You are on page 1of 8

Partial discharges in HV machines; initial

considerations for a PD specification

J.W. Wood
H.G. Sedding
W.K. Hogg
I.J. Kemp
H. Zhu

Indexing terms: Electric discharges, Generators, Motors

1 Introduction
Abstract: Partial discharge (PD) specifications
exist for all types of electrical equipment except Partial discharge (PD) acceptance tests are now applic-
motors and generators. Whereas specifications able to most HV power equipments. For example:
essentially require that the equipment is discharge-
free the stator conductor bar insulation of the
gas insulated switchgear (GIS) [l] < 2-5 pC
bushings [a] < 1opc
motors and generators under consideration is < 5 pC at 1.5 U N
cables [3]
micaceous and has excellent PD resistance. Conse- < 300 pC at 1.3 U N
quently, the intention in a specification would be transformers [4]
to permit a certain level of PD. It is therefore par-
< 500 pC at 1.6 UN
ticularly important that the problem of over- where U, = nominal voltage. Some years ago at the sug-
coming the attenuation between the PD site and gestion of a user, Ontario Hydro, collaborative work
the measurement equipment at the winding ter- began with Parsons Turbine Generators, a manufacturer,
minals be solved. Within the general context of to investigate the possibility of developing a PD test spe-
examining the feasibility of a PD specification, the cification to apply to HV generator and motor stators,
problem of PD signal attenuation is addressed. which is the last area of power equipment to require spe-
The approach adopted was to seek a region of low cifications to be defined.
attenuation by examining the whole of the pos- The probability of a ‘true’ insulation failure initiating
sible range of PD measurement frequencies. The from a PD within a high-voltage machine is small.
investigations described consist of experiments on However, machine users would welcome the introduction
a full-size 500 MW endwinding model and on two of an acceptance test for economic reasons [SI. When an
large high-voltage motor windings. Careful screen- outage is required in service, the costs can easily exceed
ing to reduce radiative pick-up from the cali- E100OOO per day for a base-load nuclear unit. Added to
bration generator simulating a PD source and a this are maintenance and perhaps extensive refur-
direct earthing scheme enabled the essential ele- bishment costs. Consequently, there is a strong desire to
ments of PD pulse transfer through a winding to reduce maintenance costs by ensuring that the machine
be determined. The frequencies investigated has been correctly manufactured and serviced. An over-
ranged from kHz to GHz. Pulse transmission and voltage test does not necessarily guarantee this. An arbi-
frequency spectrum measurements were made. It trary PD specification would not be acceptable to a
is concluded that the PD pulse transmits essen- supplier. However, suppliers recognise that failures affect
tially as a travelling wave, the high-frequency their reputation and this is of prime concern. An accept-
components being highly attenuated. No signifi- ance test might additionally enable important design
cant crosscoupling was apparent through the end- improvements to be achieved, e.g. operation at higher
winding region. The windings acted as a low-pass electrical stresses.
filter, the cut-off frequency being dependent on the The setting of a PD specification for stators is a
winding length, and being below 1 MHz. Conse- complex undertaking and involves theoretical and experi-
quently, it is concluded that it should be possible mental studies. At the start of the project there were
to measure PD, using equipment with a passband several problems to be solved before this could be
below the low-frequency cut-off, with low atten- attempted; some of these exist now in the instances above
tuation. where PD acceptance tests have been established. In

0IEE, 1993
Paper 9651A (S2), first received 9th February and in revised form 11th
This contribution has been assembled from experi-
May 1993 mental work at Ontario Hydro, Parsons Turbine
J.W. Wood is with the Generator Design Department, Parsons Turbine Generators and Glasgow Caledonian University,
Generators Ltd., Heaton Works, Newcastle on Tyne, NE6 2YL, UK and from discussions with B.K. Gupta and G.L.
H.G. Sedding is with the Ontario Hydro Research Division, 800 Ford at Ontario Hydro and G.C. Stone at Iris
Kipling Avenue, Toronto, Ontario, Canada M8Z 5S4 Power Engineering. Some components of the cali-
W.K. Hogg is at 32A Offington Lane, Worthing, Sussex, UK bration work were supported by the Electric
I.J. Kemp and H. Zhu are with the School of Engineering, Glasgow Power Research Institute under RP2577-1.
Caledonian University, Cowcaddens Road, Glasgow, G4 OBA, UK

