Load Amp Duration Of Load Start Time Of Load in Duration Of total Duration

sec from 0 Load in sec


Delta Time

AMP MINUTE Sec sec sec sec


A1 500 T1 30 1800 0 1800 1800 Load Increasing Each Section
A2 600 T2 60 3600 1800 3600 5400
A3 700 T3 90 5400 5400 5400 10800

It is assumed that there is one extra negative plate


Section Load Amp Load DATA From ETAP Typical Selected Battery Library For Average Typical AH Considered For Evaluation Of Required Average Battery AH/A Factor AH CALC PER REQUIRED AH AH CALCULATED ETAP AH Sizing ETAP & CALC SECTION
Legend SUB-SECTION PER SECTION FROM ALL SECTIONS DEVIATION IN
FACTOR PU
Average Value Of Total Plates Total Positive Plates Tmin For Each Typical ETAP Lead Acid Total Amp @ Relevant (AH/A)Tmin as
Battery AH Considered (PP) SubSection BatteryData Amp/PP @ Tmin T Per Subsection Relevant

Section 1 500 A1 1672 23 11 30 103.27 1135.97 1.4719 735.9349 Section 1


735.935 S1

Section(1+2)_1 500 A1 1672 23 11 90 60 660 2.5333 1266.6667 Section(1+2)_1


Section(1+2)_2 100 A2-A1 1672 23 11 60 75 825 2.0267 202.6667 Section(1+2)_2
1469.333 S1+2

Section(1+2+3)_1 500 A1 1672 23 11 180 39.64 436.04 3.8345 1917.2553 Section(1+2+3)_1


Section(1+2+3)_2 100 A2-A1 1672 23 11 150 45 495 3.3778 337.7778 Section(1+2+3)_2
Section(1+2+3)_3 100 A3-A2 1672 23 11 90 60 660 2.5333 253.3333 Section(1+2+3)_3
2508.366 S1+2+3
Ratio
AH Battery Required Based On Largest of all sections 2508.366 2552 1.0173952223
(All derating factors such as temperature correction, ageing,growth & DOD factors are ignored)

ETAP Library Data For Considered AH attached as extra Sheet In This EXCEL
Load Amp Duration Of Load Start Time Of Load in Duration Of total Duration
sec from 0 Load in sec
Delta Time

AMP MINUTE Sec sec sec sec


A1 700 T1 30 1800 0 1800 1800 Load Decreasing Each Section
A2 600 T2 60 3600 1800 3600 5400
A3 500 T3 90 5400 5400 5400 10800

It is assumed that there is one extra negative plate


Section Load Amp Load DATA From ETAP Typical Selected Battery Library For Average Typical AH Considered For Evaluation Of Required Average Battery AH/A Factor AH CALC PER REQUIRED AH AH CALCULATED ETAP AH Sizing ETAP & CALC SECTION
Legend SUB-SECTION PER SECTION FROM ALL SECTIONS DEVIATION IN
FACTOR PU
Average Value Of Total Plates Total Positive Plates Tmin For Each Typical ETAP Lead Acid Total Amp @ Relevant (AH/A)Tmin as
Battery AH Considered (PP) SubSection BatteryData Amp/PP @ Tmin T Per Subsection Relevant

Section 1 700 A1 1672 23 11 30 103.27 1135.97 1.4719 1030.3089 Section 1


1030.309 S1

Section(1+2)_1 700 A1 1672 23 11 90 60 660 2.5333 1773.3333 Section(1+2)_1


Section(1+2)_2 -100 A2-A1 1672 23 11 60 75 825 2.0267 -202.6667 Section(1+2)_2
1570.667 S1+2

Section(1+2+3)_1 700 A1 1672 23 11 180 39.64 436.04 3.8345 2684.1574 Section(1+2+3)_1


Section(1+2+3)_2 -100 A2-A1 1672 23 11 150 45 495 3.3778 -337.7778 Section(1+2+3)_2
Section(1+2+3)_3 -100 A3-A2 1672 23 11 90 60 660 2.5333 -253.3333 Section(1+2+3)_3
2093.046 S1+2+3
Ratio
AH Battery Required Based On Largest of all sections 2093.046 2152 1.0281664549
(All derating factors such as temperature correction, ageing,growth & DOD factors are ignored)

ETAP Library Data For Considered AH attached as extra Sheet In This EXCEL
LEAD ACID BATTERY
AMPERES ON DISCHARGE FOR VARIOUS AH AT DIFFERENT END CELL VOLTAGE FOR AH/A DiSCHARGE FACTOR INFORMATION REQUIRED
End cell voltage considered is 1.75v
ALCAD VENDOR A DISCHARGE DATA FOR VARIOUS ALCAD BATTTERY AH FOR END CELL OF 1.75 V/AND AT 1.81 V CELL