A OR B OR C

A= 1 & 2 & 3
DEH1-BRA
1 BREAKER NOT
DEH1-
A WSZSSWTCH
DEH1-GOTM 2 ZSS WITCH NOT
1
GO TO MANUAL
DEH1-WSFAIL
SPEED CHANNEL
3 FAILURE
DEH1-REQMAN
B MANUAL
PK2
C KEYBOARD

SET = A & B

A DEH1-OA
1 OPERATOR AUTO
B= 2 OR 3
B 2 DEH1-DCS-SEQ
PK2
3 KEYBOARD
RESET= C OR D OR E OR F OR G OR H
DEH1-BRA
C BREAKER NOT
DEH1-SEQ D DEH1-REQSING
2 SEQUENCIAL SINGLE MODE
VALVE E DEH1-GP001-0
OPERATION
DEH1-TNL
F TURBINE NOT
LATCH
DEH1-DCS-SING
G SINLE VALVE
OPERATION
H= 1 & 2

DEH1-OA
H OPERATOR AUTO
1
PK2
2 KEYBOARD

SET = A & B

DEH1-OA
A OPERATOR AUTO
1
B= 2 OR 3
2 DEH1-DCS-SEQ
B
PK2
3 KEYBOARD
RESET= C OR D OR E OR F OR G OR H
DEH1-BRA
C BREAKER
DEH1-SING NOT
3 SINLE VALVE D DEH1-REQSING NOT
OPERATION E DEH1-GP001-0
DEH1-TNL
F TURBINE NOT
LATCH
G DEH1-DCS-SING
H= 1 & 2

DEH1-OA
H OPERATOR AUTO
1
PK2
2 KEYBOARD
SET = A OR B
A = A1 & A2 & A3
A1 = 1 & 2
DEH1-OPCO
1 OPC ACTIVATED
A1
A DEH1-X80Q
2 SUMMATION OF FREQ DEMAND HISP: 35

DEH1-TNL
A2 TURBINE NOT LATCH NOT

A3 DEH1-BRA NOT
BREAKER
B = B1 & B2
B1 = (3 & 4 & 5) OR 6
DEH1-IVOPEN
3 INTERCEPTOR VALVES OPEN
DEH1-X80G
4 FREQ DEMAND HISP: 35
B1
DEH1-BRA
5 BREAKER
B
DEH1-TNL
6
TURBINE NOT LATCH
DEH1-BPON B2 = 7 & 8
1 BYPASS MODE ON DEH1-BPONPER
7
B2 BYPASS ON PERMISSIVE
PK1
8 KEYBOARD
RESET = C OR D
DEH1-TNL
C TURBINE NOT LATCH ONE PULSE
D= D1 & D2 & D3 & D4
D1 = 9 OR (10 & 11 & 12)
DEH1-TNL
9
TURBINE NOT LATCH
10 DEH1-80G
D1
DEH1-IVOPEN
11
INTERCEPTOR VALVES OPEN
D DEH1-BRA
12 BREAKER
DEH1-HPVLVCLS
D2 HP BYPASS VALVE CLOSE

D3 DEH1-LPVLVCLS
LP BYPASS VALVE CLOSE
PK2
D4 KEYBOARD
SET = A OR B
A = A1 & A2 & A3
A1 = 1 & 2
DEH1-OPCO
1 OPC ACTIVATED
A1
A DEH1-X80Q
2 SUMMATION OF FREQ DEMAND HISP: 35

DEH1-TNL
A2 NOT
TURBINE NOT LATCH
DEH1-BRA
A3 BREAKER NOT
B = B1 & B2
B1 = (3 & 4 & 5) OR 6

DEH1-IVOPEN
3 INTERCEPTOR VALVES OPEN

B1 DEH1-X80G
4 FREQ DEMAND HISP: 35

DEH1-BRA
5 BREAKER
B
DEH1-TNL
6
TURBINE NOT LATCH
B2 = 7 & 8

DEH1-BPOFF DEH1-BPONPER
2 7 BYPASS ON PERMISSIVE NOT
BYPASS MODE OFF B2

8 PK1
KEYBOARD
RESET = C OR D
DEH1-TNL
C TURBINE NOT LATCH ONE PULSE
D= D1 & D2 & D3 & D4
D1 = 9 OR (10 & 11 & 12)
DEH1-TNL
9
TURBINE NOT LATCH
10 DEH1-80G
D1
DEH1-IVOPEN
11 INTERCEPTOR VALVES OPEN

D 12 DEH1-BRA
BREAKER

DEH1-HPVLVCLS
D2
HP BYPASS VALVE CLOSE

D3 DEH1-LPVLVCLS
LP BYPASS VALVE CLOSE

D4 PK2
KEYBOARD

DEH1-BPIOFF = A & B

DEH1-BPIOFF DEH1-TNL
3 A TURBINE NOT LATCH NOT
BYPASS INTERFACE OFF
DEH1-BPOFF
B BYPASS MODE OFF
FOR SET = A
DEH1-OA
A OPERATOR AUTO
FOR RESET = B OR C
B=1&2
4 DEH1-IVINAUTO DEH1-BRA
1 BREAKER NOT
B
DEH1-WSFAIL
2
SPEED CHANNEL FAILURE
DEH1-OA
C OPERATOR AUTO NOT

