You are on page 1of 6

2011 IEEE Symposium on Industrial Electronics and Applications (ISIEA2011), September 25-28, 2011, Langkawi, Malaysia

Transient Stability Analysis on Sarawak’s Grid using


Power System Simulator for Engineering (PSS/E)
Arfah Marini Mohamad, Norazlan Hashim, Noraliza Hamzah, Nik Fasdi Nik Ismail, Mohd Fuad Abdul Latip
Faculty of Electrical Engineering
UniversitiTeknologi MARA (UiTM)
40450 Shah Alam, Selangor, Malaysia
azlan4477@salam.uitm.edu.my

Abstract— Transient stability analysis has become one of the leads to the impulsive transient. Transient stability studies are
major analyses in the power system to ensure the system stability important because the effect of common problem that rose
to withstand a major disturbance. The effect of transient when transient occurs can lead to malfunction of electronic
occurrence can lead to malfunction of electronic control controlled equipment. Moreover, the insulators may shatter
equipment. Transient analysis can be conducted using simulation
when high fault current flows in the transmission line,
software package. One of the commercial simulation software
package that used by industry worldwide is Siemens Power damaging the poles transformer and other equipment
System Simulation for Engineering (PSS/E). This research paper connected to the line. This problem may cause the adjustable
highlights the usage of PSS/E to analyze Sarawak’s Grid System speed drive to shut down abruptly.
stability using the simplest dynamic model that has been The objective of this paper is to analyze the transient
embedded into the program. To observe transient analysis using stability of a practical data in Sarawak Power System by
PSS/E, basic machine model such as generator, exciter and analyzing the characteristic of machine states namely; rotor
governor were used by varying default data in the program to angle, machine speed, terminal voltage and output electrical
find the best simulation output. This paper also analyzed the power with respect to the fault critical clearing time (CCT)
theory of critical clearing time (CCT) of fault occurrence
after the occurrence of a three-phase fault at the respective
between a transmission line near to the generator and far from
the generator. CCT appears to be lesser when the fault occurs at transmission line. This paper also test the theory of critical
a transmission line near to the generator. On the contrary, when clearing duration time when the fault occurred far from the
fault occurs far from the generator, the duration of CCT is generator and critical clearing time when fault occurs at the
greater. The stability of the system is observed based on the line closer to the generator.
machine rotor angle, machine speed, output electrical power and
terminal voltage. II. POWER SYSTEM SIMULATOR FOR ENGINEERING (PSS/E)
Power System Simulator for Engineering (PSS/E) is a
Keywords-Transient Stability Analysis; PSS/E; Critical Clearing
simulation software product from Siemens. The simulation
Time;
program consists of comprehensive transmission system
I. INTRODUCTION planning including optimal power flow and transient stability
analysis. The analysis that can be performed using PSS/E
Stability studies are generally categorized into two major includes load flow analysis and transient analysis. Load flow
areas: steady state stability and dynamic stability. Steady state analysis is performed under the category of steady-state
stability is the ability to regain synchronism after encountering analysis while transient stability is performed under dynamic
slow and small disturbance while dynamic stability is the analysis. In load flow analysis, PSS/E investigates the load
ability to regain synchronism after encountering small flow stability in a network. The generation and load must have
disturbance in the long time frame [1]. Transient is an event a small difference in order to achieve stability. Transient
occurs that is undesirable and momentarily in nature and analysis was performed in PSS/E to examine the immediate
categorized under dynamic stability [2]. Transient stability response after fault condition and inspect the fault critical
arises in power system in determining the stability of the clearing time (CCT). This paper uses the technique of trial and
system to withstand the transient conditions following a major error method in determining the CCT of the system. The fault
disturbance [1]. Transient analysis can be divided into two duration was increased gradually using the step time of 0.01s
types: oscillatory transient and impulsive transient. Oscillatory until the system appears to be unstable by observing
transient is a sudden, non-power frequency change in the machine’s rotor angle as a reference point. The CCT is
steady-state condition and bidirectional variation in voltage, obtained by calculating the midpoint between the fault time
current or both in power line. Impulsive transient is also a when the system starts to be unstable and the time before that
sudden, non power frequency change in the steady-state (where the system still in stable state). The stability of the
condition but unidirectional variation in voltage, current or system can be observed by using the Simulation Output File,
both in power line [2]. Capacitor switching commonly embedded within PSS/E. The procedure in running transient
happens in the power system internally, leads to the oscillatory stability analysis is shown in the flowchart in Figure 1.
transient while lightning occurs externally in the system and

