You are on page 1of 10

PAPER PRESENTATON

ON

ABSTRACT Theoretical analysis, along with


experimental results obtained from a 200-
This paper presents a fully-digital- V, 20-kW laboratory system, verifies the
controlled shunt hybrid filter for damping viability and effectiveness of the proposed
of harmonic propagation in power hybrid filter.
distribution systems. The harmonic
propagation is caused by I. INTRODUCTION
resonance between line inductances and
power capacitors installed for power factor IN RECENT years, harmonic propagation
correction. A possible solution to damping has become a serious problem in power
out harmonic propagation is based distribution systems. It consists in
on installation of a shunt pure active harmonic-voltage amplification due to
filter at the end of a feeder. This paper resonance between line inductances and
proposes a shunt hybrid active filter shunt capacitors installed for power factor
characterized by series connection of a correction. The worst case occurs under
seventh-tuned LC filter per phase and a no-load conditions from a theoretical point
small-rated three-phase active filter. Like of view. Thus, it may happen at night in a
the pure filter, the hybrid filter is real power distribution system under light-
connected to the end bus of a feeder. The load conditions. This harmonic
capacitor of the LC filter imposes a high propagation effect has been studied and
impedance to the fundamental frequency, measured in actual power distribution
so that the fundamental voltage appears systems [1], [2]. In order to damp out
across the capacitor. This unique feature harmonic propagation, a shunt pure active
allows us to directly connect the hybrid filter based on voltage detection has been
filter to the 6.6-kV power line without proposed and tested [3]–[8]. This active
step-down transformers. Furthermore, the filter is controlled in such a way as to act
capacitor used in this hybrid filter is as a damping resistor for harmonic
lighter, cheaper and smaller than the frequencies. It has been found that the best
transformer used in the pure filter. site to install the active filter is at the end
bus of a distribution feeder, thus achieving directly installed at the end of a 6.6-kV
harmonic damping throughout the distribution feeder, for the purpose of
distribution feeder [3]. The harmonic mitigating harmonic propagation
propagation may appear in several feeders throughout the feeder. Experimental
within a power distribution network. This results were obtained with a fully-digital
fact makes the treatment of this problem controlled shunt hybrid active filter
costly and technically difficult. The cost of connected to a three-phase distribution line
installing several active filters dispersed on simulator rated at 200-V, 50-Hz, and 20-
the network should be assumed by the kW. Theoretical analysis, along with
utility company. On the other hand, the experimental results, verifies satisfactory
physical size of a conventional shunt pure damping performance of the proposed
active filter is too large to be installed on hybrid filter.
electric poles. To overcome the harmonic
propagation problem, the size and cost of II. ACTIVE FILTERS FOR HARMONIC
the present solution must be reduced DAMPING
drastically. One of the main obstacles is
the transformer required for the shunt pure A. System Configuration
active filter.
This paper proposes a new Fig. 1 shows a 6.6-kV
alternative to harmonic damping in a 6.6- simplified power distribution feeder under
kV system. It consists of a shunt hybrid no-load conditions, where a shunt pure
active filter composed of series connection active filter for damping out harmonic
of a 7th-tuned LC filter per phase and a propagation is connected by a step-down
small-rated three-phase active filter. Due transformer at the end of the feeder. On the
to the presence of the LC filter, the other hand, Fig. 2 shows the simplified
fundamental voltage is decoupled from the feeder having a shunt hybrid active filter
distribution system, thus reducing the proposed in this paper. The transformer in
voltage rating of the active filter. This the pure filter is replaced by a capacitor in
remarkable feature does not require the hybrid filter. The purpose of the
any transformer for connecting the capacitor is to impose a high impedance to
hybrid filter to the 6.6-kV bus. The the fundamental frequency so that the
replacement of the transformer by the fundamental voltage appears exclusively
capacitor included in the LC filter makes across the capacitor. This means that no
