You are on page 1of 2

Operating instructions

Valve regulated stationary lead-acid batteries


Specifications: Installation by: This means that the charging voltage is the
operating voltage of the battery and at the
Nominal voltage UN: 2.0 V x number of cells same time the battery system voltage.
on:
connected in series
Under stand-by parallel operation, the direct
Nominal Capacity CN = C10: 10 hour Commissioning by: current source is at any time capable of sup-
discharge (see type label) plying the maximum load current and the
CN on: battery charging current. The battery only
Nominal discharge current: IN = I10: supplies current when the direct current
10 h
Safety markings affixed by: source fails. The charge voltage should be
Final discharge voltage Us: 1.80 V/Cell
set at 2.25 V ± 1% x number of cells in
Nominal temperature TN: 20°C series, measured at the battery’s terminals.
Valve regulated stationary lead-acid batter- To reduce the recharging time a charging
on:
ies consist of cells which for their entire ser- stage can be applied in which the charging
vice life must not be topped up with water. voltage is max. 2.35 V x number of cells
Excess pressure valves are used as vent 1. Commissioning (stand-by parallel operation with recharging
plugs and will be destroyed if opened. Before commissioning all cells/blocks must stage). Automatic changeover to the char-
be inspected for mechanical damage, cells ging voltage of 2.25 V ± 1% (2,27 V ± 1%
Observe operating instructions for power.com H.C, power.com XC, dry.power
and display visibly near to the must be connected with the correct polarity
and connectors firmly seated. and net.power 12 V 92 as well as 12 V 170)
battery. x number of cells in series follows.
Work on batteries only after The following torque applies for screw
connectors: With floating operation the direct current
instruction by qualified staff.
M8 with 20 Nm ± 1 Nm, source is not able to supply the maximum
No smoking. No open flame, load current at all times. The load current
M5/M6 with 8 Nm ± 1 Nm.
embers or sparks in the vicinity intermittently exceeds the nominal current of
of the battery, to avoid risk of If necessary the terminal covers must be the direct current source.
explosion and fire. put on.
During this period the battery supplies power.
With charger off and loads isolated, connect It is not fully charged at all times. Therefore,
Wear eye protection and protec- battery to the direct current power supply,
tive clothing when working with depending on the load, the charge voltage
maintaining correct polarity (positive termi- must be set at approx. 2.27 to 2.30 V x
batteries. nal to positive post).
Observe accident prevention re- number of cells following consultation with
Switch on the charger and charge as de- the battery manufacturer.
gulations, also DIN EN 50272 T2,
scribed in section 2.2. b) Switch mode operation
DIN EN 50110 Part 1!
When charging, the battery is separated from
Acid splashes in the eyes or on 2. Operation
the load. The charge voltage of the battery is
the skin must be washed out or For the assembly and operation of stationary max. 2.35 V/cell. The charging process must
off with plenty of water. Then battery installations DIN EN 50272 Part 1 be monitored. When the charge current has
see a doctor immediately. Acid and DIN EN 50272 Part 2 resp. IEC 62485- decreased to 1.5 A/100 Ah nominal capacity
splashes on clothing should be 2 apply. at 2.35 V/cell, the battery is switched to
washed out with water! float charging as under section 2.3 or switch-
The battery must be installed in such a way
Explosion and fire risk, avoid that an ambient temperature difference of ing takes place on reaching 2.35 V/cell.
short-circuits. > 3°C cannot occur between individual c) Battery operation (charge/discharge)
Warning! Metal parts of the bat- cells/blocks. operation
tery cells are always live. Never The load is supplied only by the battery. The
place foreign objects or tools on 2.1 Discharging charging method depends on the user and
the battery. Never allow the final discharge voltage of the must be clarified with the battery manufac-
Electrolyte is highly corrosive. In battery to drop below that assigned for the turer.
