You are on page 1of 5

2019 IEEE The 3rd International Conference on Circuits, Systems and Devices

Analysis of Lightning Performance of Overhead Transmission Lines with Insulator


Parallel Gaps

Xiangxian Zhou, Shaohua Wang, Xiaoyu Zhou, Te Li, Yang Zou


Junping Cao CEEC Zhejiang Electric Power Design Institute
State Grid Zhejiang Electric Power Research Institute Hangzhou, China
Hangzhou, China
e-mail: zhouxiangxian04@126.com

Abstract—Lightning is one of the major threats to the operation are used to predict but not to investigate the lightning
of high voltage overhead transmission lines. To improve the performance of an existing transmission line before and after
lighting performance of overhead transmission lines, various the installation of lightning protection devices. For the latter
lighting protection measures are used. The major challenge in purpose, the ideal method would be designing a controlled
choosing lightning protection measures is that it’s difficult to experiment in which the lightning incidence is the same from
quantitatively evaluate how these measures changes the year to year. However, the nature lightning incidence is of
lightning performance of the transmission lines. Parallel gap is stochastic nature [7], the lightning parameters of a
used to protect insulator from the arc caused by lightning
transmission line corridor can vary significantly from year to
discharge. Based on a large-scale insulator parallel gap
year. It’s important to eliminate the difference of lightning
installation project, this work analyzed relationship between
the insulator parallel gap installation and the lighting
incidence when designing a proper evaluation method.
performance of the transmission lines. This work first proposed Insulator parallel gap is a kind of power arc protection
a method for evaluation of lightning performance of existing device, which can guide the power-frequency arc away from
overhead transmission lines, and then the method was applied the surface of the insulator during the lightning flashover [8].
to groups of transmission lines installed with insulator parallel In China, parallel gap was introduced as a lightning
gaps. Finally, the lightning performance of the transmission protection measure [9]. The function of parallel gap is to
lines before and after the installation of insulator parallel gaps reduce the insulators’ chance of being damaged by the arc,
are compared and analyzed. and thus are expected to reduce the lightning outage rate. He
et al. designed a kind of parallel gap for 110kV composite
Keywords-flashover rate, insulator; lightning protection; insulators and applied it to 5 transmission lines, which proved
overhead transmission line; parallel gap to be effective in power arc protection [10]. Wang et al.
proposed a new jet stream arc-quenching lightning protection
I. INTRODUCTION gap, which successfully operated in a 35kV transmission line
In the coastal area of China, lightning is one of the major [11].
threats to the operation of high voltage overhead transmission When a parallel gap is installed to an existing insulator
lines. For existing transmission lines, various of lightning string, it will short the dry arcing distance of the insulator
protection measures, like surge arresters and air terminals, are string, which reduces the basic lightning impulse insulation
installed to improve the lightning performance. It is important level (BIL) of the transmission lines [12]. Although it is
to know how these protection measures changes the lightning widely recognized that the parallel gap will increase the
performance of the transmission line, because the benefit of lightning flashover rate, there are no existing research that
these measures is expected to be higher than its cost. have evaluated it.
Lightning performance is measured by the lightning From 2010 to 2016, a large-scale insulator parallel gap
flashover rate. Both IEEE and CIGRÉ have guideline on installation project was carried out in Zhejiang province of
evaluation of the lightning performance of overhead China, which provide a rare chance to evaluate how the
transmission lines [1][2]. Nucci compared these two parallel gap changes the lightning performance of
approaches and concluded that they are “somewhat the same” transmission lines. This work first introduced the parallel gap
[3]. Lambert et al. proposed a stress-strength interference installation project, then proposed an evaluation method, and
based method to calculate the lightning failure rate [4]. finally analyzed the evaluation results..
Martinez proposed a Monte Carlo procedure based lightning
flashover rate calculation method for transmission line [5], II. PARALLEL GAP INSTALLATION PROJECT
which is then used to evaluate the surge arrester’s influence A. Project Overview
on lightning performance of transmission lines [6].
The existing lightning performance evaluation methods Zhejiang province is in east coast of China, with 101,800
km2 in area and suffers from frequent thunderstorms during
Sponsored by State Grid Zhejiang Electric Power Company Research the summer season. To protect the insulators from being
Program (5211DS16002P) damage by the frequent power-frequency arc caused by