IEE PROCEEDINGS-A, Vol. 140, NO.5 , SEPTEMBER 1993 409


general, the problems can be categorised as circuit has been used to inject pulses into various posi-
(a) types of PD tions in a winding to calibrate it for discharge at various
(b) calibration positions. The calibration aspects raised were an import-
(c) stator winding attenuation and resonance effects. ant part of the considerations that laid the basis for the
work undertaken, see Section 1.4.
1.1 Types of partial discharge The basis of a calibration technique is a model for a
In any particular piece of power equipment different discharge in a test object. Although the three-capacitor
types of discharge can occur, depending on the insulat- model of Fig. 1 has been accepted for many investigators
ing materials used and the construction of the equipment.
Discharges that influence the working life of the insula- lectrodes
tion of the equipment are of concern. The effect on the
insulation of a discharge of a given magnitude will differ
for different insulations. For example, various types of solid insulation
discharge that could occur in oil/paper transformer insu- in series with void,C2
void, C,
lation have been identified and studied [6]. Not all of solid imulaton
these are damaging to the same degree. Also the sensi- in parallel with void,C3
tivity of discharge detection techniques for GIS has been
questioned [11 because experience in service has indi-
-=
cated discharges of 1 pC may be causing failures. Mica- a

ceous insulation of the type used for high-voltage


generators and motors [7, 81 has a high discharge resist-
ance [9, lo]. Discharges in the bulk insulation of magni-
tudes of several thousands of picocoulombs can be
tolerated for the entire design life of the insulation, 25
years.
More than just the occurrence of discharge can be
inferred from discharge measurements. The number of b
discharges per cycle, their amplitude and polarity with Fig. 1 Three-capacitor model for discharge
respect to phase position in an applied voltage cycle and a Idealised cavity in solid insulation
their variation with time can provide information from b Equivalent circuit
which the nature, form, extent and sometimes location of
degradation can be inferred [l 11.
Partial discharge tests are not definitive because not and is still a reasonable approximation for many practi-
enough is known about the various types of PD which cal measurements, the accuracy of representation has
exist and their long-term effect on insulation. Despite the recently been question [l, 141. This aspect is common to
wisespread use of PD measurements, there are as yet no all PD measurements and is regarded as outside the
definitive studies available which demonstrate direct scope of the paper.
correlation between PD characteristics and breakdown
voltage or remanent life. PD tests are therefore QC tests 1.3 Attenuation effects
based partly on research and partly on service experience. With a capacitive, i.e. lumped parameter, test object the
The basis of a specification has been essentially that the measured discharge signal amplitude is affected by the
equipment should be discharge free at working voltage, capacitances of the test object and coupling or blocking
and the levels set are governed by practically achievable capacitor used for a given detector impedance. Cali-
sensitivities. This is under reconsideration in the case of bration by the IEC method enables the correct discharge
GIS [l] and it would not be a suitable basis for setting a magnitude to be determined and only sensitivity is
level for generators and motors. affected. A similar effect occurs with a test object that is a
We feel that there is sufficient knowledge of the types distributed network. However, in this instance the effec-
of PD that can occur in generators and motors and their tive capacitance will depend on measurement frequency
effect for this not to inhibit and setting of a provisional and bandwidth. This is one form of discharge signal
PD specification, given the situation for other equipment attenuation that can occur.
where specifications exist. Moreover, other matters need Of much greater difficulty to overcome is the fact that
to be investigated before the feasibility of setting a specifi- a discharge signal coupled into a winding from a dis-
cation could be assessed. charge site will undergo attenuation and reflection on its
passage to the measurement terminals. Kemp et al. [151
1.2 Calibration reported no consistency in measurements on motor coils,
Calibration is an essential part of any PD test. The parallels and complete phases using different bandwidth
recommended method of calibration [12, 131 involves discharge detectors, nor indeed with a given bandwidth
injection at the terminals of the test object. Certain con- detector when the discharge source or pulse injection
ditions, e.g. of calibration generator output pulse rise point was varied with respect to the measurement point.
time, have to be fulfilled for the method to be valid. A frequency response analysis of the windings indicated a
Stator windings of generators and motors must be con- spectrum consisting of peaks and throughs whose charac-
sidered as distributed parameter networks rather than teristic depended on the propagation distance. This con-
lumped parameter ones. The Standards documents do trasted with the response for the calibration impulse
not differentiate between these. However, discharge which was, as would be expected, essentially flat across
signals from within the stator winding propagate to the the frequency spectrum. It was clear that detector band-
measurement terminals and experience attenuation, res- width, centre frequency, and the nature and length of the
onance and other effects. These effects are discussed in pulse propagation path through the winding would
further detail subsequently. In this instance, a calibration greatly affect accuracy of measurements.
410 IEE PROCEEDINGS-A, Vol. 140, N O . 5 , S E P T E M B E R 1993
1.4 PD specification considerations wound motor winding for insulation design purposes.
One of the most important factors is that of attenuation They point out that in general a winding must be con-
of discharge signal through the stator winding and how sidered as a multiconductor network. Shorted-turn detec-
to calibrate the measurement circuit in this instance. This tion techiques for generator rotors have been described
was therefore the problem to investigate first. Whereas by Wood [18]. The recurrent surge oscillograph tech-
the means of solving this problem has been seen as nique makes use of the travelling wave set up by applying
requiring a winding calibration and some technique of a step pulse to the winding. A simple analysis of wave-
locating a discharge site to enable the true discharge forms based on reflections at shorted turns usually suf-
magnitude to be estimated, the authors adopted an alter- fices but more detailed studies of pulse propagation [19]
native approach. This was to examine the frequency spec- showed that a multiconductor approach was necessary to
trum over an extremely wide range, from kHz to GHz to understand the waveforms observed.
determine whether there is, in general, a frequency band In a practical investigation of discharge detection tech-
where attenuation and resonance effects are relatively niques for stator windings, Wilson et al. [20] investigated
small. Whereas an empirical approach might have suf- pulse propagation in a 6.6 kV motor stator (rotor
ficed, it was regarded as essential that experiments be removed). They reported the presence of two forms of
undertaken to clarify methods of propagation of dis- pulse components at the measurement terminals follow-
charge signal through a winding. Hopefully, a model ing injection of fast risetime, discharge simulating pulses.