FOR SET = A
DEH1-OA
A OPERATOR AUTO
RESET = B OR C
B=1&2
5 DEH1-IVINMAN DEH1-BRA NOT
1 BREAKER NOT
B
DEH1-WSFAIL
2 SPEED CHANNEL FAILURE
DEH1-OA
C OPERTOR AUTO NOT

SET = A & B & C


DEH1-BPON
A BYPASS MODE ON
HISP: +10
B DEH1-X81M NOT
6 DEH1-IVHLDC HILP: -10
C DEH1-IVINAUTO
RESET = D & E
D DEH1-X81N HILP: -30
E DEH1-TCPERMN

SET = A & B & C


DEH1-BRA
A
BREAKER
DEH1-BPON
B BYPASS MODE ON NOT
7 DEH1-IVTRK
DEH1-IVHLDC
C IV HOLD CONDITION NOT
RESET = D & E
D DEH1-81N
E DEH1-TCPERMN

A OR B
A DEH1-IVTRK
8 DEH1-IVHOLD
DEH1-IVHLDC
B IV HOLD CONDITION
A&B
A = 1 OR 2 OR 3
1 DEH1-TCPERMN
A DEH1-OPCO
DEH1-IVCLS 2 OPC ACTIVATED
9 IV CLOSE
3 DEH1-CIV
DEH1-DEHGPO15
B NOTE: DEH1-DEHGP015-8 FOR IV1
AND DEH1-DEHGP015-9 FOR IV2

A&B
DEH1-OPENIV DEH1-BPON
10 A BYPASS MODE ON NOT
IV OPEN
B DEH1-DEHGP014-11

A&B&C
A DEH1-IVHOLD
DEH1-BRA
B NOT
BREAKER
C= C1 OR C2
C1 = 1 & 2 & 3
DEH1-TIVSPD 1 DEH1-X28T
11 IV SPEED C1 DEH1-BPLDAN
2 (ONE SHOT) NOT
C
3 DEH1-TV100
C2 = (4 & 5) & 6
4 DEH1-X210
C2
5 DEH1-X21Q
6 DEH1-TV100 NOT

SET = A
DEH1-TIVSPD
A
IV SPEED
RESET = B & (C OR D)
12 DEH1-GVHOLD
B DEH1-BPLDA NOT
DEH1-GC
C GOVERNR VALVE CONTROL
D DEH1-X78M
SL TURBINE BYPASS ON MODE SL
No ROLLING (IP ROLLING) No
Turbine on TURNING GEAR
1 Keep HP bypass and LP bypass control valve opening > 1
10%
2 Keep MS pressure >60bar and HRH pressure < 3 Bar 2

3 All MAL drains are opened 3


4 Open HP exhaust dump valve, 4
Select DEH “OPERATOR AUTO” mode &
Select “BYPASS ON” mode
5 Press turbine trip push button and reset the turbine by 5
holding the lever on reset position untill interface
diaphargm valve closes fully
6 Release turbine trip push button and LATCH the 6
turbine and immediately give close command to CRH
NRV to hold it in closed position. Note down AST,ASP
and OPC pressure
7 RSV-1 and RSV-2 are full open 7
8 GV-1,2,3&4 are full open 8
9 IV-1&2 and TV-1&2 remain close 9
10 Give speed set point to 600 rpm with a ramp of 10
150rpm/min(Below 600 rpm only IV will control
turbine speed and TV will remain close)
11 At 600 rpm check auto change over of IV to IV-TV with 11
02 min. timer (After 600 rpm both IV and TV will
control turbine speed)
&
Observe TSI parameters and charge exciter air cooler,
gas coolers and oil coolers (If required)

12 Give set point of 2900 rpm with a ramp of 250 12


rpm/min
13 Observe HP exhaust pressure and temp. when turbine 13
speed is 2636 rpm
14 At 2900 rpm check auto change over of IV-TV to TV 14
with a timer of 04 min (After 2900 rpm turbine speed
will be controlled by TV only and IV will modulate in
response to a change in HRH pressure)

15 After IV-TV to TV transfer accelerate the turbine to 15


2950 rpm with a ramp of 50 rpm/min
16 Observe lube oil temp,seal oil temp,gas temp and 16
exciter air temp.