normal operation there is no discharge current. Unless the manufacturer
possibility of contact with the has specified otherwise, no more than the 2.3 Maintaining the full charge (float
electrolyte. Should the casing be nominal capacity is to be consumed. Charge charging)
destroyed, the combined electro- immediately after discharge, including par- Devices complying with the provisions of
lyte released is as corrosive as tial discharge. DIN 41773 must be used. They are to be
liquid electrolyte. set so that the average cell voltage is 2.25 V
2.2 Charging ± 1% (2,27 V ± 1% for power.com H.C,
Monobloc batteries/cells are very power.com XC, dry.power and net.power 12 V
The charging procedure with limit values as
heavy! 92 as well as 12 V 170).
defined under DIN 41 773 (IU characteris-
Ensure secure installation! Use
tic) may be used.
only suitable conveying equip- 2.4 Equalising charge
ment! Depending on the system at hand, char-
Because it is possible to exceed the permitted
ging may be carried out under the following
Dangerous electrical voltage. load voltages, appropriate measures must be
operating modes (in accordance with DIN EN
taken, e.g. disconnection of the load.
Further information can be found 50272 Part 1 draft).
in the detailed installation, com- An equalising charge is necessary after an
a) Stand-by parallel operation and floating
missioning and operating instruc- exhaustive discharge and/or after an inade-
operation
tions under www.hoppecke.com. quate charge; it can be carried out at a con-
Here the load, direct current source and bat-
stant voltage of max. 2.35 V/cell for up to
tery are continuously connected in parallel.
48 hours. The end of equalising charge is rea-
ched when the electrolyte densities and cell 3. Battery maintenance and inspection 6. Storage and taking out of operation
voltages no longer rise within a period of 2 To avoid leakage currents keep the battery Should cells/batteries be stored or be taken
hours. The charging current should not exceed clean and dry. Cleaning the battery should be out of operation for extended periods, they
20 A per 100 Ah nominal capacity. Should the carried out as specified in the ZVEI pamphlet must be stored fully charged in a dry, frost-
maximum temperature of 45°C be exceeded, on battery cleaning. free room. Direct sunlight must be avoided.
the charging process must be interrupted or
temporarily switched to float charge to allow Plastic battery components, in particular the To prevent damage, the following charging
the temperature to drop. cell containers, must only be cleaned with conditions should be chosen:
pure water.
1. Equalizing charges as defined under 2.4
2.5 Superimposed alternating currents At least every 6 months the following must be above, to be given twice a year. At average
While recharging up to 2.35 V/cell in accor- measured and recorded: ambient temperatures in excess of 20°C,
dance with the operating modes of section - battery voltage; shorter intervals may be necessary.
2.2, the actual value of the alternating current - voltage of a few selected cells/monobloc Note: Battery charge acceptance might be
is occasionally permitted to reach a max. 20 A batteries; restricted by the end of max. storage period.
per 100 Ah nominal capacity. After recharging - surface temperature of a few selected We recommend application of a different char-
and continuous charging (float charging) in cells/monobloc batteries; ging method to ensure gentle and full rechar-
standby parallel operation or floating opera- ge. Refer to corresponding section in the
- temperature in the battery room.
tion, the effective value of the alternating detailed installation, commissioning and ope-
current must not exceed 5 A per 100 Ah nomi- Should the cell voltage deviate from the rating instructions.
nal capacity. average float charge voltage by +0.2 V/cell
or -0.1 V/cell and/or should the surface 2. Float charging as under 2.3 above.
2.6 Charging currents temperature of different cells deviate more The period of use commences with delivery
During continuous battery power supply or than 5K, customer services must be called in. of the filled and charged battery from the