could be developed which could be used to predict These two forms consisted of a fast pulse component fol-
behaviour or at least support generalisation of the results. lowed some time later by a slower pulse component with
Significant progress has been made in understanding its arrival time increasing with distance between the
the modes of propagation of a PD signal and towards injection point and the measurement terminals. Measure-
identifying a suitable frequency range for measurement. ments of a similar type made on a 500MW generator
The research which led to this is described. Three main stator produced essentially similar results. It was con-
areas for consideration to lead to a discharge specifi- cluded that the fast pulse coupled through the endwind-
cation were identified : ings and the slow pulse propagated in series mode
(i) measuring frequency range, discharge signal transfer through the windings. In addition to these investigations,
mechanisms and associated requirements for calibration which were carried out using a wideband detector (0-
(ii) test details 17 MHz), they also investigated the effect of different
(iii) acceptance levels. bandwidths on detection. Using four different detector
bandwidths, they reported that wideband detection
The position taken was that unless (i) could be satisfact- (20 kHz-3 MHz) could produce a 27 dB attenuation in
orily resolved, it was not worthwhile proceeding to a the detected signal from different injection site locations
detailed study of (ii) and (iii). This paper is confined to with the same injection pulse. Also, they reported a 24 dB
reporting the results of the study into (i), although aspects attenuation in the detected signal from the same injection
(ii) and (iii) are considered briefly in the general dis- location using the different bandwidth detectors. It is
cussion. Before describing the experiments undertaken, a clear from their results that the propagation of the dis-
summary of previous investigations is given. charge pulse to the measurement terminals can change its
characteristics quite radically. This, in turn, can lead to
2 Background to discharge signal propagation erroneous measurements of discharge pulse amplitude
studies dependent on the extent of pulse modification in propa-
Among the machine factors which may be considered to gation, which is principally a function of distance
affect measured discharge signal at a terminal are between the discharge source and the position of the
(a) stator winding geometry
detector and the effect of detector bandwidth/centre fre-
(b) multiturn coil and Roebel bar constructions quency.
(c) effect of materials of stator construction
Geary et al. [21] investigated the effect of pulse
(d) coupling impedances injection/detection distances on the obtained response for
(e)cross coupling of PD pulses a 6.6 kV stator (rotor removed). They reported the results
(f) effect of transition of the bar/coil from slot to free to two types of experiment. In the first, discharge simulat-
space. ing pulses were injected at one phase terminal of the
winding and the pulse response at intercoil links increas-
It is impractical to undertake a controlled series of ingly distant from the injection point were noted. In the
experiments in the laboratory in which these parameters second, discharge simulating pulses were injected at dif-
are varied to determine the effect of each. Machines of ferent locations and detected at the phase terminal. They
different types contain such variations and since the ulti- too reported the presence of fast and slow pulse com-
mate objective is to understand the behaviour of a ponents. The fast ‘radiative’ pulse was noted to arrive at
variety of machines it was pertinent to both review pre- the measurement terminals at a time independent of
vious such work and undertake the experiments on such injection location, whereas the slow component arrived
machines. at times dependent on distances propagated and consist-
Regarding theoretical (combined with empirical ent with a fixed propagation velocity through the
validation) approaches, Makin [16] examined the winding. They also showed the relationship between the
theoretical response of a simple distributed network to a relative magnitudes of the fast and slow components and
step pulse. Although this was related to impulse tests on the rise/falltime of the injected pulse. As the pulse rise-
transformers the analysis has relevance to a stator time was increased, the fast component decreased in mag-
winding. Makin concluded that frequencies below a nitude relative to the slow component and, indeed,
certain critical frequency were transmitted as a travelling eventually disappeared when the risetime was > 100 ns.
wave. Above the critical frequency the signal is distrib- This work has been extended by Zhu and Kemp [22].
uted capacitively. McLaren et al. [17] have studied the Sedding et al. [23] have observed actual and simulated
distribution of surge voltages in the first coil of a form discharge pulse propagation by a travelling-wave
IEE PROCEEDINGS-A, Vol. 140, N O . 5, SEPTEMBER 1993 41 1
mechanism using a wideband technique extending into Table 1 : Cable characteristics i
the GHz frequency range. This is the basis for a new Length 100 m
method of monitoring PD in service in a stator winding, Impedance 75 n
the stator slot coupler. Thus there is evidence of pulses Capacitance 67 pF/m
Attenuation 0.61 dB at 100 MHz
with very high frequency components propagating as 1.13 dB at 300 MHz
per
travelling waves within a winding. 10 m 1.70 dB at 700 MHz
Makin [16] also considered magnetic effects and 23.1 dB at 1000 MHz
deduced there were no flux-linking turns, other than
through air, above a frequency of approximately 50 kHz that the discharge source impedance did not affect wave-
because of the skin effect in the iron core. Tavener et al. shape.
[24] investigated magnetic coupling of discharge signals
and considered there could be significant coupling due to 3.2 Experiments on 500 M W stator model
this mechanism up to 20 MHz, depending on the PD The purpose of these tests was to investigate the mechan-
location and geometry. Coupling could occur through isms by which the discharge pulse signal can couple to
mutual inductance in the endwinding region, and also the measuring circuit. Radiative, capacitive, travelling
between bars in the same slot. Consequently, it was wave and magnetic couplings were investigated. The
necessary to investigate pulse propagation effects experi- physical layout of the model and measuring arrange-
mentally partly to clarify some of the differences sug- ments used are shown in Fig. 3. Pulses were injected from
gested by previous workers. a 5 ns risetime pulse generator through a small, low
inductance, capacitor. The input and output waveforms
3 Experimental investigations were observed and recorded on an oscilloscope having a
passband up to 300 MHz. A discharge detector with
Three sets of experimental investigations have been
undertaken, categorised as measuring lead
CROx10 atten probe endwinding half-length conductor
(a) fundamental experiments on a cable arrangement \ stress Daint bar with full endwindim
(b) fundamental experiments on a 500 MW model
arrangement of six half length conductor bars
(c) fundamental experiments on generator and motor model core
stator windings undertaken in the UK and Canada.
measmment earth
Preliminary conclusions have been drawn from the strip
results of these experimental investigations and have connected hollow
conductors
resulted in a decision to undertake a major investigation ~~$~~~ endwinding support
of type (c) on a large sample of machines in Canada in (brackets and cone)
1992.This study is expected to conclude the experimental injection capacitor region of screening
investigation. a

