Turbine Vibration

ALARM SETPOINT TRIP SETPOINT


DESCRIPTION
(Mils) (Mils)

Turbine Axial Displ. 10 14


(ZT-600)
Turbine Axial Displ. 10 14
(ZT-601)
Turbine Steam Brg. X 3.5 4.5
Vibr. (XT-600)
Turbine Steam Brg. Y 3.5 4.5
Vibr. (XT-601)
Turbine Exhaust Brg. X 3.5 4.5
Vibr. (XT-602)
Turbine Exhaust Brg. Y 3.5 4.5
Vibr. (XT-603)
GearBox Vibration

ALARM SETPOINT TRIP SETPOINT


DESCRIPTION
(Mils) (Mils)

Pinion Before Bearing


Vibr. 2.6 5
(XT-604)

Pinion Before Bearing


Vibr. 2.6 5
(XT-605)

Gearwhell After 3.6 6


Bearing Vibr. (XT-610)

Gearwhell After 3.6 6


Bearing Vibr. (XT-611)
Pinion After Bearing 2.6 5
Vibr. (XT-606)
Pinion After Bearing 2.6 5
Vibr. (XT-607)

Gearwhell Before 3.6 6


Bearing Vibr. (XT-608)

Gearwhell Before 3.6 6


Bearing Vibr. (XT-609)
Generator Vibration

DESCRIPTION ALARM SETPOINT TRIP SETPOINT


(Mils) (Mils)

Generator Drive End X 3.5 4


Vibr. (VXT-306)
Generator Drive End Y 2.5 3.5
Vibr. (VXT-306)

Generator Exciter End 3.5 4


X Vibr. (VXT-307)
Generator Exciter End 2.5 3.5
Y Vibr. (VXT-307)
Turbine Temperatures
ALARM SETPOINT TRIP SETPOINT
DESCRIPTION
(°C) (°C)

Turbine Inactive Thrust 95 100


Brg. (RTD-221)

Turbine active Thrust 95 100


Brg. (RTD-220)
Turbine before End Brg 95 100
(RTD-200)
Turbine After End Brg 95 100
(RTD-201)
Gearbox Temperatures
ALARM SETPOINT TRIP SETPOINT
DESCRIPTION
(°C) (°C)

Gearbox Before Brg 95 100


(RTD-204)
Gearbox Before Brg 95 100
(RTD-205)
Pinion Before Brg 95 100
(RTD-202)
Pinion Before Brg 95 100
(RTD-203)
Generator Temperatures
ALARM SETPOINT TRIP SETPOINT
DESCRIPTION
(°C) (°C)

Generator Drive End 80 85


Brg (TE-208)
Generator Exciter End 80 85
Brg (TE-209)
Generator Stator 130 140
Phase A (TE-210A)
Generator Stator 130 140
Phase B (TE-210B)
Generator Stator 130 140
Phase C (TE-210C)
Generator Stator 130 140
Phase A (TE-210D)
Generator Stator 130 140
Phase B (TE-210E)
Generator Stator 130 140
Phase C (TE-210F)
Generator Cooling
ALARM SETPOINT TRIP SETPOINT
DESCRIPTION
(°C) (°C)

Air Inlet (TE-230) 45 100


Air Outlet 80 100
Water (TE-232) 35 45
Water Flow (FT-520) 135 25
MISC
DESCRIPTION ALARM SETPOINT TRIP SETPOINT

Lub Oil Pressure (PT- 20.3 PSI 17.4PSI


200)

Lube Oil 50 °C
Temperature(PT-219)
Exhaust Steam Prsr 28 PSI 30 PSI
(PT-102)
Inlet Steam Presure 319 PSI 348 PSI
(PT-100)
Steam Flow NA
Control Oil Pressure 246.5 PSI 217.5 PSI
(PT-201)

Inlet Steam 315 °C 290 °C


Temperature (TE-100)

Exhaust Steam 0
Temperature (TE-101)

ITEM DESCRIPTION RANGE (PSI) SET POINT (PSI)


Auto START/STOP of 20.31 FOR CUT IN
PS-200 0 - 58
AOP 33 FOR CUT OFF

Auto START/STOP of 14.5 FOR CUT IN


PS-201 0 - 58
EOP 20.3 FOR CUT OFF
Lube Oil pr. Low
PS - 202 alarm 0 - 58 20.31

Lube Oil pr. V. Low


PS - 203 0 - 58 17.4
trip
Lube Oil Pressure
PS - 204 Interlock for BGM and 0 - 58 21.75
acop-1,2.
275 FOR CUT IN
PS - 207 145 - 580
391 FOR CUT OFF
Auto START/STOP of
ACOP-1.

261 FOR CUT IN


PS - 208 145 - 580
377 FOR CUT OFF
Auto START/STOP of
ACOP-2.
PS - 205 Control Oil Pr. Low 145 - 580 246
Alarm
PS - 206 Control Oil Pr. V. Low 145 - 580 217
Trip
PS - 209 Trip Oil Pressure Low 0 - 58 11.6
Alarm
PS - 102 Exhaust Steam Pr. 0 - 58 21.75
High Alarm
PS - 103 Exhaust Steam Pr. V. 0 - 58 24.6
High Trip
PS - 100 Inlet Steam Pr. High 145 - 580 319
Alarm
PS - 101 Inlet Steam Pr. V. 145 - 580 348
High Trip