You are on page 1of 7

Foundation and Soft Ground Engineering Conference Thu Dau Mot UniversityICTDMU-1, Binh Duong, June 5 –6, 2013

Verification of effectiveness of vacuum consolidation method with


air-water separation system

Teerachaikulpanich Nipon
Thai Maruyama Industry/Bangkok, Thailand. < nipon@maruyama-ind.com>
Kosaka Toshiaki
Dia Consultants Company/Sendai, Japan. < t.kousaka@diaconsult.co.jp>

Kawaida Minoru
Central Nippon Expressway Company/Nagoya, Japan. <m.kawaida.aa@c-nexco.co.jp>

ABSTRACT: In a conventional vacuum consolidation method, the vacuum pressure inside the improved
area decreases due to an elevation head difference between a vacuum pump and an improved area created
by a settlement. Air-water separation concept was proposed as a solution of this problem. This paper pre-
sented a case study of vacuum consolation equipped with air-water separation system used for an express-
way construction. Embankment about 24 m thick was successfully constructed over the soft ground about
50 m deep and induced a large consolidation settlement about 11 m. The observed vacuum pressures meas-
ured under the airtight sheet were constantly maintained over 85 kPa along the construction period. The re-
sult confirms a practical use of air-water separation system. Furthermore, the effectiveness of vacuum con-
solidation as a surcharge load was also verified by the field observed data and laboratory test results. It was
found that the soil properties after improved were greater than the theoretical calculation.

Keywords: Vacuum consolidation, Soil improvement, Surcharge preloading, Soft soil, Case history

1 Introduction not guarantee that the vacuum pressure inside the


improved area and at pump will be the same during
Vacuum consolidation method was firstly intro- vacuum operation. Therefore, the vacuum pressure
duced by Kjellman (1947). In principle, the depres- under airtight sheet shall be always monitored and
surization of atmospheric pressure by using a vacu- checked regularly to confirm the vacuum pressure
um pump distributes through the prefabricated ver- inside the improved area. Imai (2005) described the
tical drain (PVD). Airtight sheet is used to cover on
the surface of improved area in order to seal the sys-
tem. By using vacuum pump, the difference of at-
mospheric pressure between outside and inside in-
duces the force to consolidate a soil. In Japan, the
vacuum consolidation systems were developed by
improving construction materials such as PVD, air-
tight sheet, construction technique, vacuum pump,
etc. Generally, vacuum pressure measured under
the airtight sheet will be around 60-80 kPa at the
beginning of vacuum operation. It should be noted
that vacuum pressure measured at pump will be
high if the vacuum system is sealed properly from
the outside atmospheric pressure because the vacu-
um gauge or vacuum sensor measured at pump is Figure 1. Schematic of vacuum consolidation
very close to the vacuum origin. However, it does with air-water separation system

373
reason of vacuum pressure decrease during consoli- shows the interpreted soil profile. Humic soil and
dation. It is due to elevation head difference be- cohesive soil are found to form alternated layers.
tween vacuum pump and the improved area after Cohesive soils predominate at the center part of the
settlement. Vacuum pressure inside an improved valley, and humic and sandy soils can be found
area decreases 10 kPa at every 1 m settlement in partly. Humic soil predominates at the both ends
principle. To solve this problem, the proposed the of the valley with the depth of 30 to 40 meters. N
concept called air-water separation to apply with a value of standard penetration test of soils near the
conventional vacuum consolidation system. This ground surface, both humic and cohesive soils, are
concept was implemented to use in practice named almost zero, and deeper layers are less than 10.
as Compact Vacuum Consolidation (CVC). The The natural water content of humic soil and upper
schematic of CVC is illustrated in Fig. 1. This pa- cohesive soil layer are about 100-400% (Apt) and
per presents the performance and effectiveness of 100-200% (Ac1) respectively. The original uncon-
vacuum consolidation method with air-water separa- fined compressive strength of upper cohesive soil
tion system where the soft ground 50 deep existing (Ac1) and deep humic soil (Apt5 & Apt6) are
under a expressway construction with a large set- about 30 kN/m2 and 50-150 kN/m2, respectively.
tlement about 11 m. N

2 Project Site Mukasa Area


若狭町向笠地区 Tsuruga
敦賀JCTJC T

The construction site was located in Fukui Prefec- Wakasa Bay


若狭湾
ture, Japan where Maizuru-Wakasa Expressway Fikui Pref.
福井県

was constructed. The distance of expressway was


about 162 km. Vacuum consolidation was applied
Obama-Nishi
小浜西 IIC C
in Mukasa area shown in Fig. 2. Soft ground dis-
舞鶴若狭自動車道
Maizuru-Wakasa
tributes along the expressway construction around Maizuru-Higashi Expressway
舞鶴東 IC IC
50 km long from Obama-Nishi to Tsuruga. Lake Biwa
琵琶湖
ky oto Pref.
京都府 Shiga Pref.
滋賀県
Wakasa bay is the rias coast and many drowned
valleys existing around Mikata-goko lakes. As a
result, the soft ground extends to 50 m deep Fig. 3 Figure 2. Site location

