Shutdown Event
Yes
Audible Alert
High Generator Bearing #1 Temperature Shutdown Event
No
Breaker #1 Trip
High Generator Bearing #1 Temperature Shutdown Event
No
Breaker #2 Trip
No
High Generator Bearing #1 Temperature Shutdown Event

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 21 of 35

Fault Protection Timer


Low Generator Bearing #1 Temperature Warning Event
Activate Warning Condition
Response Configuration
Low Generator Bearing #1 Temperature Warning Event
Yes
Audible Alert
Low Generator Bearing #1 Temperature Warning Event
No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Warning Event
No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Warning Event
Yes
Fault Protection Timer
Low Generator Bearing #1 Temperature Shutdown Event
Disable Condition
Response Configuration
Low Generator Bearing #1 Temperature Shutdown Event
No
Audible Alert
Low Generator Bearing #1 Temperature Shutdown Event
No
Breaker #1 Trip
Low Generator Bearing #1 Temperature Shutdown Event
No
Breaker #2 Trip
Low Generator Bearing #1 Temperature Shutdown Event
No
Fault Protection Timer
Activate Hard Shutdown
Earth Fault Event Response Configuration
Condition
Earth Fault Event Audible Alert Yes
Earth Fault Event Breaker #1 Trip No
Earth Fault Event Breaker #2 Trip No
Generator Winding #1 High Temperature Warning Event
Activate Warning Condition
Response Configuration
Generator Winding #1 High Temperature Warning Event
Yes
Audible Alert
Generator Winding #1 High Temperature Warning Event
No
Breaker #1 Trip
Generator Winding #1 High Temperature Warning Event
No
Breaker #2 Trip
Generator Winding #1 High Temperature Warning Event
No
Fault Protection Timer
Generator Winding #2 High Temperature Warning Event
Activate Warning Condition
Response Configuration
Generator Winding #2 High Temperature Warning Event
Yes
Audible Alert
Generator Winding #2 High Temperature Warning Event
No
Breaker #1 Trip

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 22 of 35

Generator Winding #2 High Temperature Warning Event


No
Breaker #2 Trip
Generator Winding #2 High Temperature Warning Event
No
Fault Protection Timer
Generator Winding #3 High Temperature Warning Event
Activate Warning Condition
Response Configuration
Generator Winding #3 High Temperature Warning Event
Yes
Audible Alert
Generator Winding #3 High Temperature Warning Event
No
Breaker #1 Trip
Generator Winding #3 High Temperature Warning Event
No
Breaker #2 Trip
Generator Winding #3 High Temperature Warning Event
No
Fault Protection Timer
Generator Winding #1 High Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Generator Winding #1 High Temperature Shutdown Event
Yes
Audible Alert
Generator Winding #1 High Temperature Shutdown Event
No
Breaker #1 Trip
Generator Winding #1 High Temperature Shutdown Event
No
Breaker #2 Trip
Generator Winding #1 High Temperature Shutdown Event
No
Fault Protection Timer
Generator Winding #2 High Temperature Shutdown Event
Data Invalid
Response Configuration
Generator Winding #2 High Temperature Shutdown Event
Yes
Audible Alert
Generator Winding #2 High Temperature Shutdown Event
No
Breaker #1 Trip
Generator Winding #2 High Temperature Shutdown Event
No
Breaker #2 Trip
Generator Winding #2 High Temperature Shutdown Event
No
Fault Protection Timer
Generator Winding #3 High Temperature Shutdown Event Activate Hard Shutdown
Response Configuration Condition
Generator Winding #3 High Temperature Shutdown Event
Yes
Audible Alert
Generator Winding #3 High Temperature Shutdown Event
No
Breaker #1 Trip
Generator Winding #3 High Temperature Shutdown Event
No
Breaker #2 Trip

