(BYPASS INPUT)

M AINT BYPASS
SWITCH
Q2
ON

OUTPUT
SWITCH
Q1
L3 L1 ON
(RECTIFIER INPUT)

TR1

NOTES:
1)BYPASS INPUT REQUIRES 3ph + N + GND INPUT.
2)BYPASS AND RECTIFIER INPUT M UST BE CONNECTED WITH CLOCKWISE PHASE
ROTATION
The AC values below are current ratings per phase. These m axim um and nom inal ratings 3)UPS IS CONFIGURED FOR SINGLE INPUT AS STANDARD. UPS M AY BE
should be considered w hen choosing the appropriate AC over current protection device. CONFIGURED FOR DUAL INPUT BY REM OVING THE JUM PERS BETWEEN THE
NEC (National Electric Code) Section 210-20 a rules m ust be applied. RECTIFIER AND BYPASS INPUTS. SEE INSTALLATION M ANUAL FOR DETAILS.
DC current rating is the m axim um battery discharge current w hich the UPS allow s. 4)UPS M AY BE EQUIPPED WITH AN INTERNAL BATTERY OPTION. AN EXTERNAL
AC Input AC Input BATTERY M AY ALSO BE CONNECTED. SEE TERM INAL DETAIL DRAWING.
AC Input DC Input
Rectifier Bypass Single Input Configuration
Nom . M ax. Nom . M ax.
SG Series 10 kVA 17.2 A 20.2 A 12 A 17.2 A 20.2 A 19.6 A
SG Series 20 kVA 27.3 A 36.6 A 24.1 A 27.3 A 36.6 A 36 A

Size of Branch Circuit Over current Protection - All M odels: - "CAUTION - To reduce ELECTRICAL DETAIL
the risk of fire, only connect UPS to a circuit provided w ith (See below ) m axim um
am peres branch circuit over current protection in accordance
w ith the NEC (National Electric Code), NSI / NFPA 70
DIGITAL ENERGY SG SERIES 10-20kVA
AC Input AC Input
AC Input DC Input
Rectifier Bypass
Single Input Configuration
SG Series 10 kVA 30 A 15 A 30 A 25 A
SG Series 20 kVA 50 A 35 A 50 A 50 A