3.1 Experiments on a cable


Experiments by Kemp [l5] had shown that detector stator winding slots
\ ~

impedance can significantly effect the measured discharge bar positions


signal since the winding impedance is a function of fre- (whenin)
quency. The tests on a cable arrangement, which approx-
imates to a loss-free transmission system, were made to
examine whether the calibration impedance or an actual b
discharge arrangement represents a substantial mismatch Fig. 3 Measuring arrangements for pulse tests on 500 M W model
in the system. The cable was used to simulate a stator (I Side view of model

winding as a transmission line with respect to the trav- b Cross-section of model core
elling wave component of the discharge signal.
detection frequencies from approximately 35 to 250 kHz
A typical arrangement was as shown in Fig. 2. The was used in certain instances to obtain a relevant quant-
cable details are given in Table 1. Matched junctions with iative measure of discharge signal attenuation. The six
unequally spaced cable lengths between them enabled conductor bars (three top and three bottom bars) have
waveforms to be closely studied for evidence of reflections epoxy mica paper insulation and a low conductivity
from the injection point. No significant reflections were coating on their outer surface covering the model core
observed with the IEC method of injection. With a length (approximately 1 m); total length of each half bar
Trichel pulse generator (point-hemisphere gap) attached from one end (stator centre line) to endwinding nozzle is
to the energised cable no photographic records could be approximately 5 m.
obtained, but a similar conclusion was reached from
visual observation of waveforms on the CRO in so much When experimentation began radiative pickup was
found to be signficant. Fig. 4a shows the signal level on a

