You are on page 1of 3

DCL-90V12

Spec. No. A9:n/SP/E!700-10


ANNEXURE-I
ANNEXURE-I

PEFCO FOUNDRY
.................
Bidder's Name

ANNEXURE-I
TECHNICAL PARTICULARS

A. NEUTRAL GROUNDING RESISTOR


1.0 General
1.1 Make PEFCO FOUNDRY
1.2 Se rv ic e OUTDOOR
1.3 P'ference Standard IEEE - 32
2.0 Rating
2.1 Rated yoltage 2.5 KV
2.2 Res\stance in Ohms at 9.5 Ohms
2.3 Value of Resistance at final
operating temperature 12.848 Ohms
2.4 Tolerance in declared value of
Resistance in % + lOt
2.5 Electrical Re s is t ivi ty. ..... ... : 72 Micro Ohm CIll

2.6 Temperature C07efficient of


Resistance 0.00094 Ohms/ o C
2.7 Current Rating Amps
a. Short Rat ins . 10 Secs. 200 Amps
b. Continuous Rating 45 Amps

(NGR-TCL.ANX) - 1-
DCL-90V12
Spec. No. A9002/SP/E/700-10
ANNEXURE-I

3.0 Temperature
3.1 Tempp.rature rise over Reference
Ambient -

a. For duty at continugus


current ratin9 •••• C

b. For duty at short tiMe


current rating of "'oAmp
for ..• Secs. •••• C

3.2 Change in Resistance over tempera-


ture (over operating temperature) 3.348 Ohms

4.0 Insulation Level

4.1 One (1) minute power frequency


withstand voltage ••• KV (rms) 7.5 KV
4.2 Basic ;~pulse withstand
1 eve' •• KV (Peak) N.A for NGR

5.0 Construction

5.1 Material used Stainless Steel 316

5.2 C~oss-s~ction area 18 mm2

5.3 Type of Resistor Element Rod formed grids

S.4 Material composition A!) Per SS 316

5.5 Number of Elements per unit


(series/parallel combination 70 grid elements in
to be indicated) series.

(NGR-TCL.ANX) -2-
DCL-90V12
Spec. No. A9002/SP/E/700-10
ANNEXURE-I

5.6 Type of Insulation provided

a. Between resistor &mountin9


.frame Porcelain
b. Between Mountin9 frame &
earth
-,
B. NEUTRAL GROUNDING CUBICLES
1.0 Make Pefco foundry
2.0 Type M.S. angle Iron
Structure with 14 SWG
enclosure.
3.0 Service Outdoor
4.0 RefejenceStandard
5.0 Thickness of sheet steel 2 mm
6.0 Overall Dimension (L x W x H) 800 x 900 x 900
7.0 Weight: (Approx)

a. Self wei9ht 120 Kg


b. With all internally
installed equipment 200 Kg

8.0 Colour shade, Inside/Outside IS-5/Shade 631

.r 9.0 Ventilating louvres provided? N.A .


10.0 Internal wiring size 2.5 Sq.mm.
11.0 Complete with necessary
terminal boxes Yes
11'.0 Two (2) nos. Ground Pads complete
with hardwares furnished Yes

(NGR-TCL.ANX) - 3 -