You are on page 1of 1

Installation MCS025

Synchro-check module

Function
PE50285

1
The MCS025 module is used with (DVHUJ\Sepam series 60 and series 80.
The MCS025 module checks the voltages upstream and downstream of a circuit
breaker to ensure safe closing (ANSI 25).
It checks the differences in amplitude, frequency and phase between the two
measured voltages, taking into account voltage abscence.
Three relay outputs may be used to send the close enable to several Sepam units.
The circuit-breaker control function of each Sepam unit will take this close enable into
account.

The settings for the synchro-check function and the measurements carried out by the
module may be accessed by the SFT2841 setting and operating software, similar to
the other settings and measurements for the Sepam.

The MCS025 module is supplied ready for operation with:


b the CCA620 connector for connection of the relay outputs and the power supply
b the CCT640 connector for voltage connection
b the CCA785 cord for connection between the module and the Sepam base unit.

MCS025 synchro-check module.

Characteristics
MCS025 module
Weight 1.35 kg (2.98 lb)
Assembly With the AMT840 accessory
Operating temperature -25°C to +70°C (-13°F to +158°F)
Environmental characteristics Same characteristics as Sepam base units
Voltage inputs
Input impedance > 100 kΩ
Consumption < 0.015 VA (VT 100 V)
Continuous thermal withstand 240 V
1-second overload 480 V
Relay outputs
Relay outputs O1 and O2
Voltage DC 24/48 V DC 127 V DC 220 V DC
AC (47.5 to 63 Hz) 100 to 240 V AC
Continuous current 8A 8A 8A 8A
Breaking capacity Resistive load 8A/4A 0.7 A 0.3 A
Load L/R < 20 ms 6A/2A 0.5 A 0.2 A
Load L/R < 40 ms 4A/1A 0.2 A 0.1 A
Resistive load 8A
Load p.f. > 0.3 5A
Making capacity < 15 ms for 200 ms
Isolation of outputs from other Enhanced
isolated groups
Relay outputs O3 and O4 (O4 not used)
Voltage DC 24 / 48 V DC 127 V DC 220 V DC
AC (47.5 to 63 Hz) 100 to 240 V AC
Continuous current 2A 2A 2A 2A
Breaking capacity Load L/R < 20 ms 2A/1A 0.5 A 0.15 A
Load p.f. > 0.3 5A
Isolation of outputs from other Enhanced
isolated groups
Power supply
Voltage 24 to 250 V DC, -20 % / +10 % 110 to 240 V AC, -20 % / +10 %
47.5 to 63 Hz
Maximum consumption 6W 9 VA
Inrush current < 10 A for 10 ms < 15 A for one half period
Acceptable momentary outages 10 ms 10 ms

58 SEPED303003EN

You might also like