a
35m 40m 25m
short (1 m) length of conductor bar approximately 3 m
i i away from the injection point, lying on the earthed floor
I I plane. An unexpected amount of screening, six layers of
aluminium foil, was necessary to reduce the signal picked
up to an acceptable level. As appropriate to the experi-
mental condition the bars in the model were screened to
this degree to ensure accurate measurements were being
_L made. Fig. 4b shows the coupling from individual bars
designated A and B in the model with and without
Fig. 2 Measuring arrangements for cable pulse tests screening of bar B (which affects A transmitted pulse
412 IEE PROCEEDINGS-A, Vol. 140, NO. 5 , S E P T E M B E R 1993
waveshape). An example of the measurement logic is that connected via a coupling capacitor to the other, the
by joining at their nozzle positions two fully screened top detected signal varied with spacing as shown in Fig. 5.
bars situated in the same slots as two similarly screened
bottom bars it was possible to examine any pickup due
to common magnetic flux. No evidence of any significant
pulse coupling was observed. Fig. 4c shows a typical
example of propagation by travelling wave in which the
peak pulse amplitude is reduced as the wave progresses
-1 0
1
along the bar.

1 - 50 1
0 0.25 0.5 0.75 1.00 1.25 1.5 1 '5
endwinding separation, mm

Fig. 5 Attenuation of endwinding coupled signal (35-250 kHz


detector)

3.3 Experiments on complete stators


The work to be described utilised experimental tech-
a niques developed and reported over a number of years in
discharge detection studies undertaken in Canada [25-
271. Those earlier studies have involved pulse propaga-
tion in stator windings using a variety of time- and
frequency-domain techniques but were not undertaken
specifically for the purpose to which the present work
was applied although they do help to validate the results
and the conclusions reached. The experiments described
to examine winding behaviour were undertaken on two
large high-voltage motor windings in the laboratory and
they illustrate winding behaviour. One major benefit of
experimenting on a motor no longer in service was that
electrical connections could be made into the stator bars
and core at injection and detection points to ensure that
excellent high-frequency connections and earths were
b obtained. We are continuing work to gather similar
results from a substantial number of other machine wind-
ings.
One set of experiments described here were performed
on a 6.9 kV induction motor winding (motor A). The
other on a similar operating voltage machine with a dif-
ferent winding arrangement (motor B). The winding of
motor A is configured as four parallel paths per phase,
five coil groups/parallel, three coils per group, and six
turns per coil. Fig. 6 shows part of the winding arrange-
ment with injection/detection points. For pulse transmis-
sion experiments a repetitive pulse generator with a
risetime of 1 ns was used; pulse widths of down to 1 ns
C
A2-2 A 2 -5
Fig. 4 Results of pulse tests on 500 M W model A2-1 A2-3 A2-6 A2-4
a Top: pickup on short bar on floor outside model; Bottom: input to bar A in
model
b Top: pickup on unscreened bar B in model; Bottom: pickup on bar B in model
with effective screening on bar B
c Top: input pulse on bar A; Bottom: transmittedpulse out nozzle at bar A

The effect of direct coupling between endwinding con-


to next group
ductors was examined. The endwindings of large
-b
machines follow an involute curve to minimise generator
size, and are designed to have a specific space between
phase end
them for mechanical bracing purposes. However, in the
500 MW model the spacing could be varied by moving Fig. 6 Location of injection and detection points in stator winding of
one bar axially. This did not significantly affect the area motor A
over which coupling could occur. With a calibration A: A-phase; 2: second parallel; -1: winding number; 0 (A2-1): detection point;
2 , 3 etc.: injection points; first group: A2-i, A2-2, A2-3; second group: A2-4,
pulse injected into one bar and the discharge detector A2-5, A2-6

IEE PROCEEDINGS-A, Vol. 140, N O .5, SEPTEMBER 1993 413


could be achieved. For frequency domain measurements A2-3 injection points. The frequency characteristic below
three types of spectrum analysis were initially compared 10 kHz also has a flat transmission characteristic
(i) Spectrum analyser: A spectrum analyser with a
1.8 GHz built-in tracking generator was used. A tracking >
generator is a swept oscillator running at the observation F
>
E
frequency of its matched spectrum analyser. 0
(ii) FFT calculation: A pulse may be injected into a 0
a;
certain location in the stator winding as an input signal
and the response detected at another location as output -3
0

