9 6.3.2 Maintenance, Measure and record For ICCP system, As per OEM
Step 7 output voltage and measure and record and to
current at junction actual output voltage synchronize
box. and current at junction output
box and CRT. This parameter
test shall be performed data and
every 6 months protective
potential data
for better
monitoring and
trend purpose.
10 6.3.2 Maintenance, Added. As per OEM
Step 8 Measure
structure-to-electrolyte
potential for SACP
system. Adjust or
repair if measuring
value is not match
criteria. This test shall
be performed every 6
months
1. PURPOSE ..................................................................................................................... 8
2. SCOPE .......................................................................................................................... 8
3. RESPONSIBILITY ......................................................................................................... 8
4. DEFINITION & ABBREVIATION .................................................................................... 8
5. REFERENCE ................................................................................................................. 9
6. PROCEDURE .............................................................................................................. 10
6.1. Overview of cathodic protection system ........................................................... 10
6.2. Preparation the work ........................................................................................... 11
6.2.1. Confirmation of Work Order and safety requirements ...................................... 11
6.2.2. Special personal protective equipment ............................................................ 12
6.2.3. Environmental precautions .............................................................................. 13
6.2.4. Equipment and tools ........................................................................................ 13
6.2.5. MRO for maintenance ...................................................................................... 14
6.3. Execute the Work ................................................................................................. 14
6.3.1. Visual check ..................................................................................................... 14
6.3.1.1 Routine check ............................................................................................... 14
6.3.1.2 Periodical check............................................................................................ 14
6.3.2. Maintenance .................................................................................................... 15
6.3.3. Return equipment to service ............................................................................ 17
6.4. Work Order closure .............................................................................................. 17
6. ATTACHMENT ............................................................................................................. 18
7. APPENDIX ................................................................................................................... 18
2. SCOPE
3. RESPONSIBILITY
5. REFERENCE
Document Number Title
- ISRS V8.1 Book of Knowledge
- ISRS 8th Edition Workbook
MD-04-HSE-HS-PD-003 Permit to Work Procedure
MD-04-HSE-HS-PD-004 Job Safety Analysis(JSA) & Safe Work Method
Statement(SWMS) procedure
MD-04-HSE-HS-PD-012 Lockout/Tagout Procedure
MD-03-MT-FW-0001 Preventive Maintenance Workflow for Production
Facilities
MD-03-MT-FW-0005 Breakdown Maintenance Workflow for Production
Facilities
MD-04-MT-RSELC-PD-037 Procedure for General Electrical Work
MD-04-MT-RSELC-PD-038 Procedure for Electrical work During Outage
MD-04-MT-RSELC-PD-100 Inspection and Maintenance Cycle for Electrical
VG2187-001-A 001 Cathodic Protection Design Calculation for
Firefighting Facility
VG2187-001-A-002 Cathodic Protection Design Calculation for Sea Water
Intake Facilities
VG2187-001-A-003 Cathodic Protection Design Calculation for Sea Water
Cooling Tower
VG2187-001-A-004 Cathodic Protection Design Calculation for U/G
Onshore Pipeline
VG2187-001-A-005 Cathodic Protection Design Calculation for Tank
Internal (for Slop, Caustic and Oily Water Tank)
VS2187-001-A-C001 Cathodic Protection Design Calculation for Tank
Internal (for Sour Water Tank)
VS2187-001-A-C002 Cathodic Protection Design Calculation for Hydrant &
Monitor
VS2187-001-A-U001 Cathodic Protection Design Calculation for Tank
Internal (for Service, Potable, Fire & Filtered Water
Tanks)
6. PROCEDURE
Figure.1 General arrangement drawing for Sacrificial Anode Cathodic Protection system
Figure.2 General arrangement drawing for Impressed Current Cathodic Protection system
The personnel who involves into the activity are required to wear the standard
personal protective equipment (PPE). Additional PPE must be worn for this procedure
due to the nature of the work or the location.
- Make sure good housekeeping is carried out during and after each work.
- Do not drain or vent any liquid or gas to an open space, on the ground, or into the
sea. Use only the approved method to drain or vent the systems.
- Gather all waste maintenance materials produced during work. After work, move
and store them at the reserved place.