978-1-7281-3063-7/19/$31.00 ©2019 IEEE 87


lightning flashover, an insulator parallel gap installation lightning discharge voltage (U50) of the parallel gap linearly
project was carried out in Zhejiang province. decreases by 0.558kV as the gap length decrease 1mm. The
As listed in Table I, there were 43 220kV overhead average arcing distance of the composite insulators of group
transmission lines installed the parallel gaps (these A transmission lines is about 1900mm, which means the BIL
transmission lines will be referred as group A hereafter). of group A transmission lines decreases by 106kV to 159 kV
Group A transmission lines are consisting of 5450 towers, due to the installation of parallel gaps.
while 2397 towers are installed with the parallel gaps, which
is 44.0% of all the towers. For each transmission line in group
A, the parallel gap installation rate varies from 2.6% to 100%.
The installation work started from 2010 to 2016, while most
parallel gaps were installed in 2014 and 2015. Among the
towers with parallel gaps, all 3 phase were installed.

TABLE I. PARALLEL GAP INSTALLATION INFORMATION


Install Install Installed
N Installed

Z
Z0
ation No. ation /Total Tower
o. /Total Tower
Year Year
1 2010 34/106 23 2015 70/140
2 2011 104/104 24 2015 16/140
3 2012 17/70 25 2015 5/192
4 2014 4/32 26 2015 66/203
5 2014 15/66 27 2016 45/120
6 2014 32/68 28 2016 23/77
7 2014 27/65 29 2014 73/136
8 2014 75/169 30 2014 69/196
9 2014 45/122 31 2014 32/64 Figure 1. Structure of the installed parallel gaps.
10 2014 80/160 32 2014 96/198
11 2014 112/112 33 2014 98/98
12 2014 191/191 34 2014 47/190 III. EVALUATION METHOD
13 2014 49/122 35 2014 30/132
14 2014 51/53 36 2014 14/318
Lightning performance of overhead transmission lines is
15 2014 75/158 37 2015 24/60 determined by two categories of factors. The first category is
16 2014 77/164 38 2015 55/112 the lightning incidence, which include the ground flash
17 2014 42/102 39 2015 61/61 number and its distance to the transmission lines and the
18 2014 30/70 40 2015 84/178 lightning current parameters (magnitude, polarity and
19 2015 95/95 41 2015 107/214 waveshape). The second category is the properties of the
20 2015 182/182 42 2015 45/214 transmission lines, like the insulation level, the lightning
21 2015 49/286 43 2016 30/31 protection measures et al. The lightning incidence can vary
22 2015 77/168
from year to year, but the properties of transmission line can
be the same over long period of time.
B. Control Group To evaluate how the parallel gaps changes the lightning
performance of transmission lines, the influence of variation
To compare the difference between the lightning of lightning incidence should be decreased as much as
performance of transmission lines with and without parallel possible. The evaluation method proposed in this work is
gaps, another 34 transmission lines without parallel gaps are based on the data from lightning location system (LLS) where
selected in this work (these transmission lines will be referred the ground flash location, lightning current magnitude and
as group B hereafter). Group B transmission lines are polarity are recorded.
consisting of 6532 towers and locate in the same area as those
in group A. A. Risk of Lightning Current
C. Parallel Gap Configuration The risk of current RI is defined as:
There are two types of insulators that are used in the 𝑃𝑟(𝐼fault) 𝑃𝑟(𝐼fault )
220kV transmission lines, which are composite insulator and 𝑅𝐼 = ( )⁄Max ( ) (1)
𝑃𝑟(𝐼nature ) 𝑃𝑟(𝐼nature )
glass insulator. Most of the suspension insulators are the
composite insulators, and the structure of the composite
insulator parallel gaps is shown in Fig. 1, where Z0 is the where Pr is the probabilty density, Ifault is the distribution of
structure height of the insulator and Z is the gap distance. The lightning current that lead to tripping of transmission lines,
ratio Z/Z0 varies from 0.85 to 0.9 in this parallel gap Inature is the distribution of nature occurrence of the lightning
installation project, which represents how much arcing current. Ifault is derived from the 866 lightning tripping faults
distance is being shorted by the installation of the parallel of 220kV transmission lines of Zhejiang province from 2004
gaps. According to test results of Li et al. [13], the average to 2016. The probabilty density of Ifault is shown in Fig. 1,

