No Param Parameter Description Default Value

no-00 password 01 no-00 00 : all functions and ap


no-01 operation mode 0011 01 : enable basic motor
no-02 max output frequency 060.0 02 : enable basic applica
no-03 max voltage 200.0 03 : enable advanced ap
no-04 max voltage output frequency 060.0 06 : all fault record are c
no-05 mid output frequency 1.5 Hz 08 : initializes inverter b
no-06 mid voltage output frequency 12.0 V 09 : initializes all control
no-07 min output frequency 1.5 Hz no-01 bit 0 : frequency ref. fro
no-08 min voltage output frequency 12.0 V bit 1 : start/stop from co
no-09 acceleration time 1 10.0 bit 2 : deceleration (0) /
no-10 deceleration time 1 10.0
no-11 acceleration time 2 10.0
no-12 deceleration time 3 10.0
no-13 frequency reference 1 0.0
no-14 frequency reference 2 0.0
no-15 frequency reference 3 0.0
no-16 frequency reference 4 0.0
no-17 jog frequency reference 6.0 no-18 bit 0 : electronic therma
no-18 motor type 0000 bit 1 : standard motor (0
no-19 motor rated current bit 2 : standard ratings (
no-20 reverse rotation prevention 0000 no-20 bit 0 : reverse rotation p
no-21 S-curve pattern accel/decel 0000 bit 4 : stall (0) / no stall
no-22 frequency reference gain 1.00 no-21 00 : S-curve section not
no-23 frequency reference bias 00.00 (bit 3 & 4) 01 : S-curve section 0.2 s
no-24 output frequency upper limit 100% 10 : S-curve section 0.5 s
no-25 output frequency lower limit 0 11 : S-curve section 1.0 s
no-26 DC injection braking current 50% (bit 2) output frequency (0) / c
no-27 DC injection braking during stop 0.5 s
no-28 DC injectionbraking at start 0.0 s
no-29 automatic torque boost gain 1.0 no-32 & 33 00
operation level for stall prevention during
no-30 170% 01
acceleration

no-31 operation level for stall prevention during run 160% 02


no-32 multifunction contact input (terminal 4) 01 03
no-33 multifunction contact input (terminal 5) 03 04
no-34 multifunction photocoupler output (terminal 130 05
no-35 multifunction photocoupler output (terminal 141 06
no-36 frequency detection level 0.0 07
no-37 overtorque detection selection 0000 08
no-38 overtorque detection level 160% 09
no-39 overtorque detection time 0.1 s 10
no-40 the inverter carrier frequency 04 11
no-41 not used 12
no-42 not used 13
no-43 not used no-34 & 35 0
no-44 not used 1
no-45 analog monitor gain 1.00 2
automatic decrease stall prevention level
no-46 0000 3
during accel in constant HP (kW) Area
no-47 fault retry selection 0 4
no-48 fault record 5
no-49 PROM no no-37 bit 0 : no overtorque (0)
no-50 prohibited frequency 1 0.0 Hz bit 1 : detection only du
no-51 prohibited frequency 2 0.0 Hz bit 2 : continues operati
no-52 prohibited frequency 3 0.0 Hz no-40 01 : 2.5 kHz or less (100
no-53 prohibited width 1.0 Hz 02 : 5 kHz or less (up to 1
no-54 speed search operation level 150% 04 : 10 kHz or less (up to
no-55 min. baseblock time 0.5 s 06 : 15 kHz or less (up to
no-46
no-56 V/F during speed search 100% bit 0 : no continous (0) /
no-57 slip compensation gain 0.0% bit 3 : auto lowering disa
no-58 motor no-load current 30%
no-59 slip compensation primary delay time 2.0s
00 : all functions and application are write protected. only write 00
01 : enable basic motor function. read and write 00 to 19
02 : enable basic applications. read and write 00 to 29
03 : enable advanced applications. read and write 00 to 59
06 : all fault record are cleared
08 : initializes inverter by restoring all settings and terminal functions to factory settings
09 : initializes all control constans. terminal functions are all set to 3-wire sequence
bit 0 : frequency ref. from control circuit (0) / digital operator (1)
bit 1 : start/stop from control circuit (0) / digital operator (1)
bit 2 : deceleration (0) / coast (1) to a stop

bit 0 : electronic thermal overload enable (0) / disable (1)


bit 1 : standard motor (0) / exclusive-use motor
bit 2 : standard ratings (0) / short-term ratings
bit 0 : reverse rotation possible (0) / impossible (1)
bit 4 : stall (0) / no stall (1) prevention during deceleration
00 : S-curve section not provided
01 : S-curve section 0.2 sec
10 : S-curve section 0.5 sec
11 : S-curve section 1.0 sec
output frequency (0) / current (1) monitor

forward / reverse command


external fault (NO contact input)

external fault (NC contact input)


multi-step speed reference 1
multi-step speed reference 2
Jog command
accel/decel time select
external baseblock (NO contact input)
external baseblock (NC contact input)
search command from max frequency
search command set frequency
accel/decel hold command
local/remote selection
option/inverter selection
in operation
agreed frequency
zero speed
output frequency more than frequency detection level
overtorque detected
operation mode
bit 0 : no overtorque (0) / overtorque (1) detection
bit 1 : detection only during agreed speed (0) / during running (1)
bit 2 : continues operation after (0) / output shut off at (1) overtorque detection
01 : 2.5 kHz or less (100 m or more)
02 : 5 kHz or less (up to 100 m)
04 : 10 kHz or less (up to 50 m)
06 : 15 kHz or less (up to 30 m)
bit 0 : no continous (0) / continous (1) operation after momentary power loss
bit 3 : auto lowering disabled (0) / enabled (1)