978-1-4577-1417-7/11/$26.00 ©2011 IEEE 521


2011 IEEE Symposium on Industrial Electronics and Applications (ISIEA2011), September 25-28, 2011, Langkawi, Malaysia

Start Magnetic saturation is excluded for clarity. In PSS/E model,


rotor speed variations are reflected in the internal voltage and
Run Load Flow Analysis
in the generator terminal current [4]. The stator resistance, Ra
Convert To Dynamic Data File is neglected and the mechanical power is the input to the
Read Dynamic Data synchronous generator. The stator flux is derived from stator
(Generator, Turbine-Governor & Exciter) currents and the exciter voltage [5]. The parameters of
Run Transient Stability Analysis Increase fault GENROU model is shown in the Table I.
clearing time
Apply Three-Phase Fault at Cleared at tct gradually TABLE I. MACHINE DATA FOR GENROU MODEL FOR SARAWAK’S GRID SYSTEM
( tct=0.01s)
Analyze Graphs Obtained

Is System Stable? YES


NO
Stop

Figure 1. Flowchart of Transient Stability Analysis in PSS/E

III. MACHINE MODELS


In conducting dynamic analysis using PSS/E to performed
transient analysis, the three most important dynamic basic
machine models such as generator, exciter and governor must
be taken into account.
B. Simplified Exciter Model (SEXS)
A. Round Rotor Generator Model (GENROU)
Figure 3 below illustrate the block diagram of simplified
In this research, the generator model used is round rotor exciter system. SEXS model represents no specific type of
machine model, GENROU for thermal generation units as excitation system, but rather the general characteristics of a
shown in Figure 2 below [4]. GENROU represent solid rotor wide variety of properly tuned excitation systems. SEXS
generator at sub-transient level. GENROU was used to model is particularly useful in cases where an excitation
produce machine speed and rotor angle for transient stability system must be represented and its detailed design is not
observation. All generator models in PSS/E ultimately present known. The gain, K, time constant, TE, and limits EMAX, EMIN,
the electric transmission network with a positive sequence are a basic representation of the excitation power source. Time
source voltage where instantaneous amplitude and phase are constants TA and TB provide the transient gain reduction
known and current is to be determined. needed to allow satisfactory dynamic behavior with high
X 'd' − X ι steady-state gain. SEXS model is the most common exciter
X 'd − X ι model used in order to perform analysis and producing
generator main field voltage, EFD. [3]
1 − 1 X 'd − X 'd' +
E fd + + + ψd
− Td' 0S − Td''0S X 'd − X ι
X 'd' − X ι
' ''
X ad I fd X −Xd d
(X 'd − X ι ) 2

+ Id
X d − X 'd +

X q − X 'q Iq
Figure 3. Simplified Excitation System in PSS/E
' ''
X −X
q q
TABLE II. EXCITER DATA FOR SEXS MODEL FOR SARAWAK’S GRID SYSTEM
(X 'q − X q ) 2
X 'q' − X ι

1 1 X 'q − X 'q'
Tq' 0S Tq''0S X 'q − X ι − ψq
''
X − Xι
q
'
X − Xι
q

Figure 2. Block Diagram of flux-current relationships of GENROU model in


PSS/E with magnetic saturation neglected.

522
2011 IEEE Symposium on Industrial Electronics and Applications (ISIEA2011), September 25-28, 2011, Langkawi, Malaysia

