You are on page 1of 6

www.hilti.ca Profis Anchor 2.8.

1
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2019-04-22
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-HY 200 + HAS-R 316 SS 3/4
Effective embedment depth: hef,opti = 89 mm (hef,limit = 381 mm)
Material: ASTM F 593
Evaluation Service Report: ESR-3187
Issued I Valid: -|-
Proof: Design method CSA A23.3-14 / Chem.
Stand-off installation: eb = 0 mm (no stand-off); t = 13 mm
Anchor plate: lx x ly x t = 508 mm x 508 mm x 13 mm; (Recommended plate thickness: not calculated
Profile: S shape (AISC); (L x W x T x FT) = 76 mm x 59 mm x 4 mm x 7 mm
Base material: cracked concrete, fc' = 20.68 N/mm2; h = 10,668 mm, Temp. short/long: 20/20 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < 15M bar

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.8.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2019-04-22
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [kN] 3 4


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 0.000 14.500 0.000 14.500
2 0.000 14.500 0.000 14.500 x
3 0.000 14.500 0.000 14.500
4 0.000 14.500 0.000 14.500

max. concrete compressive strain: - [‰] 1 2


max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 0.000 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load
Load Nf [kN] Capacity Nr [kN] Utilization bN = Nf/Nr Status
Steel Strength* N/A N/A N/A N/A
Bond Strength** N/A N/A N/A N/A
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Strength** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.8.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2019-04-22
E-Mail:

4 Shear load
Load Vf [kN] Capacity Vr [kN] Utilization bV = Vf/Vr Status
Steel Strength* 14.500 41.927 35 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength controls)** 58.000 131.422 45 OK
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength


Vs,uta = ESR value refer to ICC-ES ESR-3187
Vsar = 0.6 Ase,V f s futa R CSA A23.3-14 Eq. D.31
Vsar ≥ Vfa CSA A233-14 Table D.1

Variables
n Ase,V [mm2] futa [N/mm2]
1 216 586.05
Calculations
Vs,uta [kN]
75.887
Results
Vs,uta [kN] fs R Vsar [kN] Vfa [kN]
75.887 0.850 0.650 41.927 14.500

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.8.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2019-04-22
E-Mail:

4.2 Pryout Strength (Bond Strength controls)

Vcpgr =kcp [(AA ) y


Na
Na0
ec,Na ]
y ed,Na y cp,Na Nba R CSA A23.3-14 Eq. D.45
Vcpgr ≥ Vfa,g CSA A23.3-14 Table D.1
ANa see CSA A23.3-14, Part D.6.5.1, Fig. D.11
ANa0 = (2 cNa)2 CSA A23.3-14 Eq. D.22
cNa = 10 da √ t uncr
7.60
CSA A23.3-14 Eq. D.23

( )
1
y ec,Na = e' ≤ 1.0 CSA A23.3-14 Eq. D.25
1+ N
cNa
y ed,Na = 0.7 + 0.3 ( )ca,min
cac
≤ 1.0 CSA A23.3-14 Eq. D.27

y cp,Na = MAX ( )
ca,min cNa
,
cac cac
≤ 1.0 CSA A23.3-14 Eq. D.29
Nba = l a f c t r p da hef CSA A23.3-14 Eq. D.24

Variables
2
kcp t uncr [N/mm ] da [mm] hef [mm] ca,min [mm]
2.000 15.59 19 89 ∞

2
t cr [N/mm ] e'1,N [mm] e'2,N [mm] cac [mm] la
8.85 0 0 119 1.000

Calculations
cNa [mm] ANa [mm2] ANa0 [mm2]
273 639,438 297,733
y ed,Na y ec1,Na y ec2,Na y cp,Na
1.000 1.000 1.000 1.000
Results
fc Nba [kN] Vcpg [kN] R Vcpgr [kN] Vfa,g [kN]
0.650 30.596 131.422 1.000 131.422 58.000

5 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This
means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate
thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate
assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and
for plausibility! 
• Condition A applies when supplementary reinforcement is used. The R factor is increased for non-steel Design Strengths except Pullout Strength
and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to
your local standard.
• Checking the transfer of loads into the base material is required in accordance with CSA A23.3!
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. CSA A23.3-14 Annex D,
Clause D.10.1

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.8.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2019-04-22
E-Mail:

6 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-HY 200 + HAS-R 316 SS 3/4
Profile: S shape (AISC); 76 x 59 x 4 x 7 mm Installation torque: 0.136 kNm
Hole diameter in the fixture: df = 21 mm Hole diameter in the base material: 22 mm
Plate thickness (input): 13 mm Hole depth in the base material: 89 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 133 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required

6.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required accessories • Dispenser including cassette and mixer
• Properly sized drill bit to blow from the bottom of the hole • Torque wrench
• Proper diameter wire brush
y

254 254

127

254
3 4 254

x
254

1 2
127

127 254 127

Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 -127 -127 - - - -
2 127 -127 - - - -
3 -127 127 - - - -
4 127 127 - - - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.ca Profis Anchor 2.8.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 2019-04-22
E-Mail:

7 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan