Type Size Capacity and Protection of Conductors and required ECC-sizes

BYA
450/750V
(Plain Annealed Copper Conductor, Single Core, PVC Insulated, Non-sheathed Cables)

Current Rating at 35o C, Derated value of


No. and
Overall Nominal Cross- Clipped to a surface or Ampacity of
Nominal
Diameter Sectional Area on a cable tray bunched Conductor for ECC-size
Diameter of
of Conductor & unenclosed two cables Selecting CB/Fuse
Wires
single phase Sizes
No./mm mm mm 2
A A mm2
1 / 1.13 2.55 – 3.0 1 x 1.0 re 16 11 4
1 / 1.38 2.80 – 3.3 1 x 1.5 re 20 14 4
7 / 0.50 2.90 – 3.4 1 x 1.5 rm 20 14 4
1 / 1.78 3.40 – 3.9 1 x 2.5 re 28 20 4
7 / 0.67 3.60 – 4.2 1 x 2.5 rm 28 20 4
7 / 0.85 4.15 – 4.8 1 x 4 rm 37 26 4
7 / 1.04 4.72 – 5.4 1 x 6 rm 47 33 6
7 / 1.35 6.05 – 6.8 1 x 10 rm 63 44 10
7 / 1.70 7.10 – 8.0 1 x 16 rm 85 60 16
19 / 1.04 7.20 – 8.1 1 x 16 rm 85 60 16
7 / 2.14 8.85 – 9.8 1 x 25 rm 110 77 16
19 / 1.30 8.90 – 9.9 1 x 25 rm 110 77 16
19 / 1.53 10.05 – 11.0 1 x 35 rm 136 95 16
19 / 1.78 11.70 – 13.0 1 x 50 rm 164 130 25
19 / 2.14 13.50 – 15.0 1 x 70 rm 207 166 35
19 / 2.52 15.80 – 17.0 1 x 95 rm 253 202 50
37 / 2.03 17.40 – 19.0 1 x 120 rm 291 232 70
37 / 2.25 19.35 – 21.0 1 x 150 rm 333 266 95
37 / 2.52 21.64 – 23.5 1 x 185 rm 381 305 95
61 / 2.25 24.65 – 26.5 1 x 240 rm 452 360 120
61 / 2.52 27.50 – 29.5 1 x 300 rm 526 420 150
61 / 2.85 30.85 – 33.5 1 x 400 rm 639 511 240
61 / 2.20 34.40 – 37.0 1 x 500 rm 752 600
127 / 2.52 38.40 – 41.0 1 x 630 rm 855 684
NYY
600/1000V
(Plain Annealed Copper Conductor, PVC Insulated and PVC-sheathed Cables)
Single Core

Derated value of
No. and Approximat
Cross-Sectional Current Rating Ampacity of
Approximate e Outer
Area of 35 C ambient
o
Conductor for ECC-size
Diameter of Diameter
Conductor temperature in air Selecting CB/Fuse
Wires
Sizes
No./mm. mm mm2 A A mm2
1/1.38 6.6 1 x 1.5 re 22 16 4
1/1.78 7.2 1 x 2.5 re 30 21 4
7/0.85 8.2 1 x 4 rm 39 27 4
7/1.05 8.7 1 x 6 rm 50 35 6
7/1.35 9.7 1 x 10 rm 69 48 10
7/1.71 10.7 1 x 16 rm 94 66 16
7/2.13 12.4 1 x 25 rm 125 88 16
19/1.53 13.7 1 x 35 rm 160 112 16
19/1.83 15.6 1 x 50 rm 195 156 25
19/2.17 17.3 1 x 70 rm 245 196 35
19/2.52 19.4 1 x 95 rm 300 240 50
37/2.03 21.0 1 x 120 rm 350 280 70
37/2.27 23.1 1 x 150 rm 405 324 95
37/2.52 25.6 1 x 185 rm 460 368 95
61/2.24 28.6 1 x 240 rm 555 444 120
61/2.50 31.3 1 x 300 rm 640 512 150
61/2.89 35.3 1 x 400 rm 770 616 240
61/3.23 39.2 1 x 500 rm 900 720
127/2.52 43.2 1 x 630 rm 1030 824
NYY
600/1000V
(Plain Annealed Copper Conductor, PVC Insulated and PVC-sheathed Cables)
Three Core

