Professional Documents
Culture Documents
6, NOVEMBER/DECEMBER 2014
TABLE I
C IRCUIT B REAKER R EQUIRED A SYMMETRICAL C APABILITY FOR
G ENERAL -P URPOSE AND G ENERATOR R ATED C IRCUIT B REAKERS
Taking Iacsym as 1.0 PU, composition is not known; thus, the development of similar
√ X/R √ 2πf t multiplying curves is done by using data read from the Fig. A.9
Idc = 2 × ε− tc ; tc = = 2 × ε− X/R
t
; thus Idc curves. Dividing any of the total fault currents in Table II
2πf
(2) by the generator circuit breaker S-factor of Table I yields a
multiplication factor of less than 1.0 for all values in Table I.
where Therefore, for a system where all the current is from a local
t time (in seconds); generator without any impedance between the generator and the
tc time constant (in seconds); fault, the multiplication factor is set equal to 1.0.
f frequency (in hertz).
For an X/R ratio = 17, tc = 0.045 s, and for X/R = 50,
III. E XAMPLE
tc = 0.133 s.
Fig. A.9 of IEEE C37.010-1999 has the multiplication fac- The example of a typical combined cycle generating station
tors for currents that have both ac and dc decrements (not stated is shown in Fig. 3. The combustion and steam turbine genera-
in IEEE C37.010-1999 as having ac decay, but it is the same tors (identified as “CTG” and “STG” in the figure) share a com-
as Fig. A.9 in C37.010-1979). The origin of the amount of ac mon transformer, but each generator is required to have its own
decay given in the curve is not based on equation, and its exact circuit breaker. The data for the station are given in Table III.
4166 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 6, NOVEMBER/DECEMBER 2014
TABLE III
DATA FOR THE E XAMPLE IN F IG. 3 less than the generator reactance, the resistance component of
voltage has been neglected.
IEC equation
Vinternal = 1 + Xdv × sin [ar cos(P F )] . (3)
Detailed equation
Vinternal = (1 + Xdv × sin [ar cos(P F )])2 + (X × PF )2
dv
(4)
X dv
generator impedance modifier = . (5)
VINTERNAL
IV. P ROCEDURE
Using the system diagram in Fig. 3, a three-phase fault is
placed at location A–B with all connections active. Then, a fault
is placed at A with the STG out of service. This will give the
fault point X/R ratio of the system for the current flowing from
the transformer. Finally, a fault is placed at location B with the
transformer out of service; this will give the fault point X/R of
the STG plus any bus duct/cable current following the circuit
breaker from the STG.
Using IEEE C37.010 procedures, a fault at location A or B
on Fig. 3 gives the total system symmetrical fault of 114.59 kA
with an IEEE X/R ratio = 80.61. In Fig. 3, the symmetrical
fault current for the first half-cycle and instantaneously cleared
Fig. 4. Vector diagram for generator internal voltage calculation for STG. interrupting time is the same since the IEEE C37.010 suggested
that generator impedance is the same for both times.
In the upcoming analysis, to provide some conservatism, The symmetrical fault current from the STG is 39.71 kA at
the voltage behind the subtransient reactance will be used −89.560 (X/R = 130.2) and 74.88 kA at −88.830 (X/R =
(see Fig. 4). This is a deviation from 1.0 PU driving voltage 48.96) from the transformer. The current via the transformer
suggested in IEEE C37.010 and is similar to the effect of the has two components: 35.14-kA contribution from the CTG and
generator impedance modifier used in IEC 60909. To calculate 39.75 kA from the 400-kV system. The fault point IEEE X/R
this per-unit internal voltage for the generator at rated load, ratio from the STG is 130.3 when the transformer is out of
the approximate equation from IEC 60909 or a more detailed service, and the IEEE X/R for the current via the transformer
equation can be used. With the generator resistance being much is 53.99 when the STG is out of service. The IEEE X/R ratio
DARTAWAN AND PIERRE: EVALUATING CIRCUIT BREAKERS DUTY USING IEEE C37.010 AND C37.013 4167
for the current via the transformer is 53.99, as compared with terrupting time duties. We look at several approaches, each
the complex jX/R ratio of 48.96. having a different level of conservatism for the interrupting time
If an auxiliary station were connected to location B, then calculations.
