SFT2841 with Goose

HOW TO USE GOOSE

●SFT2841
●Set communication ACE 850 => Ethernet TP
●Assign goose to LDC
●Set goose features

Schneider Electric - Division - Name – Date 2


Series 60 & 80 base unit
C1 for Sepam 60
C2 for S 80
F C1 and C2 for
Series 80 Modbus
& RJ45 connector
Series 60 ● Modbus ports

B2 B1
F Ethernet ACE850
for IEC 61850
H3 H2 H1

Schneider Electric - Division - Name – Date 3


ACE850

Two Ethernet ports for redundancy (RSTP) or


dual network connections (VLAN)

Warning Cable CCA 614 only

Direct Sepam connection to


C port (Sepam40)
or F port (Sepam80)

Schneider Electric - Division - Name – Date 4


HARDWARE SETUP SERIES 60 & 80

Schneider Electric - Division - Name – Date 5


HARDWARE SETUP SERIES 60 & 80

Choice Ethernet
shows parameters

Schneider Electric - Division - Name – Date 6


ACE850 Settings
● Parameters to be set :

●Ethernet and Web


●SNMP
●SNTP
● IP filter
●Switch and RSTP
●User Account
●For each parameter a specific window in the SFT2841
● access with ethernet interface option and Web

Schneider Electric - Division - Name – Date 7


Ethernet and TCP/IP configuration
Before configuring the ACE850, obtain a unique static IP address, subnet
mask, and default gateway address from the network administrator.

● Frame format
● Used to select the format for data sent over an Ethernet connection.
● Ethernet II, 802.3, Auto
● Media type
● Used to define the physical Ethernet connection
● ACE850TP
●10T/100Tx Auto, 10BaseT-HD, 10BaseT-FD, 100BaseTX-HD,
100BaseTX-FD
● ACE850FO
●100BaseFX-HD, 100BaseFX-FD

In red default setting

Schneider Electric - Division - Name – Date 8


Ethernet and TCP/IP configuration
●IP address Used to enter the static IP address of
the ACE850. 0.0.0.0 to 255.255.255.255 169.254.0.10

●Subnet mask Used to enter the subnet mask of your network.


0.0.0.0 to 255.255.255.255 255.255.0.0

●Default gateway Used to enter the default gateway (router) IP


address used for wide area
network (WAN)
communications.
0.0.0.0 to 255.255.255.255 0.0.0.0

●Allow CID file to override IP parameters


not checked

●Keep alive Timeout value used to test for session


1 to 60 seconds disconnection.
30 seconds
●FTP session inactivity timeout Timeout value used to force
disconnection of an inactive FTP
session
30 to 900 seconds 30 seconds
In red default setting
Schneider Electric - Division - Name – Date 9
Parameters Ethernet et Web

Schneider Electric - Division - Name – Date 10


Parameters SNMP
« Enable All Traps» is
selected : all the settings of the
box « SNMP Trap
Parameters » can be changed

« Enable All Traps» is not


selected by default : all the
others setting of the
box« SNMP Trap
Parameters » are shown in
grey and can not be changed.

Schneider Electric - Division - Name – Date 11


SNTP
SNTP configuration
●SNTP is a time synchronization protocol that can be used
to synchronize the Sepam. SNTP is used in mode 3-4
(unicast mode).
●If SNTP is used, the synchronization source for
Sepam must be defined as Ethernet.
●If SNTP is not used, the Sepam synchronization must be
ensured by other means (Modbus frames,
synchronization tops).

Schneider Electric - Division - Name – Date 12


Parameters SNTP
● Enable SNTP Enables the time and date of the Sepam to be set by the
Simple not enabled Network Time Protocol (SNTP) server.
● Time Zone Offset Determines the difference between local time and
UTC Coordinated Universal Time (UTC) (same as GMT).
UTC-12 to UTC+14
● Enable Daylight Enables the use of Daylight Saving Time (Summer time)
not enabled
● DST offset Difference between standard time and Daylight Saving Time.
60minutes + 30 or + 60 minutes
● DST starts If enabled, DST starts on the selected date.
last Sunday of March
● DST ends If enabled, DST ends on the selected date.
last Sunday of October
● Primary Server IP Address The IP address of the SNTP server the ACE850 contacts to
0.0.0.0 get the time message.
● Secondary Server IP Address The IP address of another SNTP server the
0.0.0.0 ACE850 contacts in case the primary server is
down.
● Poll Interval Controls how often the ACE850 contacts the SNTP server for
1 hour the correct time. 10 minutes to 1 day

Schneider Electric - Division - Name – Date 13


Parameters SNTP

Schneider Electric - Division - Name – Date 14


RSTP configuration

● RSTP
● It must be enabled each time the ACE850 is included in a loop. It
may be disabled in other cases.
● Changing the default settings is normally not required and should be
performed with extreme care as it could jeopardize the stability of the
Ethernet network.
● If in doubt, it is always possible to revert to the default values using the
"default settings" button.

