PROJECT DOCUMENT NO. Rev.

Sheet
SHARM ELSHEIKH 12015-J-022-REP-111
6 x LM6000 50Hz SIMPLE CYCLE 0 1
CONTRACTOR VENDOR MAIN CONTRACTOR

CONTRACTOR SUB-CONTRACTOR

Title
UNIT(2) - BECKWITH PROTECTION RELAY (M-3425A)
TEST REPORT

TESTED BY APPROVED BY WITNESSED BY


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 2 of 50
TEST REPORT

Contents
 SCOPE:.............................................................................................................................................................................5

 Function: 87 (Phase Differential Current) .......................................................................................................................6

 Setting ...................................................................................................................................................................... 6
 Relay Secondary Metering ....................................................................................................................................... 6
 Injecting on Terminal CT’s between G.C.B & GSU................................................................................................ 6
 Pick-up Test ...................................................................................................................................................... 6
 Time Test .......................................................................................................................................................... 7

 Function: 27 (Phase Under-voltage) ................................................................................................................................8

 Setting ...................................................................................................................................................................... 8
 Relay Secondary Metering ....................................................................................................................................... 8
 Pick-up Test ............................................................................................................................................................. 8
 Time Test ................................................................................................................................................................. 9
 Blocking Inputs Test .............................................................................................................................................. 10

 Function: 59 (Phase Over-voltage) ................................................................................................................................ 11

 Setting .................................................................................................................................................................... 11
 Relay Secondary Metering ..................................................................................................................................... 11
 59 (#1) Testing ....................................................................................................................................................... 11
 Pick-up Test .................................................................................................................................................... 11
 Time Test ........................................................................................................................................................ 12
 Function: 59 (#2).................................................................................................................................................... 13
 Pick-up Test .................................................................................................................................................... 13
 Time Test ........................................................................................................................................................ 13

 Function: 24 (Volts/Hz Over-excitation) ........................................................................................................................ 14

 Setting .................................................................................................................................................................... 14
 Relay Secondary Metering ..................................................................................................................................... 14
 24 (#1) Testing ....................................................................................................................................................... 14
 Pick-up Test .................................................................................................................................................... 14
 Time Test ........................................................................................................................................................ 15
 24 (#2) Testing ....................................................................................................................................................... 16
 Pick-up Test .................................................................................................................................................... 16
 Time Test ........................................................................................................................................................ 16

 Function: 50 (Breaker-Failure) ...................................................................................................................................... 17

 Setting .................................................................................................................................................................... 17
 Pick-up Test ........................................................................................................................................................... 17
 Time Test ............................................................................................................................................................... 18
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 3 of 50
TEST REPORT

 Input Initiate Test ................................................................................................................................................... 18

 Function: 81 (Under/Over Frequency) ........................................................................................................................... 19

 Setting .................................................................................................................................................................... 19
 81 (#2) Testing ....................................................................................................................................................... 19
 Pick-up Test .................................................................................................................................................... 19
 Time Test ........................................................................................................................................................ 20
 81 (#4) Testing ....................................................................................................................................................... 20
 Pick-up Test .................................................................................................................................................... 20
 Time Test ........................................................................................................................................................ 21
 Blocking Input Test ................................................................................................................................................ 21

 Function: 60 (VT Fuse-Loss Detection).......................................................................................................................... 22

 Setting .................................................................................................................................................................... 22
 Time Test ............................................................................................................................................................... 22

 Function: 46 (Negative Sequence Over-current) ............................................................................................................ 23

 Setting .................................................................................................................................................................... 23
 Definite-Time Testing ............................................................................................................................................ 23
 Pick-up Test .................................................................................................................................................... 23
 Time Test ........................................................................................................................................................ 24
 Inverse-Time Testing ............................................................................................................................................. 24
 Time Test ........................................................................................................................................................ 24
 Reset Time Test ..................................................................................................................................................... 25

 Function: 32 (Directional Power) .................................................................................................................................. 26

 Setting .................................................................................................................................................................... 26
 Relay Secondary Metering ..................................................................................................................................... 26
 Pick-up Test ........................................................................................................................................................... 26
 Time Test ............................................................................................................................................................... 27
 Blocking Input Test ................................................................................................................................................ 27

 Function: 50/27( Inadvertent Energizing) ...................................................................................................................... 28

