Professional Documents
Culture Documents
DC ELECTRICS
Chapter 1: INTRODUCTION
UNITS of ELECTRICITY
COMPLEX DC CIRCUITS
Q5. /18. Resistors in parallel – the total current consumed is sum of currents
taken by the resistors
Chapter 2: SWITCHES
Toggle switches, rocker switches and switch lights can be momentary action type
or they may remain in the selected position until another selection is made
Both toggle switches and switch lights can be guarded to prevent inadvertent
operation
AUTOMATIC SWITCHES
Blown fuses have to be discarded. A tripped CB may be reset once the fault has
been rectified
An operator shall not operate an aeroplane unless spare fuses at least 10 % of each
rating or 3 whichever is greater
FUSES
Fuses cannot be reset and must be discarded and replaced if they blown or are
ruptured
Current limiters can carry a considerable overload current for a short period of
time before blowing or rupturing
Dummy fuses are red with corrugated sides; they should have a red streamer
attached
Flt deck CBs are usually trip free thermally tripped CBs, which need to be reset
manually
A trip free CB can be reset once the fault has cleared. Holding the reset button
will not make the circuit live.
In the event of CB trip only one reset should be attempted before the defect is
investigated
Q 8/p47. Non trip-free CB cannot be reset – but can be held in and circuit
made operational – dangerously.
Chapter 3 (continues): CAPACITANCE
A capacitor stores electrical energy in the electrical field that can be created
between two conductors that are separated by an insulator
Primary cell batteries cannot be recharged and need to be discarded once their
chemical energy ha s been used up
The capacity of a cell is a measure of how much current it can provide for a
specific period of time. It is measured in ampere-hours
Parallel connection – Voltage of one cell or battery, but the capacity is sum of
individual cell or battery capacities
Greater cost
A flight deck battery check is carried out on load, which is a load applied.
Q4/p63. Nominal voltage 24 v. Full charged without load 26 v (12 cells *2.2)
Q7/p65. The capacity of L-A battery is determined by the area of the plates.
Chapter 5: MAGNETISM
A magnet is an object, which has a magnetic field, which behaves like a magnet
Magnetically soft material has micros – magnets, which are easy to realign
ELECTROMAGNETISM
Magnetic field around a wire will be in concentric circles around the wire
A field coil is used to control the voltage of the generator at a fixed value
irrespective of the drive speed
The output or terminal voltage of a series wound generator varies (reduces) with
applied load
Q8/p101. A generator is governed so that the EMF is constant and the rate of
flow (amperage output) varies
The voltage output of a shunt wound generator reduces slightly as the load
increases.
GENERATOR CONTROL
In parallel generator system the load sharing or equalizing circuit maintains both g
generator voltages by sending signals to individual VRs. This ensures that each
generator takes equal share of applied load.
Q4/p102. An a/c having a battery with nominal voltage of 24v, the generator
output would be 28 volts.
Chapter 7: DC MOTORS
If a wire carrying a current is placed at right angles to a magnetic field, the wire
experiences a resultant force
Fleming’s LH Rule enables us to determine the direction in which the force acts
PRACTICAL MOTORS
Back EMF is
Proportional to field strength
Proportional to armature speed
Opposes applied EMF
Opening the generator or alternator master switch breaks the field circuit
Busbars are the collection and distribution points for gene or alternator supply
The battery switch allows the pilot to connect the battery to, or to disconnect the
battery from the Bus bar
SYSTEMS MONITORING
Ammeter
Moving coil instrument
After engine start, battery ammeter shows a high charge rate for a short period
Voltmeter
The gene or alternator warning light indicates that the gene or alternator voltage
has fallen below battery voltage
Each generator or alternator has sufficient capacity to carry the extra load in the
event of single gene or alternator failure
System having more than one BB, any of which can be isolated from the supply in
event of a fault
In the event of a gene or alternator failure the other unit must be able to take the
entire load
The battery must be able to supply the vital and essential loads for a min of 30 /
60 minutes
Load shedding is a term used to describe the switching off of certain electrical
loads to prevent overloading a generator or alternator
Questions Generator Cut-out (P 137)
Q6/. To prevent recirculating currents when more than one generator on the
same bus-bar DIFFERENTIAL CUTOUTS are used.