17 At 2950 rpm TV to GV transfer to be done manually 17


(During this transfer process GVs will close fully and TV
will take control when turbine speed goes below 2920
rpm )
18 Give set point of 3000 rpm with a ramp of 50 rpm/min 18
19 After getting 3000 rpm switch ON excitation, generator 19
terminal voltage will rise to 20 KV
20 Gradually reduce GV valve limiter to 30% 20
21 Select “AUTO SYNC IN” from DEH screen and then 21
select SYNC and switch ON "ASS" and push “START
SYNC” (During synchronization keep HP exhaust press.
as low as possible)
22 After synchronization open CRH NRV and close HP 22
exhaust dump valve and increase GV valve limiter to
100%
23 Raise load set point to 120 MW with a ramp of 23
30MW/min
24 Close HP-LP bypass slowly and raise the load 24
25 Once HP-LP bypass fully closed & IV fully opened, 25
switch OFF bypass ON mode and select MW loop in
service
TURBINE BYPASS OFF MODE
ROLLING (HP ROLLING)
Turbine on TURNING GEAR
Close HP and LP bypass fully

Main steam pressure > 45 bar and HRH pressure < 1.0
bar
All MAL drains are opened
Select DEH “OPERATOR AUTO” mode and ensure that
BYPASS MODE is OFF

Press turbine trip buttons and Reset the turbine by


holding the lever on reset position untill interface
diaphargm valve closes fully
Release turbine trip push button and LATCH the
turbine, check the auto opening of CRH NRV and note
down AST,OPC and ASP pressure

RSV-1& RSV-2 and IV-1& IV-2 are full open


GV-1,2,3&4 are full open
TV-1& TV-2 remain close
Give speed set point to 600 rpm with a ramp of
150rpm/min

Observe TSI parameters at 600 rpm

Give set point of 2040 rpm with a ramp of 250


rpm/min
Observe HP exhaust temp and LP exhaust hood temp
and eccentricity.
At 2040 check turbine casing top-bottom DT, steam
chest deep and shallow temp., casing expansion and
differential expansion and allow the turbine to warm
up for recommended parametrs and charge Exciter air
cooler, gas cooler and oil coolers to maintain temp.

After getting recommended parameters accelerate the


turbine for 2950 rpm with the ramp of 250 rpm/min
At 2950 rpm TV to GV transfer to be done manually
(During this transfer process GVs will close fully and TV
will take control when turbine speed goes below 2920
rpm )
Observe lube oil temp and seal oil temp.

Give set point of 3000 rpm with a ramp of 50 rpm/min


After getting 3000 rpm switch ON excitation and
monitor generator terminal voltage (20 KV)
Gradually reduce GV valve limiter to 30%
Select “AUTO SYNC IN” from DEH screen and push
"SYNC" and put ASS ON and then push “START SYNC”

After synchronization take MW loop in service and


increase GV valve limiter to 100%

Raise load set point to 25 MW with the ramp of


5MW/min
A OR B OR C
DEH1-GC
A GOVERNOR VALVE CONTROL
1 DEH1-IVTVXFER
B DEH1-HOLD7REF
C DEH1-TC

A&B&C
DEH1-IVTVXFER
A IV-TV TRANSFER NOT
2 DEH1-IVXTVCLS
DEH1-BPON
B BYPASS MODE ON
C DEH1-IVINAUTO

A&B&C
DEH1-IVTVXFER
A IV-TV TRANSFER NOT
3 DEH1-IVXTV NOT
DEH1-BPON
B BYPASS MODE ON
C DEH1-IVINAUTO

A&B
DEH1-BRA
A
4 DEH1-IVLDPRTC BREAKER
DEH1-GC
B GOVERNOR VALVE CONTROL

A&B&C
A DEH1-TC
5 DEH1-P15M33 B DEH1-HOLD7REF
DEH1-BPON
C
BYPASS MODE ON
A&B&C&D
DEH1-BPON
A BYPASS MODE ON
6 DEH1-P15M30 DEH1-IVTVXFER
B IV-TV TRANSFER
C DEH1-X81N NOT
D DEH2-SOAKDUN

(A & B) OR C
A= A1 OR A2
DEH1-HPVLVCLS
A1 HPBP VALVE CLOSE
A
DEH1-LPVLVCLS
A2 LPBP VAVE CLOSE
7 DEH1-BPTRIP
B =B1 & B2
B1 DEH1-X80K
B
DEH1-BRA 60 S TDON
B2 BREAKER
DEH1-HEXHTT1
C EXHAUST TEMP

A OR B
A HPEXTRTBP
8 DEH1-HPEXTRTBP PK1
SET KEYBOARD
B
RESET DVALGEN

A&B
A1= 1 OR 2
DEH1-HPVLVCLS
1
HPBP VALVE CLOSE
A1
DEH1-LPRT DEH1-LPVLVCLS
2
9 HP EXHAUST PRESSURE A LPBP VAVE CLOSE
RATIO LO TRIP A2 =3 & 4
3 DEH1-X80K
A2 DEH1-BRA 60 S TDON
4 BREAKER
B HPEXTRTBPON NOT

