You are on page 1of 5

M-3425A All Setpoints

Software Version: D-0345V01.03.04


Relay Firmware Version: D-0150V05.00.08
Serial Number: 10012
BECKWITH ELECTRIC CO.
M-3425A

Setup System
Setup
CT Type: 1A Frequency Type: 50Hz
Phase Rotation: ABC Expanded I/O: Disabled
Active Profile: 1
Nominal Voltage: 110.0 (V) Nominal Current: 0.79 (A)
Delta-Y Transform: Delta-AB VT Configuration: Line-Ground to Line-Line
50DT Split Phase
59/27 Magnitude Select: RMS Differential: Disable
V.T. Phase Ratio: 100.0 (:1) V.T. Neutral Ratio: 57.3 (:1)
V.T. VX Ratio: 1.0 (:1) C.T. Phase Ratio: 4000 (:1)
C.T. Neutral Ratio: 1 (:1)
I/O Settings
Latched Outputs: Pulsed Outputs:
Active Inputs (Open): Active Inputs (Close): 1, 2, 3, 4, 5, 6
Sealin Time
Output 1: 25 (Cycles) Output 2: 25 (Cycles)
Output 3: 25 (Cycles) Output 4: 25 (Cycles)
Output 5: 25 (Cycles) Output 6: 25 (Cycles)
Output 7: 25 (Cycles) Output 8: 25 (Cycles)

21: Phase Distance


21 #1 (Disabled)
21 #2 (Disabled)
21 #3 (Disabled)

24: Volts/Hz Overexcitation


24 DT #1
Blocking Inputs: Outputs: 1, 7
Pickup: 118 (%) Time Delay: 300 (Cycles)
24 DT #2
Blocking Inputs: Outputs: 1, 7
Pickup: 110 (%) Time Delay: 3000 (Cycles)
24 IT (Disabled)

25: Sync Check


25S
Blocking Inputs: 5 Outputs: 6
Phase Angle Window: 10 (Degree) Upper Voltage Limit: 126 (V)
Lower Voltage Limit: 58 (V) Sync Check Delay: 1 (Cycles)
Delta Voltage: 11.0 (V) Delta Frequnecy: 0.250 (Hz)
Sync Check Phase: Phase A
25D
Blocking Inputs: 5 Outputs: 5

24/06/2015 Page 1 of 5
Dead Voltage Limit: 11 (V) Time Delay: 1 (Cycles)
Dead Input Enable: Dead V1 Hot VX:
Hot V1 Dead VX: Enabled Dead V1 Dead VX:

27: Phase Undervoltage


27 #1
Blocking Inputs: FL, 1 Outputs: 8
Pickup: 88 (V) Time Delay: 150 (Cycles)
27 #2 (Disabled)
27 #3 (Disabled)

27TN: Third Harmonic Undervoltage, Neutral


27TN #1 (Disabled)
27TN #2 (Disabled)

32: Directional Power


32 #1
Blocking Inputs: FL Outputs: 1, 7
Pickup: -0.005 (PU) Time Delay: 50 (Cycles)
Target LED: Enabled Power Selection: Overpower
32 #2 (Disabled)
32 #3 (Disabled)

40: Loss of Field


40 #1
Blocking Inputs: FL Outputs: 1, 7
Circle Diameter: 80.5 (Ohm) Offset: -9.0 (Ohm)
Time Delay: 4 (Cycles)
40 #2
Blocking Inputs: FL Outputs: 1, 7
Circle Diameter: 209.3 (Ohm) Offset: -9.0 (Ohm)
Time Delay: 25 (Cycles)
40 VC#1 (Disabled)
40 VC#2 (Disabled)
Setting
Voltage Control: 180 (V) Directional Element: 13 (Degree)

46: Negative Sequence Overcurrent


46 DT
Blocking Inputs: Outputs: 8
Pickup: 15 (%) Time Delay: 50 (Cycles)
46 IT
Blocking Inputs: Outputs: 1, 7
Pickup: 15 (%) Time Dial: 30
Maximum Time: 54580 (Cycles) Reset Time: 10 (Seconds)

49: Stator Overload Protection


49 #1 (Disabled)
49 #2 (Disabled)

24/06/2015 Page 2 of 5
50: Instantaneous Phase Overcurrent
50 #1 (Disabled)
50 #2 (Disabled)