Figure 3. Soil profile

3 Design and Construction struction time could not be satisfied. Increasing


rate of embankment construction was required to
Originally, Prefabricated Vertical Drain (PVD) accelerate the construction. Therefore, vacuum
with surcharge load was selected as a ground im- consolidation method was selected to apply be-
provement work. PVDs were installed up to 34 m cause it can provide a higher stability during the
deep. By this improvement method, the embank- construction. Moreover, vacuum pressure was also
ment construction rate at 3 cm/day was limited by used as a surcharge load replacing a part of em-
design criteria. Later on, it was found that the con- bankment surcharge. Finally, the membrane type

374
of vacuum consolidation with air-water separation 35.4 m. It should be noted that all piezometers
system was selected to use. For CVC construction, were installed at the center of PVDs location be-
PVDs (7 mm thick) were installed up to 20 m deep cause it was considered to be the most difficult
between the existing PVDs (3 mm thick) which were point for an excess pore water pressure dissipation.
previously installed at 34 m in square grid pattern of
1.2 m x 1.2 m. It should be noted in advance that the 4.4 Vacuum sensor
top of existing PVDs were not directly connected to
In vacuum consolidation method, a vacuum gauge
vacuum consolidation system. The area of improve-
or sensor is usually used to measure the negative
ment was about 9,000 m2. Accordingly, the vacuum
pressure. Two of vacuum sensors were embedded
consolidation system was divided into 3 areas with
inside the horizontal drains at each area to check
three vacuum pumps operated simultaneously.
the vacuum pressure inside the improved area. It
Moreover, an embankment height including a sur-
will be called as vacuum pressure under airtight
charge backfill was designed to 14 m.
sheet in this paper. In addition, the vacuum gauge
attached at the vacuum pump will be called as vac-
uum pressure at pump.
4 Field Instrumentation

In order to monitor field data during a construc-


5 Field data analysis
tion, basic field instruments for embankment con-
struction over a soft ground were installed as illus-
According the field monitoring data, the following
trated in Fig. 4. It should be noted that the instru-
categories were analyzed to verify the performance
ments shown in Fig. 4 were installed at the center
of vacuum consolidation method with air-water
of embankment. but illustrated separately for a
separation system.
simple view.
5.1 Vacuum pressure
Fig. 5 shows embankment thickness/elevation,
surface settlement and vacuum pressure with time.
Embankment thickness was about 24 m at the
completion of construction. The settlement in-
duced by working platform load was about 1 m
prior the start of vacuum pump. It can be seen that
vacuum pressure and embankment load induced
the large settlement about 11 m. Therefore, the
vacuum pressure inside the improved area shall be
zero in principle after the settlement reaches over
Figure 4. Location of field instrument
10 m. According to monitoring data, the vacuum
4.1 Surface settlement pressures measured at pumps were over 90 kPa
during vacuum operation. The average vacuum
Settlement plates were placed on the airtight sheet pressures under airtight sheet in all areas were
prior the start of vacuum operation at the center about 75~85 kPa in the beginning of construction
and both side of area. Only surface settlement data and slightly increased after the embankment thick-
at the center of area was presented in this study. ness was over 10 m. Then, the values were main-
tained at 88~94 kPa after the completion of em-
4.2 Extensometer bankment filling.
Settlement of sub-soil layer was measured by In fact, the pressure measured inside the im-
extensometers. They were installed at the depth of proved area will be usually lower than the pressure
-3.8 m, -9.8 m, -17.7 m, -25.7 m, and -31.0m, re- measured at pump due to the imperfection of air-
spectively tightness related with the construction condition
and technique. According to the result, it can be
4.3 Electrical piezometer considered that the airtightness became higher after
embankment was started. The embedded airtight
Electrical piezometers were installed at depth of - sheet was lowered down by the settlement. Thus,
7.0 m, -14.2 m, -17.0 m, -22.3 m, -28.8 m and - vacuum pressures inside the improved area were

375
gradually increasing in all areas especially in area pressures at the shallow depths; -7.0, -17.0, and -
3, which showed the lowest vacuum pressure in the 22.3 m were significantly different from the raw
beginning. Consequently, it can be concluded that data. The excess pore water pressure after the cor-
the air- water separation concept proposed by Imai rection shall be used in the data analysis.
(2005) was true and applicable in practice.