88
which shows that most of the lightning tripping faults are B. Risk of Lightning Location
caused by lightning currents that are smaller than 40kA. The lateral distance between the center of transmission
The polarity effect has not been taken into consideration lines to the location of ground flash decides the odd of a
in the proposed method, because only 46 out 866 lightning ground flash strike to transmission lines. The normalized
tripping faults are caused by positive polarity lightning probability density distribution of the distance between
current, it’s difficult to obtain the probability density transmission lines to the ground flash of 866 lightning
distribution of positive fault current. tripping faults is shown in Fig. 4. The risk of ground flash
The ratio between the probability density of fault current that are shorter than 20m away from transmission line is
and the nature current represents the risk of lightning currents, much high than the risk of other ground flashes, which is
which is shown in Fig. 3. The risk of current below 5kA is 0, defined as 1. The risk of other ground flashes is relative to the
because this range of lightning current is too small to cause ground flashes that are shorter than 20m away from
flashover. The risk increases with the current magnitude transmission lines. The risk of lightning location is fitted by a
between 5kA and 25kA, because the lightning overvoltage step function:
increase with the current magnitude. The risk decrease with
the increase of current magnitude between 25kA and 50kA, 1.0000 𝐷 ≤ 20m
because the shielding failure rate decreases with the increase 0.1563 𝐷 > 20m and D ≤ 1000m
of current magnitude. The risk increase again with the 0.0455 𝐷 > 1000m and D ≤ 2000m
𝑅𝐷 = (2)
increase of current magnitude above 50kA, because the 0.0131 𝐷 > 2000m and D ≤ 3000m
lightning current starts to cause back flashover. The risk of 0.0048 𝐷 > 3000m and D ≤ 5000m
{ 0 𝐷 > 5000m
lightning current equal or bigger than 400kA is defined as 1,
and the risk of other lightning currents is relative to it.
where D is the distance between center of the transmission
line to the lightning location.

Figure 2. Lightning tripping current magnitude distribution. Figure 4. Risk of lightning location.

C. Risk of Lightning Incidence


The risk of lightning incidence to a transmission line in 1
year is defined in

𝑅𝐿 = ∑𝑁
𝑛=1 Interp(𝑅𝐼 , 𝐼𝑛 )𝑅𝐷 (𝐷𝑛 ) (3)

where RL is the risk lightning incidence, N is the total number


of ground flashes that are in the 5km vicinity of the
transmission lines in 1 year, In is the lightning current
magnitude of nth ground flash, Dn is the lateral distance
between the ground flash and the center of transmission.
Interp(RI, In) is to obtain the risk of In through linear
interpolation from Fig. 3. RD(Dn) is defined in Eq. (3). The
lightning performance of a group of transmission lines in 1
year is measured by
Figure 3. Risk of lightning current.
𝑁
lines
𝑃 = (∑𝑛=1 𝑁fault,𝑛 ⁄𝑅𝐿,𝑛 )⁄𝑁lines (4)