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 23 of 35

Generator Winding #3 High Temperature Shutdown Event


No
Fault Protection Timer
Generator High Power Warning Event Response
Activate Warning Condition
Configuration
Generator High Power Warning Event Audible Alert Yes
Generator High Power Warning Event Breaker #1 Trip No
Generator High Power Warning Event Breaker #2 Trip No
Event Response Configuration - Other System
Events
High Ambient Air Temperature Warning Event Response
Activate Warning Condition
Configuration
High Ambient Air Temperature Warning Event Audible Alert Yes
High Ambient Air Temperature Warning Event Breaker #1
No
Trip
High Ambient Air Temperature Warning Event Breaker #2
No
Trip
High Ambient Air Temperature Warning Event Fault
No
Protection Timer
High Ambient Air Temperature Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Ambient Air Temperature Shutdown Event Audible
Yes
Alert
High Ambient Air Temperature Shutdown Event Breaker
No
#1 Trip
High Ambient Air Temperature Shutdown Event Breaker
No
#2 Trip
High Ambient Air Temperature Shutdown Event Fault
No
Protection Timer
Low Ambient Air Temperature Warning Event Response
Activate Warning Condition
Configuration
Low Ambient Air Temperature Warning Event Audible Alert Yes
Low Ambient Air Temperature Warning Event Breaker #1
No
Trip
Low Ambient Air Temperature Warning Event Breaker #2
No
Trip
Low Ambient Air Temperature Shutdown Event Response
Disable Condition
Configuration
Low Ambient Air Temperature Shutdown Event Audible
No
Alert
Low Ambient Air Temperature Shutdown Event Breaker #1
No
Trip

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 24 of 35

Low Ambient Air Temperature Shutdown Event Breaker #2


No
Trip
Automatic Transfer Switch In Normal Position Event
Active Only Condition
Response Configuration
Automatic Transfer Switch In Normal Position Event
No
Audible Alert
Automatic Transfer Switch In Emergency Position Event
Active Only Condition
Response Config
Automatic Transfer Switch In Emergency Position Event
No
Audible Alert
High Battery Voltage Warning Event Response
Activate Warning Condition
Configuration
High Battery Voltage Warning Event Audible Alert Yes
High Battery Voltage Warning Event Breaker #1 Trip No
High Battery Voltage Warning Event Breaker #2 Trip No
High Battery Voltage Shutdown Event Response Activate Soft Shutdown
Configuration Condition
High Battery Voltage Shutdown Event Audible Alert Yes
High Battery Voltage Shutdown Event Breaker #1 Trip No
High Battery Voltage Shutdown Event Breaker #2 Trip No
Low Battery Voltage Warning Event Response
Activate Warning Condition
Configuration
Low Battery Voltage Warning Event Audible Alert Yes
Low Battery Voltage Warning Event Breaker #1 Trip No
Low Battery Voltage Warning Event Breaker #2 Trip No
Low Battery Voltage Warning Event Fault Protection Timer No
Low Battery Charging System Voltage Warning Event
Disable Condition
Response Configuration
Low Battery Charging System Voltage Warning Event
No
Audible Alert
Low Battery Charging System Voltage Warning Event
No
Breaker #1 Trip
Low Battery Charging System Voltage Warning Event
No
Breaker #2 Trip
Low Battery Charging System Voltage Warning Event Fault
No
Protection Timer
Engine In Cooldown Event Response Configuration Active Only Condition
Engine In Cooldown Event Audible Alert No
Engine Speed-Generator Output Freq Mismatch Warning
Activate Warning Condition
Event Response Config
Engine Speed-Generator Output Freq Mismatch Warning

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 25 of 35

Event Audible Alert Yes


Engine Speed-Generator Output Freq Mismatch Warning
No
Event Breaker #1 Trip
Engine Speed-Generator Output Freq Mismatch Warning
No
Event Breaker #2 Trip
High Fire Extinguisher Pressure Warning Event Response
Activate Warning Condition
Configuration
High Fire Extinguisher Pressure Warning Event Audible
Yes
Alert
High Fire Extinguisher Pressure Warning Event Breaker #1
No
Trip
High Fire Extinguisher Pressure Warning Event Breaker #2
No
Trip
High Fire Extinguisher Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
High Fire Extinguisher Pressure Shutdown Event Audible
Yes
Alert
High Fire Extinguisher Pressure Shutdown Event Breaker
No
#1 Trip
High Fire Extinguisher Pressure Shutdown Event Breaker
No
#2 Trip
Low Fire Extinguisher Pressure Warning Event Response
Activate Warning Condition
Configuration
Low Fire Extinguisher Pressure Warning Event Audible
Yes
Alert
Low Fire Extinguisher Pressure Warning Event Breaker #1
No
Trip
Low Fire Extinguisher Pressure Warning Event Breaker #2
No
Trip
Low Fire Extinguisher Pressure Warning Event Fault
No
Protection Timer
Low Fire Extinguisher Pressure Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Low Fire Extinguisher Pressure Shutdown Event Audible
Yes
Alert
Low Fire Extinguisher Pressure Shutdown Event Breaker
No
#1 Trip
Low Fire Extinguisher Pressure Shutdown Event Breaker
No
#2 Trip
Low Fire Extinguisher Pressure Shutdown Event Fault
No
Protection Timer
Generator Control Not in Automatic Warning Event