the hybrid filter compact, light and fundamental voltage is applied across the
inexpensive. Hybrid active filters have active filter. Note that the weight of a 6.6-
been researched and tested [9]–[14]. It is kVcapacitor ranges from one-tenth to one-
well known that a hybrid filter twentieth as light as that of a 6.6-kV/400-
configuration helps to reduce the active V step-down transformer with the same
filter rating. Nevertheless, the solutions kVA rating as the capacitor.
presented in the available literature are
intended, not for harmonic damping in
power distribution systems, but for
harmonic compensation of nonlinear
loads. For example, a hybrid filter in [15]
and [16] is the same in circuit
configuration as that in this paper, but
different in control strategy. The hybrid
filter in this paper is based on voltage
detection, and behaves as a damping
resistor for harmonic frequencies. It is
Voltage is amplified by a control gain KV .
Thus the harmonic current reference is
Fig. 3 shows the detailed power circuit given by i*ch.
of the hybrid filter, which consists of a
three-phase voltage-fed PWM inverter,
and a series connection L of and C per The actual harmonic compensating current
phase. Note that the tuned frequency L of i*ch is extracted from the detected
and C is not the fifth-harmonic frequency compensating current ic . Assuming that ich
but around the seventh-harmonic is equal to its reference, the hybrid filter
frequency. The reason is that the seventh- behaves as a damping resistor of 1/ KV
tuned LC filter is less bulky than the fifth- [V/A] for harmonic frequencies. The
tuned LC filter as long as both filters have optimal value KV of is equal to the inverse
the same inductor as . The dc-bus of the of the characteristic impedance of the
PWM inverter has only a capacitor without distribution feeder. With this value, the
external supply, and the dc-bus voltage is hybrid filter can damp out harmonic
controlled by the hybrid filter. The hybrid propagation effectively.
filter is controlled so as to draw the
compensating current from the C. Experimental System
distribution line. Fig. 4 shows the experimental system
under no-load conditions. A three-phase
B. Operating Principle power distribution feeder simulator rated
The hybrid filter with current at 200 V, 50 Hz, and 20 kW is used for the
control is based on voltage detection. The laboratory experiments. This feeder
compensating current of the hybrid filter simulator has a harmonic generator
consists of a fundamental component and connected at bus V1 . This produces an
harmonic components. The fundamental amount of harmonic voltage at. Table I
component is determined by the Summarizes the line simulator parameters.
impedance of the LC filter while the When a lossless line is assumed, the
harmonic components are controlled by characteristic impedance of the feeder
the active filter. Three-phase voltages and simulator, Zo Can be calculated as
currents are detected at the installation bus.
The harmonic voltage in each phase is
extracted from the detected three-phase
voltage, and then the harmonic A shunt hybrid active filter is installed at
bus V4 . It consists of a 100- F, 2-mH LC
filter and a voltage-source PWM inverter
using power MOSFETs. The LC filter has 2105 (Analog Devices) unit. The sampling
a tune frequency of 356 Hz. Table II period of the digital controller is 50 s (20
summarizes the hybrid filter parameters. kS/s). The digital signals in the A/D and
The dc-bus voltage of the PWM inverter D/A units are limited to 10 V.
is controlled to be 40 V. Note that the dc-
bus voltage as low as 40 V in the 200-V
system corresponds to a dc-bus voltage as To cope with the time and phase delays
low as 1.3 kV in a 6.6-kV system. This inherent to the digital controller, the signal
means that adopting a diode-clamped sampling is synchronized with the 50-Hz
three-level inverter allows us to use 1200- line frequency. This also prevents data
V IGBTs that are easily available on the aliasing from the digital controller. The
market at low cost. phase reference is obtained from the
Referring to [7], the control gain Kv fundamental voltage detected at the
should be set to the inverse of the installation bus, and it is processed in the
characteristic impedance of the feeder. PLL unit to create both phase signal Wst
That is and triangular carrier wave Vtri used in the
PWM unit. The sine waveform used for
co- ordinates transformation is created by
using a sine table in the DSP unit.