FOR SET = A & B


DEH1-BPON
A BYPASS MODE ON
B DEH1-X81N
FOR RESET =C OR D OR E
DEH1-BPON
C BYPASS MODE ON NOT
10 DEH1-IC
DEH1-IVTVXFER
D IV-TV TRANSFER
E=1&2
DEH1-OA
E 1 OPERATOR AUTO NOT
2 DEH1-TVCLOSED NOT
FOR SET = A OR B
A= 1 OR 2
DEH1-DCS-AS
1
A AUTO SYNC IN DCS
PK1
2
KEYBOARD
B=3&4
B 3 DEH2-ATC
AUTO TURBINE CONTROL
4 DEH2-ATCASPB
DEH1-AS FOR RESET = C OR D OR E OR F
1
AUTO SYNC CONTROL PK2
C
KEYBOARD
D = 5 OR 6
DEH1-ASPERM
5 NOT
D AUTO SPEED PERMISSIVE
DEH1-OA
6
OPERATOR AUTO
DEH1-BRA
E
BREAKER
DEH1-TNL
F
TURBINE NOT LATCH

A&B
2 DEH1-ASTRK
REMOTE TRACK DEH1-AS
A
AUTO SYNC IN DCS
B DEH1-DEMDTRK NOT

A&B
3 REMOTE STOP FAIL A DEH1-REMSTPB1
B DEH1-REMSTPB2
SET = A OR B
PK1
A KEYBOARD
DEH1-DCS-ADS
B
REMOTE IN DCS
RESET = C OR D OR E OR F OR G
C= 1 OR 2 OR 3
DEH1-BRA
1 BREAKER NOT
DEH1-ADS C
4
AUTO DISPATCH SYSTEM 2 DEH1-LOADSHED
3 DEH1-OA NOT
OPERATOR AUTO

D PK2
KEYBOARD
E DEH1-RUNBACKA
DEH1-ADSPERM
F AUTO DISPATCH SYSTEM PERMISIVE NOT
G REMOTE STOP FAIL

A OR B
A DEH1-AS
5 DEH1-REMOTE AUTO SYNC CONTROL
DEH1-ADS
B AUTO DISPATCH SYSTEM

A&B&C
A DEH1-GC NOT
GOVERNOR VALVE CONTROL

B DEH1-IC NOT
DEH1-TC INTERCEPTOR VALVE CONTROL
6
TV CONTROL C = 1 OR 2
DEH1-BPON
1 BYPASS MODE ON NOT
C
DEH1-TNL
2 NOT
TURBINE NOT LATCH
A OR B
A = 1 & 2 & 3 &4
PK1
1
KEYBOARD
DEH1-LPVLVCL
2
A LP BYPASS VALVE CLOSED

3 DEH1-HPVLVCL
DEH1-LATCH HP BYPASS VALVE CLOSED
1
TURBINE LATCH
DEH1-BPON
4 NOT
BYPASS MODE ON
B=1&2
PK1
1
B KEYBOARD

2 DEH1-BPON
BYPASS MODE ON

A OR B OR C
1&2
A 1 DEH1-ASL11
2 DEH1-ASL31
DEH1-TNL B=3&4
2 TURBINE NOT LATCH NOT
B 3 DEH1-ASL31
4 DEH1-ASL21
C=5&6
C 5 DEH1-ASL11
6 DEH1-ASL21

A OR B OR C
1&2
A 1 DEH1-ASL11
2 DEH1-ASL31
B=3&4
3 DEH1-TVCL NOT
B 3 DEH1-ASL31
4 DEH1-ASL21
C=5&6
C 5 DEH1-ASL11
6 DEH1-ASL21

A OR B OR C
A DEH1-TNL
4 DEH1-GVCL DEH1-OPCO
B
OPC ACTIVATE
C DEH1-GVHOLD

A OR B OR C
1&2
DEH1-ASL11
A 1
2 DEH1-ASL31
5 DEH1-ASL B=3&4
AUTO STOP LATCH B 3 DEH1-ASL31
4 DEH1-ASL21
C=5&6
C 5 DEH1-ASL11
6 DEH1-ASL21

A&B&C
A DEH1-IVAUTO
6 DEH1-OA
B DEH1-TVAUTO
C DEH1-GVAUTO
A OR B
A= 1 & 2
DEH1-OA
A 1 NOT
OPERATOR AUTO
2 DEH1-X70K
B = B1 & B2
B1 DEH1-OA
OPERATOR AUTO
SET = B2 = V & W & X & Y
V= 3 & 4
3 DEH1-X28S
W
4 DEH1-OA
OPERATOR AUTO
X DEH1-GO NOT
Y = 5 OR (6 & 7 & 8 & Y1) OR Y1
PK2
5 KEYBOARD
7 DEH1-TVXCVCLS 6 DEH1-P15M14
7 ATCSPDHOLD-OUT NOT
8 DEH2-ATC
B
Y X1 = 9 & 10
B2
9 DEH2-ATC
Y1
TIME DELAY 120S
DEH1-WS
10 SPEED O/P TO DCS
(HI MONITORING: 2945)

