SAFETY MODULE

NA13CT

User Manual
Table of Contents
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . .3

2. PACKAGE CONTENTS . . . . . . . . . . . . . . . . . . . . .3

3. FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

4. INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4.1 Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4.2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.3 Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.4 E-STOP connection . . . . . . . . . . . . . . . . . . . . . . . . .5
4.5 START Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.6 Safety Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
4.7 Auxiliary output . . . . . . . . . . . . . . . . . . . . . . . . . .5

5. OPERATING MODE . . . . . . . . . . . . . . . . . . . . . . . .5

6. TEST & ACTIVATION . . . . . . . . . . . . . . . . . . . . . . .6

7. USAGE PRECAUTIONS . . . . . . . . . . . . . . . . . . .6

8. INSPECTIONS AND MAINTENANCE . . . . . . . . . .7

9. APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . .8

10. TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . .10

2
1. INTRODUCTION nel unspecialised and/or insuffi-
This user manual must be read ciently informed on the contents of
and understood completely, prior this manual and the machine safety
to carrying out any operation on directives, Carlo Gavazzi is not
the module, by personnel dealing responsible for the functioning of
with all the activities of the the NA13CT and its capacity to
NA13CT safety module. It must be guarantee the operator’s safety.
stored in a dry clean place close to The NA13CT module does not
where the module is used for easy require internal maintenance: if it is
consultation. tampered or if the case is opened,
All the operations described in this the module looses its safety func-
manual must be carried out by tions and the guarantee is
carefully following all the indica- annulled.
tions given exclusively by spe- 2. PACKAGE CONTENTS
cialised personnel.
The package contains:
Contact Carlo Gavazzi and do not
• n.1 safety module model NT13CT
carry out any operations on the
safety module, ensuring the safety • n.1 user manual
of the operators, if there are any If any anomalies are found with the
doubts over the contents of this package, its contents or with the
manual, or if there is a fault or a safety module do not install and
malfunction. contact Carlo Gavazzi.
The user of the module is respon- 3. FUNCTION
sible for the evaluation of the risks
The safety module NA13CT is
of the entire system.
designed to control emergency
Based on the evaluation and on the stop (E-STOP) devices. It has
standards in force in the country of been designed according to safety
use, the user decides with com- category 3 of EN 954-1.
plete responsibility that the func-
Three N.O. force-guided and
tions described in the user manual
delayed safety outputs and one
are suitable for use on his machine.
auxiliary delayed N.C. output are
Whenever the NA13CT safety available, so that the NA13CT
module is improperly used, by not safety module is suitable for cate-
following only and all the indications gory 1 E-STOP (EN 60204-1)
of this manual or whenever these applications.
indications are partially, incorrectly
The delay is set up to 1 second.
or incompletely applied by person-