floating operation without a recharging stage, Note: Voltages of batteries with electrolyte HOPPECKE plant. Storage times are to be
the charging currents are not limited. The fixed in gel can vary within approximately the added to the period of use in full. In addition,
charging current should lie between 10 A and first 2 to 4 years after commissioning. Hence batteries require recharging.
20 A per 100 Ah nominal capacity (standard the cell voltage in float charge can differ from
value). Note: Max. two recharges during storage
2.12V/cell ± 1% to 2.5 V/cell ± 1%. These period. Battery has to be operated under per-
variations are normal phenomenon for gel manent float voltage thereafter.
2.7 Temperature type batteries without negative influence on
The recommended operating temperature capacity resp. efficiency of single battery cells 7. Transport
range for lead-acid batteries is 10°C to 30°C. or blocs.
The ideal operating temperature range is 20°C Filled lead-acid batteries which are undama-
± 5K. The following must be measured and recorded ged, show no leaks and are firmly secured on
annually: pallets with protection against sliding, over -
Higher temperatures will reduce battery service - battery voltage; turning and short-circuits are not treated as
life. The technical data apply to the nominal dangerous goods for conveyance by road so
- battery voltage of all cells/monobloc batteries;
temperature of 20°C. Lower temperatures long as there are no dangerous traces (acid,
reduce the available capacity. The maximum - surface temperature of all cells/monobloc
batteries; lye) visible on the outside of the package.
temperature of 55ºC must nor be exceeded.
Continuous operating temperatures in excess - temperature in the battery room. ATTENTION:
of 45ºC are to be avoided. Annual visual checks: It is essential that loads on road vehicles
- on all bolted connectors, are properly secured!
2.8 Temperature-related charge voltage - check all bolt connectors are firmly seated
Within the operating temperature range of 8. Technical data
- on battery installation or arrangement,
15°C to 25°C, temperature-related adjustment The nominal voltage, the number of
- on ventilation.
of the charge voltage is not necessary. cells/blocks, the nominal capacity (C10 = CN)
4. Tests and the battery type can be obtained from
Should the operating temperature constantly
the identification plate.
lie outside this temperature range, the voltage Tests must be conducted in accordance with
should be adjusted. The temperature correc- DIN 60896 Part 21 / Part 22. In addition,
tion factor is 0.005 V/Cell per K. special test in-structions, e.g. as set out in 8.1 Example
DIN VDE 0100-710 and DIN 0100-718 Identification plate: 4 OPzV 200
Temperature -10 0 10 20 30 40 should be observed. 4 = number of positive plates
[°C] OPzV = battery type
Charge voltage 2.40 2.35 2.30 2.25 2.20 2.15 5. Faults 200 = nominal capacity C10
[V/Cell] Should faults be detected in the battery or (capacity for discharge with ten hours’
the charging device, customer services should current (I10) over a discharge time of 10 h
be called in immediately. Measured data (t10))
2.9 Electrolyte
as under section 3 simplify fault detection and
The electrolyte is dilute sulphuric acid. elimination. A service contract with us facili-
tates the timely detection of faults.
HOPPECKE service number: + 49 (0) 800 246 77 32
Teil-Nr. 7340204011/03.13/3 K Printed in Germany

Type Float charge voltage


HOPPECKE OPzV, power.bloc OPzV, net.power 12 V 100 and 12 V 150 Ah,
2,25 ± 1%
power.com SB, power.com HC, OPzV solar.power, OPzV bloc solar.power, solar.bloc
net.power 12 V 92 and 170 Ah, power.com XC 2,27 ± 1%
Voltage per unit 2V 4V 6V 12 V
Tolerance for float charge voltage for single cells/blocks -0,10 V/+0,20 V -0,14 V/+0,28 V -0,17 V/+0,35 V -0,25 V/+0,50 V

Old batteries with this marking are recyclable goods and must be sent for recycling.
Pb
Used batteries which are not sent for recycling are to be disposed of as special waste under the relevant regulations.

HOPPECKE Batterien GmbH & Co. KG


P.O. Box 1140 · D-59914 Brilon Phone +49(0)2963 61-0 Email info@hoppecke.com
Bontkirchener Straße 1 · D-59929 Brilon-Hoppecke Fax +49(0)2963 61-449 www.hoppecke.com

You might also like