PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.1 Tangga – Siguragura Line (CH2) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.2 Tangga – Siguragura Line (CH1) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit Bus-Tie A bus side (CH3) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit Bus-Tie B bus side (CH4) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.2 Tangga – Kuala Tanjung Line (CH5) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.1 Tangga – Kuala Tanjung Line (CH6) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.4 Generator (CH7) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.2 Generator (CH9) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.1Generator (CH10) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.3Generator (CH8) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Operating current test

Test Item DS Position


Phase Signal No.
A B Criteria I pick Up Mode Zone
Check Zone R (A)
pick up S 0,975A ±5%
current
(DIFCH) T

III. Operating time test


Test Item Phase Signal No. Criteria Input (A) Time pick up Remark
DIFCH-A
op.time R 541 1 cycle±5% 3 x Ipu 1 cycle = 20 ms

Note :

Approved Checked Prepared


Name Jhony BS Sunarno AR
Position
Sign/Date
No. Dokumen / Revisi
PT INDONESIA ASAHAN ALUMINIUM (Persero)

LOW IMPEDANCE BUSBAR PROTECTION INSPECTION RECORD

Relay Type GRB100-……. Inspection Date


Location TNP CT Ratio 2000/1A
275 kV
Bay Unit No.3Generator (CH8) VT Ratio / 110 V
√3
I. Setting √3

Item Range Setting


Check Zone pick up current (DIFCH) 500 – 3000A 1950A
Discriminating Zone pick up current (DIFZ) 500 – 3000A 1950A
SLOP check zone protection 0,30 – 0,90 0,30
Under Voltage Element phase - phase
60 – 100V 77V
(UVSF)
Under Voltage Element phase – ground (UVGF) 20 – 60V 45V
Over Voltage Element phase – ground
0,1 – 10V 10V
(OVGF)
Erroneous differential current
20 – 3000A 470A
monitoring (DIFSV)
II. Percentage Restraining Characteristic test

Phase
Mode Zone
A
B
C
Note :