3
Fig. 1 - NA13CT diagram
4. INSTALLATION electrical board in a dry and
4.1 Warning clean place (minimum protection
degree: IP54), fixed on the spe-
• The NA1/3-C-T safety module cial DIN rail.
must be installed following the
standards in force in the country • If the safety module is tampered,
of use, when the machine is not it can not ensure the safety of
powered and with no dangers for the operator any more and the
the operator, on the machine’s warranty is void.
• To avoid interference due to cou-
TERM. CONNECTION pling, run the limit switches con-
A1 +24VDC / 18VAC necting conductors separately
A2 GND / 18 VAC from the power conductors.
S1-S2
Feedback loop and • Avoid the risk of short-circuits
START terminals between the terminals caused
13-14 by free cables, wires or material
23-24 N.O. Safety delayed outputs
that could come close to the
33-34
safety module.
N.C. Auxiliary delayed
41-42 • Avoid installation during storms.
output
Tab. 1: Terminal description
4
• Do not dispose of the packaging itored for welding fault) or auto-
in the environment. matic START.
4.2 Wiring To set up the manual START con-
figuration, it is necessary to con-
It is recommended to use conduc-
nect a N.O. pushbutton to the S1-
tors with section and length ade-
S2 terminals, while to set up the
quate to the terminals, currents
automatic START configuration
and distances involved, ensuring
the two terminals must be short-
that the conductors are not exces-
circuited (directly or via the
sively tight, that their positioning
N.C.contacts of external relays).
avoids potential cuts or squashing
and that they are not in the way of 4.6 Safety Outputs
people or things. Three N.O. voltage-free safety
4.3 Power supply outputs are available between the
Connect the A1 & A2 terminals to 13-14, 23-24 and 33-34 terminals:
the power supply source via the their contacts are closed when the
E-STOP device(s). safety module is correctly pow-
ered, the E-STOP is not pushed,
4.4 E-STOP connection and the START circuit has been
The NA13CT safety module can activated, as described in this
be connected to one or more sin- user manual.
gle-channel or double-channel E-
4.7 Auxiliary output
STOP devices (see the applica-
tion examples). One N.C. auxiliary voltage-free
relay output is available between
The E-STOP contact(s) must be
the 41-42 terminals. It can be
closed when the E-STOP button is
used only for signalling functions
not pushed, open when the E-
and not for safety functions.
STOP is pushed.
The contacts of the E-STOP must 5. OPERATING MODE
be connected between the power With manual START configuration,
supply terminals of the midule (A1 the safety outputs close and the
and eventually A2) and the power auxilary output opens when the E-
supply source, so that when the STOP is not pushed and the N.O.
E-STOP is pushed the safety START pushbutton is pressed.
module is switched off. With automatic START configura-
4.5 START Circuit tion, the safety outputs close and
The safety module can be config- the auxilary output opens as soon
ured for manual START (not mon- as the E-STOP is released (not
5
pushed). the POWER LED turns on, while
The CH1 & CH2 LEDs turn on as the CH1 and CH2 LEDs are off, the
soon as the safety outputs close. safety outputs are open and the
Pushing the E-STOP button leads auxiary output is closed (in auto-
to a safety condition, forcing the matic START configuration all the
safety outputs to an open status LEDs are on, the safety outputs
when the delay has expired. The are closed and the auxiliary output
POWER, CH1 & CH2 LEDs turn off. is open).
A new operating cycle is possible Close the N.O.START contact: the
only after releasing the E-STOP safety outputs close, the auxiliary
button (and pushing the START output opens and the CH1, CH2
button, if the safety module has LEDs turn on.
been set up with manual START STEP 3 Push the E-STOP button:
configuration). the safety outputs open (after the
delay has expired), the auxiliary
6. TEST & ACTIVATION output closes and the POWER,
The following operations must be CH1, CH2 LEDs turn off (always
repeated when the module is when the delay has expired).
installed and every time the wiring Repeat STEP 2 checking that the
is changed and at regular intervals safety outputs do not close - with
by carrying out in sequence all the manual START configuration - sim-
steps described below without any ply releasing the E-STOP device,
type of dangerous condition for the without pushing the START button.
operators. Check also that the safety outputs
STEP 1 Check the integrity, the do not close, that the auxiliary out-
correct installation, the correct put does not open, and that the
positioning on the machine and the POWER, CH1, CH2 LEDs are off
correct functioning of all the simply pushing the START button
devices connected to the inputs with E-STOP button pushed.
and to the outputs of the NA13CT If more than one E-STOP is used,
safety module. Check also the cor- the STEPS 2 and 3 must be
rect wiring of all the devices (See repeated for each device.
4.2) and the integrity of the labels
and documentation. 7. USAGE PRECAUTIONS
STEP 2 Power on the safety mod- The safety module can check the
ule with E-STOP button not pushed: integrity of external contactors or
with manual START configuration expansion modules simply con-

6
necting their N.C. control contacts hazardous areas when dangerous
in series to the START contact (or situations are still active.
to the bridge, in automatic START The NA13CT safety relay can be
configuration) between S1-S2 ter- employed also with mechanical or
minals. magnetic limit switches or sensors,
It is recommended to connect a if these devices have one/two con-
fuse in series to the safety outputs tacts, closed when there is no dan-
to reduce the risk of safety outputs ger for the operator (e.g. gate/door
contacts welding (see outputs closed), open when there are dan-
technical data). gerous situations fot the operator
Never, in any situation, connect (e.g. gate/door open).
spark quenching unit circuits in Never, in any circumstance,
parallel to safety outputs contacts: exceed the electrical ratings stated
the safety function would no longer in the technical data table of this
be guaranteed. manual.
The safety outputs open with a
8. INSPECTIONS AND
delay that is defined within a range
MAINTENANCE
(see technical data): the user must
always consider the worst case The integrity of the safety module
(maximum delay allowed by the and of all the connected devices
range) in designing his own must be checked regularly accord-
machine, in order to avoid the pos- ing to the risk evaluation of the
sibility for the operator to reach machine, under the complete

