VT‐MV

Technical Schedule Particulars of Voltage Transformer MV

No. Particulars Unit Technical Requirement Offered

1 Manufacturer
2 Manufacturer's Code N° 
3 Type 
4 Standard IEC
5 Rated Voltage  kV 24
6 Power Frequency Voltage(r.m.s) kV 50
7 Lightning Impulse Withstand Voltage (Peak) kV 125
8 Insulation Material Cycloaliphatic Epoxy Resin
9 Rated Primaries Voltage V 22/√3
10 Rated Secondary Voltage V 100/√3
11 Primary Terminal Marking A‐N
12 Secondary Terminal Marking 1a‐1n
13 Accuracy Class 75 VA Class 0.5
14 Voltage Factor
15 Rated Frequency Hz 50
16 Maximum Ambient Temperature °C 40
17 Earth Terminal
18 Material of Core Copper
19 Diameter:
20 ‐ Height mm
21 ‐ Width mm
22 ‐ Depth mm
23 Temperature °C +45
24 Air Humidity % 90
25 Weight Kg

Technincal Office 1/1