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 26 of 35

Response Configuration Activate Warning Condition


Generator Control Not in Automatic Warning Event Audible
Yes
Alert
Generator Breaker Locked Out Warning Event Response Warning & Active Only
Configuration Condition
Generator Breaker Locked Out Warning Event Audible Alert Yes
Generator Breaker Locked Out Warning Event Breaker #1
No
Trip
Generator Breaker Locked Out Warning Event Breaker #2
No
Trip
Utility Breaker Locked Out Warning Event Response Warning & Active Only
Configuration Condition
Utility Breaker Locked Out Warning Event Audible Alert
Yes
Utility Breaker Locked Out Warning Event Breaker #1 Trip
No
Utility Breaker Locked Out Warning Event Breaker #2 Trip
No
Activate Hard Shutdown
Earth Leakage Event Response Configuration
Condition
Earth Leakage Event Audible Alert Yes
Earth Leakage Event Breaker #1 Trip No
Earth Leakage Event Breaker #2 Trip No
Emergency Power System Supplying Load Event Response Warning & Active Only
Configuration Condition
Emergency Power System Supplying Load Event Audible
No
Alert
Low Cranking Voltage Warning Event Response
Disable Condition
Configuration
Low Cranking Voltage Warning Event Audible Alert No
Low Cranking Voltage Warning Event Breaker #1 Trip No
Low Cranking Voltage Warning Event Breaker #2 Trip No
Event Response Configuration - Custom Events
Custom Event #1 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #1 High Warning Event Audible Alert Yes
Custom Event #1 High Warning Event Breaker #1 Trip No
Custom Event #1 High Warning Event Breaker #2 Trip No
Custom Event #1 High Warning Event Fault Protection
No
Timer
Custom Event #1 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #1 High Shutdown Event Audible Alert Yes

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 27 of 35

Custom Event #1 High Shutdown Event Breaker #1 Trip No


Custom Event #1 High Shutdown Event Breaker #2 Trip No
Custom Event #1 High Shutdown Event Fault Protection
No
Timer
Custom Event #1 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #1 Low Warning Event Audible Alert Yes
Custom Event #1 Low Warning Event Breaker #1 Trip No
Custom Event #1 Low Warning Event Breaker #2 Trip No
Custom Event #1 Low Warning Event Fault Protection
No
Timer
Custom Event #1 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #1 Low Shutdown Event Audible Alert Yes
Custom Event #1 Low Shutdown Event Breaker #1 Trip No
Custom Event #1 Low Shutdown Event Breaker #2 Trip No
Custom Event #1 Low Shutdown Event Fault Protection
No
Timer
Custom Event #1 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #1 Condition Exists Event Audible Alert No
Custom Event #1 Condition Exists Event Loss of Utility No
Custom Event #1 Condition Exists Event Breaker #1 Trip No
Custom Event #1 Condition Exists Event Breaker #2 Trip No
Custom Event #1 Condition Exists Event Fault Protection
No
Timer
Custom Event #2 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #2 High Warning Event Audible Alert Yes
Custom Event #2 High Warning Event Breaker #1 Trip No
Custom Event #2 High Warning Event Breaker #2 Trip No
Custom Event #2 High Warning Event Fault Protection
No
Timer
Custom Event #2 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #2 High Shutdown Audible Alert Yes
Custom Event #2 High Shutdown Breaker #1 Trip No
Custom Event #2 High Shutdown Breaker #2 Trip No
Custom Event #2 High Shutdown Fault Protection Timer No