P 128. (The on coming generator cannot switch on-line until its voltage is 2%
more than the voltage of generator, which is already on-line. The 2 %
difference in potential is between the oncoming generator output and the
battery bus-bar).
Q1. In twin engine a/c with two gene there would be individual ammeters for
each generators but only one switchable voltmeter to indicate generator or
battery voltage
Q5. In the event of a cut-out sticking in the closed position then with the
engine stopped would result in a burnt-out generator
Q9. A field switch in the generator circuit is to “shut-off” the generator field.
Questions Generator Distribution System (p143)
Q5. If on a single pole circuit the positive conductor is shorted the FUSE will
blow
Chapter 9: BONDING & SCREENING
Static Dischargers or wicks are fitted to the tips of the engine and tail
P 128. (The on coming generator cannot switch on-line until its voltage is 2%
more than the voltage of generator, which is already on-line. The 2 %
difference in potential is between the oncoming generator output and the
battery bus-bar).
OXFORD
AC ELECTRICS
BASIC AC THEORY
Summary – Terms
A cycle is one complete series of values One cycle represents from zero to 360
degrees of phase
The number of cycles occurring in each second is the frequency of AC. Frequency
is measured in cycles/second or Hertz
The amplitude or peak value is the maximum value attained in one cycle
Diagram
AC Current and Voltage have same frequency and wave form (cycle) –
sinusoidal.
In DC Ohms Law (V = IR). In resistive circuit Voltage and Current are in phase.
That is frequency is same but values of Voltage and Current are not in phase. That
is they not Zero at the same time. They differ in phase angle.
DIAGRAMS
Resistance
Inductance
Mutual Induction
Self Induction
Lenz’s Law
The self-induced voltage will oppose any oppose any change of current in circuit.
This self-induced voltage is called BACK EMF. It is proportional to number of
turns; intensity of flux using iron core; frequency (rate of change) of alteration
Inductance
Unit Henry.
One amp/sec induces Back EMF of 1volt.
Current LAGS Voltage by 90º.
Inductive Reactance (XL opposes current flow (like resistance) – only its value
depends on frequency and value (turns). XL = 2πf L
If FREQ increases Inductive Reactance (OHMS) shall increase and Current flow
will decrease.
Capacitance in AC
Unit is FARAD.
If 1 amp/sec current flow enables it to store 1 volt Potential difference then it
is a 1 Farad capacitor.
IMPEDANCE
It is vector sum of REACTANCE (Inductance XL and Capacitive XC) and pure
Resistance measured in OHMS = √R2 + (XL + XC).
Power in AC Circuits
A Circuit having equal Resistance and Inductance, the Ø angle diff will be 45 º.
Now the amount of +ve power and –ve power will not be equal.
The excess +ve power in the circuit is the USEFUL Power (WATT) consumed in
operating a GADGET.
Thus PF ≈ Cos ø.
In an AC generator System the voltage and the current waveform are both
sinusoidal.
In an AC circuit having inductance only the current lags the voltage by 90˚ of
phase. Unit of Inductance is HENRY. Symbol is L
In an AC circuit having only capacitance the current leads the voltage by 90˚ of
phase. The unit of capacitance is FARAD
CIVIL (p 179)
For a fixed value of capacitance the capacitive reactance will increase if the
frequency of the supply voltage is decreased; this will lead to an increase in
current flow in the circuit.( XC = 1 /2π f C)
Resonant Circuit
When the capacitive and inductive reactance in a circuit, are equal, the circuit is
said to be resonant. And the frequency at which this occurs is known as the
circuit’s resonant frequency.
AC Power
Power produced in a purely inductive and / or capacitive circuit (to overcome that
type of resistive reactance) is known as reactive or wattles power.
The total power (APPARENT POWER) is the power being felt in a circuit
containing both resistance and reactance. It is the vector sum of the real and
reactive power and shown as apparent power.
