PROJECT Industrial Cable tray Rack REV - R0 DOC. ECR-001 DATE 19-Mar-20
FORCES
Max force - Fy = 70.00 KN
INPUT DATA
ALLOWBLE BEARING PRESSURE FOR CONC. Wal = 0.25 x Fck = 6.25 N / mm2 (REFER IS 456)
HENCE SAFE
3w
a2 - ( b2 / 4 )
THICKNESS OF THE BASE PLATE, Tp reqd. = σbs
Tp reqd. = 14.31 mm
PROJECT Industrial Cable tray Rack REV - R0 DOC. ECR-001 DATE 19-Mar-20
DESIGN OF BOLT
DIAMETER OF BOLT, Ф = 20 mm
FOR WIND & SEISMIC CASE ADD 25% TO σtf, σws = 150 N / mm2
HENCE SAFE