C. Turbine-Governor Model (TGOV1) inspect the worst condition, the same fault is applied to the
The turbine-governor models are designed to give nearest transmission line from bus 4501 to bus 9501. The
representations of the effects of power plants on power system second case study using Sarawak practical data is to inspect
stability. They are not intended to be used in studies of the the CCT during fault occurrence far from the generator.
detailed behavior of individual plants. Because of the wide Taking further transmission line connecting Grid area with
variety in the details of individual turbine controls, the PSS/E Bintulu area, the fault is applied between the bus 5501 and
models do not attempt to give a high degree of exactness for 3501. The Sarawak’s Grid network was reconstructed in
any given plant; rather they represent the principal effects PSS/E and was illustrated in the Figure 21 under appendix
inherent in conventional steam turbine, gas turbine, nuclear, section.
and hydro plants. Governor model used in this research paper
TABLE IV. SUMMARY OF MACHINE AND LOAD DATA
is TGOV1, a simple model representing governor action and
the reheater time constant effect for a steam turbine. The ratio, Bus PG (MW) QG (Mvar)
Machine 1509 101.4 -27.9
T2/T3, equals the fraction of turbine power that is developed 1101 0.0 0.0
by the high-pressure turbine. T3 is the reheater time constant, Bus PL (MW) QL (Mvar)
and T1 is the governor time constant. The TGOV1 governor Load 3101 12.2 0.0
3115 0.0 0.0
diagram is shown in Figure 4 below.

V. RESULTS AND DISCUSSIONS


In this paper, the analysis is perform in order to observe the
response of machine states in the Sarawak’s Grid data after
occurrence of three-phase fault at the respective transmission
lines. The critical fault clearing time is determined using trial
and error method in PSS/E by increasing the fault duration
time gradually using a step time of 0.01s from the minimum
Figure 4. TGOV1 governor model in PSS/E value to maximum value. The critical fault clearing time (tcct)
is obtained by calculating the midpoint between the fault time
TABLE III. GOVERNOR DATA FOR TGOV1 MODEL FOR SARAWAK’S GRID when the system starts to be unstable and the time before that,
SYSTEM where the system still in stable state. Transient stability
analysis in this research paper observes the rotor angle,
voltage, machine speed and electrical power of the respective
system.
Figure 5 to 8 shows that graph of rotor angle, voltage, speed
and electrical power at Sarawak’s Grid Network Data when
the fault occurs at transmission line near to the generator. The
fault clearing time is less that critical clearing time (tct < tcct).
After fault removal, the rotor angle seems to be settling back
IV. SYSTEM MODEL
to its original phase, and the system is said to be transiently
A. Sarawak System Network stable. The voltage, speed and electrical power also follow the
Sarawak practical data consists of 131 buses located in same phase as the rotor angle, by returning to its stable state
seven different areas in Sarawak, Malaysia. The areas covered after occurrence of a small transient due to the three-phase
are Kuching, Sri Aman, Kemantan, Sibu, Bintulu, Miri and fault.
Grid. The highest bus base kV is 275kV and the lowest is Figure 9 to 12 shows the result when the fault clearing time
11kV. The data consists of 34 machines and 65 loads. The exceeds the critical clearing time (tct > tcct). The machine’s
swing bus is bus 1509 located within the Grid area. The swing rotor angle in figure 9 will continue to go out of phase,
bus real generation power, PG after solving load flow solutions without returning to the original phase. This can be said as the
are 101.4MW and reactive power generation, QG is - network system is in unstable condition. The dynamic system
27.9Mvar. The load flow was solved using full Newton model is unable to sustain the fault and loses its synchronism.
Rhapson method and the system reached the tolerance after 3 Based on this case, the critical clearing time obtained was at
iterations. The Swing bus holds the largest power generation 0.105s. Similar to the case of fault occurrence on the line near
throughout the system. The highest and lowest real power, P the generator, figure 13 to 20 shows the result for stable and
and apparent power, Q in the Sarawak practical data is unstable condition at fault occurrence at a transmission line
summarize in Table IV below. In observing the dynamic located far from the generator. Table V and VI showed the
stability of the network system, the three-phase fault was summary of result in all three cases that was done in this
applied at two transmission lines; closest to the generator and research.
far from the generator. This method was applied to observe the
difference in CCT at two different locations. In order to

523
2011 IEEE Symposium on Industrial Electronics and Applications (ISIEA2011), September 25-28, 2011, Langkawi, Malaysia

A. Sarawak System Network (near the generator)

Figure 5. Plots of rotor angle at all generator (tct = 0.10). (Stable) Figure 9. Plots of rotor angle at all generator (tct = 0.11). (Unstable)

Figure 6. Plots of voltage at all busses (tct = 0.10). (Stable) Figure 10. Plots of voltage at all busses (tct = 0.11). (Unstable)

Figure 7. Plots of Speed at all generator (tct = 0.10). (Stable) Figure 11. Plots of Speed at all generator (tct = 0.11). (Unstable)

Figure 8. Plots of electrical power at all generator (tct = 0.10).