B. Harmonic Detection
There are several methods to extract the
harmonic components from the detected
three-phase waveforms. Among them, the
so-called p-q theory based on time domain
has been widely applied to the harmonic
extraction circuit of active filters. The
detected three-phase voltage and current
are transformed into the d-q coordinates as
shown in Fig. 7. Two first-order digital
high-pass filters (HPFs) with the same
cutoff frequency as 17 Hz extract the dc
Passage of 300 ms, the magnetic contactor component which corresponds to the
will be turned on, thus bypassing the fundamental frequency in the d-q
resistor. Once the starting procedure is coordinates. Finally the obtained harmonic
complete, the PWM signal will be voltage and current are transformed from
provided to the gate circuit of each the d-q coordinates into the three-phase
MOSFET. The dc-bus voltage will begin harmonic voltage and current.
to increase, and finally it will reach its
reference value.
III. CONTROL SYSTEM

A. Digital Controller

The active filter is controlled


by a digital controller which consists of an
A/D unit, a DSP unit, a digital PWM unit
and a phase-locked-loop (PLL) unit as
shown in Fig. 6. The DSP unit used for
processing is a 16-bit fixed-point ADSP-
Note that the first-order digital filters sudden increments or decrements in the
require one sampling delay (50 s) for dc-bus voltage. It is also designed to
calculation. However, this delay is short prevent the control loop from numerical
enough to be neglected. saturation in the DSP signals. The limiter
On the other hand, the two digital is set to 2.5-V in the digital controller
filters cause a delay as slow as 60 ms due which corresponds to 25% of the
to their time response. However, this delay maximum control signal. For a 40-V dc-
would produce little bad effect on its bus voltage, the maximum dc-bus control
dynamic operating performance because
the hybrid filter is intended for harmonic
voltage damping in power distribution
systems. Moreover, dynamic changes in
harmonic voltages are usually slow
because a dynamic load change is hidden
by the other static loads connected to the
same feeder.

C. DC-Bus Voltage Control


A critical issue in this hybrid
active filter is the dc-bus voltage control.
The dc bus consists of a single capacitor signal corresponds to a 10-V peak-to-peak
charged from the power supply. During fundamental voltage for the inverter. A
operation, the active filter may absorb an low-pass filter (LPF) with a cutoff
amount of active power into, or release it frequency of 10 Hz eliminates ripples from
from, the dc capacitor. Excessive active the detected dc-bus voltage. Hence, no
power absorption will increase the dc-bus harmonic components appear in the dc-bus
voltage, and may damage the active filter. voltage control signal.
The strategy used to control the dc-bus
voltage is based on active-power control. D. Current Control
According to the – theory, a dc component Fig. 9 shows a control block diagram of
in the – coordinates corresponds to active the hybrid filter. The detected harmonic
power. No direct axis current on the d-q voltage Vh is multiplied by a gain Kv to
coordinates flows in the LC filter. Thus, produce the current reference i*ch . The
the active power is controlled by adjusting current reference is compared with the
the quadrature axis component. The direct detected harmonic compensating current
axis is set to zero. ich and the difference between i*ch and ich is
Fig. 8 shows a block diagram for multiplied by a control gain Kc . This
the dc-bus voltage control. The dc-bus results in producing the inverter voltage
voltage is detected and compared with a reference V*c . The effect of a time delay,
reference, amplifying the error signal by a that is, one sampling period T(=50µs)
control gain of 10 A/V. Finally, the inherent to the digital controller is
obtained control signal on the – represented as e-st in the control block
coordinates is transformed into a three- diagram.
phase fundamental voltage reference by
using the inverse d-q transformation. The IV. STABILITY ANALYSIS OF
resultant dc-bus voltage control signal is CURRENT CONTROL LOOP
added to the voltage reference V*c .
A limiter is included in the dc- The stability of the current control
bus control loop. It is designed to ensure a loop is analyzed based on
smooth transient response and to avoid
the experimental setup shown in Fig. 4 and Wc(s). when K=10 V/A. To observe the
the parameters contained effect of the harmonic detection transfer
in Tables I and II. An arithmetic software function on the current loop stability, the
package “Mathematica,” is used for open-loop transfer function is calculated
analysis. Fig. 10 shows a current-control with and without the harmonic detection
block diagram of the hybrid filter. The transfer function. In both cases, the system
supply voltage and the dc-bus voltage is stable with a gain margin of 15 dB. The
control signal V*R can be assumed as harmonic detection scheme does not affect
disturbance signals in the current control. the performance of the current controller.
Since the current control emphasizes to
control the harmonic current, these A gain margin of 15 dB means
disturbance signals having the that Kc could be increased to 31.6 V/A
fundamental frequency can be ignored. without instability. In this system,
The harmonic current ich is obtained however, Kc is set to 10 V/A in order to
from the detected hybrid filter current ic , keep a 15-dB stability margin.
as shown in Fig. 7. The transfer function Experimental verifications show that the
for the harmonic detection scheme can be gain of Kc=10 V/A is high enough to keep
generally expressed as the steady-state error below 5% of the
reference signal while it is low enough to
prevent the DSP signals from numerical
saturation.
Where Tc is the time constant of the two V. ANALYSIS OF DAMPING
identical high-pass filters which extracts PERFORMANCE
the dc component in the d–q coordinates, Fig. 12 shows an equivalent circuit
and for analysis. In order to analyze harmonic
damping performance, the supply voltage
is assumed to be a harmonic voltage of
Vsh=V1 . This means that no fundamental
component exists. According to Fig. 9, the
ac output voltage of the active filter, Vc
for harmonic frequencies can be expressed
as