 Setting .................................................................................................................................................................... 28
 Pick-up Test ........................................................................................................................................................... 28
 Over-current Pick-up Test ............................................................................................................................... 28
 Under-voltage Pick-up Test ............................................................................................................................ 28
 Time Test ............................................................................................................................................................... 29
 Pick-up Time Test ........................................................................................................................................... 29
 Drop-Out Time Test ........................................................................................................................................ 30

 Function: 51V (Inverse Time Phase Overcurrent) .......................................................................................................... 31


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 4 of 50
TEST REPORT

 Setting .................................................................................................................................................................... 31
 Relay Secondary Metering ..................................................................................................................................... 31
 Pick-up & Time Test .............................................................................................................................................. 31
 At 100 % Voltage. ........................................................................................................................................... 32
 At 50 % Voltage. ............................................................................................................................................. 35
 At 25 % Voltage. ............................................................................................................................................. 37
 At Values Less Than 25 % Voltage. ............................................................................................................... 39
 At Values Greater Than 100 % Voltage. ......................................................................................................... 40

 Function: 40 (Loss of Field) ........................................................................................................................................... 41

 Setting .................................................................................................................................................................... 41
 Zones boundaries Test............................................................................................................................................ 41
 Time Test ............................................................................................................................................................... 41
 Zone-1 (40 #1) Time Test. .............................................................................................................................. 41
 Zone-2 (40 #2) Time Test. .............................................................................................................................. 42

 Function: 59N (Neutral Over-voltage) ........................................................................................................................... 43

 Setting .................................................................................................................................................................... 43
 51N (#1) Testing .................................................................................................................................................... 43
 Pick-up Test .................................................................................................................................................... 43
 Time Test ........................................................................................................................................................ 44
 51N (#2) Testing .................................................................................................................................................... 44
 Pick-up Test .................................................................................................................................................... 44
 Time Test ........................................................................................................................................................ 45

 Function: 25 (Sync Check).............................................................................................................................................. 46

 Setting .................................................................................................................................................................... 46
 Phase Angle Window: 10 (Degree) ........................................................................................................................ 46
 Delta Voltage: 11.0 (V) .......................................................................................................................................... 46
 Lower Voltage Limit: 58 (V) ................................................................................................................................. 47
 Upper Voltage Limit: 126 (V) ................................................................................................................................ 48
 Sync Check Delay: 1 (Cycles) ............................................................................................................................... 48
 Blocking Input: 5 ................................................................................................................................................... 49

 Function: 25D (Dead Check).......................................................................................................................................... 49

 Setting .................................................................................................................................................................... 49
 Dead Voltage Limit: 11 (V) ................................................................................................................................... 49
 Time Delay: 1 (Cycle) ............................................................................................................................................ 50
 Blocking Input: 5 ................................................................................................................................................... 50
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 5 of 50
TEST REPORT

 SCOPE:
Purpose of this document is to provide the tests of BECKWITH (M-3425A Generator Protection
Relay) functions for unit (2) for SHARM ELSHEIKH 6 x LM6000 50 Hz SIMPLE CYCLE COMBINED
CYCLE PROJECT.

Figure 1: One-Line Functional Diagram of (M-3425A) Generator Protection Relay


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 6 of 50
TEST REPORT

 Function: 87 (Phase Differential Current)


 Setting

Figure 2: Phase Differential Current Setting Values.

 Relay Secondary Metering

Figure 3: Relay Secondary Metering.

 Injecting on Terminal CT’s between G.C.B & GSU


 Pick-up Test
This test is done by using Ramp function on secondary injection tester.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 7 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 0.051 A.

 Time Test

The Value obtained as shown in previous snap-shoot was 0.021 Sec.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 8 of 50
TEST REPORT

 Function: 27 (Phase Under-voltage)

 Setting

Figure 4: Phase Under-voltage Setting Values.

 Relay Secondary Metering

Figure 5: Relay Secondary Metering.

 Pick-up Test

This test is done by using Ramp function on secondary injection tester and decreasing time delay
to the minimum value then re-entering the time delay value after finishing pick-up test.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 9 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 50.79 V (Phase-Value).

 Time Test

The Value obtained as shown in previous snap-shoot was 3.1 Seconds.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 10 of 50
TEST REPORT

 Blocking Inputs Test


Firstly, for input-1 blocking test:
Jumper on input-1 (point 10 (IN1) and point 11(INRTN- common)), the function will block.