signal. A FFT calculation is applied to both input and timebase 50 nsldiv


output signals to obtain their frequency spectra and the a
ratio at any frequency gives the attentuation.
(iii) Sine wave sweeping: A sine wave generator was 5.
u
used to generate a series of sine waves at particular fre- s
E
quencies at the injection point. The magnitude of the 0
U
response at the detection point is recorded to give the a;
attenuation. -
0
-0
The spectrum analyser measurement was finally chosen
as the main test method for frequency domain studies on
timebase 50 nsldiv
motors A and B due to its high accuracy, wide frequency
b
band (10 kHz to 1.8 GHz) and easy operation.
In both pulse propagation and frequency domain >
-
measurements the input to the winding was matched to
the winding impedance via a specially designed connec- 2
E
0
tor. The response signal was detected in either instance R
by a FET probe. The FET probe and its coaxial cable ai
have a flat amplitude response characteristic to 1 GHz -3
c

0
which assures signals in that frequency band are trans-
mitted without distortion. timebase 500nsldiv
The form of the detected signal as a simulated dis- C
charge pulse progresses from an injection point around Fig. 8 Voltage induced in adjacent endwindingsfrom discharge simu-
one coil of motor A is shown in Fig. 7. In this instance lated in endwinding ofA2-I, motor A
a Applied voltage
IA 6 b Induced voltage
c As above, with slower sweeps
> (i) A2-1; (ii) A2-2; (iii) A2-3; (iv) A2-4
e
> 20
E
R 10
al
m 0
-?
c
0
U

U
a J -.1 0

I
= -2 0
I I I ul
I I I I E - 30
4 0 ~
.50 I I iiiiiii I I IIIIIII i iiiiiiii -T MII I
I IIIIIII
lo4 lo5 lo6 10’ lo8 lo9
frequency,Hz
a
20
10
m
u 0
5
u -10
=c - 20
E - 30
LO
50
1o4 lo5 1o6 td lo9
frequency,Hz
b
Fig. 9 Motor A stator winding frequency characteristics
a Injection points: 6 of A2-1, A2-2, A2-3
Detection point: 0 of A2-1
-A2-1 _______ A2-2
-A2-3
-A2-4 - _ _ _ _ _A2-5
_ A2-6~

b Injection points: 5 of A2-4, A2-5, A2-6


Detection point: 0 of A2-1

IEE PROCEEDINGS-A, Vol. 140, N O .5, SEPTEMBER 1993


although this is not shown in Fig. 9. The flat character- magnitude. To demonstrate the accuracy of the experi-
istics indicate that the signals in this frequency band pro- mental measurements described the simulated discharge
pagate as components of a travelling wave without loss pulse was reconstructed from the detected pulse using the
and reflection. The overshoot resonance frequency shifts appropriate, previously measured, transfer functions. This
lower as the discharge signal travels through more of the is illustrated in Fig. 11 for injection at points 6 (A2-1)
winding. and 5 (A2-2), detection being in both instances at the
There is severe attenuation of high-frequency signals in phase terminal, 0 (A2-1).
stator windings. High-frequency signal attenuation may
be clearly observed and quantitatively shown in different
frequency ranges in the winding frequency characteristics.
Signals start to attenuate above the cut-off frequency and
may attenuate typically 30 to 40 dB.
There are a number of resonances in high frequencies
above 10 MHz. There is another broadband overshoot
resonance peak between the frequencies 40 and 100 MHz.
The magnitude of this overshoot resonance peak as well
as that of the first one is over 0 dB i.e. signals may be
highly amplified instead of attenuated. This result is con- 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140150
sistent in the resonance frequency bands with that of tirne,ns
Kemp et al. [l5]. a
The frequency characteristics for the winding of motor
B are shown in Fig. 10. They show a similar region of
low attenuation exists in the low-frequency region.

40 60 80 100 120 U0 160 180200220240260280300320340360


t Irne,ns
b

1 oL lo5 106 lo7 108 io9 Fig. 11 Pulse reconstruction


frequency, Hz a Injection point: 6 (A2-1)
a
Detection point: 0 (A2-1)
b Injection point : 5 (A2-2
Detection point: 0 (A2-1)
____---real PD pulse
__ reconstructedPD
--_- detected PD