50/27: Inadvertent Energizing


50/27
Blocking Inputs: Outputs: 1, 7
Overcurrent Pickup: 0.39 (A) Undervoltage Pickup: 77 (V)
Pick-up Delay: 200 (Cycles) Drop-out Delay: 300 (Cycles)

50BF: Breaker Failure


50BF
Blocking Inputs: Outputs: 4
Phase Current: 0.08 (A) Time Delay: 9 (Cycles)
Input Initiate: 4 Output Initiate: 1, 2

50DT: Definite Time Overcurrent


50DT #1 (Disabled)
50DT #2 (Disabled)

50N: Instantaneous Neutral Overcurrent


50N (Disabled)

51N: Inverse Time Neutral Overcurrent


51N (Disabled)

51V: Inverse Time Phase Overcurrent


51V
Blocking Inputs: Outputs: 2
Pickup: 1.18 (A) Curve: BECO Inverse
Time Dial: 0.70 Voltage Control: 100 (V)
Voltage Control Option: Voltage Restraint

59: Phase Overvoltage


59 #1
Blocking Inputs: Outputs: 2
Pickup: 132 (V) Time Delay: 200 (Cycles)
Input Voltage Selection: Phase Voltage
59 #2
Blocking Inputs: Outputs: 2
Pickup: 152 (V) Time Delay: 50 (Cycles)
Input Voltage Selection: Phase Voltage
59 #3 (Disabled)

59D: Third Harmonic Voltage Differential


59D (Disabled)

59N: Neutral Overvoltage

24/06/2015 Page 3 of 5
59N #1
Blocking Inputs: Outputs: 2
Pickup: 5.5 (V) Time Delay: 250 (Cycles)
59N #2
Blocking Inputs: Outputs: 4
Pickup: 5.5 (V) Time Delay: 500 (Cycles)
59N #3 (Disabled)
Setting
20Hz Injection: Disabled

59X: Multi-purpose Overvoltage


59X #1 (Disabled)
59X #2 (Disabled)

60FL: VT Fuse-Loss Detection


60FL
Blocking Inputs: Outputs: 8
Three Phase Fuse Loss
Time Delay: 20 (Cycles) Detection: Enabled
Input Initiate: FL

64F/B: Field Ground Protection

64S: 100% Stator Ground Protection by Low Frequency Injection

67N: Residual Directional Overcurrent


67N DT (Disabled)
67N IT (Disabled)

78: Out of Step


78 (Disabled)

81: Overfrequency/Underfrequency
81 #1 (Disabled)
81 #2
Blocking Inputs: 1 Outputs: 8
Pickup: 48.00 (Hz) Time Delay: 250 (Cycles)
81 #3 (Disabled)
81 #4
Blocking Inputs: Outputs: 8
Pickup: 52.00 (Hz) Time Delay: 250 (Cycles)

81A: Frequency Accumulation


81A #1 (Disabled)
81A #2 (Disabled)
81A #3 (Disabled)
81A #4 (Disabled)
81A #5 (Disabled)

24/06/2015 Page 4 of 5
81A #6 (Disabled)

81R: Rate of Change of Frequency


81R #1 (Disabled)
81R #2 (Disabled)

87: Phase Differential Current


87 #1
Blocking Inputs: Outputs: 2
Pickup 0.05 (A) Percent Slope 10 (%)
Time Delay: 1 (Cycles)
87 #2 (Disabled)
Setting
Phase CT Correction: 1.00

87GD: Ground Differential Current


87GD (Disabled)

BM: Breaker Monitoring


BM (Disabled)

TC: Trip Circuit Monitoring


TC (Disabled)

IPS
IPSlogic #1 (Disabled)
IPSlogic #2 (Disabled)
IPSlogic #3 (Disabled)
IPSlogic #4 (Disabled)
IPSlogic #5 (Disabled)
IPSlogic #6 (Disabled)

Setup Oscillograph Recorder


Setup
Triggered Inputs: Triggered Outputs: 1, 2, 4, 8
Partitions: 2 Post Delay: 10 (%)

Setup Sequence of Events Recorder


Setup
Function Pickup:

Function Trip:

Function Dropout:

Inputs Pickup: 1, 2, 3, 4, 5, 6 Outputs Pickup: 1, 2, 3, 4, 5, 6, 7, 8


Inputs Drop: 1, 2, 3, 4, 5, 6 Outputs Drop: 1, 2, 3, 4, 5, 6, 7, 8