Secondly, for 27 blocking with FL (VT Fuse Loss – virtual input-)


Loss of one phase voltage, the fuse loss function will activate and under voltage function will be
blocked.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 11 of 50
TEST REPORT

 Function: 59 (Phase Over-voltage)


 Setting

Figure 6: Phase Over-voltage Setting Values.

 Relay Secondary Metering

Figure 7: Relay Secondary Metering.

 59 (#1) Testing
 Pick-up Test

This test is done by using Ramp function on secondary injection tester and decreasing time delay
to the minimum value while de-activating 59 (#2) then re-entering the time delay value after
finishing pick-up test.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 12 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 76.14 V (Phase-Value).

 Time Test

The Value obtained as shown in previous snap-shoot was 4.289 Seconds.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 13 of 50
TEST REPORT

 Function: 59 (#2)
 Pick-up Test

The Value obtained as shown in previous snap-shoot was 87.4 V (Phase-Value).

 Time Test

The Value obtained as shown in previous snap-shoot was 1.184 Seconds.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 14 of 50
TEST REPORT

 Function: 24 (Volts/Hz Over-excitation)


 Setting

Figure 8: Volts/Hz Over-excitation Setting Values.

 Relay Secondary Metering

Figure 9: Relay Secondary Metering.

 24 (#1) Testing
 Pick-up Test
This test is done by using Ramp function on secondary injection tester and decreasing time
delay to the minimum value while de-activating 24 (#2) then re-entering the time delay value
after finishing pick-up test.

The Frequency is constant and only voltage is increased.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 15 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 74.76 V (Phase-Value).

 Time Test

The Value obtained as shown in previous snap-shoot was 6.317 Seconds.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 16 of 50
TEST REPORT

 24 (#2) Testing
 Pick-up Test

The Value obtained as shown in previous snap-shoot was 69.76 V (Phase-Value).

 Time Test

The Value obtained as shown in previous snap-shoot was 60.214 Seconds.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 17 of 50
TEST REPORT

 Function: 50 (Breaker-Failure)
 Setting

Figure 10: Breaker-Failure Setting Values.

 Pick-up Test
This test is done by using Ramp function on secondary injection tester and decreasing time delay
to the minimum value then re-entering the time delay value after finishing pick-up test.

The Value obtained as shown in previous snap-shoot was 0.082 A.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 18 of 50
TEST REPORT

 Time Test

The Value obtained as shown in previous snap-shoot was 0.182 Seconds.

 Input Initiate Test

This test is done by making jumper on input-4. The breaker-failure is initiated.

Figure 11: Breaker Failure Logic Diagram.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 19 of 50
TEST REPORT

 Function: 81 (Under/Over Frequency)


 Setting

Figure 12: Under/Over Frequency Setting Values.

 81 (#2) Testing
 Pick-up Test
This test is done by using Ramp function on secondary injection tester and decreasing time
delay to the minimum value then re-entering the time delay value after finishing pick-up test.

The Value obtained as shown in previous snap-shoot was 48.016 Hz.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 20 of 50
TEST REPORT

 Time Test

The Value obtained as shown in previous snap-shoot was 5.014 Seconds.

 81 (#4) Testing
 Pick-up Test

The Value obtained as shown in previous snap-shoot was 51.991 Hz.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 21 of 50
TEST REPORT

 Time Test

The Value obtained as shown in previous snap-shoot was 5.015 Seconds.

 Blocking Input Test

This test is done by making jumper on input-1 while applying a frequency of 47 Hz. Then the
output is blocked.
If jumper is removed, the output comes-back.
Checking: Ok.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 22 of 50
TEST REPORT

 Function: 60 (VT Fuse-Loss Detection)


 Setting

Figure 13: VT Fuse-Loss Detection Setting Values.

 Time Test

Dropping of one phase voltage suddenly and measuring time.

The Value obtained as shown in previous snap-shoot was 0.407 second.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 23 of 50
TEST REPORT

 Function: 46 (Negative Sequence Over-current)


 Setting

Figure 14: Negative Sequence Over-current Setting Values.

 Definite-Time Testing
 Pick-up Test
This test is done by using Ramp function on secondary injection tester and decreasing time
delay to the minimum value while de-activating 46 (IT) then re-entering the time delay value after
finishing pick-up test. The current injected is in negative-sequence.