4 Discussion

4.1 Pulse propagation studies


The laboratory experiments in a 500MW model were
designed to investigate mechanisms of discharge pulse
transfer. When extensive precautions were taken to
prevent radiative coupling of signal from injection to
frequency,Hz detection points no significant magnetic coupling of
b signal could be observed. Capacitive coupling in the end-
Fig. 10 Motor B stator winding frequency characteristics winding region was not significant.
a Injection points: 6 of C3-1, C3-2, C3-3 When experiments were undertaken on a large motor
Detection point: 0 of C3-I with a good high-frequency earth connected directly to
-c3-1 _ _ _ _ - -C3-2
- -3c-3
b Injection points: 6 of C3-4, C3-5, C3-6 the core at the injection and detection points it was
Detection point: 0 of C3-1 observed that the injected pulse coupled predominantly
-c3-4 _ _ _ _ - -c3-5
- ~ C3-6
by a travelling-wave mechanism. Even for injection in the
The transfer function of the whole system from dis- endwinding region low levels of crosscoupling were
charge site in the winding to instrument output can be observed.
split into various subtransfer functions. For example, In these comments we distinguish between what we
transfer functions for the part of the winding between dis- term capacitive coupling which instantaneously induces a
charge site and winding phase terminal, for the measur- voltage in a conductor which then can propagate in it as
ing circuit, and for the measuring instrument. Exactly a travelling wave, and electromagnetic coupling which
how the split is done should not affect the overall transfer occurs from a conductor with a travelling wave in it
function provided all subtransfer functions are included. coupling another travelling wave in time synchronism
The winding itself can be viewed as comprising a number into an adjacent conductor (classic two-wire transmission
of subtransfer functions. Only those subtransfer functions line). As a consequence we find that a discharge signal
of the winding between the discharge site and the propagates through a stator winding significantly only
measurement terminal affect the measured discharge through a travelling-wave mechanism. Thus it should be
IEE PROCEEDINGS-A, Vol. 140, NO. 5, SEPTEMBER 1993 415
possible to construct a model based on the foregoing as 2 ‘Bushings for alternating voltages above 1OOOV’. IEC publication
has been done for surges. 137,1984
3 BS 6622: 1991 ‘Specification for cables with extruded cross-linked
The winding frequency response characteristics polyethylene or ethylene propylene rubber insulation for rated volt-
obtained show that there is a frequency region of low ages from 3800/6600 V up to 19000/33000 V’
(zero) attenuation. This lies between 10 kHz and several 4 WOOD, J.W.: ‘Assessment of machine and transformer insulation’.
hundred kilohertz for practical purposes. Winding reson- IEE colloquium on Insulation diagnostics, March 1991, digest 070
pp. 611-614
ances occur at higher frequencies and their values depend 5 SEDDING, H.G.: ‘The partial discharge calibration problem in
on winding type and geometry, i.e. winding, coil length, rotating machines’. Proceedings of IEEE Winter power meeting
core length, etc. 1992, Panel session 92TH0425 9PWR, pp. 24-28
These provisional findings need to be backed by an 6 WOOD, J.W., HICKLING, G.H., HINDMARCH, R.T., and
extensive programme of measurements on a wide range RAJU, B.P.: ‘Electrical and ultrasonic characteristics of partial dis-
charges in oil immersed insulation’. IEE conference publication 129,
of machine sizes to establish their general validity. 1975, pp. 28-31
7 NEAL, J.E., and SCARLETT, E.: ‘The progress in resin-rich insu-
4.2 PD specification lating materials for use in HV rotating machines’. Presented at 11th
It is not the purpose of this Section to discuss a PD spe- conference on Electrical and electronics insulation, Chicago, USA,
1973
cification in detail, rather to identify some of the param- 8 BRITSCH, H., and SCHULER, R.: ‘Micadur-Compact, a fully
eters that need to be fixed. The feasibility of setting a impregnated stator insulation for HV machines’, Brown Boueri Rev.,
specification, we believe, has been established by the Sept. 1967, pp. 531-538
work done, but it will take a considerable amount of time 9 WOOD, J.W., RYDER, D.M., and HOGG, W.K.: ‘Discharge
and effort to agree details. The form of the test will be studies of epoxy/mica turbine generator insulation’. Presented at
IEEE PES winter meeting, 1973, paper T73-118-7
determined by the objective, which is to ensure that the 10 RYDER, D.M., WOOD, J.W., and HOGG, W.K.: ‘The deterio-
electrical insulation of the equipment is satisfactory when ration of mica under the action of electrical discharge’. Presented at