Where Zf is the impedance of the LC


filter. Kv and Kc are the control gains of
W1 is the angular frequency of the
the hybrid filter. Note that the positive
extracted frequency which in this case
direction of Vc is to draw the
orresponds to the fundamental frequency.
compensating current Ic from the
The PWM inverter is assumed to
distribution system. From (8), it is clear
be an ideal inverter[H(s)=1]. Therefore,
that the hybrid filter is characterized as a
the current-control stability depends on the
voltage-controlled voltage source. Kv ,Kc ,
control gain Kc . The system becomes
marginally stable when the open-loop
transfer functionWc(s).

Fig. 11 shows the frequency


response of the open-loop transfer function
frequency in a 50-Hz system. A fifth
harmonic voltage can be found easily in
real distribution systems, as well as third-
and seventh-harmonic voltages.
Theoretically, the fifth-harmonic voltage is
amplified by 21 times, the third- and
seventh-harmonic voltages are amplified
by four times.
When only the LC filter is
connected to the feeder simulator, the
characteristic impedance of the system
changes, and consequently the frequency
response of the harmonic propagation
changes substantially. The presence of the
LC filter makes the system resonant at 350
Hz, where the terminal voltage is
attenuated. The LC filter can be considered
as a passive filter tuned to the seventh-
harmonic frequency. The fifth-harmonic
voltage amplification is considerably
lower than that in the previous

Zf and the delay time e-st are constant


parameters whereas the hybrid filter
voltage varies according to the harmonic
voltage at the installation bus V4 .
Fig. 13 shows the frequency
characteristics of harmonic propagation
and damping, calculated as the ratio of the
voltage at the installation bus,V4 with
respect to the voltage at the source, V1 for
the system shown in Fig. 12. The hybrid
filter voltage is calculated according to (8).
Note that the line simulator is designed to
emulate a real distribution line, including
the line impedance and the shunt
capacitors normally installed for power
factor correction.
According to Fig. 13, when no
filter is connected, the characteristic
impedance of the system, which
corresponds to the characteristic
impedance of the line simulator only, has
three resonance frequencies. The lowest case, having an amplification ratio of
resonance frequency which happens to about 12 times. This value is still unsafe,
have also the highest amplification ratio is because when the fifth-harmonic
at 250 Hz, that is, the fifth-harmonic
frequency becomes high, the terminal
voltage become highly distorted.

