Model Number SLP1 Threshold Test SLP2 Thresh

SEL- 787 Minimum IRT = 1.30 Minimum IRT =


Selected IRT = 2.00 Selected IRT =
Relay Settings SLP1 Threshold Values SLP2 Thresho
W1CT = WYE Current Magnitude (A) Angle (deg) Current
W2CT = WYE IAW1 7.32 0 IAW1
CTR1 = 80 IBW1 7.32 -120 IBW1
CTR2 = 160 ICW1 7.32 120 ICW1
MVA = 28 IAW2 5.49 -210 IAW2
VWDG1 = 34.5 IBW2 5.49 -330 IBW2
VWDG2 = 13.8 ICW2 5.49 -90 ICW2
W1CTC = 0 SLP1 Initial Values SLP2 Initial
W2CTC = 1 Current Magnitude Angle Current
TAP1 = 5.86 IAW1 7.32 0 IAW1
TAP2 = 7.32 IBW1 7.32 -120 IBW1
O87P = 0.3 ICW1 7.32 120 ICW1
SLP1 = 25 IAW2 6.86 -210 IAW2
SLP2 = 60 IBW2 6.86 -330 IBW2
IRS1 = 3 ICW2 6.86 -90 ICW2
PHROT = ABC
SLP2 Threshold Test
Minimum IRT = 3.10
Selected IRT = 4.00
SLP2 Threshold Values
Magnitude (A) Angle (deg)
15.67 0
15.67 -120
15.67 120
9.70 -210
9.70 -330
9.70 -90
SLP2 Initial Values
Magnitude Angle
15.67 0
15.67 -120
15.67 120
10.67 -210
10.67 -330
10.67 -90