PERHITUNGAN POWER FAKTOR FAKTOR

UNTUK PEMASANGAN KAPASITOR BANK

I. Perhitungan Power Factor pada SDP

1. Pada SDP 1 (Prioritas)


Inominal = 32 ∠ 0°

2. Pada SDP 2 (Prioritas)


Standart Power Factor PLN = 0.8 – 0.99 (mendekati 1)

PF AC = 0.6 dan Inominal =2 A


PF Komputer = 0.8 dan Inominal = 0.4 A
PF KK 100VA =1 dan Inominal = 0.5 A
PF KK 1000VA =1 dan Inominal = 4.5 A
PF KK 1000VA =1 dan Inominal = 4.5 A
Maka,
Arc Cos PF AC (0.6) = 53.13°
Arc Cos PF Komp (0.8) = 36.86°
Arc Cos PF KK (1) = 0°

Sehingga PF total SDP 2 (Ia + Ib + Ic + Id + Ie)

PF total = Ia + Ib + Ic + Id + Ie
= 2∠ 53.13° + 0.4∠ 36.86° + 0.5∠ 0° + 4.5∠ 0° + 4.5∠ 0°
= 11.02 + 1.83i
= 11.17∠ 9.42°
Maka Pf total = Cos 9.42°
= 0.98
3. Pada SDP 3 (Non Prioritas)
Standart Power Factor PLN = 0.8 – 0.99 (mendekati 1)

PF Refrigenerator = 0.87 dan Inominal = 0.9 A


PF AC = 0.6 dan Inominal =2 A
PF Cooker = 0.68 dan Inominal = 2.3 A
PF Mesin LAS = 0.68 dan Inominal = 15.2 A
PF KK 100VA =1 dan Inominal = 0.5 A
Maka,
Arc Cos PF AC (0.6) = 53.13°
Arc Cos PF Ref (0.87) = 29.54°
Arc Cos PF Cook (0.68) = 47.15°
Arc Cos PF M.Las (0.68) = 47.15°

Sehingga PF total SDP 3 (Ia + Ib + Ic + Id + Ie)

PF total = Ia + Ib + Ic + Id + Ie
= 2∠ 53.13° + 0.9∠ 29.54° + 2.3∠ 47.15° + 15.2∠ 47.15° + 0.5∠ 0°
= 14.38 + 14.87i
= 20.68∠ 45.95°
Maka Pf total = Cos 45.95°
= 0.69

4. Pada SDP 4 (Prioritas)


Standart Power Factor PLN = 0.8 – 0.99 (mendekati 1)

PF Mesin A = 0.86 dan Inominal = 15.5 A


PF Mesin B = 0.87 dan Inominal = 29.5 A
Maka,
Arc Cos PF Mesin A (0.86) = 30.38°
Arc Cos PF Mesin B (0.87) = 29.54°

Sehingga PF total SDP 4 (Ia + Ib )

PF total = Ia + Ib
= 15.5∠ 30.38° + 29.5∠ 29.54°
= 38.96 + 22.4i
= 44.94∠ 29.86°
Maka Pf total = Cos 29.86°
= 0.86

5. Pada SDP 5 (Prioritas)


Standart Power Factor PLN = 0.8 – 0.99 (mendekati 1)

PF Mesin C = 0.87 dan Inominal = 42 A


PF Mesin D = 0.87 dan Inominal = 60 A
Maka,
Arc Cos PF Mesin C (0.87) = 29.54°
Arc Cos PF Mesin D (0.87) = 29.54°

Sehingga PF total SDP 5 (Ia + Ib )


PF total = Ia + Ib
= 42∠ 29.54°+ 60∠ 29.54°
= 88.74 + 50.28i
= 101.99∠ 29.53°
Maka Pf total = Cos 29.53°
= 0.87

6. Pada SDP 6 (Non Prioritas)


Standart Power Factor PLN = 0.8 – 0.99 (mendekati 1)

PF Mesin E = 0.86 dan Inominal = 23 A


PF Mesin F = 0.87 dan Inominal = 38 A
Maka,
Arc Cos PF Mesin E (0.86) = 30.38°
Arc Cos PF Mesin F (0.87) = 29.54°

Sehingga PF total SDP 6 (Ia + Ib )


PF total = Ia + Ib
= 23∠ 30.38°+ 38∠ 29.54°
= 52.90 + 30.36i
= 60.99∠ 29.85°
Maka Pf total = Cos 29.58°
= 0.86
7. Pada SDP 7 (Non Prioritas)
Standart Power Factor PLN = 0.8 – 0.99 (mendekati 1)

PF Mesin G = 0.87 dan Inominal = 72 A


PF OVEN = 0.87 dan Inominal = 17 A
Maka,
Arc Cos PF Mesin G (0.87) = 29.54°
Arc Cos PF OVEN (0.87) = 29.54°

Sehingga PF total SDP 7 (Ia + Ib )


PF total = Ia + Ib
= 72∠ 29.54°+ 17∠ 29.54°
= 77.43 + 43.87i
= 88.99∠ 29.53°
Maka Pf total = Cos 29.53°
= 0.87
II. Pemasangan Capasitor Bank