Apparent Power is also called Theoretical Power or Rated Power. It is
measured in volt-amps or kilovolt-amps. (VA or KVA).
Here A stands for “Apparent” and not ampere). (SORRY). It does indeed
stand for Volt – ampere or Kilovolt - ampere
True Power = Apparent Power but only when Voltage and Current are in
phase.
˚
True power is ZERO if Voltage and Current are 90 out of phase.
Q14. The RMS value of alternating current is .707 times the peak value.
Q24 The RMS value of AC is same as the value of DC which would provide
the same heating effect.
Q33 The output of an alternator is rated in real and apparent power (KW /
KVA)
Chapter 2: BASIC ALTERNATORS
Types of Alternators
DIAGRAM 12.1
3 – Ø Connection
If earth fault NEUTRAL carries out of balance current. If Earth fault – neutral
carries excessive high current.
Balanced load is current flow and Ø voltage across each phase is same. Under
these conditions current neutral cancels out, and there is no NEUTRAL current.
Star connection can cope with different loads on each Bus -Bar. The Delta (∆)
connection cannot.
Star Connection
Line Voltage = √ 3 Ø Voltage = 1.73 Ø Voltage (Vector addition)
Line Voltage = 1.73*115 = 200 Volt
Line current = Ø current (because the path is same)
∆ Connection
Fig 12.6
Line Voltage = Ø Voltage; but Line Current = √3 Ø Current = 1.73 Ø current.
No neutral point to carry unbalanced current. Used in Tacho - gene indicators.
Practical AC Generators
Rotating Armature
Rotating Field – Brushed and Brushless
Brushed Generators.
DC generated.
Later AC rectified to DC via slip-rings and commutators.
Control of excitation current by Voltage Regulator, by adjusting current
irrespective of Alternator speed and load usingVariable Resistance in series with
Field Coil.
Brushless.
Exciter Generator on same shaft as Main Generator. Voltage Regulator by
controlling Exciter Field ----- and thereby current at main field coil.
Used to power de-icing. Resistance of heater mats not affected by changing freq.
Frequency wild gives Dc to Static Inverter to Constant frequency AC.
CSDU
Engine-driven hydraulic pump drives Hydraulic motor drives Constant frequency
Alternator
The field windings are on the rotor and the armature windings are on the stator
Aircraft AC generator are usually 115/200 volt, 400 Hz, 3 ø, star connected
machines
PRACTICAL AC GENERATORS
A brushless AC generator has the main generator and an exciter generator on the
same shaft
The frequency of the frequency wild generator varies with engine speed
The engine input drive to the CSDU can be disconnected. This would allow both
the CSDU and gene to become stationery
Q 37. If the CSDU oil pressure becomes excessively low or the oil temp
excessively (LIGHTS ILLUMINATE) high the CSDU should be disconnected
from the engine drive
Constant frequency AC generators normally have an output of 115v / 200v, 400
Hz, 3 ø
PRACTICAL GENERATORS
Q26. The output voltage, frequency, phase sequence of all generator must be
the same synchronous (They must be in phase with each other)
Q24. Real load sharing is achieved by controlling the CSDUs and adjusting
the torque at their output shafts so that all paralleled generator are experiencing
the same torque
Q27. Only constant speed generators can be paralleld. Such Generators have
their individual CSDUs.
SYSTEM COMPONENTS
GCU
Regulates generator voltage
Monitors over/under voltage and frequency, incorrect phase sequence
The GCUs in conjunction with the Bus Power Control unit (BPCU) protect
against differential current faults. It isolates the defective generator or faulty
bus-bar and reconfigures the electrical system.
Protection is provided for
Over / Under Voltage
Over / Under Frequency
Over / Under Excitation
Differential current faults; short circuit between bus-bars or bus-bar
to ground (earth) or open circuit faults unbalancing phase outputs
Q 49. Frequency controlled generators are not always paralled –e.g. Split
System.