Z DEH1-BRA
BREAKER
RESET = B2 = (11 & 12) OR 13
DEH1-TNL
11
TURBINE NOT LATCH
DEH1-BRA
12 BREAKER NOT

13 ATCSPDHOLD-OUT

SET = A OR B
A= 1 & 2
A 1 DEH1-OA NOT
OPERATOR AUTO
2 DEH1-X70K
B = B1 & B2
SET = V & W & X & Y
V= 3 & 4
3 DEH1-X28S
W
DEH1-OA
4
OPERATOR AUTO
X DEH1-GO NOT
Y = 5 OR (6 & 7 & 8 & Y1) OR Y1
5 PK2
KEYBOARD
6 DEH1-P15M14
8A DEH1-TV100
7 ATCSPDHOLD-OUT NOT
Y 8 DEH2-ATC
B B1 X1 = 9 & 10
9 DEH2-ATC
Y1 DEH1-WS TIME DELAY 120S
10 SPEED O/P TO DCS
(HI MONITORING: 2945)

Z DEH1-BRA
BREAKER
RESET = (11 & 12) OR 13
DEH1-TNL
11
TURBINE NOT LATCH
DEH1-BRA
12 BREAKER NOT
13 ATCSPDHOLD-OUT
B2 DEH1-X160
RESET = 14 & 15 = C
14 DEH1-TNL
8B DEH1-TV100 TURBINE NOT LATCH
C
DEH1-BRA
15 BREAKER NOT

A&B
DEH1-TRTVGV A DEH1-TVXCVCLS
9
TVGV TRANSFER
B DEH1-TV100 NOT

A OR B
DEH1-GC A DEH1-TRTVGV
10 GV CONTROL TVGV TRANFER
B DEH1-TV100
A&B
DEH1-MWI1
A PULSE
1 DEH1-NIPIMWI MW LOOP IN SERVICE
DEH1-IPI1
B NOT
IMPULSE LOOP IN SERVICE

A&B
DEH1-MWI1
A MW LOOP IN SERVICE
2 DEH1-IPIMWI PULSE
DEH1-IPI1
B IMPULSE LOOP IN SERVICE

A&B
DEH1-MWI1
A MW LOOP IN SERVICE NOT PULSE
3 DEH1-MWINIPI
DEH1-IPI1
B IMPULSE LOOP IN SERVICE

A OR B
A DEH1-BRA NOT
B = B1 OR B2 OR B3 OR B4
B1 = 1 & 2
DEH1-MWI1
B1 1 MW LOOP IN SERVICE
2 DEH1-BRA NOT
DEH1-IPI1
B2 IMPULSE LOOP IN SERVICE
B3 = (3 & 4) & 5
4 DEH1-HOLDGVS DEH1-MWI1
3 TDOFF
B MW LOOP IN SERVICE
B3 NOT
4 DEH1-BRA NOT
DEH1-IPI1
5 IMPULSE LOOP IN SERVICE
B4 = (6 & 7) & 8
DEH1-MWI1
MW LOOP IN SERVICE NOT
B4
DEH1-BRA NOT
DEH1-IPI1
IMPULSE LOOP IN SERVICE

SET = A OR B
PK1
A
KEYBOARD
B DEH1-LOADSHED
RESET = C OR D OR E OR F OR G
DEH1-SPI PK2
5 C
SPEED LOOP IN SERVICE KEYBOARD
DEH1-WSFAIL
D
SPEED CHANNEL FAILURE
E DEH1-X27U
F DEH1-OA NOT
G DEH1-BRA NOT

SET = A
PK1
A
KEYBOARD
RESET = B OR C
B = B1 OR B2 OR B3 OR B4 OR B5
B1 DEH1-BPON
B2 = 1 OR 2
1 DEH1-TNL
B2
B DEH1-RUNBACKA
2
DEH1-IPI1 RUN
6 IMPULSE LOOP IN SERVICE B3 DEH1-DEHGP013-12
PK2
B4
KEYBOARD
B5 DEH1-REJIMP
C = C1 OR C2 OR C3 OR C4
DEH1-PIFAIL
C1
IMPULSE PRESSURE TRANSDUCER FAIL
C
C2 DEH1-X27U
C3 DEH1-OA NOT
C4 DEH1-BRA NOT
SET = A
PK1
A
KEYBOARD
RESET = B OR C
B = B1 OR B2 OR B3 OR B4 OR B5 OR B6
PK2
B1
KEYBOARD
B2 DEH1-DCS-MWLOOP
MW LOOP OUT SER DCS
B3 DEH1-REJMW
B
DEH1-MWI1 DEH1-MWFAIL
7 B4 MW TRANSDUCER FAILED
MW LOOP IN SERVICE
B5 DEH1-DEHGP013-12
B6 = 1 OR 2
B6 1 DEH1-TNL
2 DEH1-RUNBACKA
C = C1 OR C2 OR C3 OR C4 OR C5
C1 DEH1-X27U
C2 DEH1-OA NOT
C
C3 DEH1-BRA NOT
C4 DEH1-BPON
C5 DEH1-LOADSHED