its protective device would be evaluated with the 114.59-kA
symmetrical current and an X/R ratio of 80.61. The limiting
circuit breaker duty for circuit breaker STG would be either the A. Peak Current Calculation
current from the transformer for fault location A or the current The peak current is associated with the first half-cycle and
from the generator for fault location B. While the current from is approximated by (6) or (7). Since the peak actually occurs
the transformer is greater than the current via the STG, the duty before the half-cycle, using the time as 0.5 cycle would result
for both conditions should be evaluated since the STG current in a small error. To correct for this error, a fictitious time of τ is
has a higher X/R ratio and could result in the duty current used, as shown in the IEEE Violet Book (6) and IEC-60909 (7)
being greater than the transformer current. √
IEEE Violet Book → IP K = 2IacRMS 1 + ε− X/R
2πτ
Circuit breakers that are classified as generator rated circuit (6)
breakers have several ratings that are different than general-
X/R
purpose circuit breakers. The two key ratings, as far as this τ = 0.49 − 0.1 × ε− 3
paper is concerned, are the “close and latch” rating and the √
IEC-60909 → IP K = 2IacRMS 1.02 + 0.98ε− X/R . (7)
3
test X/R ratio. A general-purpose circuit breaker has a peak
current “close and latch” rating of 2.6 times the interrupting,
and its interrupting rating is based on the fault current X/R From STG
ratio of 17 (45-ms dc decay rate). The generator rated circuit
τ = 0.49 − 0.1 × ε− 3 = 0.49
130.2
breaker has a peak current “close and latch” rating of 2.74 times
the interrupting, and its interrupting rating is based on the fault √ 2π×0.49
current X/R ratio of 50 (133-ms dc decay rate). IP K = 2 × 39.71 1 + ε− 130.2 = 111.0 kA.
For circuit breaker duty calculations, it is important to obtain
the system X/R that represents the dc decay. In IEEE C37.010- From transformer
1999, section 6.3.2 provides a method to determine the fault
τ = 0.49 − 0.1 × ε− 3 = 0.49
53.99
The duty multiplier can be also calculated from (1) and (2). gives 40.214 kA plus the 35.14 kA from the CTG gives a total of
First, the circuit breaker interrupting rating capability (includ- 75.355 kA. Allowing for 5% high voltage, the total duty current
ing ac and dc) at the circuit breaker test X/R ratio of 50 at would be 79.12 kA or 98.9% of the circuit breaker rating. In
40 ms needs to be determined. Second, calculate the current this case, this decrease in rating to duty is small (from 99.4%
via STG and transformer if the fault X/R ratio is greater to 98.9%) and would be greater if the IEEE X/R ratio of the
than 50. The duty multiplier is the value from the second step current from the transformer was greater.
divided by the value from the first step. If the fault point X/R
ratio is less than 50 (circuit breaker test X/R ratio), the duty
C. Calculations Using IEEE C37.013-1997
multiplier (other than 1.0) is not required, and the symmetrical
interrupting current can be compared to the circuit breaker’s Generally, the generator transformer impedance and source
interrupting rating directly. impedance are less than the generator impedance; thus, the cur-
Circuit breaker interrupting rating capability (including ac rent via transformer is used for circuit breaker duty evaluation.
and dc, or ITOT ) can be calculated from (1) and (2) as follows: In rare cases where the current from the generator dictates the
√ circuit breaker duty, the refinement in the current from the gen-
Idc = 2 × ε− 50 = 1.046
377∗0.04
All interrupting duty currents determined using Fig. 2 and Adjusting for the generator internal voltage rather than
(1) and (2) are less than the circuit breaker rating. Allowing for 1.0 PU V that was used in (8) has the generator PU A at
105% operating voltage, the circuit breaker interrupting current 4.3033 ∗ 1.14274 = 4.9176 PU A. The generator symmetrical
is at 99.4% of the circuit breaker rating. If this system were fault current at the circuit breaker CPT allowing a 105%
in the design stage, a larger margin between the duty and the generator voltage is 1.05 ∗ 4.9176 ∗ 7.506 = 38.76 kA (note,
circuit breaker rating would be warranted. STG-rated amps is 7506 from Table III). Using (6), correcting
For discussion purposes, let us assume that the interrupting the symmetrical current for the generator X/R ratio of 130.2
time current is slightly greater than the circuit breaker rating and τ = 0.49, gives the generator circuit breaker close and
and a further refinement in the calculation is desired. For latch duty for the current from the STG as 38.76 ∗ 2.7953 =
example, [2] uses graduated curves where the fault current 108.34 kA.