The Value obtained as shown in previous snap-shoot was 0.112 A.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 24 of 50
TEST REPORT

 Time Test

The Value obtained as shown in previous snap-shoot was 0.996 second.

 Inverse-Time Testing
 Time Test

K 30
I rated 0.79
Injected Current Value 200% 1.58 A
Calculated Tripping Time 7.5 Sec. 375 Cycle

K 30
I rated 0.79
Injected Current Value 300% 2.37 A
Calculated Tripping Time 3.333333 Sec. 166.6667 Cycle
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 25 of 50
TEST REPORT

 Reset Time Test

Reset time is 10 SEC. (from threshold of trip)


The time is measured between when the current is removed and when the relay is able to be reset
using the reset button on the Beckwith.
Checking: Ok.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 26 of 50
TEST REPORT

 Function: 32 (Directional Power)


 Setting

Figure 15: Directional Power Setting Values.

 Relay Secondary Metering

Figure 16: Relay Secondary Metering.

 Pick-up Test
Injecting rated voltage and increase current from zero in opposite direction (180 degree shift).
So pick-up will be at 0.005 PU= 0.005*0.79 Amp = 0.004 Amp.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 27 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 0.004 A.

 Time Test

The Value obtained as shown in previous snap-shoot was 1.117 second.

 Blocking Input Test


32 directional power Blocking by FL, so do loss of one volt and inject a reverse current (0.005A at
180 degree), the directional power function will not operate.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 28 of 50
TEST REPORT

 Function: 50/27( Inadvertent Energizing)


 Setting

Figure 17: Inadvertent Energizing Setting Values.

 Pick-up Test
 Over-current Pick-up Test
This test is done by using Ramp function of injected current values on secondary injection
tester while injecting under-voltage value.

The Value obtained as shown in previous snap-shoot was 0.388 A.

 Under-voltage Pick-up Test


This test is done by using Ramp function of injected voltage values on secondary injection
tester while injecting under-voltage value and decreasing pick-up and drop-out time to the
minimum values then re-entering the time values after finishing pick-up test.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 29 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 44.43 V.

 Time Test
 Pick-up Time Test
Applying –firstly- Over-current and then under-voltage when the leads of timer are out and not
connected to tester. Then connect timer before pick-up time comes.
Do not forget to reduce the drop-out time to be less value.

Figure 18: 50/27 Logic Diagram.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 30 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 4.098 Seconds.

 Drop-Out Time Test

The Value obtained as shown in previous snap-shoot was 5.930 Seconds.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 31 of 50
TEST REPORT

 Function: 51V (Inverse Time Phase Overcurrent)


 Setting

Figure 19: 51V (Inverse Time Phase Overcurrent) Setting Values.

 Relay Secondary Metering

Figure 20: Relay Secondary Metering.

 Pick-up & Time Test

Figure 21: 51V C/CS as pick-up percentage related to input voltage as percentage.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 32 of 50
TEST REPORT

 At 100 % Voltage.
So the Pick-up will be 100% (1.18 Amp.).

Figure 22: 51V C/CS at 100 % voltage.

Injected current value Calculated Time (Sec.) Measured Actual Time (Sec.)
11.7 A 0.165 0.172
5A 0.359 0.357
3.6 A 0.605 0.585
2.13 A 1.96 1.941
Table 1: Summary of injected values results at 100 % voltage.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 33 of 50
TEST REPORT
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 34 of 50
TEST REPORT

Injected on phase A only


2.13 A 1.95 Sec

Injected on phase B only


2.13 A 1.943 Sec

Injected on phase C only


2.13 A 1.958 Sec
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 35 of 50
TEST REPORT

 At 50 % Voltage.

So the Pick-up will be 50% (0.59 Amp.).


Voltage restrain: Half rated voltage and half pickup current,
Voltage injection = 63.5/2 = 31.75 V
Pickup current =1.18/2 = 0.59 A
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 36 of 50
TEST REPORT

Figure 23: 51V C/CS at 50 % voltage.

Injected current value Calculated Time (Sec.) Measured Actual Time (Sec.)
1.19 A 1.53 1.514
3.66 A 0.23 0.243
Table 2: Summary of injected values results at 50 % voltage.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 37 of 50
TEST REPORT

 At 25 % Voltage.
So the Pick-up will be 25% (0.295 Amp.).
Voltage restrain: quarter rated voltage and quarter pickup current,
Voltage injection = 63.5/4 = 15.88 V.
Pickup current =1.18/4 = 0.295 A.