89
where P is the lightning performance index of a group of B. Effect of Parallel Gaps
transmission lines in 1year. Nfault,n is the number of lightning The lightning performance of group A transmission lines
tripping faults of the nth transmission lines in the group in 1 and the number of installed parallel gaps in group A
year, Nlines is the total number of transmission lines in the transmission lines from 2006 to 2016 is shown in Fig.6.
group, and RL,n is the risk of lightning incidence to nth Before 2010, the lightning performance index of group A is
transmission line in 1 year. The physical meaning of P is that in the range of 0.05 to 0.1. From 2010 to 2013, 3 transmission
the average tripping time when there is a 400kA lightning lines were installed the parallel gaps and the lightning
flash strikes in the 20m vicinity of the transmission line. The performance index increases to 0.15. From 2013 to 2014, 16
lower P is, the better the lightning performance of the transmission lines were installed the parallel gaps and the
transmission line is. lightning performance index increases from 0.15 to 0.37.
IV. EVALUATION RESULTS
A. Variation of Lightning Incidence
The characteristics of ground flash in 5km vicinity of
group A transmission lines and the ground flash in the whole
Zhejiang province are compared in Fig.5, in which the
correlation is measured by the Pearson correlation coefficient
(PCC) [14]:
cov(𝑋,𝑌)
𝜌𝑋,𝑌 = (4)
𝜎𝑋 𝜎𝑌

where 𝜌𝑋,𝑌 is the PCC of X and Y, cov(X,Y) is the covariance


of X and Y, 𝜎𝑋 and 𝜎𝑌 are the standard deviation of X and Y
respectively. In this work, the PCC between 0.6 to 1 is
interpreted as strong correlation, the PCC between 0.4 to 0.6 Figure 6. Lightning performance of group A and number of installed
is interpreted as moderate correlation and the PCC between 0 parallel gaps.
to 0.4 is interpreted as weak correlation.
For the variation of average lightning current magnitude After 2014, the parallel gaps installation continued but the
from 2006 to 2016, 72.2% of the transmission lines have lightning performance index decreases from 0.37 to 0.29.
strong correlation, 20.9% of the transmission lines have This is because there was a major upgrade for the LLS of
moderate correlation and 6.9% of the transmission lines have Zhejiang province in the end of 2014, and the detection
weak correlation with that of the Zhejiang province. For the efficiency of LLS increased after the upgrade. In compare
variation of ground flash number from 2006 to 2016, 76.8% with the data before 2015, more ground flashes were detected
of the transmission lines have strong correlation, 16.3% of the and thus the lighting performance index is lower even when
transmission lines have moderate correlation and 6.9% of the the lightning performance of the transmission lines are the
transmission lines have weak correlation with that of the same.
Zhejiang province. For large part of the transmission lines, Generally, the average lightning performance index
the variation of annual lightning incidence is like that of the before 2011 is 0.07, the average lightning performance index
whole area. However, there are still transmission lines that from 2011 to 2013 is 0.11, and the average lightning
have lightning incidence deviates significantly from that of performance index from 2014 to 2016 is 0.31. It can be
the whole area. concluded that the lightning performance of group A trans
mission lines degraded by 77% due to the large-scale
installation of the parallel gaps.
C. Control Group
The lightning performance of group B transmission lines
from 2006 to 2016 is shown in Fig. 7. The lightning
performance of group B vary significantly from year to year,
but the lightning performance index does not increase from
2010 to 2016 like that of group A. The average lightning
performance index of group B from 2006 to 2016 is 0.23,
which is much higher than that of group A before 2011. This
is because when choosing the transmission lines for
installation of parallel gaps, those transmission lines with
poorly lightning performance were preclude to avoid further
degraded by parallel gaps.
Figure 5. Relationship between ground flash parameters in line corridors
and the Zhejiang province.

90
3) As 44% of the towers of group A transmission lines
were installed with insulator parallel gaps, the lightning
performance of group A transmission lines decreased by
77%.
4) Although only the insulator parallel gap is analyzed in
this work, the proposed method can be used to evaluate other
lighting protection measures.