Custom Event #2 Low Warning Event Response Activate Warning Condition

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 28 of 35

Configuration
Custom Event #2 Low Warning Audible Alert Yes
Custom Event #2 Low Warning Breaker #1 Trip No
Custom Event #2 Low Warning Breaker #2 Trip No
Custom Event #2 Low Warning Fault Protection Timer No
Custom Event #2 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #2 Low Shutdown Event Audible Alert Yes
Custom Event #2 Low Shutdown Event Breaker #1 Trip No
Custom Event #2 Low Shutdown Event Breaker #2 Trip No
Custom Event #2 Low Shutdown Event Fault Protection
No
Timer
Custom Event #2 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #2 Condition Exists Event Audible Alert No
Custom Event #2 Condition Exists Event Loss of Utility No
Custom Event #2 Condition Exists Event Breaker #1 Trip No
Custom Event #2 Condition Exists Event Breaker #2 Trip No
Custom Event #2 Condition Exists Event Fault Protection
No
Timer
Custom Event #3 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #3 High Warning Event Audible Alert Yes
Custom Event #3 High Warning Event Breaker #1 Trip No
Custom Event #3 High Warning Event Breaker #2 Trip No
Custom Event #3 High Warning Event Fault Protection
No
Timer
Custom Event #3 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #3 High Shutdown Event Audible Alert Yes
Custom Event #3 High Shutdown Event Breaker #1 Trip No
Custom Event #3 High Shutdown Event Breaker #2 Trip No
Custom Event #3 High Shutdown Event Fault Protection
No
Timer
Custom Event #3 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #3 Low Warning Event Audible Alert Yes
Custom Event #3 Low Warning Event Breaker #1 Trip No
Custom Event #3 Low Warning Event Breaker #2 Trip No
Custom Event #3 Low Warning Event Fault Protection

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 29 of 35

Timer No
Custom Event #3 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #3 Low Shutdown Event Audible Alert Yes
Custom Event #3 Low Shutdown Event Breaker #1 Trip No
Custom Event #3 Low Shutdown Event Breaker #2 Trip No
Custom Event #3 Low Shutdown Event Fault Protection
No
Timer
Custom Event #3 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #3 Condition Exists Event Audible Alert No
Custom Event #3 Condition Exists Event Loss of Utility No
Custom Event #3 Condition Exists Event Breaker #1 Trip No
Custom Event #3 Condition Exists Event Breaker #2 Trip No
Custom Event #3 Condition Exists Event Fault Protection
No
Timer
Custom Event #4 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #4 High Warning Event Audible Alert Yes
Custom Event #4 High Warning Event Breaker #1 Trip No
Custom Event #4 High Warning Event Breaker #2 Trip No
Custom Event #4 High Warning Event Fault Protection
No
Timer
Custom Event #4 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #4 High Shutdown Event Audible Alert Yes
Custom Event #4 High Shutdown Event Breaker #1 Trip No
Custom Event #4 High Shutdown Event Breaker #2 Trip No
Custom Event #4 High Shutdown Event Fault Protection
No
Timer
Custom Event #4 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #4 Low Warning Event Audible Alert Yes
Custom Event #4 Low Warning Event Breaker #1 Trip No
Custom Event #4 Low Warning Event Breaker #2 Trip No
Custom Event #4 Low Warning Event Fault Protection
No
Timer
Custom Event #4 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #4 Low Shutdown Event Audible Alert Yes

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 30 of 35

Custom Event #4 Low Shutdown Event Breaker #1 Trip No


Custom Event #4 Low Shutdown Event Breaker #2 Trip No
Custom Event #4 Low Shutdown Event Fault Protection
No
Timer
Custom Event #4 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #4 Condition Exists Event Audible Alert No
Custom Event #4 Condition Exists Event Loss of Utility No
Custom Event #4 Condition Exists Event Breaker #1 Trip No
Custom Event #4 Condition Exists Event Breaker #2 Trip No
Custom Event #4 Condition Exists Event Fault Protection
No
Timer
Custom Event #5 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #5 High Warning Event Audible Alert Yes
Custom Event #5 High Warning Event Breaker #1 Trip No
Custom Event #5 High Warning Event Breaker #2 Trip No
Custom Event #5 High Warning Event Fault Protection
No
Timer
Custom Event #5 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #5 High Shutdown Event Audible Alert Yes
Custom Event #5 High Shutdown Event Breaker #1 Trip No
Custom Event #5 High Shutdown Event Breaker #2 Trip No
Custom Event #5 High Shutdown Event Fault Protection
No
Timer
Custom Event #5 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #5 Low Warning Event Audible Alert Yes
Custom Event #5 Low Warning Event Breaker #1 Trip No
Custom Event #5 Low Warning Event Breaker #2 Trip No
Custom Event #5 Low Warning Event Fault Protection
No
Timer
Custom Event #5 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #5 Low Shutdown Event Audible Alert Yes
Custom Event #5 Low Shutdown Event Breaker #1 Trip No
Custom Event #5 Low Shutdown Event Breaker #2 Trip No
Custom Event #5 Low Shutdown Event Fault Protection
No
Timer

