You are on page 1of 1

1.

1 Air Conditioing and Mechanical Ventilation System


Project Name TCMA - NEW ASSEMBLY SHOP Issue Date January 31, 2017 Revise 00

"Follow Thai "Envelope Load" : Conduction & Radiation "Machine Load" : 50w / m2 (Recommend By
HVAC SYSTEM CALCULATION SHEET from wall , roof , window

SELECTION
ROOM CONDITION (SPEC.) ROOM SIZE VENTILATION VOLUME TYPE OF EQUIPMENT ROOM SENSIBLE HEAT LOAD (RSH Kcal/H) RLH SUPPLY AIR VOLUME AC EQUIPMENT AC EQUIPMENT
TOTAL RSH OA LOAD TOTAL LOAD
ROOM NAME D.B. R.H. CLEAN ROOM AREA CH V VOLUME-1 VOLUME-2 VOLUME-3 GENERAL PROCESS GENERAL PROCESS Envelope Load Lighting Human (P) Machine Load Human (P) SHF delta- t SA V V.TIME SA V Q'TY UNIT Cap. Q'TY UNIT Cap. Average
TYPE TYPE Type
( °C ) (%) CLASS PRESS ( m2 ) (m) ( m3 ) V.TIME CMH CMH/m2 CMH CMH/P CMH EA(CMH) OA(CMH) EA(CMH) OA(CMH) EF SF EF SF Kcal/m2 Kcal/H. LUX W/m2 (Kcal/H) 65 Kcal/H.P kw (Kcal/H) Kcal/H Kcal/H.m2 47 Kcal/H.P ( °C ) CMH (Time/H) CMH Kcal/H Kcal/H.m2 Kcal/H Kcal/H.m2 Set Kcal/H Set Kcal/H Kcal/H.m2

1 FL.
M-Toilet 1 N.A N.A. 37.6 2.4 90.2 15 1,354 1,400 WM

W-Toilet 1 N.A N.A. 18.0 2.4 43.2 15 648 650 WM

Utility 1 N.A N.A. 5.7 2.4 13.7 10 137 140 See Calculation WM

MDB Rm. N.A N.A. 96.0 6.0 576.0 6,400 IW

Assembly Shop Area N.A N.A. 13,162.0 10.0 131,620.0 4 526,480 528,000 IW

QA Shop 26±3 N.A. 187.5 3.8 712.5 2 375 9 108 375 375 WM MS 45 8,438 400 24 3,870 12 780 9 8,063 21,150 113 12 564 0.97 11 6,700 5,190 28 26,904 143 CS 4 6,800 CS 4 7,500 160 SPLIT
VES Area 26±3 N.A. 150.0 3.8 570.0 2 300 9 108 375 375 WM MS 45 6,750 400 24 3,096 12 780 8 6,450 17,076 114 12 564 0.97 11 5,400 5,190 35 22,830 152 CS 4 5,800 CS 4 6,000 160 SPLIT
2 FL.
Office & MGR 26±3 N.A. 440.0 3.0 1,320.0 2 880 9 648 900 900 MS 64 28,160 600 35 13,244 72 4,680 22 18,920 65,004 148 84 3,948 0.94 11 20,400 12,457 28 81,409 185 CS 12 6,800 CC 12 7,700 210 VRV
Conference Rm. 26±3 N.A. 30.0 3.0 90.0 6 180 9 126 180 180 MS MS 148 4,440 500 30 774 14 910 6,124 204 14 658 0.90 11 2,000 2,491 83 9,273 309 CS 1 9,300 CC 1 9,600 320 VRV
Printing Rm. N.A N.A. 11.2 3.0 33.6 12 403 9 410 MS

Pantry Rm. N.A N.A. 11.6 3.0 34.8 12 418 9 420 MS

M-Toilet 2 N.A N.A. 16.8 2.4 40.3 15 605 9 610 MS

W-Toilet 2 N.A N.A. 14.0 2.4 33.6 15 504 9 510 MS

Utility 2 N.A N.A. 5.0 2.6 13.0 10 130 9 130 CC

Storage Rm. N.A N.A. 19.5 3.0 58.5 6 351 9 360 MS Standby 1
Staircase-2 N.A N.A. 2,030 TA TA

