Professional Documents
Culture Documents
(SVL) Series
Often, conductive structures like pipelines, data lines and physical
entities such as fencing and barriers, run parallel to Overhead or
Underground power transmission lines. In these situations, dangerous
and damaging voltages can be induced as a function of normal
operating or fault currents.
Characteristics: SVL4/RA/ALC
Max. Continuous Operating Voltage 310v rms
Min Voltage @ 10mA DC 510v min
Max. Rated Voltage (2s/50Hz) 400v rms
Max. Residual Voltage @ 10kA (8/20μs duration) <1.2kV
2 part black epoxy,
Encapsulation
except on mounting feet
Weight 0.45kg nominal
Part Codes: SVL4, SVL4/RA, SVL4/ALC
Diagram of SVL08
Characteristics: SVL8/RA/ALC
Max. Continuous Operating Voltage 625V rms
Min Voltage @ 10mA DC 1020V min
Max. Rated Voltage (2s/50Hz) 800v rms
Max. Residual Voltage @ 10kA (8/20μs duration) <2.3kV
2 part black epoxy,
Encapsulation
except on mounting feet
Part Codes: SVL8, SVL8/RA, SVL8/ALC
PD Devices Ltd. Unit 1, Old Station Yard, South Brent, Devon. TQ10 9AL. Revision: PD2, 06/12/12
Characteristics: SVL16/RA/ALC
Max. Continuous Operating Voltage 1250V rms
Min Voltage @ 10mA DC 2040V min
Max. Rated Voltage (2s/50Hz) 1600v rms
Max. Residual Voltage @ 10kA (8/20μs duration) <4.5kV
2 part black epoxy,
Encapsulation
except on mounting feet
Weight 0.98kg nominal
Part Codes: SVL16, SVL16/RA, SVL16/ALC
Diagram of SVL28
Characteristics: SVL28/RA/ALC
Max. Maximum Continuous Operating Voltage 2240V rms
Min Voltage @ 10mA DC 3650V min
Max. Rated Voltage (2s/50Hz) 2800v rms
Max. Residual Voltage at 10kA (8/20μs duration) <8.5kV
2 part black epoxy,
Encapsulation
except on mounting feet
Weight 1.4kg nominal
Part Codes: SVL28, SVL28/RA, SVL28/ALC
Diagram of SVL30/RA
Extent of Protective Coating
Characteristics: SVL30/RA/ALC
Max. Continuous Operating Voltage 2800V rms
Min Voltage at 10mA DC 4600V min
Max. Residual Voltage @ 10kA (8/20μs
90
<10.0kV
duration)
Max. Residual Voltage @ 15kA (8/20μs
<10.6kV
Mounting Slots
14 x 18
duration)
35 60 90
High Current Withstand (4/10μs) 100kA
2 part black epoxy,
Encapsulation
except on mounting feet
Weight 1.61kg nominal
Part Codes: SVL30, SVL30/RA, SVL30/ALC
PD Devices Ltd. Unit 1, Old Station Yard, South Brent, Devon. TQ10 9AL. Revision: PD2, 06/12/12
SVL4
SVL16
SVL32
SVL8 SVL28
SVL40/RA/ALC
Diagram of SVL40/RA
Extent of Protective Coating
Characteristics:
Max. Continuous Operating Voltage 3700V rms
Min Voltage at 10mA DC 6000V min
90
Max. Residual Voltage @ 10kA (8/20μs duration) <13.4kV
Max. Residual Voltage @ 15kA (8/20μs duration) <14.2kV
Mounting Slots
14 x 18
Max. Residual Voltage @ 40kA (8/20μs duration) <16.4kV
100 x 18kA 8/20μs
Repeated Impulse Withstand
75+/-5 with 5 min. interval
110
5 Impulses of 8.0kJ for 2ms
Repeated Energy Withstand
with 60 sec intervals
Leakage Current at Uc <100μA typical
High Current Withstand (4/10μs) 100kA
35 60 90
2 part black epoxy,
Encapsulation
except on mounting feet
Weight 1.61kg nominal
Part Codes: SVL40, SVL40/RA, SVL40/ALC
PD Devices Ltd. Unit 1, Old Station Yard, South Brent, Devon. TQ10 9AL. Revision: PD2, 06/12/12
90
Max. Residual Voltage at 10kA (8/20μs duration) <11.8kV
Max. Residual Voltage at 15kA (8/20μs duration) <12.5kV
Extent of Protective Max. Residual Voltage at 40kA (8/20μs duration) <14.5kV
Coating
197+/-5
Contains 3 Discs
Characteristics: SVL60/RA/ALC
Max. Continuous Operating Voltage 5600V rms
Min Voltage at 10mA DC 9200V min
90
PD Devices Ltd. Unit 1, Old Station Yard, South Brent, Devon. TQ10 9AL. Revision: PD2, 06/12/12
Diagram of SVL30/ALC
SVL30/ALC
75+/- 5
110
All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct
and reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an
assurance of any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements.
Our liability for these products is set forth in our standard terms and conditions of sale.
We, PD Devices Ltd are continually improving our technology within our products we offer and therefore reserve the right to amend any of the specifications at anytime.
PD Devices Ltd. Unit 1, Old Station Yard, South Brent, Devon. TQ10 9AL. Revision: PD2, 06/12/12