via the transformer could be treated as a composite of a The interrupting time calculation using the 40 ms CPT of the
decaying ac component and a nondecaying component. The circuit breaker in (8) gives
graduated curves given in [2] are widely used in software
IGEN = (4.63 − 3.4) × ε−0.04/0.033 + (3.4 − 0.51)
programs for industrial and commercial systems. Note that the
IEEE C37.010-1999 has curves for the current either being with × ε−0.04/0.419 + 0.5089
no ac decay or having ac decay from nearby generators. As IGEN = 0.365 + 2.629 + 0.51 = 3.504 PU.
given above, the current via the transformer has two compo-
nents: 35.14 kA from the CTG and 39.75 kA from the 400-kV Adjusting for the generator internal voltage rather than 1.0
system. It was shown earlier that the total current with decay PU V that was used in (8) has the generator PU A at 3.504 ∗
would not have any duty multiplier other than 1.0. This leaves 1.14274 = 4.0036 PUA. The generator symmetrical fault cur-
the multiplier to be applied only to the current component from rent at the circuit breaker CPT allowing a 105% generator
the 400-kV system. Using the 1.0117 multiplier on 39.75 kA voltage is 1.05 ∗ 3.504 ∗ 7.506 = 27.62 kA (note, STG-rated
DARTAWAN AND PIERRE: EVALUATING CIRCUIT BREAKERS DUTY USING IEEE C37.010 AND C37.013 4169
[12] International Standard Short-Circuit Current Calculation in Three-Phase Conrad St. Pierre received the B.S.E.E. degree
a.c. Systems, IEC Std. 60909-02001, Jul. 2001. from The University of Maine, Orono, ME, USA,
[13] IEEE Standard for AC High Voltage Generator Circuit Breakers Rated on in 1965 and the M.S. degree from Union College,
a Symmetrical Current Basis, IEEE Std. C37.013-1997, 1997. Schenectady, NY, USA, in 1983.
[14] IEEE Standard for AC High Voltage Generator Circuit Breakers Rated He is currently the President of Electric Power
on a Symmetrical Current Basis Amendment 1: Supplement for Use With Consultants, LLC, Schenectady, where he provides
Generators Rated 10-100 MVA, IEEE Std. C37.013a-2007 (Amendment analytical studies for industrial clients. He has writ-
to IEEE Std C37.013-1997), 2007. ten numerous IEEE papers and magazine articles and
[15] IEEE Recommended Practice for Calculating Short-Circuit Currents published a book, A Practical Guide to Short-Circuit
in Industrial and Commercial Power Systems, IEEE Std 551—(Violet Calculations, and coauthored a book titled Industrial
Book), 2006, Chapter 2. Power System Grounding Design Handbook.
[16] Application Guide for AC High-Voltage Circuit Breakers Rated on a Mr. St. Pierre has been a senior member of several subcommittees, and he
Symmetrical Current Basis, ANSI/IEEE Std. C37.010-1979, 1979. was the Chairman of the Violet Book Working Group that deals with short-
[17] IEC Standard for High-Voltage Switchgear and Controlgear, circuit calculations. He was also a member of the U.S. National Committee of
IEC Std. 62271-100, 2008. the International Electrotechnical Commission Technical Advisory Group for
[18] C. St. Pierre, A Practical Guide to Short-Circuit Calculations, TC73/WG1 and WG2 concerning short-circuit currents and calculation method.
(self-published book), Jul. 2001, ch. 3.
[19] W. D. Stevenson, Elements of Power System Analysis, 3rd ed. New York,
NY, USA: McGraw-Hill, 1975.
[20] D. Beeman, Industrial Power Systems Handbook. New York, NY, USA:
McGraw-Hill, 1955.
[21] , Westinghouse Transmission and Distribution Book. New Delhi, India:
Oxford & IBH, 1950, ch. 11.