Figure 5. Vacuum pressure during

5.2 Pore water pressure


Fig. 6 shows the excess pore water pressure with
time. Due to the large settlement, the locations of
the installed piezometers were changed according
with the quantity of settlement. In order to obtain
the more precise pore water pressure, the correc-
tion of piezometer depth was carried out by using
the data from extensometers. (Kosaka et al. 2011).
It can be clearly seen that the excess pore water Figure 6. Excess pore water pressure with time

376
According to monitoring data, the excess pore water pressure at the completion time of embank-
water pressures were reduced to a negative value ment construction. It can be clearly seen that the
after the start vacuum operation. After the start of excess pore water pressures induced by embank-
embankment construction, the embankment load ment load were different in each zone depending
induces the excess pore water pressure in a positive on soil type. The maximum excess pore water
side. The maximum of excess pore water pressure pressures were Δu=20kPa, Δu=60kPa, and
was at the completion of embankment construction. Δu=90kPa in the vacuum consolidation, non-
After waiting for the pore water pressure dissipa- vacuum and non-improvement zone, respectively.
tion, the vacuum pumps were decided to terminate. The last profile was the pore water pressure at the
It can be seen that the excess pore water pressures in termination of vacuum pump. At this profile, the
the vacuum zone was below hydrostatic pressure different status of pore pressure within each zone
and returned to a hydrostatic pressure. It should be can be clearly seen. The pore water pressure in the
consider that the primary consolidation was com- vacuum zone was lower than the hydrostatic pres-
pleted in this zone. On the contrary, the excess sure as described in previous. On the contrary, the
pore water pressure in non-vacuum and non- pore water pressure at non-vacuum and non- im-
improvement zone were higher than hydrostatic provement zone still remained over the hydrostatic
pressure. The increase of the excess pore water pressure around 30 kPa and 50 kPa, respectively.
pressure could be clearly observed at the depths of - According to the result, it can be seen that the de-
22.3m and -28.8m but very slightly at depth -35.4 pressurized atmospheric pressure was not only effect
m. The rebound behavior confirms the effective of to vacuum zone but also effect to non-vacuum zone
vacuum consolidation as a surcharge load. and somewhat in non-improvement zone. This is
probably due to the sand backfill under the vacuum
Pore pressure (kPa)
consolidation system being as a media for vacuum
0
-100 0 100 200 300 400 500 distribution between the vacuum pump and PVDs 3
Start of embankment mm thick. However, the reduction of hydrostatic
Finish of embankment pressure alone is not enough for vacuum consolida-
Stop of vacuum pump tion. Providing a path for water dissipation as same
Hydrostatic as in the vacuum zone is a key of success.
10 Theory vacuum at 70 kPa

5.3 Rate of settlement


The vacuum pressure is considered as a temporary
Depth (m)

Vacuum zone load and disappears after a termination of vacuum


20
pump. Vacuum surcharge effect can be also ob-
served by the rebound of settlement. Hyperbolic
method is a graphical technique using for estimat-
Non vacuum zone ing a final settlement and degree of consolidation
30
by plotting a rate of settlement against time. Fig. 8
shows the relationship between (St-S0)/t and t.
Without a surcharge removal, the rate of settlement
Non improvement zone shall align in straight line as similar as the regres-
40 sion curve. In this study, the attention shall be paid
Figure 7. Pore water pressure profile
to the data curve after the termination of vacuum
pump. It can be clearly seen that data curve
Fig. 7 shows the pore water pressure with depth. changed significantly comparing to the regression
The first profile was the pore water pressure at the line in the vacuum consolidation zone (depth 0.0~-
start of embankment construction. At this time, the 17.0 m). The smaller changes were also observed
ground was subjected to vacuum pressure only. in the non-vacuum zone (depth -17.0~-25.7 m) and
The pore water pressure was reduced about 40 to (depth -25.7~-30.96 m) respectively. On the con-
60 kPa in the vacuum consolidation zone and trary, the change of curve could not be observed in
around 40 kPa in the non-vacuum zone. Moreover, non-improvement zone (below -30.96 m). The re-
the pore water pressure was also reduced about 20 sult showed a good agreement with the pore water
kPa in the non-improvement zone where PVDs pressure the vacuum surcharge did not effect to the
were not installed. The second profile was the pore ground below -30 m.