Except conventional equipment and tools, the following equipment and tools may be
necessary for maintenance work:
• Insulation resistance tester DC 500V
• Multimeter
• Clamp Multimeter
• Earth tester
• Phase rotation meter
• Voltage detector
• Humidity/temperature testing equipment
• Infrared thermography equipment
• Proper insulated tools
• Cleaning equipment and vacuum cleaner
• Electrical maintenance toolbox
• Communication equipment (handheld radio)
• Portable Reference Electrode
6. ATTACHMENT
Attachment-1: Cause of deterioration & Replacement cycle of Component
Attachment-2: Table 1 of NACE 2012-1401-Cathodic Protection for Stainless and
other CRAs
7. APPENDIX
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Item NO.
Item NO.
Item NO.
Item NO.
Item NO.
Item NO.
Item NO.
Item NO.
Inspection Item Criteria Remark
I TR rectifier
II TR rectifier cabinet
Remarks:
Signature
Name
Date
1
MD-04-MT-RSELC-PD-18
APPENDIX-1
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Panel NO.
Item NO.
Item NO.
Item NO.
Item NO.
Item NO.
Item NO.
Item NO.
Item NO.
Inspection Item Criteria Remark
within vendor
8 Measure actual current
critera
within vendor
9 Perform continuity test all field cables
critera
Signature
Name
Date
2
MD-04-MT-RSELC-PD-18
APPENDIX-2
1 ***-CTB-001 60*-RE-01
2
Note 1 & 2
3
10
NOTE:
1. Minimum negative protective potential w.r.t. Reference Cell : -850mV (Cu/CuS04), -800mV(Ag/AgCl)
2. Protective potential for Seawater electrolyte only wrt Ag/AgCl reference cell: -700mV to -900 mV(stainless),
-600mV to -900mV(duplex stainless steel)
3. Measurement device: Tester Model No Expired Date:
Remark:
Contractor
NSRP-Maintenance Third party (if any)
Technician Leader/Supervisor
Signature
Name
Date
1
MD-04-MT-RSELC-PD-18
APPENDIX-3
1 SS**-CRT-60* N/A
2 60*-AN-01
3 SS**-CRT-60*- 60*-AN-02
ATB-01
4 60*-AN-03
5 60*-AN-01
SS**-CRT-60*-
6 60*-AN-02
ATB-02
7 60*-AN-03
10
NOTE:
1. Criteria for voltage & current will be based on SAT recorded data or last acceptable recorded readings
2. Ir=Es X shunt rating (A/mV)
3. Measurement device: Tester Model No Expired Date:
Multimeter Fluke 87 V 3/31/2020
Current clamp Meter Peaktech 1625 3/31/2020
4. Tank Level:
Remark:
Contractor
NSRP-Maintenance Third party (if any)
Technician Leader/Supervisor
Signature
Name
Date
1
MD-04-MT-RSELC-PD-18
APPENDIX-4
Inspection
Potential (Portable Reference Electrode)
No. Box No. Result Date Remark
(△mV)
(DD/MM/YY)
10
11
NOTE:
1. Criteria for Cu/CuSO4 Reference electrode : ±50mV
Contractor
NSRP-Maintenance Third party (if any)
Technician Leader/Supervisor
Signature
Name
Date
1
MD-04-MT-RSELC-PD-18
APPENDIX-5
1 60*-AN-01 60*-RE-01
2 60*-AN-02 60*-RE-02
See Note. 3
3 60*-AN-03 60*-RE-03
4 60*-AN-04 60*-RE-04
NOTE:
1. Reference Electrode :
2. Anode type:
3
Contractor
NSRP-Maintenance Third party (if any)
Technician Leader/Supervisor
Signature
Name
Date
1
MD-04-MT-RSELC-PD-18
APPENDIX-6
Inspection
No. Inspection name Activity Description Measurement Criteria Judgment Date Remark
(DD/MM/YY)
2 HMI
DC Output
Voltage
∆ ±10%
Visual check for
3 TR/Rectifier DCS
SS**-CRT-6**
4 HMI
DC Output
Current
∆ ±10%
5 DCS
6 HMI -
Common
Alarm
Alarm
function triggered
7 DCS
NOTE:
1. Measurement device: Tester Name Model No Expired Date:
Remark:
Contractor
NSRP-Maintenance Third party (if any)
Technician Leader/Supervisor
Signature
Name
Date