the new or refurbished machine leaves the manufacturer’s IEEE PES winter meeting, 1975, paper T75-214-2
factory. Among the parameters to be fixed are 11 KREUGER, F.G.: ‘Recognition of discharges’, Electra, 1970,
pp. 61-98
(a) test voltage and duration 12 ‘Partial-discharge measurements’. IEC publication 270,1968
(b) duration and amplitude of any voltage applied to 13 ASTM ‘Method of detection and measurement of partial discharge
condition the stator (Corona) in evaluation of insulation systems’, standard D1868-81,
(c) winding configuration (single, all three phases or 1990
both) 14 PEDERSEN, A., CRIGHTON, G.C., and McALLISTER, I.W.:
‘The theory and measurement of partial discharge transients’, IEEE
(d)gaseous environment Trans., 1991, El-26,(3), pp. 487-497
(e) quantity/quantities to be measured 15 KEMP, I.J., GUFTA, B.K., and STONE, G.C.: ‘Calibration diff-
(f)acceptable values and range of quantities to be culties associated with partial discharge detectors in rotating
measured and permissible error machine applications’. Proceedings of 18th converence on Electrical
and electronic insulation, Chicago, USA, 1987, pp. 92-97
(g) calibration method, which should be capable of 16 MAKIN, A.W.: ‘Surges in transformer windings’. PhD thesis,
being performed between terminals to determine London University, 1952
maximum attenuation for a particular winding. 17 McLAREN, P.J., and ORAEE, H.: ‘Multiconductor transmission
line model for the line end coil of large AC machines’, Proc. IEE B,
1985,132, pp. 149-156
18 WOOD, J.W., and HINDMARCH, R.T.: ‘Rotor winding short
5 Conclusions detection’, Proc. IEE B, 1986,133, (3), pp. 181-189
19 HINDMARCH, R.T., and WOOD, J.W.: ‘Developments in detect-
The discharge pulse in a generator or motor stator ing interturn shorts in generator rotors using the RSO technique’.
winding propagates only significantly as a travelling Fifth international conference on Dielectric materials, measurements,
and applications, Canterbury, Kent, 1988
wave. Very high frequencies, hundreds of megahertz to 20 WILSON, A., JACKSON, RJ., and WANG, N.: ‘Discharge detec-
gigahertz, are highly attenuated. tion techniques for stator windings’, Proc. IEE B, 1985, 132,
The winding of a generator or motor stator acts as a pp. 234-244
low-pass filter. There will, in general, be a region at low 21 GEARY, R., KEMP. LJ., WILSON, A., and WOOD, J.W.: ‘Pulse
propagation characteristics of partial discharge pulses in electrical
frequencies where attenuation is low. This low-frequency machines’. Proceedings of sixth BEAMA international conference
range is the only one suitable for measuring discharge on Insulation, Brighton, UK, 1990, pp. 218-222
from the point of view that attenuation will be low. A 22 ZHU, H., and KEMP, I.J.: ‘Pulse propagation in rotating machines
simple terminal-to-terminal calibration should suffice to and its relationship to partial discharge measurements’. Proceedings
determine winding attenuation. A method has to be of IEEE international conference on Electrical Insulation, Baltimore,
MD, USA, 1992, pp. 41 1-441
defined. 23 SEDDING, H.G., KLEMPRER, G. KAPLER, J., CAMPBELL,
Ultimately it should be possible to model a stator S.R., STONE G.C., and KINGSLEY, A.: ‘A new on-line partial dis-
winding and determine the winding frequency response charge test for turbine generators’. CIGRE paper, 11403,1992
characteristics from machine materials and dimensions. 24 TAVENER, P.J., and JACKSON, R.G.: ‘Coupling of discharge cur-
Work on a range of high-voltage stator windings is rents between conductors of electrical machines owing to laminated
steel core’, Proc. IEE 8,1988,135, pp. 295-307
continuing to determine how general is the low-frequency 25 KURTZ, M., LYLES, J.F., SEDDING, H.G., and STONE G.C.:
behaviour observed in the present study. ‘On-line partial discharge measurements: a powerful maintenance
tool for rotating machines’, Ontario Hydro Research Review, June
1992
26 CAMPBELL, S.R., STONE G.C., and SEDDING, H.G.: ‘Applica-
6 References tion of pulse width analysis to partial discharge detection’. Pro-
ceedings of IEEE international conference on Electrical insulation,
1 BRAUN, J.M., FUJIMOTO, N., DIRVEN, N., TENG, M., and Baltimore, MD, USA, June 1992, pp. 345-348
ADDIS, G.: ‘PD scaling relationships in CIS insulators: theory and 27 SEDDING, H.G., CAMPBELL, S.R., and STONE, G.C.: ‘On-line
experimental verification’. Proceedings of sixth international con- partial discharge detection in turbine generators’. Proceedings of
ference on Dielectric materials, measurements and applications, Sep- IEE conference on Electrical machines and drives, Sept. 1991, pp.
tember 1992, pp. 166-169 250-254

416 IEE PROCEEDINGS-A, Vol. 140, N O . 5 , SEPTEMBER 1993

You might also like