A OR B OR C OR D OR E OR F OR A4

A = A1 OR A2 OR A3 OR A4
A1 = 1 & 2
DEH1-MWI1
A1 1
MW LOOP IN SERVICE
2 DEH1-BRA NOT
DEH1-IPI1
A2
IMPULSE LOOP IN SERVICE
A3 = (3 & 4) & 5
DEH1-MWI1
3
A MW LOOP IN SERVICE
A3 NOT
4 DEH1-BRA NOT
DEH1-DEMDTRK
8 DEH1-IPI1
TRACK TARGET 5
IMPULSE LOOP IN SERVICE
(6 & 7) & 8
DEH1-MWI1
6 MW LOOP IN SERVICE NOT
A4
7 DEH1-BRA NOT
DEH1-IPI1
8 IMPULSE LOOP IN SERVICE NOT
B DEH1-BRA NOT
C DEH1-OA NOT
D DEH1-TCPERMN
E DEH1-DEHGP013-12
DEH1-BRCL
F
BREAKER CLOSED PULSE

A&B&C
DEH1-ATC
A AUTO TURBINE CONTROL NOT
9 DEH1-DEHGP013-15
DEH-ATCSPDS
B IN ATC SPEED CONTROL NOT
C DEH2-INRNG NOT
SET = A OR B OR C

A=1&2
DEH1-GO
1A
SELECT RATE A
PK1
1 KEYBOARD
2 DEH1-TRTVGV NOT
B DEH1-REMOTE
C DEH1-ATC
RESET = D OR E
D DEH1-ATCHOLD
E = E1 OR E2 OR E3 OR E4 OR E5 OR E6 OR E7 OR E8
E1 PK2
KEYBOARD
E2 DEH1-DEHGP013-15
E3 DEH1-RUNBACKA
E4 = (3 & 4) & 5
3 DEH1-X08S
E4
4 DEH1-TV100 NOT
5 DEH1-X03X
E5 = (6 & 7 & 8) & 9
6 DEH1-X09O
7 DEH1-BRA
DEH1-GO E5
1B SELECT RATE DEH1-HLLI
8
E HI LOAD LIMITTER IN IN
9 DEH1-X03X
E6 = 10 OR 11
E6 10 DEH1-X03X NOT
11 DEH1-XO3N
E7 = 12 &(13 & 14 & 15)
12 DEH1-X03N
13 DEH1-X09Q
E7
14 DEH1-BRA
15 DEH1-LLLI
LO LOAD LIMITTER IN IN
E8 = 16 & 17
E8 16 DEH1-X03X
17 DEH1-X27U

SET = A & B
PK1
A
KEYBOARD
B DEH1-X10K NOT HIMON = 0.001
RESET = C OR D OR E OR F
DEH1-HLLI
2 PK2
HI LOAD LIMITER IN C
KEYBOARD

D DEH1-ADS
AUTO DISPATCH SYSTEM
E DEH1-BRA NOT
F DEH1-OA NOT

SET = A & B
PK1
A KEYBOARD
B DEH1-X10M NOT LOMON = -0.001
RESET = C OR D OR E OR F
3 DEH1-LLLI
LO LOAD LIMITER IN PK2
C
KEYBOARD
DEH1-ADS
D
AUTO DISPATCH SYSTEM
E DEH1-BRA NOT
F DEH1-OA NOT
A&B
4 DEH1-GOGCA A DEH1-X80S
B DEH1-TV100 NOT

A&B&C
A DEH1-X09O
DEH1-HLL1
5 B DEH1-BRA
HI LOAD LIMITER LIMITING 1
DEH1-HLLI
C
HI LOAD LIMITER IN

A&B&C
A DEH1-X09Q
6 DEH1-LLL1
LO LOAD LIMITER LIMITING 1 B DEH1-BRA
DEH1-LLLI
C LO LOAD LIMITER IN

A&B
DEH1-ADSUPL
7 AUTO DISPATCH SYSTEM UPPER A DEH1-X03X
LIMIT
B DEH1-ADS

A&B
DEH1-ADSDNL
8 AUTO DISPATCH SYSTEM DOWN A DEH1-X03N
LIMIT
B DEH1-ADS
A&B
A = A1 & A2 & A3 & A4 & A5 & A6
A1 DEH1-BPOFF
A2 DEH1-BRA NOT
A3 = X1 & X2
DEH1-TV1POS HIMON= 2
X1 TV1 POSITION LOMON= -2
A3 TDON = 5 SEC
X2 DEH1-TV2POS HIMON= 2
TV2 POSITION LOMON= -2
1 DEH1-TVCOMMANDHOLD A
A4 DEH1-REFDMD HIMON= 2050
SET = Y
PK1
Y
A5 KEYBOARD
NOT
RESET = Z
Z DEVAL GEN
A6 DEH1-TV100 NOT
DEH1-WS
B HIMON= 2050
SPEED OUTPUT TO DCS