Figure 24: 51V C/CS at 25 % voltage.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 38 of 50
TEST REPORT

Injected current value Calculated Time (Sec.) Measured Actual Time (Sec.)
0.63 A 1.31 1.306
1.45 A 0.296 0.328
Table 3: Summary of injected values results at 25 % voltage.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 39 of 50
TEST REPORT

 At Values Less Than 25 % Voltage.


Same Values of 25% voltage were obtained and same Pick-up value at 25% voltage
Measured Time (Sec.) Measured Time (Sec.)
Injected current value
At 25% Voltage At 10% Voltage (6.35 V)
0.63 A 1.306 1.306
1.45 A 0.328 0.328
Table 4: Summary of injected values results at values less than 25 % voltage.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 40 of 50
TEST REPORT

 At Values Greater Than 100 % Voltage.


Same Values of 100% voltage were obtained and same Pick-up value at 100% voltage.
Measured Time (Sec.) Measured Time (Sec.)
Injected current value
At 100% Voltage At 120% Voltage (76.21 V)
11.7 A 0.172 Sec 0.172 Sec
1.45 A 0.357 Sec 0.357 Sec

Table 5: Summary of injected values results at values greater than 100 % voltage.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 41 of 50
TEST REPORT

 Function: 40 (Loss of Field)


 Setting

Figure 25: Loss of Field Setting Values.


 Zones boundaries Test

 Time Test
 Zone-1 (40 #1) Time Test.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 42 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 0.077 second.

 Zone-2 (40 #2) Time Test.

The Value obtained as shown in previous snap-shoot was 0.498 second.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 43 of 50
TEST REPORT

 Function: 59N (Neutral Over-voltage)


 Setting

Figure 26: Neutral Over-voltage Setting Values.

 51N (#1) Testing


 Pick-up Test
This test is done by using Ramp function of injected voltage on secondary injection tester and
decreasing time delay to the minimum value then re-entering the time delay value after finishing
pick-up test.

The Value obtained as shown in previous snap-shoot was 5.53 Volt.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 44 of 50
TEST REPORT

 Time Test

The Value obtained as shown in previous snap-shoot was 5.007 Seconds.

 51N (#2) Testing


 Pick-up Test
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 45 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 5.52 Volt.

 Time Test
De-activating firstly, the function 51N (#1).

The Value obtained as shown in previous snap-shoot was 10.007 Seconds.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 46 of 50
TEST REPORT

 Function: 25 (Sync Check)


 Setting

Figure 27: Sync Check Setting Values.

 Phase Angle Window: 10 (Degree)

The Value obtained as shown in previous snap-shoot was 10.1 Degrees.

 Delta Voltage: 11.0 (V)


The ranges of injected voltages must be between the lower and upper voltage values.
Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 47 of 50
TEST REPORT

The Value obtained as shown in previous snap-shoot was 11.14 Volt (= 70 – 58.86).

 Lower Voltage Limit: 58 (V)

The Value obtained as shown in previous snap-shoot was 57.97 Volt.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 48 of 50
TEST REPORT

 Upper Voltage Limit: 126 (V)

The Value obtained as shown in previous snap-shoot was 126.1 Volt.

 Sync Check Delay: 1 (Cycles)

The Value obtained as shown in previous snap-shoot was 0.040 second.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 49 of 50
TEST REPORT

 Blocking Input: 5
This test is done by making jumper on input-5 while all synchronization conditions are satisfied.
Then the output is blocked.
If jumper is removed, the output comes-back.
Checking: Ok.

 Function: 25D (Dead Check)


 Setting

Figure 28: Dead Check Setting Values.

 Dead Voltage Limit: 11 (V)

The Value obtained as shown in previous snap-shoot was 10.95 Volt.


Title: Document No. Rev. Page

UNIT(2) - BECKWITH (M-3425A GENERATOR PROTECTION) RELAY 12015-022-J-REP-111


0 Page 50 of 50
TEST REPORT

 Time Delay: 1 (Cycle)

The Value obtained as shown in previous snap-shoot was 0.035 second.

 Blocking Input: 5
This test is done by making jumper on input-5 while all synchronization conditions are satisfied.
Then the output is blocked.
If jumper is removed, the output comes-back.
Checking: Ok.