Server / EE Rm. 26±3 N.A. 16.5 3.0 49.5 2 33 9 18 50 50 CC 94 1,551 400 24 341 2 130 3 2,838 4,860 295 2 94 0.98 11 1,600 692 42 5,646 342 WM 1 5,700 WM 2 6,000 364 SPLIT
Meeting Rm. 1 26±3 N.A. 20.0 3.0 60.0 6 120 9 72 120 120 CC 132 2,640 500 30 516 8 520 3,676 184 8 376 0.91 11 1,200 1,661 83 5,713 286 CS 1 5,800 CC 1 6,000 300 VRV
Meeting Rm. 2 26±3 N.A. 20.0 3.0 60.0 6 120 9 72 120 120 CC 132 2,640 500 30 516 8 520 3,676 184 8 376 0.91 11 1,200 1,661 83 5,713 286 CS 1 5,800 CC 1 6,000 300 VRV
Meeting Rm. 3 26±3 N.A. 20.0 3.0 60.0 6 120 9 72 120 120 CC 82 1,640 500 30 516 8 520 2,676 134 8 376 0.88 11 900 1,661 83 4,713 236 CS 1 4,800 CC 1 6,000 300 VRV
Plant MGR Rm. 26±3 N.A. 26.0 3.0 78.0 2 52 9 63 80 80 CC 89 2,314 600 35 783 7 455 3,552 137 7 329 0.92 11 1,200 1,107 43 4,988 192 CS 1 5,000 CC 1 6,000 231 VRV

Calculation "A" for MDB Rm. (1,500 kVA x 1 set)


- Heat Generate from MDB & Cable = 9,050 kcal/h x 1 Set
= (9,050 x 1) / ((0.29 x (40-35))
- Total Room Ventilation = 6,242 CMH

AIR CONDITIONING EQUIPMENT VENTILATION EQUIPMENT DESIGN CONDITION RATES OF HEAT GAIN FROM OCCUPANTS (ASHRAE 1997) (Kcal/H) DIFFERENTIAL TEMPERATURE ( C) ABSOLUTE HUMIDITY (Kg/Kg.DA)
1, CS - CEILING SUSPENDED 1, CC - CEILING CASSETTE OUTDOOR CONDITION : DB35 C / WB29.13 C (RH65%) DEGREE OF ACTIVITY SH LH RM Temp. DX COIL Lev. ⊿t 40% 45% 50% 55% 60%
2, CD - CEILING CONCEALED DUCT 2, MS - MINI SIROCCO ABSOLUTE HUMIDITY 0.02327 Kg/Kg.DA
22 C 0.0066 0.00739 0.00822 0.00905 0.00989
3, CC - CEILING CASSETTE 3, WM - WALL MOUNT ENTHALPY 22.67 Kcal/Kg SEATED , VERY LIGHT WORK 60 39 30 - 16 = 14
4, WM - WALL MOUNT 4, IW - INDUSTRIAL WALL FAN MODERATELY ACTIVE OFFICE WORK 65 47 28 - 16 = 12 23 C 0.007 0.00785 0.00874 0.00963 0.01052
5, FF - FLOOR MOUNTED FREE BLOW 5, AX - AXIAL FLOW FAN (IN LINE) INDOOR CONDITION : DB26 C / WB20.34 C (RH60%) 24 C 0.0074 0.00835 0.00929 0.01023 0.01118
STANDING LIGHT WORK 65 47 26 - 16 = 10
6, FD - FLOOR MOUNTED DUCT 6, CR - CENTRIFUGAL FAN ABSOLUTE HUMIDITY 0.01263 Kg/Kg.DA
7, AHU - AIR HANDLING UNIT 7, RF - ROOF FAN LIGHT BENCH WORK AT FACTORY 69 120 24 - 16 = 8 25 C 0.0079 0.00887 0.00987 0.01088 0.01188
8, OAC - OUTER AIR CONDITIONER 8, DC - DUST COLLECTOR HEAVY WORK AT FACTORY 146 219 22 - 16 = 6 26 C 0.0084 0.00942 0.01049 0.01155 0.01263
9, NV - NATURAL VENTILATOR 27 C 0.0089 0.01000 0.01113 0.01227 0.01341
OCCUPANCY 20 - 16 = 4
- Office General 10 m2/Person LUX W/m2 28 C 0.0094 0.01062 0.01182 0.01302 0.01423
Private 13 m2/Person Corridor, Machine room, MDB room, Toilet 200 12 ENVELOPE LOAD 29 C 0.01 0.01126 0.01254 0.01382 0.01511
- Factory Light 15 m2/Person Canteen, Lobby, Locker, Factory 300 18 OUTSIDE WALL HEAT LOAD 30 C 0.0106 0.01194 0.01330 0.01466 0.01603
N , NE 80 Kcal/H.m2
Heavy 25 m2/Person QC room, Server room, First aid 400 24 E , SE 100 KcaL/H.m2
Assembly Line 4 m2/Person Meeting room 500 30 S, NW 120 KcaL/H.m2
- Resturant Large 1.5 m2/Person Office 600 35 W , SW 130 KcaL/H.m2
- Meeting General 1.2 m2/Person Assembly line 700 41 INSIDE WALL 60 Kcal/H.m2

Calculation-TCMA_Assembly Shop.xls, HVAC