A&B
DEH1-WS
2 DEH1-TVCOMMAND5 A HIMON= 2950
SPEED OUTPUT TO DCS
B DEH1-TVCOMMANDHOLD

A OR B
A = A1 OR A2
A1-SET = X OR Y
X = X1 & X2
X1-SET = (1 & 2) & 3
1 DEH1-DEHGP001-0 NOT
2 DEH1-SING
PK1
3
KEYBOARD
X1-RESET = 4 OR 5 OR 6 OR 7
X1 DEH1-BPON
4
X BYPASS MODE ON
ONE PULSE
DEH1-OA
5 OPERATOR AUTO NOT

PK2
6
KEYBOARD
7 DEH1-BRA NOT
X2 = 8 & 9
X2 8 DEH1-X38O
9 DEH1-X46O
Y = Y1 & Y2
X = X1 & X2
A1 X1-SET = (1 & 2) & 3
A 1 DEH1-DEHGP001-0 NOT
2 DEH1-SING
3 DEH1-TVCLOSE PK1
3 KEYBOARD
X1-RESET = 4 OR 5 OR 6 OR 7
X1 DEH1-BPON
4
Y1 X BYPASS MODE ON
Y DEH1-OA
5 NOT
OPERATOR AUTO
PK2
6 KEYBOARD
7 DEH1-BRA NOT
X2 = & 9
X2 8 DEH1-X38O
9 DEH1-X46O
Y2 = 10
Y2 PK3
10
KEYBOARD
A1- RESET = Z
Z DEH1-X21Q
A2 = 11
A2 DEH1-TNL
TURBINE NOT LATCH
B = B1 & B2 & B3 & B4
DEH1-OA
B1 OPERATOR AUTO
B
B2 DEH1-BRA NOT
B3 DEH1-X08T
B4 DEH1-TV100 NOT
X&Y&Z
X-SET = (1 & 2) & 3 = X1
1 DEH1-DEHGP001-0 NOT
2 DEH1-SING
X1
PK1
3 KEYBOARD
X-RESET = 4 OR 5 OR 6 OR 7 = X2
X DEH1-BPON
4 DEH1-TV1TEST 4
BYPASS MODE ON
DEH1-OA
5 OPERATOR AUTO NOT
X2
6 PK2
KEYBOARD
7 DEH1-BRA NOT
Y DEH1-GV1THOLD NOT
Z DEH1-GV3THOLD NOT
NOTE:
FOR DEH1-TV2TEST: Y= DEH1-GV2THOLD & Z = DEH1-TGV4THOLD & X ARE BEING SAME

SET = X
X-SET = (1 & 2) & 3 = X1
1 DEH1-DEHGP001-0 NOT
2 DEH1-SING
X1
3 PK1
KEYBOARD
X-RESET = 4 OR 5 OR 6 OR 7 = X2
X DEH1-BPON
4
BYPASS MODE ON
5 DEH1-DEHGP009-4
DEH1-OA
5 OPERATOR AUTO NOT
X2
PK2
6
KEYBOARD
7 DEH1-BRA NOT
RESET = Y = Y1 & Y2 & Y3
Y1 DEH1-X34U
Y Y2 DEH1-X42U
Y3 DEH1-DEHGP001-0
A = A1 OR A2 OR A3 OR A4 OR A5 OR A6
A1 DEH1-GV1TEST
A2 DEH1-GV2TEST
1 DEH1-DEHGP001-0 A3 DEH1-GV3TEST
A
A4 DEH1-GV4TEST
A5 DEH1-DEHGP015-8
A6 DEH1-DEHGP015-9

A&B
2 DEH1-GV1TOPN A DEH1-GV1TEST
B DEH1-GV1TCLS NOT

A&B
A SET = A1 & A2 & A3
A1 DEH1-DEHGP001-0 NOT
PK1
A2
KEYBOARD
A3 DEH1-SING
A RESET = A4 OR A5 OR A6 OR A7 OR A8
DEH1-BRA
A A4 NOT
3 DEH1-GV1TCLS BREAKER HEALTHY
DEH1-BPON
A5
BYPASS MODE ON

A6 PK2
KEYBOARD
A7 DEH1-X34O
DEH1-OA
A8 NOT
OPERATOR AUTO
B DEH1-GV1THLD

SET = A = A1 & A2
A1 DEH1-DEHGP001-0
A2 = 1 OR 2
A
A2 PK1
KEYBOARD
RESET = B = B1 OR B2 OR B3
4 DEH1-GV1THLD DEH1-OA
B B1 NOT
OPERATOR AUTO
PK2
B2
KEYBOARD
B3 = 1 OR 2
1 PK4
B3 KEYBOARD
2 DEH1-PK046RT
A&B&C
A DEH1-ADSUP
B = 1 OR 2
1 DEH1-ADSUPC
REMOTE CONTROL LOAD REF UP B 1 DEH2-HOLDLOAD NOT
2 DEH2-ATC NOT
DEH1-ADS
C AUTO DISPATCH SYSTEM