No. and Ampacity of


Approximat Cross-Sectional Current Rating
Approximate Conductor for
e Outer Area of 35oC ambient ECC-size
Diameter of Selecting CB/Fuse
Diameter Conductor temperature in air
Wires Sizes

No./mm. mm mm2 A A mm2


1/1.38 11.6 3 x 1.5 re 16 16 4
1/1.78 12.9 3 x 2.5 re 23 23 4
7/0.85 15.0 3 x 4 rm 32 32 4
7/1.05 16.3 3 x 6 rm 41 41 6
7/1.35 18.3 3 x 10 rm 56 56 10
7/1.71 21.4 3 x 16 rm 75 75 16
7/2.13 25.4 3 x 25 rm 98 98 16
20-wire 23.2 3 x 35 sm 120 120 16
20-wire 27.1 3 x 50 sm 150 150 25
20-wire 30.0 3 x 70 sm 190 190 35
20-wire 34.5 3 x 95 sm 230 230 50
39-wire 37.2 3 x 120 sm 270 270 70
39-wire 41.1 3 x 150 sm 305 305 95
39-wire 45.3 3 x 185 sm 350 350 95
39-wire 50.9 3 x 240 sm 410 410 120
39-wire 57.3 3 x 300 sm 470 470 150
61-wire 62.0 3 x 400 sm 530 530 240
61-wire 72.1 3 x 500 sm 600 600
61-wire 80.2 3 x 630 sm 690 690
NYY
600/1000V
(Plain Annealed Copper Conductor, PVC Insulated and PVC-sheathed Cables)
Four Core
Derated value of
No. and
Approximat Cross-Sectional Current Rating Ampacity of
Approximate
e Outer Area of 35oC ambient Conductor for ECC-size
Diameter of
Diameter Conductor temperature in air Selecting CB/Fuse
Wires
Sizes
No./mm. mm mm2 A A mm2
1/1.38 12.4 4 x 1.5 re 16 16 4
1/1.78 13.8 4 x 2.5 re 23 23 4
7/0.85 16.2 4 x 4 rm 32 32 4
7/1.05 17.6 4 x 6 rm 41 41 6
7/1.35 19.8 4 x 10 rm 56 56 10
7/1.71 23.2 4 x 16 rm 75 75 16
7/2.13 27.6 4 x 25 rm 98 98 16
20-wire 25.4 4 x 35 sm 120 120 16
20-wire 29.3 4 x 50 sm 150 150 25
20-wire 32.4 4 x 70 sm 190 190 35
20-wire 38.3 4 x 95 sm 230 230 50
39-wire 40.4 4 x 120 sm 270 270 70
39-wire 45.4 4 x 150 sm 305 305 95
39-wire 51.1 4 x 185 sm 350 350 95
39-wire 58.4 4 x 240 sm 410 410 120
39-wire 63.8 4 x 300 sm 470 470 150
IYAL
250/440V
(Plain Annealed Copper Conductor, Single Core, PVC Insulated, Non-sheathed Cables)

Current
Rating at
35o C
Clipped to a
Overall Nominal Cross- surface or Derated Ampacity
No. and Nominal
Diameter Sectional Area on a cable for Selecting ECC-size
Diameter of Wires
of Conductor tray CB/Fuse Sizes
bunched &
unenclosed
two cables
single phase
No./inch. No./mm. mm mm2 A A mm2
1/0.044 1/1.12 3.03 1.00 16 11 4
3/0.029 3/0.74 3.43 1.30 20 14 4
3/0.036 3/0.91 3.88 1.95 25 18 4
7/0.029 7/0.74 4.11 2.98 31 22 4
7/0.036 7/0.91 4.90 4.55 41 29 6
7/0.044 7/1.12 5.51 6.85 51 36 10
7/0.052 7/1.32 6.12 9.58 65 46 10
7/0.064 7/1.63 7.03 14.53 83 58 16