377
3.0 Consolidation Yield Stress (kPa)
0 200 400 600 800
2.5 0

2.0
t/(S -S )
0

1.5
t

1.0 Depth 0-17.68 m


Regression Line 10
0.5 Stop of vacuum pump

0.0
0 20 40 60 80 100 120 140 160

Depth (m)
18 20
16
14
12
t/(S -S )
0

10
t

8 30
6 Depth 17.7-25.0 m
4 Regression Line
2 Stop of vacuum pump
0
0 20 40 60 80 100 120 140 160 40
Max. past pressure by CRS
25 Effective overburden pressure (P 0 )
P 0 +P emb
20
P 0 +P emb +P vac at 70 kPa
t/(S -S )

15
0

P 0 +P emb +P vac at 80 kPa


t

10 P 0 +P emb +P vac at 90 kPa


Depth 25.65-30.96 m
5 Regression Line Figure 9. Profile of consolidation yield stress
Stop of vacuum pump
0 obtained at the center of embankment were used
0 20 40 60 80 100 120 140 160
and compare the results to the theoretical compu-
40 tation. Soils were assumed in a normally consoli-
dated state prior the construction. Thus, the effec-
30 tive overburden pressure (P0) is equal to consoli-
dation yield stress used to compare. The consoli-
t/(S -S )
0

20 dation yield stress by embankment load (Pemb)


t

Depth 0-17.68 m
was considered to the effect of buoyancy force
10
Regression Line and loading stress distribution. The field density
Stop of vacuum pump examined during the embankment construction
0
0 20 40 60 80 100 120 140 160 was used in the calculation. Load by vacuum
t (day) pressure (Pvac) was assumed to be constantly
along the depth. It can be seen that the obtained
Figure 8. Plot of hyperbolic method
consolidation yield stresses down to a depth of 30
m were higher than the theoretical lines where
6 Soil Investigation data PVD existing. On the contrary, the values were
lower than theoretical line at the location deeper
After the termination of vacuum pump, the soil in- than 30 m. The interest should be paid in the vac-
vestigation program was carried out. The following uum zone because the consolidation yield stresses
soil properties are presented to evaluate the effec- were quite higher than theoretical value. The soil
tiveness of vacuum consolidation with air-water characteristic in a similar case should be further
separation system. investigated in a future study.

6.1 Consolidation yield stress 6.2 Undrained shear strength


Fig. 9 shows the consolidation yield stress obtained by The undrained shear strength versus depth by un-
constant rate of strain consolidation. The specimens confined compressive test at the center of em-

378
bankment is shown in Fig. 10. Kosaka et al. - The vacuum pressures under airtight sheet were
(2012) described the strength increment parameter maintained over 85 kPa during consolidation
for the case of the embankment combined with process even after subjected to the settlement
vacuum consolidation method. It was used for cal- over 10 m.
culation in this study. As a result, the obtained un- - Pore water pressure, rate of settlement, consoli-
drained shear strength for vacuum consolidation dation yield stress and undrained shear strength
zone was higher than the theoretical line in all cas- data could be combined to confirm the effec-
es. On the contrary, the undrained shear strength tiveness of vacuum consolidation as a surcharge
tended to be lower than the theoretical line in the load.
non-vacuum consolidation zone. The result agrees - Vacuum consolidation with air-water separation
well with the observed the excess pore water pres- concept was verified to be effectively used in
sure data which shows the incompletion of a pri- practice.
mary consolidation for the soils below 20 m.

Undrained shear strength (kPa) References


0 50 100 150 200 250
0
Imai, G., For the Further Development of "Vacuum
Induced Consolidation Method"-Present Under-
standings of its Principle and Applications in
Journal of Construction management and Engi-
10
neering, Japan Society of Civil Engineers,
No.798/6:1-16, 2005
Kjellman, W. Consolidation of clayey soils by at-
Depth (m)

mospheric pressure. In Proceeding of the Con-


20
ference on Soil Stabilization, Boston, Mass.,
June 1952. Massachusetts Institute of Technol-
ogy, Cambridge, Mass, pp. 258-263, 1952
30
Vacuum Consolidation Technology Association,
Compact Vacuum Consolidation Technical
Manual, 2004
Kosaka, T., Kawakita, M., Inagaki, M., Teerachai-
40
kulpanich, N., Performance of vacuum consoli-
Su after improved dation for high embankment of expressway con-
Su before improved struction on an extremely soft ground, in Ge-
Su for P 0 +P emb otechnics for Sustainable Development-Geotec
Su for P 0 +P emb +P vac at 70 kPa Hanoi 2011, Phung (ed), Hanoi, Vietnam: 65-
Su for P 0 +P emb +P vac at 80 kPa 74, 2011
Su for P 0 +P emb +P vac at 90 kPa
Kosaka, T., Teerachaikulpanich, N., Kawaida, M.,
Nakakuma, K. Soft ground characteristics after
Figure 10. Profile of undrained shear strength subjected to the large settlement induced by
vacuum consolidation combined with
embankment preloading, in International Con-
7 Conclusion ference on Ground Control Improvement and
Ground Control (ICGI 2012), B. Intraratna, C.
In this study, the conclusion could be drawn as Rujikiatkamjorn and J S Vinod(ed), Wollon-
follows: gong, Australia, 2012
- Settlement about 11 m was induced by the em-
bankment 24 m thick and vacuum surcharge.

379

You might also like