A&B&C
A DEH1-ADSDN
B = 1 OR 2
2 DEH1-ADSDNC
REMOTE CONTROL LOAD REF DOWN B 1 DEH2-HOLDLOAD NOT
2 DEH2-ATC NOT
DEH1-ADS
C
AUTO DISPATCH SYSTEM
A&B
1 DEH1-TNL600 A DEH1-TCPERMN
B DEH1-X17A NOT

2 DEH1-IV600SEC DEH1-X16D NOT TDON= 120 S

A&B&C
A DEH1-BRA NOT
B DEH1-BPON
BYPASS MODE ON
SET =C1
3 TIMER_120 DEH1-X16D
C1 NOT TDON= 120 S
DEH1-IV600SEC
C RESET = C2
C2 = 1 & 2
C2 1 DEH1-TCPERMN
2 DEH1-X17A NOT

SET = A & B & C


A TIMER1
B DEH1-BRA NOT
C DEH2-ATC
RESET = D OR E OR F OR G OR H
D DEH2-TSICHK120S
E TOFF-130S
4 TIMER-TSI
F DEH1-WS LOSP= 590
SPEED OUTPUT TO DCS
G DEH2-ATC
H= H1 OR H2
H1 DEH1-BRA
H
H2 DEH1-TNL
TURBINE NOT LATCH

SET = A & B
A DEH1-240S
B DEH1-BPON
BYPASS MODE ON
5 TIMER_240
RESET = C OR D
C DEH1-BRA
DEH1-TNL
D
TURBINE NOT LATCH

SET = A
A DEH1-X16D NOT TDON= 120 S
6 DEH1-HOLD7REF RESET = B & C
B DEH1-TCPERMN
C DEH1-X17A NOT
A OR B OR C OR D
A1 & A2
A1 DEH1-OST NOT
A2 = 1 OR 2
A
1 DEH1-X16C HISP=3090
A2
MEDIAN SELECTION
2 HISP=3090
OF SPEED CHANNEL
B = B1 & B2
B B1 DEH1-OPCT
B2 DEH1-BRA NOT
C SET = PULSE OF (C1 & C2)
C1 DEH1-BRA NOT
C2 = W OR X
DEH1-OPXFAIL
DEH1-OPCO W IP EXHAUST PRESS
OPC ACTIVATED C2 TRANSDUCER FAIL
OR X = 3 OR 4
DEH1-OPCO1 X 3 DEH1-X67A
1
OPC SOLENOID1
OR 4 DEH1-XX09J
DEH1-OPCO2 C C RESET = C3 OR C4 OR C5
OPC SOLENOID 2 C3 = Y & Z
Y = 5 OR 6
5 DEH1-X16C HISP = 3090
C3 Y NOT
6 MEDIAN SELECTION HISP=3090
OF SPEED CHANNEL
Z DEH1-BRA NOT
DEH1-TNL
C4
TURBINE NOT LATCH
C5 DEH1-BRA
D SET = D1 & D2
D1 DEH1-LOADSHED
D2 DEH1-BRA
D
D RESET = (D1 & D2)TDON
D1 DEH1-LOADSHED
TDON
D2 DEH1-BRA

A SET = PULSE OF (A1 & A2)


A1 DEH1-BRA NOT
A2 = W OR X
DEH1-OPXFAIL
W IP EXHAUST PRESS
A2 TRANSDUCER FAIL
X = 1 OR 2
X 1 DEH1-X67A
2 DEH1-XX09J
2 DEH1-LDA A A RESET = A3 OR A4 OR A5
A3 = Y & Z
Y = 3 OR 4
3 DEH1-X16C HISP = 3090
A3 Y NOT
MEDIAN SELECTION
4 HISP=3090
OF SPEED CHANNEL
Z DEH1-BRA NOT
DEH1-TNL
A4
TURBINE NOT LATCH
A5 DEH1-BRA
A OR B
A = A1 & A2 & A3 & A4 & A5 & A6
DEH1-X31O
A1
GV CONTROL
DEH1-X39O
A2
GV CONTROL
DEH1-X43O
A3
A GV CONTROL
DEH1-X47O
A4
GV CONTROL
3 DEH1-LOPTVLV
A5 DEH1-X51O
DEH1-SEQ
A6 SEQUENCE VALVE
OPERATION
B = B1 & B2
DEH1-SING
B1 SINGLE VALVE
B OPERATION
DEH1-X30W
B2
GV CONTROL

DEH1-OSPD
4 110 PCT WHEN DEH1-X16 IS INCREASED FROM 3300
OVERSPEED

A&B
A PK1
5 DEH1-SETUP KEYBOARD

B DEH1-ASL
AUTO STOP LATCH

A&B
A PK2
6 DEH1-SETDOWN KEYBOARD

B DEH1-ASL
AUTO STOP LATCH