1. Capasitor Bank 1 dipasang pada MDP PRIORITAS

Sehingga PF total = PFtotal SDP 1 + SDP 2 + PF Total SDP 4 + PF total SDP 5


= 32 ∠ 0°+ 11.17∠ 9.42°+ 44.94∠ 29.86°+ 101.99∠ 29.53°
= 32 + (11.02 + 1.83i) + (38.96 + 22.4i) + (88.74 + 50.28i)
= 138.73 + 74.47i
= 157.45∠ 28.22°
= cos 28.22
= 0.88
Diketahui
Daya total (SDP 2, SDP 3, dan SDP 4) = 1221.43 kVA x 0.88 = 1074.85 kW
Pf total tanpa kompensasi = 0.85
Pf Kompensasi = 0.95

Sehingga,
Daya Total Kompensasi = (daya SDP 2 + daya SDP 4 + daya SDP 5) x 0.8
= 1074.85 x 0.5 (Daya Terpakai)
= 1074.85 x 0.5
= 537.42 kW

Daya Kompensasi < Daya Beban

Perhitungan
a. Tanpa Kompensasi
Cos ∅ 1 Tanpa Kompensasi = arc cos 0.88 = 28.22 °
Tan ∅1 Tanpa Kompensasi = Tan 28.22° = 0.53

b. Dengan Kompensais
Cos ∅ 1 Tanpa Kompensasi = arc cos 0.95 = 18.19 °
Tan ∅ 1 Tanpa Kompensasi = Tan 18.19° = 0.32

Q = Pkompensasi x ( ∅ 1−∅ 2 – ) = kVAR


Q = 537.42 kW x ( 0.53 – 0,32 ) = 112.85 kVAR

Sehingga dipilih Capasitor dengan 125 kVAR


Sehingga menggunakan kapasitor bank merk Scheider 125 kVAR

Penentuan Jenis Kapasitor

Qb = √ 3 x V x I x sin ∅

= 1081.87 kVAR

Sn = 1600

Qb 1081,87
¿= = =67 % <15 %
Sn 1600

Pengaman utama kapasitor

1. MCCB
Q 125 kVAR
¿= = =180.42 A
400 √3 400 √ 3
KHA = In x 125 %
= 180.42x 125 % = 225.52 A

Berdasarkan perhitungan pengaman diatas maka dipilih pengaman genset dengan Ip maks =
225.52 A maka pengaman menggunakan MCCB:

Merk : Schneider

Tipe : Compat NSX 100/150/250 A

Isc : 50 kA

In : 250 A
2. Kontaktor

I = 115% x Inom
= 1.15 x 180.42

= 207.48 A EasyPact CVS100-250 N (50 kA) In 250 A

3. Pemangan Short Circuit


I = 115% x IFL
= 1.15 x 180.42
= 207.48 A

2. Capasitor Bank 2 dipasang pada MDP NON PRIORITAS

Sehingga PF total = PFtotal SDP 3 + PF Total SDP 6 + PF total SDP 7


= 20.68∠ 45.95°+ 60.99∠ 29.85°+ 88.99∠ 29.53°
= (38.96 + 22.4i) + (52.90 + 30.36i) + (77.43 + 43.87i)
= 144.7 + 89.08i
= 169.92∠ 31.61°
= cos 31.61
= 0.85
Diketahui
Daya total (SDP 2, SDP 3, dan SDP 4) = 663.37kVA x 0.85 = 564
Pf total tanpa kompensasi = 0.85
Pf Kompensasi = 0.95

Sehingga,
Daya Total Kompensasi = (daya SDP 3 + daya SDP 6 + daya SDP 7) x 0.5 (Simen)
= ( 12.95 + 342.05 + 561.63 )kVA x 0.5 (Simens)
= 563 x 0.5
= 381.91 kW

Daya Kompensasi < Daya Beban

Perhitungan
c. Tanpa Kompensasi
Cos ∅ 1 Tanpa Kompensasi = arc cos 0.85 = 31.61 °
Tan ∅1 Tanpa Kompensasi = Tan 31.61° = 0.61
d. Dengan Kompensais
Cos ∅ 1 Tanpa Kompensasi = arc cos 0.95 = 18.19 °
Tan ∅ 1 Tanpa Kompensasi = Tan 18.19° = 0.32

Q = Pkompensasi x ( ∅ 1−∅ 2 – ) = kVAR


Q = 381.91 kW x ( 0.61 – 0,32 ) = 110.75 kVAR

Sehingga dipilih Capasitor dengan 125 kVAR

Sehingga menggunakan kapasitor bank merk Scheider 125 kVAR

Qb = √ 3 x V x I x sin ∅

= 389.12 kVAR

Sn = 1600

Qb 389.12
¿= = =24 %< 15 %
Sn 1600

Pengaman utama kapasitor

1. MCCB
Q 125 kVAR
¿= = =180.42 A
400 √3 400 √ 3
KHA = In x 125 %
= 180.42x 125 % = 225.52 A

Berdasarkan perhitungan pengaman diatas maka dipilih pengaman genset dengan Ip maks =
225.52 A maka pengaman menggunakan MCCB:
Merk : Schneider

Tipe : Compat NSX 100/150/250 A

Isc : 50 kA

In : 250 A

2. Kontaktor

I = 115% x Inom
= 1.15 x 180.42

= 207.48 A EasyPact CVS100-250 N (50 kA) In 250 A

3. Pemangan Short Circuit


I = 115% x IFL
= 1.15 x 180.42
= 207.48 A