REFERENCES
[1] "IEEE Guide for Improving the Lightning Performance of
Transmission Lines", IEEE Standard 1243-1997.
[2] CIGRÉ WG 33-01, “Guide to Procedures for Estimating the Lightning
Performance of Transmission Lines”, CIGRÉ Technical Brochure, Nr.
Figure 7. Lightning performance of group B. 63, October 1991.
D. Lightning Outage Rate [3] C. A. Nucci,. "A survey on Cigré and IEEE procedures for the
estimation of the lightning performance of overhead transmission and
The parallel gaps are expected to protect the insulator distribution lines.", IEEE 2010 Asia-Pacific Symposium on
from arc and avoid lightning outage. For the single-phase Electromagnetic Compatibility (APEMC), 2010.
lightning tripping fault, the relay protection system will [4] R. Lambert, E. Tarasiewicz, A. Xemard, G. Fleury. “Probabilistic
automatically reclose. If the reclose fails, the lighting tripping evaluation of lightning-related failure rate of power system apparatus”,
will become lighting outage. The reclose failure rate after IEEE transactions on power delivery, vol. 18, pp. 579-586, 2003.
lightning tripping of group A and group B is listed in Table II. [5] J. A. Martinez, A. Juan., and F. Castro-Aranda. "Lightning
performance analysis of overhead transmission lines using the EMTP",
Unfortunately, it’s not possible to draw any conclusion from IEEE Transactions on Power Delivery, vol. 20, pp. 2200-2210, 2015.
this reclose failure rate data, because lightning tripping [6] J. A. Martinez., and F. Castro-Aranda. "Lightning flashover rate of an
reclose failure in 220kV transmission lines is quite rare. overhead transmission line protected by surge arresters." Power
Engineering Society General Meeting,. IEEE, 2007.
TABLE II. RECLOSE FAILURE RATE [7] A. Rakov and M. A. Uman, Lightning: physics and effects. Cambridge
University Press, 2003, pp. 24–52.
Group 2006 2007 2008 2009 2010 2011
[8] C. deTourreil and F. Schmuck, "On the use of power arc protection
Group A 0.0% 0.0% 12.5% 0.0% 0.0% 10.0% measures for composite insulators on transmission lines," CIGRE WG
Group B 0.0% 13.0% 3.6% 0.0% 3.3% 0.0% B2.21 Report, 2009.
Group 2012 2013 2014 2015 2016 / [9] "Guide for Lightning Protection of Overhead Transmission Lines",
State Grid Standard QGDW 11452, 2015. (in Chinese)
Group A 0.0% 10.0% 0.0% 7.1% 0.0% /
[10] Z. M. He, D. Ge, C.X. Zhang and X. L. Wang, "Application
Group B 0.0% 0.0% 5.3% 22.2% 0.0% / investigation on parallel gap of composite insulators for 110 kV
transmission line in high intensity lightning area," 2011 7th Asia-
Pacific International Conference on Lightning, Chengdu, 2011, pp.
288-291.
V. CONCLUSION [11] J. F. Wang et al., "Research and application of jet stream arc-
quenching lightning protection gap (JSALPG) for transmission lines",
This work proposed a new lightning performance Dielectrics and Electrical Insulation IEEE Transactions on, vol. 22,
evaluation method for existing transmission lines and applied pp. 782-788, 2015.
it to evaluate the lightning performance of 220kV [12] Insulation Co-ordination-Part 1: Definitions, Principles and Rules, IEC
transmission lines with and without insulator parallel gaps. Standard 60071-2, 2006.
The conclusions are: [13] T. Li et al., "Lightning Discharge Character of Shunt Gap Used for
1) About 7% of the transmission lines have very different 220 kV Glass Insulator String", Electric Power, vol. 48, pp. 92-103,
2015. (in Chinese)
lightning parameter with that of the large area.
[14] J. K. Sharma, Business Statistics. Pearson Education India, 2012,
2) The shielding failure risk of 220kV transmission line pp. 454.
peak at 25kA lightning current. The risk of ground flashes
locate in 20m vicinity of 220kV transmission lines is much
higher than other ground flashes.

91

You might also like