Fig. 2: NA13CT application with one single-channel E-STOP device

7
Fig. 3: NA13CT application with one double-channel E-STOP device

responsibility of the user. is pushed, the safety module is


Regular inspections must be per- switched off: the safety outputs
formed repeating all the operations open and the auxiliary output clos-
listed in the TEST & ACTIVATION es as soon as the releasing delay
section. has expired.
The safety module doesn’t require In Fig. 4 and 5, if both the
internal maintenance: it must be onechannel (two-channels) E-
periodically cleaned - with machine STOP buttons are not pushed, the
and module powered off - together safety outputs close (with automat-
with all the connected devices, ic START) or are enabled to close
removing dust, liquids and conden- (with manual START). When even
sation. one of the E-STOP buttons is
pushed, the safety module is
9. APPLICATIONS switched off: the safety outputs
In Fig. 2 and 3, if the one-channel open and the auxiliary output clos-
(two-channels) E-STOP button is es as soon as the releasing delay
not pushed, the safety outputs has expired.
close (with automatic START) or
are enabled to close (with manual
START). When the E-STOP button

8
Fig. 4: NA13CT application with two double-channel E-STOP devices

Fig. 5: NA13CT application with two single-channel E-STOP devices

9
10. TECHNICAL DATA
ELECTRICAL CHARACTERISTICS
18 Vac -15/+10% 50 ÷ 60Hz,
Supply Voltage 24 Vdc -15/+10%
Current Consumption 50 mA (@ 24Vdc, without load)
Power Consumption Max. 2 VA
Input 1 or 2 N.O. Voltage-free
Safety Category (EN 954-1) 3
E-STOP Category (EN 60204-1) 1
Short-Circuit Protection Internal PTC
SAFETY OUTPUTS
Function Force-guided N.O. contacts
Max Switching Voltage AC 250 V
Max. Switching Current 6A
Max. Switching Power
1500 VA
(Resistive Load)
Output contacts protection External fuse: 4 A
Mechanical Life > 107 switching cycles
Electrical Life (with max. load) > 105 switching cycles
AUXILIARY OUTPUT
Function Force-guided N.C. contacts
Ratings See Safety Outputs ratings
TIMINGS
Response time (from E-STOP
pushed to safety outputs open):
a) @ 24 Vdc 1.0 ± 0.2 seconds
b) Within the supply range 1.0 -0.3/+0.5 seconds
START delay (from START button
Max. 100 ms
pushed to safety outputs closed)

10
LED WARNINGS
ON : Module supplied
POWER
OFF : Module not supplied
ON : Safety outputs closed
CH1 & CH2
OFF : Safety outputs open
MECHANICAL AND ENVIRONMENTAL CHARACTERISTICS
PA 6.6 flammability class
Housing
VO-UL94
Fixing OMEGA - DIN EN 50022 Rail
Protection degree of the module IP30
Minimum Protection degree of
IP54
the installation location
EMC compatibility EN 61000-6-2; EN 61000-6-3;
Operating Temperature -20 ÷ 55°C
Storage Temperature -25 ÷ 75°C
Relative Operating Humidity 10 ÷ 95%
Relative Storage Humidity 10 ÷ 95%
Cross-Section of the cables to
0.14 ÷ 2.5 mm2 (rigid & flexible)
connect to the terminals
Torque setting on connection
0.5 Nm
terminals
Dimensions 99 x 22.5 x 115 mm
Weight 200 g

11
8020731 - MOD.NA13CT

CARLO GAVAZZI reserves the right to make improvements or


changes without prior notice.

12