Standby Alarm
Battery Calculations Current Current
Control Panel Card Power 0.450 0.850
Power For External Peripheral Devices 0.78000 5.65600
1.230 <-- Sub Totals --> 6.506
Additional Current Draws
MAPNET/IDNet Device Addresses ordered / used 197 197.0 0.158 0.197
Add to above for each IDNet LED On (20 maximum). 0.040
Spare addressable point capacity included for battery calc 10% 20 0.016 0.020
1.403 <--Grand Totals --> 6.763
Additional Battery Capacity Required 10% 0.140 0.676
Standby Time = 24 Hrs 37.049 Standby Ah
Alarm Time = 5 Mins. 0.620 Alarm Ah
Required Capacity 37.669 Total Ah
Battery Supplied 2 x 40.000 40.000 Ah ( 2 x NPX-150RFR )