Figure 12. Plots of electrical power at all generator (tct = 0.11).
(Stable)
(Unstable)

524
2011 IEEE Symposium on Industrial Electronics and Applications (ISIEA2011), September 25-28, 2011, Langkawi, Malaysia

B. Sarawak System Network (far)

Figure 13. Plots of rotor angle at all generator (tct = 0.17). (Stable) Figure 17. Plots of rotor angle at all generator (tct = 0.18).
(Unstable)

Figure 14. Plots of voltage at all busses (tct = 0.17). (Stable) Figure 18. Plots of voltage at all busses (tct = 0.18). (Unstable)

Figure 15. Plots of Speed at all generator (tct = 0.17). (Stable) Figure 19. Plots of Speed at all generator (tct = 0.18). (Unstable)

Figure 16. Plots of electrical power at all generator (tct = 0.17). Figure 20. Plots of electrical power at all generator (tct = 0.18).
(Stable) (Unstable)

525
2011 IEEE Symposium on Industrial Electronics and Applications (ISIEA2011), September 25-28, 2011, Langkawi, Malaysia

TABLE V. SUMMARY OF RESULT ANALYSIS WHEN THREE-PHASE FAULT ACKNOWLEDGMENT


OCCURS NEAR A GENERATOR FOR SARAWAK’S GRID SYSTEM
The financial assistance of the Faculty of Electrical
Faulted line Fault Duration (sec) Stability
0.10 Stable
Engineering, Universiti Teknologi MARA is greatly
4501-9501 0.105 tcct appreciated.
0.11 Unstable
REFERENCES
TABLE VI. SUMMARY OF RESULT ANALYSIS WHEN THREE-PHASE FAULT [1] K.C. Tham, "Power System Stability", Information Technology
OCCURS FAR FROM THE GENERATOR FOR SARAWAK’S GRID SYSTEM and Electrical Engineering, University of Queensland, pp. 1-109,
2003.
Faulted line Fault Duration (sec) Stability
[2] P. Kundur, "Power system stability and control", New York: Mc-
0.17 Stable
Graw-Hill, 1994
5501-3501 0.175 tcct
[3] Siemens, "Program Application Guide, Volume II for PSS®E
0.18 Unstable
Version 32.0", Siemens Power Technologies International, 2009.
[4] “PSS/E 25, On-line Documentation”, Schenectady, US: Power
Technologies, Inc., December 1997.
VI. CONCLUSIONS [5] J.G Slootweg, "A Study of the Eigencalur Analysis Capabilities of
Power System Dynamics Simulation Software", Department of
This research paper conducts a transient stability analysis Electrical Engineering, Royal Institute of Technology, Stockholm,
on Sarawak’s Grid data system. The response of transient Sweden, June 2002.
stability was observed using PSS/E simulation package, based [6] P.K. Iyambo, R. Tzoneva, "Transient Stability Analysis of the
on machine’s rotor angle, terminal voltage, speed and also IEEE 14-Bus Electric Power System", AFRICON 2007, pp. 1-9,
2007
electrical power. Sarawak’s Grid data was used to clarify the [7] H. Li and Z. Chen, "Transient Stability Analysis of Wind Turbines
theory said that the line far from a major generator held a with Induction Generators Considering Blades and Shaft
longer CCT. This paper proves the theory by applying the Flexibility", 33rd Annual Conference of the IEEE Industrial
same three-phase fault at two different transmission lines; one Electronics Society, 2007. (IECON 2007), pp. 1604-1609, 2007
[8] A. M. Mihirig and M. D. Wvong, "Transient Stability Analysis of
nearer the generator and another far from the generator but Multimachine Power Systems By Catastrophe Theory", IEE
within the same area. The results showed that CCT near the Proceedings C Generation, Transmission and Distribution, , vol.
generator is 0.105s and CCT far from the generator is 0.175s. 136, pp. 254-258, 1989.
Thus the theory is proven.

APPENDIX

FIGURE 21.SARAWAK’S GRID MODEL IN PSS/E

526

You might also like