Q60. Advantage of STAR one phase fault would not affect operation of
others
In Split BB system the various sources of AC power are never connected to the
same bus-bar
In the event of loss of all generators a static inverter powered from the battery will
supply the essential AC loads
The generators are connected to the load Bus-bars by Generator Control breakers
(GCBs)
Q10. If in parallel alternator operation if one generator fails then the SSB
will close allowing the remaining three geneartors to share the all the load.
Q 11. In SBS if external power is plugged into an aircraft it will supply all the
all the services. On the ground an external power supply can be used to
power all the bus-bars
The output voltage, frequency and phase rotation of each generator is adjusted to
align with voltage, frequency and phase rotation of any generator or generator
already supplying the BB, before it is allowed to connect with the BBs
Q5 In SBS system if both generators fail – all NON ESSENTIAL services are
lost.
Q6. In SBS AC system under normal operation takes its DC supply two
TRUs which are connected together by the DC Isolation Relay ( No 1TRU for
Ess DC and No 2 TRU for Non ESS DC bus). (P 228)
Chapter 14: TRANSFORMERS
In a step-up transformer the output voltage is greater than the input, but in a step
down it is lower
Q5. The power in the primary winding of a transformer is equal to the power
in the secondary winding
The input supply into the Primary coil of the transformer must be of the correct
frequency. If the input frequency is low it is possible that the transformer will
overheat due to excessive current flow
Auto Transformers
A ZENER diode acts in the same manner as normal diode until a pre-determined
reverse voltage is reached at which point it allows unrestricted reverse flow in the
reverse direction
Inverters
Convert DC in to AC. Usually solid state – rotary or static type.
An AC motor is made of two main parts: Stationery Stator and a rotating rotor
AC rotors use a rotating magnetic field in the stator to drive the rotor
If two phases of the supply to a three phase rotating field are reversed the
direction of the rotation of the field and thus that of the rotor being driven will be
reversed
The difference between the speed of the rotating field of an induction motor and
rotor speed is known as the slip speed or the rotor slip
In a synchronous motor the rotor rotates at the same speed as the rotating field
Q1
Q3
Q4
Q5
Q6
Q7
Q8
Q9
Q10
Chapter 16: BASIC COMPUTERS
NUMBERING SYSTEMS
Digital computers use the binary number sys to manipulate data. In the v binary
system any number can be represented using only two symbols, zero and one
Binary 10th 9th 8th 7th 6th 5th 4th 3rd 2nd 1st
Digit
Power 29 28 27 26 25 24 23 22 21 20
Decimal 512 256 128 64 32 16 8 4 2 1
Value
Digital electronic computers use digit al data in their operations and this form of
data has only two levels of voltage. The two levels correspond to ON or OFF in
than electrical circuit
The term bit is used when referring to a binary digit. One bit is equal to one
binary digit. A number of bits handled as a group are referred to as byte.
Software is a general term used for digitally stored data such as program of
instructions read from or written to by computers
Performs, organizes, and controls all operations the computer can carryout
ALU performs arithmetic calculations and logic operations using binary numbers
The shift registers are temporary stores of data
The control unit contains the computer clock
Memory
Computer memory that retains the data when the power is switched off is called
non-volatile memory
Memory that loses data in the event of a power failure or switched off is called
volatile memory
Buses or BBs are used used to connect the CPU to the computers memory and to
the peripheral equipment
Multiprocessing is the use of two or more CPUs within a single computer system
Permanent storage of computer programs and the work they generate can take the
form of magnetic discs, optical discs or solid state electronic chip devices
Assembly languages use a symbolic representation of the binary codecs and other
constants needed to program a particular CPU
Q8
Q9
Q14
Q15
Q23
Q24
AND
OR
INVERT or NOT
NAND
NOR
EXCLUSIVE OR
TRUTH TABLES
Q8
Q9
Q10
Chapter 17: SEMICONDUCTORS
Germanium and Silicon are two S/C used in production of electronic components
You can change the behavior of Si or Ge and turn it into a conductor by a process
known as doping
In P- type doping Al or Indium is the dopant. This produces holes in the lattice
structure
A Junction diode allows current to flow freely through it in one direction but
resists current flow in the opposite direction
The End
Thanks GOD!