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 31 of 35

Custom Event #5 Condition Exists Event Response


Active Only Condition
Configuration
Custom Event #5 Condition Exists Event Audible Alert No
Custom Event #5 Condition Exists Event Loss of Utility No
Custom Event #5 Condition Exists Event Breaker #1 Trip No
Custom Event #5 Condition Exists Event Breaker #2 Trip No
Custom Event #5 Condition Exists Event Fault Protection
No
Timer
Custom Event #6 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #6 High Warning Event Audible Alert Yes
Custom Event #6 High Warning Event Breaker #1 Trip No
Custom Event #6 High Warning Event Breaker #2 Trip No
Custom Event #6 High Warning Event Fault Protection
No
Timer
Custom Event #6 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #6 High Shutdown Event Audible Alert Yes
Custom Event #6 High Shutdown Event Breaker #1 Trip No
Custom Event #6 High Shutdown Event Breaker #2 Trip No
Custom Event #6 High Shutdown Event Fault Protection
No
Timer
Custom Event #6 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #6 Low Warning Event Audible Alert Yes
Custom Event #6 Low Warning Event Breaker #1 Trip No
Custom Event #6 Low Warning Event Breaker #2 Trip No
Custom Event #6 Low Warning Event Fault Protection
No
Timer
Custom Event #6 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #6 Low Shutdown Event Audible Alert Yes
Custom Event #6 Low Shutdown Event Breaker #1 Trip No
Custom Event #6 Low Shutdown Event Breaker #2 Trip No
Custom Event #6 Low Shutdown Event Fault Protection
No
Timer
Custom Event #6 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #6 Condition Exists Event Audible Alert No
Custom Event #6 Condition Exists Event Loss of Utility No

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 32 of 35

Custom Event #6 Condition Exists Event Breaker #1 Trip No


Custom Event #6 Condition Exists Event Breaker #2 Trip No
Custom Event #6 Condition Exists Event Fault Protection
No
Timer
Custom Event #7 High Warning Event Response
Activate Warning Condition
Configuration
Custom Event #7 High Warning Event Audible Alert Yes
Custom Event #7 High Warning Event Breaker #1 Trip No
Custom Event #7 High Warning Event Breaker #2 Trip No
Custom Event #7 High Warning Event Fault Protection
No
Timer
Custom Event #7 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #7 High Shutdown Event Audible Alert Yes
Custom Event #7 High Shutdown Event Breaker #1 Trip No
Custom Event #7 High Shutdown Event Breaker #2 Trip No
Custom Event #7 High Shutdown Event Fault Protection
No
Timer
Custom Event #7 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #7 Low Warning Event Audible Alert Yes
Custom Event #7 Low Warning Event Breaker #1 Trip No
Custom Event #7 Low Warning Event Breaker #2 Trip No
Custom Event #7 Low Warning Event Fault Protection
No
Timer
Custom Event #7 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #7 Low Shutdown Event Audible Alert Yes
Custom Event #7 Low Shutdown Event Breaker #1 Trip No
Custom Event #7 Low Shutdown Event Breaker #2 Trip No
Custom Event #7 Low Shutdown Event Fault Protection
No
Timer
Custom Event #7 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #7 Condition Exists Event Audible Alert No
Custom Event #7 Condition Exists Event Loss of Utility No
Custom Event #7 Condition Exists Event Breaker #1 Trip No
Custom Event #7 Condition Exists Event Breaker #2 Trip No
Custom Event #7 Condition Exists Event Fault Protection
No
Timer