When the hybrid filter is


connected, the harmonic propagation is
completely eliminated, so that no
amplification occurs at any frequency.
Thus, the hybrid filter effectively damps
out the harmonic propagation throughout
the feeder. Connected and the inverter shut off. The
PWM pulses will be activated after the
VI. EXPERIMENTAL RESULTS transient ends.
A harmonic voltage generator
The worst case for harmonic injects a fifth-harmonic voltage of 2% at
voltage propagation occurs under no-load V1 under no-load conditions, as shown in
conditions when one of resonant Fig. 4. Experimental waveforms of bus
frequencies between line inductance and voltages V1-V4 and compensating current
shunt capacitors is close to one of Ic for three different operating conditions
dominant harmonic frequencies. The are shown in Fig. 14. Additionally, Table
presence of resistive loads contributes to III summarizes the third-, fifth-, and
mitigating harmonic voltage propagation. seventh-harmonic voltages and the THD
Hence, dynamic load changes may not values for the operating conditions
produce any serious indicated in Fig. 14.
effect on the hybrid filter for harmonic When no filter is connected, the
voltage damping in power distribution fifth-harmonic voltage is amplified by
systems. In contrast, conventional active eight times due to harmonic propagation,
and hybrid filters for harmonic current distorting severely the voltage waveform.
compensation of nonlinear loads would be The eighth-harmonic voltage as well as the
strongly affected by dynamic load third-harmonic voltage are amplified
changes. Dynamic changes in harmonic slightly. This result shows the effect of
voltages are usually slow in power harmonic propagation on the distribution
distribution systems because dynamic load system.
changes are hidden by other static loads. When only the LC filter is
According to the above considerations, the connected, the harmonic propagation is
following experiments were carried out reduced considerably, because its
under steady state and no-load conditions. connection changes the characteristic
If, eventually, a dynamic load impedance of the system. However,
change causes over voltages or Over harmonic amplification still occurs so that
currents to the hybrid filter, the PWM the voltage waveform is still distorted. The
inverter in the hybrid filter leaves the three THD value reaches 6.1%. This does not
upper MOSFETs turned on and the three comply with harmonic mitigation
lower MOSFETs turned off. This standards and guidelines. However, the LC
operation keeps the LC filter filter reduces considerably the harmonic
propagation, compared with the previous
case.
When the hybrid filter is
connected, the harmonic propagation is
completely eliminated. None of the
harmonic frequencies are amplified. The
THD value in V4 is kept as low as 2.1%,
because the harmonic components at the No phase delay occurs in the
installation bus or bus 4 are reduced. The compensating current with respect to the
fundamental component is the same as that current reference. The hybrid filter is
in case of the LC filter connected because stable and robust, being a solution
the active filter presents a high recommended to deal with harmonic
impedance to the fundamental frequency. propagation. The viability and
These experimental results conclude that effectiveness of the proposed shunt hybrid
the hybrid filter effectively damps out active filter have been confirmed
harmonic propagation. theoretically and experimentally,
Fig. 15 shows the transient response of achieving good performance in damping
the dc-bus controller, where V*B is the dc- out harmonic propagation in power
bus voltage reference Vdc and is the actual distribution systems.
dc-bus voltage. Due to the presence of the
limiter in Fig. 8, the transient response is REFERENCES
smooth enough to reach the steady state in [1] Task Force on Harmonics modeling
0.2 s. Fig. 16 shows a steady-state and Simulation, “Modeling and simulation
characteristic of the current control, where of the propagation of harmonics in electric
I*ch corresponds to the harmonic current power networks. II. Sample systems and
reference, and Ich to the actual harmonic examples,” Trans. Power Delivery, vol.
current. The steady-state error is small in 11, no. 1, pp. 466–474, Jan. 1996.
amplitude, and moreover no phase delay [2] S. M. Williams, G. T. Brownfield, and
exists between the current reference and J. W. Duffus, “Harmonic propagation on
the actual detected current. Note that Fig. an electric distribution system: field
16 uses the same experimental data as Fig. measurements compared with computer
14(c). simulation,” Trans. Power Delivery, vol. 8,
no. 2, pp. 547–552, Apr. 1993.
[3] H. Akagi, “Control strategy and site
selection of a shunt active filter for
damping of harmonic propagation in
power distribution systems,” IEEE Trans.
Power Delivery, vol. 12, no. 1, pp. 354–
363, Feb. 1997.
[4] H. Akagi, H. Fujita, and K.Wada, “A
It is clear that Ich is the same as Ic shunt active filter based on voltage
when the fundamental component is detection for harmonic termination of a
extracted from Ic . The current control radial power distribution line,” IEEE
loop as well as the dc-bus control loop Trans. Ind. Applicat., vol. 35, no. 3, pp.
works properly and stably. 638–645, May/Jun. 1999.
[5] P. Jintakosonwit, H. Fujita, and H.
VII. CONCLUSION Akagi, “Control and performance of a
This paper has discussed fully-digital-controlled shunt active filter
control and performance of a transformer for installation on a power distribution
less shunt hybrid active filter for system,” IEEE Trans. Power Electron.,
installation on 6.6-kV power distribution vol. 17, no. 1, pp.132–140, Jan. 2002.
systems. The replacement of a 6.6-kV
transformer by a 6.6-kV capacitor
contributes to a significant reduction in
cost, size and weight. Moreover it allows
us to use 1200-V IGBTs that are easily
available on the market and at a low cost.

You might also like