Dead tests radial final ............................................................................................................................. 2
Dead tests ring final ................................................................................................................................ 2
Live tests ................................................................................................................................................. 3
1. One way two plate .......................................................................................................................... 3
2. One way three plate loop in method .............................................................................................. 4
3. One way three plate neutral at each point ..................................................................................... 4
4. Two way two plate .......................................................................................................................... 5
5. Two way three plate loop in conversion method ........................................................................... 5
6. Two way three plate neutral at each point..................................................................................... 6
7. Two way three plate loop in conversion with two fittings and one way three plate loop in ......... 6
Dead tests radial final
Test 1 – Continuity, Polarity and R1+R2
• Install a temporary link between the live conductor of the circuit under test and the cpc
• Set test instrument to low ohms
• Continuity - Place test probes on the live and cpc at each point (a low ohm reading is
expected, a high ohm reading is either a fault or switches in the off position)
• Polarity – Place test leads on the switched live and the cpc at the ceiling rose, operate all
switches to confirm only the live conductor is switched.
• R1+R2 – During the polarity test, record the highest reading when the switches are operated
• Remove temporary link
Test 2 - Insulation resistance for both ring and radial final circuits and three phase
RCDs
Functional test
Fault finding
Fault type Test required Instrument used Healthy circuit Faulty circuit
Open circuit Continuity Low resistance ohm Low reading No reading
meter
Short circuit Insulation Insulation resistance >1MΩ 0Ω
resistance tester
High resistance Insulation Insulation resistance >1MΩ >0.01, <1MΩ
resistance tester
Crossed polarity Continuity Low resistance ohm Low reading • No reading
meter • Check other terminals
7. Two way three plate loop in conversion with two fittings and
one way three plate loop in