Schneider Electric - Division - Name – Date 15


RSTP configuration
● Parameters
● Enable RSTP Check this box to activate the use of the RSTP protocol
enabled
● Bridge priority Priority of the bridge. The bridge with the lowest priority becomes root.
61440 0 - 61440, by steps of 4096
Hello time Amount of time between the transmission of configuration messages
2 seconds 1 to 10 seconds
● Forward delay time Time value to control how fast a port changes its spanning state when
15 seconds moving towards the forwarding state 4 to 30 seconds
● Max age time Valid duration of configuration message once sent by the root bridge
20 seconds 6 to 40 seconds
● Max transmit count Maximum BPDUs that can be transmitted
32 by the Port Transmit state machine in any Hello time. This value limits
the maximum transmission rate. 3 to 100
● Cost style RSTP (32 bits) or STP (16 bits) cost style selection
RSTP

● Note: RSTP parameters must verify the following relationships:


● 2 x (Forward_delay_time - 1 second) ≥ Max_age_time
● Max_age_time ≥ 2 x (Hello_time + 1 second)

● Example below with default setting


● (2x15s) -1s ≥ 20s ≥ (2X2s) + 1s=
● 29s ≥ 20s ≥ 5s

Schneider Electric - Division - Name – Date 16


Setting of the parameters Switch and
RSTP
Bridge Priority :
To configure the switch
priority of a bridge. For
priority, the range is 0 to
61440 in increments of 4096;
the default is 32768. The
lower the number, the more
likely the switch will be
chosen as the root switch.
The value entered is
rounded to the lower
multiple of 4096. The actual
number is computed by
adding this number to the
bridge group number

Schneider Electric - Division - Name – Date 17


Parameters IP filter
IP filtering configuration
● The IP filtering function allows the administrator to specify which Modbus/TCP
clients and which IEC 61850 clients have access to the ACE850 services.
● Note: if IP filtering is enabled, access is forbidden to any client not in the filtered
list.
● Parameters Description Authorized values
● Enable filtering Check this box to activate filtering based on IP
not enabled addresses.
● IP address The IP address of a client for which filtering options
0.0.0.0 are defined. 0.0.0.0 to 255.255.255.255
● IEC 61850 Check this box to grant IEC 61850 access to the given
not checked IP address.t:
● Modbus Check this box to grant Modbus/TCP access to the
not checked given IP address.

Schneider Electric - Division - Name – Date 18


User accounts configuration
ACE850 users are assigned Usernames and Passwords used to gain
access to the FTP or WEB servers.
Each user belongs to a group which determines their access rights:

● Administrator: read-write access to the FTP server, access to the


WEB server
● Operator: read-only access to the FTP server, access to the WEB
server
● Guest: no access to the FTP server, access only to the WEB server
● Maxi => Up to 4 user accounts can be defined.

●The following account is always created by default as user 1:


●Name: Admin
●Password: ACE850

Schneider Electric - Division - Name – Date 19


User Account settings

Name
User name String (1 to 8 characters)
Password
User password String (4 to 8 characters)

Schneider Electric - Division - Name – Date 20


HOW TO USE GOOSE
● SFT2841

● Set communication ACE 850


● Assign goose to LDC
● Set goose features

Schneider Electric - Division - Name – Date 21


Standard goose assignment
● the Gxx have a standard assignment :
● G401 : AL1 : blocking 1
● G402 : AL2 : blocking 2
● G403 : external trip
● G404 : Closing inhibition
● Goose Defaut reception
● Load Schedding (application moteur only)
● Reception Test Goose
● Other use Not used

● G516 : module ACE850 present (not modifiable)

Schneider Electric - Division - Name – Date 22


GOOSE configuration
● SFT2841
● Set communication ACE 850
● Assign goose to LDC => Goose Input
● Set goose features

Schneider Electric - Division - Name – Date 23


Assign the Gxx (Goose) to a function

Select the function of the Gxx like an


input
Standard LDC
( blocking external trip, inhibit
closing)
Other Use
Not use

Schneider Electric - Division - Name – Date 24


HOW TO USE GOOSE
● SFT2841
● Set communication ACE 850
● Assign goose to LDC
● Set goose features => Matrix

Schneider Electric - Division - Name – Date 25


Matrix

Assign output, led or message to the


Gxx

Schneider Electric - Division - Name – Date 26


Matrix

Schneider Electric - Division - Name – Date 27