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 33 of 35

Custom Event #8 High Warning Event Response


Activate Warning Condition
Configuration
Custom Event #8 High Warning Event Audible Alert Yes
Custom Event #8 High Warning Event Breaker #1 Trip No
Custom Event #8 High Warning Event Breaker #2 Trip No
Custom Event #8 High Warning Event Fault Protection
No
Timer
Custom Event #8 High Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #8 High Shutdown Event Audible Alert Yes
Custom Event #8 High Shutdown Event Breaker #1 Trip No
Custom Event #8 High Shutdown Event Breaker #2 Trip No
Custom Event #8 High Shutdown Event Fault Protection
No
Timer
Custom Event #8 Low Warning Event Response
Activate Warning Condition
Configuration
Custom Event #8 Low Warning Event Audible Alert Yes
Custom Event #8 Low Warning Event Breaker #1 Trip No
Custom Event #8 Low Warning Event Breaker #2 Trip No
Custom Event #8 Low Warning Event Fault Protection
No
Timer
Custom Event #8 Low Shutdown Event Response Activate Hard Shutdown
Configuration Condition
Custom Event #8 Low Shutdown Event Audible Alert Yes
Custom Event #8 Low Shutdown Event Breaker #1 Trip No
Custom Event #8 Low Shutdown Event Breaker #2 Trip No
Custom Event #8 Low Shutdown Event Fault Protection
No
Timer
Custom Event #8 Condition Exists Event Response
Active Only Condition
Configuration
Custom Event #8 Condition Exists Event Audible Alert No
Custom Event #8 Condition Exists Event Loss of Utility No
Custom Event #8 Condition Exists Event Breaker #1 Trip No
Custom Event #8 Condition Exists Event Breaker #2 Trip No
Custom Event #8 Condition Exists Event Fault Protection
No
Timer
Event System
Event Warning Condition Response Auto Reset Enable
Enabled
Status
Event Audible Alert Response Auto Reset Enable Status Enabled

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 34 of 35

Event Loss Of Utility Response Auto Reset Enable Status Enabled


Event Breaker #1 Trip Response Auto Reset Enable Status Enabled
Event Breaker #2 Trip Response Auto Reset Enable Status Enabled
Generator AC Monitor
Generator Connection Configuration Wye (or Star) Connection
Generator Potential Transformer Primary Winding Rating 1 Volts
Generator Potential Transformer Secondary Winding Rating 1 Volts
Generator Current Transformer Primary Winding Rating 1000 Amps
Generator Current Transformer Secondary Winding Rating 5 Amps
Number of Generator Poles 4 Poles
Generator Rated Frequency 60 Hz
Generator Rated Voltage 480 Volts
Generator Rated Power 545 kW
Generator Rated Apparent Power 709 kVA
Governor Desired Engine Speed Request
Maximum Engine Speed Bias 400 rpm
Generator Nominal Output Frequency 60.0 Hz
Electronic Control Module Reduced Power Mode
Electronic Control Module Reduced Power Mode Enable
Disabled
Status
Electronic Control Module Reduced Power Mode Delay
30 min
Time
Relay Outputs
Relay Output #1 Active State Configuration High
Relay Output #2 Active State Configuration High
Relay Output #3 Active State Configuration High
Relay Output #4 Active State Configuration High
Relay Output #5 Active State Configuration High
Relay Output #6 Active State Configuration High
Programmable Trip Point Function
Programmable Trip Point Function #1 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #1 Percentage
Disabled or Not Installed
Threshold
Programmable Trip Point Function #1 Hysteresis
Disabled or Not Installed
Percentage
Programmable Trip Point Function #1 Trip Activation Delay
Disabled or Not Installed
Time
Programmable Trip Point Function #1 Trip Deactivation
Disabled or Not Installed
Delay Time

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020
Page 35 of 35

Programmable Trip Point Function #2 Trigger Condition Disabled or Not Installed


Programmable Trip Point Function #2 Percentage
Disabled or Not Installed
Threshold
Programmable Trip Point Function #2 Hysteresis
Disabled or Not Installed
Percentage
Programmable Trip Point Function #2 Trip Activation Delay
Disabled or Not Installed
Time
Programmable Trip Point Function #2 Trip Deactivation
Disabled or Not Installed
Delay Time
Programmable Trip Point Function #3 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #3 Percentage
Disabled or Not Installed
Threshold
Programmable Trip Point Function #3 Hysteresis
Disabled or Not Installed
Percentage
Programmable Trip Point Function #3 Trip Activation Delay
Disabled or Not Installed
Time
Programmable Trip Point Function #3 Trip Deactivation
Disabled or Not Installed
Delay Time
Programmable Trip Point Function #4 Trigger Condition Disabled or Not Installed
Programmable Trip Point Function #4 Percentage
Disabled or Not Installed
Threshold
Programmable Trip Point Function #4 Hysteresis
Disabled or Not Installed
Percentage
Programmable Trip Point Function #4 Trip Activation Delay
Disabled or Not Installed
Time
Programmable Trip Point Function #4 Trip Deactivation
Disabled or Not Installed
Delay Time
Configuration Data
Engine Serial Number Not Programmed
Display Preferences
Display Pressure Units Configuration psi
Display Temperature Units Configuration Degrees Farenheit
Display Volume Units Configuration liters

file:///C:/ProgramData/Caterpillar/Electronic%20Technician/temp/STPLReport4.HTM 3/18/2020